The Edwards 2440S & 2441S Series
synchronous strobes are visual alarm
signals designed for use in fire alarm
applications.
The strobes employ a unique microprocessor design that assures all units
operate at the same time and at a
rate of one flash per second thereby
reducing the risk of causing disorientation of a small portion of the population having photosensitivity.
Screw terminals are provided for
easy installation. The strobes require
a continuous (non-pulsed) DC source.
Agency Approvals
• Strobe: UL 1971 Listed for the
Hearing Impaired
• Strobe: UL 1638 Listed Private
Mode (Indoor and not for the hearing impaired)
• Meets NFPA and ADA require-
ments
• Engineered thermoplastic housing
UL flame rated 94V-0
Specifications
• See Specification Information Table
on page 12-24.
Installation
See Strobe Application Data, page
12-38, for the following: sizing wall
and ceiling mounted strobes to room
size, mounting strobes in corridors,
and mounting strobes in sleeping
rooms.
See System Design Criteria on page
12-51.
Applications
The 2440S & 2441S series strobe is a
visual signaling appliance for installations that operate in conjunction with
an installed fire alarm panel and detection devices.
Cat. No. 2440S
Cat. No. 2441S
5"
(127mm)
1 7/8"
(48mm)
1/4"
(6mm)
Equipment
Fire Alarm
Polarity of signal circuit shown in supervisory state. On alarm, polarity reverses. For wiring installation details, see the applicable
control panel installation manual.
+
To Listed Fire Alarm Control Panel
(signal circuit)
End-of-line-resistor
(supplied with control panel)
-
CAUTION: This unit is designed to be used on signal circuits that output a constant voltage of 20-24V DC. Do not connect this unit
to a coded or pulsating voltage. Electrical supervision requires wire run to be broken at each terminal. Do not loop signaling circuit field wires around terminals.
UL 1638 StrobeNot UL 1638 Rated30 cd60 cd75 cd120 cd
Flash Output
UL 1971 Strobe15 cd30 cd Wall60 cd Wall15 cd Wall110 cd Wall
Flash Output(Wall Mount Only)15 cd Ceiling30 cd Ceiling15 cd Ceiling60 cd Ceiling
Operating Voltage20 to 24V DC Continuous (Non-pulsed)
Avg. Operating70 mA @ 24V DC105 mA @ 24V DC160 mA @ 24V DC105 mA @ 24V DC219 mA @ 24V DC
Current (1,4)79 mA @ 20V DC125 mA @ 20V DC190 mA @ 20V DC125 mA @ 20V DC272 mA @ 20V DC
Peak Operating125 mA @ 20V DC185 mA @ 20V DC240 mA @ 20V DC185 mA @ 20V DC340 mA @ 20V DC
Current (1,3)
Avg. Operating60 mA @ 24V DC90 mA @ 24V DC130 mA @ 24V DC90 mA @ 24V DC190 mA @ 24V DC
Current (2)70 mA @ 20V DC102 mA @ 20V DC155 mA @ 20V DC102 mA @ 20V DC235 mA @ 20V DC
Peak Operating375 mA @ 20V DC530 mA @ 20V DC700 mA @ 20V DC530 mA @ 20V DC910 mA @ 20V DC
Current (2,3)
Peak Inrush7.6 A @ 24V DC7.6 A @ 24V DC7.6 A @ 24V DC7.6 A @ 24V DC7.8 A @ 24V DC
Current (4)
Strobe Flash RateSynchronized at 1 flash per second (no external control module required)
Lens MarkingsRed "FIRE" Vertical Both Sides (Wall Mount)
Faceplate MaterialTextured Color-Impregnated Noryl (Exceeds 94V-0 UL Flammability Rating)
MountingFlush: 1-Gang (2" Deep Min.) Standard Electrical Box
Surface: 1-Gang Wiremold Box
Operating85% Relative Humidity @ 86°F (30C); 32° to 120°F (0° to 49°C) Variable Ambient Temp.
