Edwards Signaling 2400 User Manual

Installation Instructions &
Owner’s Operation Manual
for Two to Eight Zone
2400 Series
Fire Alarm Control Panels
P/N 46000-1320, Rev . 1.6
© Edwards
FCC WARNING: This equipment can generate and r adiate radio frequency energy. If this equipment is not installed in accordance with this manual, it may cause interference to radio communications. This equipment has been t est ed and found to comply within the limits for Class A computing devices pursuant to Subpart J of part 15 of the FCC Rules. These rules ar e designed to provide reasonable protection against such int er ference when this equipment is operated in a commercial environment. Oper at ion of this equipment in a residential environment is likely to cause interference, in which case the user at his own expense, will be required to take whatever measures may be required to correct t he interference.
CAUTION
1. Read and thoroughly understand this manual befor e pr oceeding to install and operate the control panel.
2. To ensure proper operation of t h e cont r ol of the panel, only those initiating, signaling, and other devices whose compatibility with the panel has been established by Underwriters Laboratories may be connected to the control panel. Refer to the compatability inform ation supplement supplied with the panel for a complete list of compatible devices.
3. Test all installation wiring for opens, short s or grounds and correct any fault found before connecting wiring to the control panel.
4. Do not connect AC or battery power until indicated.
5. Servicing of the control panel must be per formed by qualified fire alarm service technicians only.
i
FCC Information
1. The dialer complies with Part 68 of the FCC rules. The Dialer’ FCC registration number and the Ringer
Equivalence Number (REN) are on the back of the dialer. This information must be provided to the telephone company, if requested.
2. An FCC compliant telephone cord and modular plug cord is supplied with the dialer. The dialer is designed to be
connected to the telephone network using the supplied cord and an RJ31X or RJ38X jack, which must also comply with FCC Part 68 rules.
3. The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive
RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of RENs should not exceed five (5). To be certain the number of devices that may be connected to a line, as determined by the total RENs, contact the local telephone company.
5. If the dialer causes harm to the telephone network, the telephone company will notify you in advance that
temporary discontinuance of service may be required. If advance notice isn’t practical, the telephone company will notify you as soon as possible. You will also be advised of your right to file a complaint with the FCC, if you believe it is necessary.
6. The telephone company may make changes in it’s facilities, equipment, operations, or procedures that could
affect the operation of the dialer. If this happens, the telephone company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service.
7. If trouble is experienced with the dialer, for repair or warranty information, contact Edwards Co. 90 Fieldstone
Court, Cheshire, Ct 06410-1212 Telephone: 1-203-699-3000. If the dialer is causing harm to the telephone network, the telephone company may request you disconnect the dialer until the problem is resolved.
8. No repairs may be performed on the dialer by the user.
9. The dialer cannot be used on public coin phone or party line service provided by the telephone company.
CANADA DOC Information
NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational,
and safety requirements. The Department does not guarantee the equipment will operate to the user’s satisfaction
Before installing this equipment, users should ensure that is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines, and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate
NOTICE: The Load Number (LN) assigned to each terminal device denotes the percentage of the total load to be connected to a telephone loop which is used by the device, to prevent overloading. The termination on a loop may consist of any combination of devices subject only to the requirements that the sum of the Load Numbers of all the devices does not exceed 100.
ii
FOR TECHNICAL ASSISTANCE PLEASE CALL YOUR LOCAL REPRESENTATIVE
LISTED ON THE FOLLOWING PAGE.
Effectivity Page for P/N 46000-1320, Edwards 2400 Manual
Revision Description
0.0 Initial Release
0.1 Editorial Corrections
0.2 Add 2400-ADM, 2400 -ADS, & 2400-RTU Module Information
1.0 Renamed Table 2.1 to Table 1.1. Add Table 1.2. Correct Cat. # 2245 to 2445.
1.3 Revise part numbers; Delete Table 5.9; Add Table 10.11
1.4 Add Battery Box & revise battery tables; Revise 4-wire EOL Relay; Add Auxiliary Power note; Revise RCT; d elete remote station from RCT module; Add 2400-DL1 Dialer Module; Revise 2400-ADMM supervisory operation; add additional replacement parts.
