Edwards Signaling 2447T User Manual

C
C
Integrity Temporal Horn Installation Sheet
Description
The Integrity Temporal Horn is a fire alarm notification appliance designed for indoor or outdoor walls and ceilings. See Table 1 for temporal horn model numbers and Table 2 for accessory model numbers.
Table 1: Models
Description Numbers
XLS757-1A-T
Temporal horn, white 757-1A-TW
XLS757-1A-TW
Table 2: Accessories
Description Numbers
Surface box, red, indoor 757A-SB
XLS757A-SB
Surface box, white, indoor 757A-SBW
XLS757A-SBW
Weatherproof box, red, outdoor
Weatherproof box, white, outdoor
Bi-directional mounting frame, red, indoor
Bi-directional mounting frame, white, indoor
757A-WB XLS757A-WB
757A-WBW XLS757A-WBW
757A-BDF XLS757A-BDF
757A-BDFW XLS757A-BDFW
INT-T 2447TH-R
INT-TW 2447TH-W
INT-SB 2459-SMB-R
INT-SBW 2459-SMB-W
INT-WB 2459-WPB-R
INT-WBW 2459-WPB-W
INT-BDF
INT-BDFW
Installation
WARNING: Electrocution hazard. To avoid personal injury or
death from electrocution, remove all sources of power and allow stored energy to discharge before installing or removing equipment.
To install the temporal horn:
1. Select and install a suitable electrical box. See “Mounting the electrical box” on page 2 for details.
Note: Outdoor installations require a weatherproof backbox.
2. Set the tone and pattern. See “Selecting the volume and pattern” on page 2 for details.
3. Bring the signal circuit field wiring into the electrical box.
4. Position the mounting plate on the electrical box with the hook flange up and facing outward as shown in Figure 2. Fasten the plate using the screws provided.
5. Connect the signal circuit field wiring. For the unit to function properly, observe polarity. See Figure 1.
For additional wiring details, see the installation instructions for the signaling modules or circuits used in the fire alarm control panel.
6. After completing the connections, attach the unit to the mounting plate, as noted below.
a. The grille has tabs (at the top of the inner face) that
engage with the hook flange on the mounting plate. Angle the bottom of the grille out slightly, and then slide the unit into place so that the tabs engage the flange.
b. Seat the grille by pressing the bottom in.
c. Fasten the bottom of the grille to the mounting plate
by tightening the captive locking screw.
7. Apply power and activate the unit to verify that it is operating properly.
Figure 1: Typical wiring diagram
Note: Electrical supervision requires the wire run to be broken
at each terminal. Do not loop the signaling circuit field wires around the terminals.
Install this product in accordance with applicable requirements in the latest editions of NFPA 72 National Fire Alarm and Signaling Code, CSA C22.1 the Canadian Electrical Code, Part 1, Section 32, CAN/ULC-S524 Installation of Fire Alarm Systems, and in accordance with the local authority having jurisdiction.
© 2011 UTC Fire & Security. All rights reserved. 1 / 4 P/N P-047550-1779 • REV 7.0 • ISS 06MAY11
NAC + NAC +
()1(2)
NA
–NA
Polarity is shown in the active state.
(1) From UL/ULC Listed fire alarm control panel signal circuit. (2) To next device or end of line resistor for Class B. Return to control
panel for Class A connection.
()1()
Figure 2: Mounting diagram
)
(8)
5-1/2 in.
(140 mm)
5-1/2 in.
(140 mm)
(1)
(2)
(9)
5/8 in.
(16 mm)
5-59/64 in.
(150 mm)
5-59/64 in.
(150 mm)
()7
3-13/32 in.
(87 mm)
2-1/8 in. (54 mm)
(6)
(3)
3-5/16 in
(84 mm)
(4)
.
5-5/8 in.
(143 mm)
5-5/8 in.
(143 mm
(5)
(1) Gasket with adhesive backing (2) Weatherproof box (3) Standard box (4) Knockouts for 1/2 in. (13 mm) or 3/4 in. (19 mm) conduit top,
bottom, back
Mounting the electrical box
Figure 2 shows mounting details for:
Standard box. When using a 4 in. square box, use an extension ring for additional wiring space, if needed. If using a double-gang electrical box that is 2-1/2 in. (64 mm) deep, locate the conduit only at the rear of the box.