Environment
Agency ListingUL 1971, UL 1638 and UL 464
(All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule)
† The 2440S & 2441S strobes are available with either a red faceplate or a white faceplate; for a red faceplate, put an "R" in this position
and for a white faceplate, put a "W" in this position.
Note 1: Connected to filtered DC source.
Note 2: Connected to unfiltered DC source (full wave rectified)
Note 3: Use the peak current rating to establish the maximum number of strobes, wire gauge and standby power requirements. Consult
the panel manufacturer to determine the maximum number of strobes for each signaling circuit.
Note 4: Peak inrush current at 24V DC for less than 50 microseconds.
12-24
Fax-on-Demand # 1170
Page 3
Signals
Control
Process
NEMA &
Hazardous,
IP Definitions
Visual
Signals
Signals
Electronic
Bells &
Buzzers
Sirens
Horns &
Message
Centers &
Annunciators
Signals
Outdoor
Warning
Electric
Chimes
Contactors
Push Buttons
Door Devices
Transformers
Fire Alarm
Equipment
Edwards® Strobe
Application Data
Description
The National Fire Protection Association (NFPA) has established guidelines for the installation of visual signaling appliances for rooms, corridors, and sleeping areas. These
guidelines, referenced in NFPA 72,
Chapter 6, take into consideration
the effective intensity of the strobe
light, the size of the space, and
whether the appliance is installed on
the wall or ceiling. Edwards synchronous, fire alarm strobes are listed to
UL Standard 1971 and conform to
the ADA (Americans with Disabilities
Act) equivalent facilitation when installed using these guidelines. When
employing these guidelines consult
the Authority Having Jurisdiction.
Space Allocation for Rooms
Table 1 provides the candela rating
required for strobes when installed
on walls in rooms of varying size.
When ceiling mounted, the number
of strobes may be reduced while continuing to provide equivalent facilitation. Table 2 lists room, ceiling
height, and appropriate light intensity for the given space.
Space Allocation for
Corridors
Strobes mounted in corridors not
greater than 20 feet (6.1m) wide
shall be located no more than 15
feet (4.6m) from the end of the corridor with a separation no greater
than 100 feet (30.5m) between appliances. They shall be wall mounted
in accordance with Table 3.
Space Allocation for
Sleeping Rooms
Strobes mounted on the wall with
the top of the strobe greater than
24 inches (61cm) from the ceiling
shall be rated 110 cd. Strobes closer
to the ceiling than 24 inches (61cm)
shall be rated 177 cd.
Max. RoomOne Light Per(On Opposite(One per Wall)
SizeRoom (CD)Walls) (CD)(CD)
20' x 20'15——
30' x 30'3015—
40' x 40'603015
50' x 50'956030
60' x 60'1359530
70' x 70'18511060
80' x 80'—14060
Note: The bottom of the wall mounted appliance should be not less than 80 inches (203cm) or more
than 96 inches (244cm) from the floor.
Max. RoomMaximum Ceiling
SizeHeight (ft.)One Light (CD)
20' x 20'1015
30' x 30'1030
40' x 40'1060
50' x 50'1095
20' x 20'2030
30' x 30'2045
40' x 40'2080
50' x 50'20115
20' x 20'3055
30' x 30'3075
Note: Where ceiling heights exceed 30 ft. (91.4m), visible signaling appliances should be suspended at
or below 30 ft. (91.4m) or wall mounted.
Note: The above table is based on locating the visible signaling appliance at the center of the room.
Where it is not located at the center of the room, the effective intensity (cd) should be
determined by doubling the distance from the appliance to the farthest wall to obtain the max.
room size.
Table 1
Minimum Required Light Output, Candela (CD)
Effective Intensity
Two Per RoomFour Per Room
Table 2
Minimum Required Light Output, Candela (CD)
Effective Intensity
Table 3
Min. Number of 15 cd Visible
Corridor Length (ft.)Appliances Required
0-301
31-1302
131-2303
231-3304
331-4305
431-5306
12-38
Fax-on-Demand # 1297
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.