1.5 Revised dialer and compatibility information
1.6 Editorial corrections. Revised: Dialer Information. Added programming warning.
iii
Table of Contents
1.0 DESCRIPTION
1.1 Components.....................................................................................................2
................................................................................................. 1-4
2.0 APPLICATION......................................................................................................5
2.1 Fire Alarm System Limitations..........................................................................5
3.0 THEORY OF OPERATION........................................................................... 5-8
3.1 Initiating Device Circuits (IDCs)........................................................................5
3.2 Indicating Appliance Circuits (IACs).................................................................8
4.0 INSTALLATION.............................................................................................. 9-15
4.1 Codes and Standards.......................................................................................9
4.2 Site Storage......................................................................................................9
4.3 Drawing References.........................................................................................9
4.4 Installation Instructions...................................................................................10
5.0 PROGRAMMING......................................................................................... 16-20
5.1 Programming Initiating Device Circuits (IDCs)...............................................17
5.2 Programming Indicating Appliance Circuits (IACs).........................................18
5.3 Configuring System Timers............................................................................19
5.4 Programming Auxiliary Power........................................................................19
5.5 Returning to Panel Default Settings...............................................................20
5.6 Dialer Module.................................................................................................20
6.0 OPERATION..................................................................................................22-26
Normal Mode............................................................................................................22
Alarm Mode..............................................................................................................22
Reset Mode..............................................................................................................23
Trouble Mode...........................................................................................................23
Supervisory Mode....................................................................................................24
Drill Mode.................................................................................................................24
IDC Zone Disable.....................................................................................................24
Test Mode................................................................................................................25
Dialer Module...........................................................................................................26
Remote Trouble Unit................................................................................................26
7.0 TROUBLESHOOTING.....................................................................................27
iv
8.0 PREVENTIVE MAINTENANCE
8.1 Preventive Maintenance Schedule ................................................................29
8.2 Testing Procedures for the Dialer Module .....................................................31
8.3 Testing Procedures for Compatible 2-Wire Smoke Detectors....................... 31
8.4 Replacement Parts........................................................................................ 32
...............................................................29-32
9.0 SPECIFICATIONS.......................................................................................33-36
10.0 APPENDICES.............................................................................. 37-59
10.1 Appendix 1 - Battery Calculations.................................................................. 37
Using the Battery Tables ...............................................................................40
Example #1....................................................................................................41
Example #2....................................................................................................42
Battery Calculation Worksheets..................................................................... 43
Example #3....................................................................................................44
Example #4....................................................................................................45
10.2 Appendix 2 - Compatible Devices.................................................................. 46
ULI Compatibility Listings...............................................................................46
ULC Compatibility Listings.............................................................................49
10.3 Appendix 3 - Glossary ...................................................................................53
10.4 Appendix 4 - Standards Relevant to the Installation of this Product.............. 55
10.5 Appendix 5 - Fire Alarm Trouble & Maintenance Log....................................56
10.6 Appendix 6 - Panel Configuration & Programming Worksheet...................... 57
v
List of Tables, Figures, & Illustrations
Table 1.1 Base Panel Capacity................................................................................. 2
Table 1.2 2400-RCT Battery Standby Requirements ............................................... 3
Table 3.1 IDC Operation........................................................................................... 5