Weatherproof box. Peel off the adhesive backing from the gasket and adhere to the box.
Surface mount box.
Selecting the volume and pattern
The horn has a jumper for selecting a high or low volume output level. The default is high volume. To set the output to low volume, remove the output jumper from the circuit board on the rear of the unit. See Figure 3.
The horn has a jumper for selecting either a temporal or steady tone. The default is temporal tone. To set the output to steady tone, remove the tone jumper from the circuit board on the rear of the unit. See Figure 3.
Tip: Save the jumper by sliding it onto a single pin.
(5) Surface mount box
(6) Mounting plate (supplied with horn) (7) #8-32 screw (8) Captive locking screw (9) Hook flange
Figure 3: Jumper setup and terminal block
2
REMOVE FOR LOW OUTPUT
Item In Out
(1) High output Low output
(2) Temporal tone Continuous tone
REMOVE FOR CONT. TONE
STROBE +
HORN –
HORN +
3
4
2
STROBE –
1
2 / 4 P/N P-047550-1779 • REV 7.0 • ISS 06MAY11
Maintenance
Note: Do not change the factory-applied finishes.
This unit is not serviceable or repairable. Should the unit fail to operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a year or as directed by the local authority having jurisdiction.
Table 5: ULC directional characteristic
Angle dBA
90° 0 (ref)
57° and 123° −3
37° and 143° −6
Note: Horizontal and vertical axes provide the same pattern.
Specifications
Operating voltage 16 to 33 VDC; 16 to 33 VFWR
Operating current 16 to 33 VDC 16 to 33 VFWR
Sound output See Table 3 and Table 4
Synchronization Pulses at temporal rate within 200 ms on
Horn temporal pattern 0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s
Wire size 12 to 18 AWG (0.75 to 2.50 mm²)
Compatible electrical boxes
Operating temperature Indoor UL outdoor ULC outdoor
Relative humidity Indoor Outdoor
Table 3: Reverberant room sound output (dBA) [1]
Method Temporal Continuous Low High Low High
UL464 at 16 VDC 73 80 77 83
ULI at 24 VDC 77 83 82 86
ULI at 33 VDC 78 85 82 88
[1] Sound level output at 10 ft. (3.05 m)
85 mA 105 mA
common circuit for 30 minutes
on, 1.5 s off, repeat cycle
2-1/2 in.(64 mm) deep double-gang; Standard 4 in. square box 2-1/8 in. (54 mm) deep; surface or weatherproof mounting box per Table 1
32 to 120°F (0 to 49°C)
31 to 150°F (35 to 66°C)
40 to 150°F (40 to 66°C)
93% noncondensing 98% noncondensing
Regulatory information
Manufacturer Edwards, A Division of UTC Fire & Security
Year of manufacture
UL/ULC rating Regulated 24 DC and Regulated 24 FWR [1]
Environmental class
North American standards
[1] This device was tested to the regulated 24 DC/FWR operating voltage limits of 16 V and 33 V.
Contact information
For contact information, see www.utcfireandsecurity.com.
Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA
The first two digits of the date code (located on the product identification label) are the year of manufacture.
Indoor or outdoor
Meets: UL 464 and CAN/ULC-S525-07 Follow: NFPA 72 and CAN/ULC-S524
2002/96/EC (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see: www.recyclethis.info.
Table 4: ULC anechoic room sound output (dBA) [1]
Method Temporal Continuous Low High Low High
16 to 33 VDC 93 98 86 91
16 to 33 VFWR 96 100 90 93
[1] Average peak sound level output at 10 ft. (3.05 m) Meets or exceeds CAN/ULC-S525-07, 85 dBA minimum anechoic at 3
meters, all settings
P/N P-047550-1779 • REV 7.0 • ISS 06MAY11 3 / 4
4 / 4 P/N P-047550-1779 • REV 7.0 • ISS 06MAY11
Loading...