Integrity Temporal Horn Installation Sheet
Description
The Integrity Temporal Horn is a fire alarm notification
appliance designed for indoor or outdoor walls and ceilings.
See Table 1 for temporal horn model numbers and Table 2 for
accessory model numbers.
Table 1: Models
Description Numbers
Temporal horn, red 757-1A-T
XLS757-1A-T
Temporal horn, white 757-1A-TW
XLS757-1A-TW
Table 2: Accessories
Description Numbers
Surface box, red, indoor 757A-SB
XLS757A-SB
Surface box, white, indoor 757A-SBW
XLS757A-SBW
Weatherproof box, red,
outdoor
Weatherproof box, white,
outdoor
Bi-directional mounting
frame, red, indoor
Bi-directional mounting
frame, white, indoor
757A-WB
XLS757A-WB
757A-WBW
XLS757A-WBW
757A-BDF
XLS757A-BDF
757A-BDFW
XLS757A-BDFW
INT-T
2447TH-R
INT-TW
2447TH-W
INT-SB
2459-SMB-R
INT-SBW
2459-SMB-W
INT-WB
2459-WPB-R
INT-WBW
2459-WPB-W
INT-BDF
INT-BDFW
Installation
WARNING: Electrocution hazard. To avoid personal injury or
death from electrocution, remove all sources of power and
allow stored energy to discharge before installing or removing
equipment.
To install the temporal horn:
1. Select and install a suitable electrical box. See “Mounting
the electrical box” on page 2 for details.
Note: Outdoor installations require a weatherproof
backbox.
2. Set the tone and pattern. See “Selecting the volume and
pattern” on page 2 for details.
3. Bring the signal circuit field wiring into the electrical box.
4. Position the mounting plate on the electrical box with the
hook flange up and facing outward as shown in Figure 2.
Fasten the plate using the screws provided.
5. Connect the signal circuit field wiring. For the unit to
function properly, observe polarity. See Figure 1.
For additional wiring details, see the installation
instructions for the signaling modules or circuits used in
the fire alarm control panel.
6. After completing the connections, attach the unit to the
mounting plate, as noted below.
a. The grille has tabs (at the top of the inner face) that
engage with the hook flange on the mounting plate.
Angle the bottom of the grille out slightly, and then
slide the unit into place so that the tabs engage the
flange.
b. Seat the grille by pressing the bottom in.
c. Fasten the bottom of the grille to the mounting plate
by tightening the captive locking screw.
7. Apply power and activate the unit to verify that it is
operating properly.
Figure 1: Typical wiring diagram
Note: Electrical supervision requires the wire run to be broken
at each terminal. Do not loop the signaling circuit field wires
around the terminals.
Install this product in accordance with applicable requirements
in the latest editions of NFPA 72 National Fire Alarm and
Signaling Code, CSA C22.1 the Canadian Electrical Code, Part
1, Section 32, CAN/ULC-S524 Installation of Fire Alarm
Systems, and in accordance with the local authority having
jurisdiction.
© 2011 UTC Fire & Security. All rights reserved. 1 / 4 P/N P-047550-1779 • REV 7.0 • ISS 06MAY11
NAC + NAC +
()1(2)
NA
–NA
Polarity is shown in the active state.
(1) From UL/ULC Listed fire alarm control panel signal circuit.
(2) To next device or end of line resistor for Class B. Return to control
panel for Class A connection.
–
Figure 2: Mounting diagram
5-1/2 in.
(140 mm)
5-1/2 in.
(140 mm)
(1)
(2)
(9)
5/8 in.
(16 mm)
5-59/64 in.
(150 mm)
5-59/64 in.
(150 mm)
()7
3-13/32 in.
(87 mm)
2-1/8 in.
(54 mm)
(6)
(3)
3-5/16 in
(84 mm)
(4)
.
5-5/8 in.
(143 mm)
5-5/8 in.
(143 mm
(5)
(1) Gasket with adhesive backing
(2) Weatherproof box
(3) Standard box
(4) Knockouts for 1/2 in. (13 mm) or 3/4 in. (19 mm) conduit top,
bottom, back
Mounting the electrical box
Figure 2 shows mounting details for:
• Standard box. When using a 4 in. square box, use an
extension ring for additional wiring space, if needed. If
using a double-gang electrical box that is 2-1/2 in.
(64 mm) deep, locate the conduit only at the rear of the
box.
• Weatherproof box. Peel off the adhesive backing from the
gasket and adhere to the box.
• Surface mount box.
Selecting the volume and pattern
The horn has a jumper for selecting a high or low volume
output level. The default is high volume. To set the output to
low volume, remove the output jumper from the circuit board
on the rear of the unit. See Figure 3.
The horn has a jumper for selecting either a temporal or steady
tone. The default is temporal tone. To set the output to steady
tone, remove the tone jumper from the circuit board on the rear
of the unit. See Figure 3.
Tip: Save the jumper by sliding it onto a single pin.
(5) Surface mount box
(6) Mounting plate (supplied with horn)
(7) #8-32 screw
(8) Captive locking screw
(9) Hook flange
Figure 3: Jumper setup and terminal block
2
REMOVE FOR
LOW OUTPUT
Item In Out
(1) High output Low output
(2) Temporal tone Continuous tone
REMOVE FOR
CONT. TONE
STROBE +
HORN –
HORN +
3
4
2
STROBE –
1
2 / 4 P/N P-047550-1779 • REV 7.0 • ISS 06MAY11