Edwards Signaling 2440S Series, 2441S Series Catalog Page

Edwards® 2440S & 2441S Series Strobe Signals
Features
Low current draw synchronous
strobe
Supervised wiring
Terminals for easy wiring
Red or white flame resistant
housing
Strobe available in 15, 30, 60, 15/75,
and 110 candela models
Control modules not required
Description
The Edwards 2440S & 2441S Series synchronous strobes are visual alarm signals designed for use in fire alarm applications.
The strobes employ a unique micro­processor design that assures all units operate at the same time and at a rate of one flash per second thereby reducing the risk of causing disorien­tation of a small portion of the popu­lation having photosensitivity.
Screw terminals are provided for easy installation. The strobes require a continuous (non-pulsed) DC source.
Agency Approvals
Strobe: UL 1971 Listed for the
Hearing Impaired
Strobe: UL 1638 Listed Private
Mode (Indoor and not for the hear­ing impaired)
Meets NFPA and ADA require-
ments
Engineered thermoplastic housing
UL flame rated 94V-0
Specifications
See Specification Information Table
on page 12-24.
Installation
See Strobe Application Data, page 12-38, for the following: sizing wall and ceiling mounted strobes to room size, mounting strobes in corridors, and mounting strobes in sleeping rooms.
See System Design Criteria on page 12-51.
Applications
The 2440S & 2441S series strobe is a visual signaling appliance for installa­tions that operate in conjunction with an installed fire alarm panel and de­tection devices.
Cat. No. 2440S
Cat. No. 2441S
5"
(127mm)
1 7/8"
(48mm)
1/4"
(6mm)
Equipment
Fire Alarm
Polarity of signal circuit shown in supervisory state. On alarm, polarity reverses. For wiring installation details, see the applicable control panel installation manual.
+
To Listed Fire Alarm Control Panel (signal circuit)
End-of-line-resistor (supplied with control panel)
-
CAUTION: This unit is designed to be used on signal circuits that output a constant voltage of 20-24V DC. Do not connect this unit to a coded or pulsating voltage. Electrical supervision requires wire run to be broken at each terminal. Do not loop signaling cir­cuit field wires around terminals.
12-23
Fax-on-Demand # 1170
Clocks
ADA/Hospital
Signaling
Devices
Telephone
Signals &
Appendix
Signals
Control
Process
NEMA &
Hazardous,
IP Definitions
Visual
Signals
Signals
Electronic
Bells &
Buzzers
Sirens
Horns &
Specification Information
Catalog Number 2440S-15-(†) 2440S-30-(†) 2440S-60-(†) 2440S-15/75-(†) 2440S-110-(†)
2441S-15-(†) 2441S-30-(†) 2441S-60-(†) 2441S-15/75-(†) 2441S-110-(†)
UL 1638 Strobe Not UL 1638 Rated 30 cd 60 cd 75 cd 120 cd Flash Output
UL 1971 Strobe 15 cd 30 cd Wall 60 cd Wall 15 cd Wall 110 cd Wall Flash Output (Wall Mount Only) 15 cd Ceiling 30 cd Ceiling 15 cd Ceiling 60 cd Ceiling
Operating Voltage 20 to 24V DC Continuous (Non-pulsed)
Avg. Operating 70 mA @ 24V DC 105 mA @ 24V DC 160 mA @ 24V DC 105 mA @ 24V DC 219 mA @ 24V DC Current (1,4) 79 mA @ 20V DC 125 mA @ 20V DC 190 mA @ 20V DC 125 mA @ 20V DC 272 mA @ 20V DC
Peak Operating 125 mA @ 20V DC 185 mA @ 20V DC 240 mA @ 20V DC 185 mA @ 20V DC 340 mA @ 20V DC Current (1,3)
Avg. Operating 60 mA @ 24V DC 90 mA @ 24V DC 130 mA @ 24V DC 90 mA @ 24V DC 190 mA @ 24V DC Current (2) 70 mA @ 20V DC 102 mA @ 20V DC 155 mA @ 20V DC 102 mA @ 20V DC 235 mA @ 20V DC
Peak Operating 375 mA @ 20V DC 530 mA @ 20V DC 700 mA @ 20V DC 530 mA @ 20V DC 910 mA @ 20V DC Current (2,3)
Peak Inrush 7.6 A @ 24V DC 7.6 A @ 24V DC 7.6 A @ 24V DC 7.6 A @ 24V DC 7.8 A @ 24V DC Current (4)
Strobe Flash Rate Synchronized at 1 flash per second (no external control module required)
Message
Centers &
Annunciators
Signals
Outdoor
Warning
Electric
Chimes
Contactors
Push Buttons
Door Devices
Transformers
Fire Alarm
Equipment
Strobe Lens Clear Lexan
Wire Connection Terminals, Polarized Input, #12 AWG
Lens Markings Red "FIRE" Vertical Both Sides (Wall Mount)
Faceplate Material Textured Color-Impregnated Noryl (Exceeds 94V-0 UL Flammability Rating)
Mounting Flush: 1-Gang (2" Deep Min.) Standard Electrical Box
Surface: 1-Gang Wiremold Box
Operating 85% Relative Humidity @ 86°F (30C); 32° to 120°F (0° to 49°C) Variable Ambient Temp. Environment
Agency Listing UL 1971, UL 1638 and UL 464
(All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule)
The 2440S & 2441S strobes are available with either a red faceplate or a white faceplate; for a red faceplate, put an "R" in this position
and for a white faceplate, put a "W" in this position.
Note 1: Connected to filtered DC source. Note 2: Connected to unfiltered DC source (full wave rectified) Note 3: Use the peak current rating to establish the maximum number of strobes, wire gauge and standby power requirements. Consult
the panel manufacturer to determine the maximum number of strobes for each signaling circuit.
Note 4: Peak inrush current at 24V DC for less than 50 microseconds.
12-24
Fax-on-Demand # 1170