FIRE ALARM EQUIPMENT
Bell/Strobe
Adaptor Plate
(Bell purchased separately)
FEATURES
> 30, 15/75 and 110 candela
models
> Control modules not required
> Low current draw synchronous
strobe
> Mounts to a variety of electrical
boxes
AGENCY APPROVALS
> Strobe: UL 1971 Listed for the
Hearing Impaired
> Strobe: UL 1638 Listed Private
Mode (Indoor and not for the
hearing impaired)
> Meets NFPA and ADA
requirements
2453BSA Series
The Edwards 2453BSA Series Bell/Strobe Adaptor Plate contains a
30, 15/75, or 110 candela strobe. The unit is specifically designed
for use with the 439D-AW-R series of 6" (152mm), 8" (203mm) and
10" (254mm) red fire alarm bells (ordered separately). The Adaptor
Plate is available in red.
The strobes employ a unique microprocessor design that assures
all units operate at the same time and at a rate of one flash per
second thereby reducing the risk of causing disorientation of a
small portion of the population having photosensitivity. Wire leads
are provided for easy installation of the strobe. The units are rated
for indoor use. The strobes require a continuous (non-pulsed) DC
source.
The 2453BSA Series is designed for indoor wall mounting on a vari-
ety of standard, flush mounted, North-American electrical boxes.
These include 1-gang, 2-gang, 3-1/2" & 4" octagon and 4" square
boxes. Edwards recommends that these fire alarm bell/strobes al-
ways be installed in accordance with the latest recognized edition
of national and local fire alarm codes.
D-04
12-44
The Bell/Strobe Adaptor Plate is ideal for renovation, retrofit
projects and new construction.
© Copyright 2004 Edwards
TECHNICAL INFORMATION
FIRE ALARM EQUIPMENT
5 5/16"
(135mm)
10 9/16"
(268mm)
6" (152mm) bell
shown for
illustration
purposes only
3/8"
(10mm)
(48mm)
1 7/8"
2 5/8"
(67mm)
Catalog Number 2453BSA-30-R 2453BSA-15/75-R 2453BSA-110-R
Faceplate Color Red Red Red
Strobe Operating Volts 20 to 31V DC (Continuous)
UL 1638 Strobe Flash Output 30 cd 75 cd 120 cd
UL 1971 Strobe Flash Output 30 cd Wall 15 cd Wall 110 cd Wall
Mean Operating 89 mA @ 24V DC 96 mA @ 24V DC 197 mA @ 24V DC
1,4
Current
Peak Operating Current
1,3
Mean Operating Current FWR
2
107 mA @ 20V DC 115 mA @ 20V DC 241 mA @ 20V DC
189 mA @ 20V DC 204 mA @ 20V DC 338 mA @ 20V DC
75 mA @ 24V DC 79 mA @ 24V DC 338 mA @ 24V DC
91 mA @ 20V DC 97 mA @ 20V DC 202 mA @ 20V DC
Peak Operating Current FWR
2,3
402 mA @ 24V DC 446 mA @ 24V DC 788 mA @ 24V DC
Strobe Flash Rate Synchronized at one flash per second. External control module (EG1M-RM) necessary to meet
UL 1971 synchronization requirements of 10 milliseconds over a two-hour period.
Synchronization Module EG1M, EG1-RM
Strobe Lens Clear Lexan
Wire Connection Wire Leads, Polarized Input, #12 AWG
Lens Markings Red "FIRE" Vertical Both Sides (Wall Mount)
Faceplate Material Textured Color-Impregnated Noryl (Exceeds 94V-0 UL Flammability Rating)
Mounting Flush (Indoor Only): 1-Gang (2" Deep Min.) Standard Electrical Box
Operating Environment Indoor: 85% Relative Humidity @ 86F (30C); 32 to 120F (0 to 49C) Variable Ambient Temperature
Agency Listing UL 1971 and UL 1638
(All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule)
Note 1: Use the mean current rating to establish the maximum number of strobes, wire gauge and standby power requirements. 2400 Series uses 24V DC. Fire Shield uses 24V DC FWR.
Note 2: From a FILTERED DC source.
Note 3: From an UNFILTERED (Full Wave Rectified) DC source.
Note 4: Peak inrush current at 24V DC = 7.8 Amps for less than 50 microseconds.
D-04
© Copyright 2004 Edwards