Table 4.1 Drawing References ................................................................................. 9
Table 5.1 Programmable Features ......................................................................... 16
Table 5.2 Programming Step Indications................................................................ 17
Table 5.3 IDC Zone Type Codes............................................................................ 17
Table 5.4 Panel Indicating Appliance Circuit Status ............................................... 18
Table 5.5 IAC Signal Output Rates......................................................................... 18
Table 5.6 Alarm Silence Inhibit Timer Status.......................................................... 19
Table 5.7 Automatic Alarm Silence Timer Status.................................................... 19
Table 5.8 Auxiliary Power on Reset Status............................................................. 19
Table 6.1 Front Panel Controls and Indicators........................................................ 22
Table 6.2 Test Mode............................................................................................... 25
Table 6.3 Dialer LED Indications............................................................................. 26
Table 7.1 Trouble LEDs.......................................................................................... 27
Table 7.2 Panel Trouble.......................................................................................... 27
Table 7.3 Dialer Module Trouble Codes ................................................................. 28
Table 8.1 Preventive Maintenance Schedule.......................................................... 29
Table 8.2 Related/Spare Parts................................................................................ 32
Table 9.1 Specifications
(Base Panel Assemblies, BPA)............................................................... 33
Table 9.2 Specifications
(2400-BPA Class A (Style D/Z) Converter Module)................................ 34
Table 9.3 Specifications
(2400-2IDC IDC Module)........................................................................ 34
Table 9.4 Specifications
(2400-IDCA IDC Class A (Style D) Zone Converter Module) ................. 34
Table 9.5 Specifications
(2400-RCT Relay/City-Tie Module)......................................................... 34
Table 9.6 Specifications
(2400-ADM Annunciator Driver Master Module)..................................... 35
Table 9.7 Specifications
(2400-ADS Annunciator Driver Slave Module)........................................ 35
Table 9.8 Specifications
(Remote Annunciators)........................................................................... 35
Table 9.9 Specifications
(2400-BATBOX) Battery Box .................................................................. 35
Table 9.10 Specifications
(2400-DL1) Dialer Module....................................................................... 36
Table 10.1 24 Hours Supervisory, 5 Minutes of Alarm.............................................. 37
Table 10.2 60 Hours Supervisory, 5 Minutes of Alarm.............................................. 38
Table 10.3 24 Hours Supervisory, 30 Minutes of Alarm............................................ 39
Table 10.4 ULI Control Unit Compatibility Specifications - Edwards......................... 46
Table 10.5 ULI Compatible Receivers for the 2400-DL1 Dialer................................ 46
Table 10.6 ULI Device & Panel Compatibility - Initiating Devices............................. 47
Table 10.7 ULI Compatibility Signaling Appliances................................................... 47
Table 10.8 ULI Compatibility Accessories................................................................. 48
Table 10.9 ULC Control Unit Compatibility Specification - Edwards......................... 49
Table 10.10 ULC Compatible Receivers for the 2400-DL1 Dialer .............................. 49
vi
Table 10.11 ULC Device & Panel Compatibility - Initiating Devices............................ 50
Table 10.12 ULC Compatible Signaling Appliances ................................................... 51
Table 10.13 ULC Compatible Accessories ................................................................. 51
Table 10.14 Mixed Ion/Photo Detector Maximum Devices per Circuit........................ 52
Figure 3.1 Unsustained Alarm Operation................................................................... 7
Figure 3.2 Verified Alarm Operation........................................................................... 7
Figure 3.3 IAC Signal Rates....................................................................................... 8
Drawing #1.......................................................
Drawing #2........................................................CONTROL PANEL INSTALLATION 2
Drawing #3.........................................................................................CONTROL PANEL
Drawing #4....................................................INITIATING DEVICE CIRCUIT WIRING
Drawing #5...........................................................................RELAY/CITY-TIE MODULE
Drawing #6.......................................................................................... DIALER MODULE
Drawing #7........................................................................ REMOTE ANNUNCIATORS
Drawing #8......................................................CONTROL PANEL APPLICATIONS 1
Drawing #9......................................................CONTROL PANEL APPLICATIONS 2
Drawing #10......................................................................... PANEL PROGRAMMING
Drawing #11................................................................................... PANEL OPERATION
Drawing #12................................................................................DIALER OPERATIONS
CONTROL PANEL INSTALLATION 1
vii
Fire Alarm Control Panel
Two Zone, Three Expansion Space Panel, Cat. # 2412(R)
Four Zone, Two Expansion Space Panel, Cat. # 2414(R)
Eight Zone, Six Expansion Space Panel, Cat. # 2418(R)
1.0 DESCRIPTION
The 2412, 2414, & 2418 Fire Alarm Control Panels are protective signaling systems which feature modular construction and installer programmable microprocessor technology.
m Panel Supervisory Features include: continuous internal testing; a CPU watchdog timer; and module
placement supervision.
m Operational Features include: alarm, supervisory, and trouble resound; fire drill mode; one man test
mode; lamp test; alarm silence inhibit; and automatic alarm silence.
m Programmable Options include: verified or non-verified alarm; waterflow with or without retard; and
supervisory Initiating Device Circuits (IDCs). Verified circuits support dry contact alarm initiating devices when used with high impedance smoke detectors. Indicating Appliance Circuits (IACs) may be programmed as silenceable or non-silenceable with continuous, March Time at 120 Strokes per Minute (SPM), California, or temporal rates (Figure 3.3). The temporal rate meets the requirements of the national emergency evacuation signal. Alarm silence/reset inhibit, automatic alarm silence, and off­premise AC/brownout 6 hr. trouble delay timers are provided. Resettable power for 4-wire smoke detectors is provided.
m Hardware Options include an 2400-RCT Relay/City-Tie Module with provisions for municipal box,
reverse polarity and dry relay contact operation. The 2400-BPA Class A Base Panel Converter is available to convert the IDC and IAC circuits on the Base panels to Class A (Style D) IDC and Class A (Style Z) IAC wiring. The 2400-IDCA Class A (Style D) IDC Converter is available to convert 2400­2IDC Two Zone IDC Modules to Class A (Style D) wiring. The 2400-DL1 Dialer Module provides a supervised connection to a Central Monitoring Station via dial-up telephone lines. The 2400-ADM Four Circuit Remote Anunciator Driver Master Module and the 2400-ADS Four Circuit Remote Annunciator Driver Slave Module are available to supervise and drive remote annunciation panels. All circuits external to the panel are transient protected. All circuits except the AC power wiring, municipal box, and relay contacts are power limited. Panel option module capacity is indicated in Table 2.1. The panels have steel enclosures with a textured baked enamel finish. The enclosure has a Lexan viewing window, key lock, and is suitable for semi-flush or surface mounting. Room is provided in the enclosure for standby batteries. Conduit and nail knockouts, and keyhole style mounting holes help support quick installation. An optional battery enclosure, model 2400-BATBOX (R), is available when 10 Amp-Hour batteries are required.
The panel is listed by ULI to standard UL 864 and ULC to standard ULC S527.
1
1.1 Components
2412 Two Zone Base Panel w/3 Option Module Expansion Spaces, Gray Enclosure (Cat.# 2412) Two Zone Base Panel w/3 Option Module Expansion Spaces, Red Enclosure (Cat.# 2412-R)
This panel provides two Class B (Style B) Initiating Device Circuits (IDCs) and two Class B (Style Y) Indicating Appliance Circuits (IACs). There is space for three option modules. Option modules include a Relay/City-Tie, Two Zone Initiating Device, a Dialer Module, and Remote Annunciator Driver Modules. Space for standby batteries is provided in the enclosure. Refer to the Appendix to select the proper battery for your application.
2414 Four Zone Base Panel w/2 Option Module Expansion Spaces, Gray Enclosure (Cat.# 2414) Four Zone Base Panel w/2 Option Module Expansion Spaces, Red Enclosure (Cat.# 2414-R)
This panel provides four Class B (Style B) Initiating Device Circuits (IDCs) and two Class B (Style Y) Indicating Appliance Circuits (IACs). There is space for two option modules. Option modules include a Relay/City-Tie, Two Zone Initiating Device, a Dialer Module, and Remote Annunciator Driver Modules. Space for standby batteries is provided in the enclosure. Refer to the Appendix to select the proper battery for your application.
2418 Eight Zone Base Panel w/3 Option Module Expansion Spaces, Gray enclosure (Cat.# 2418) Eight Zone Base Panel w/3 Option Module Expansion Spaces, Red enclosure (Cat.# 2418-R)
This panel provides eight Class B (Style B) Initiating Device Circuits (IDCs) and two Class B (Style Y) Indicating Appliance Circuits (IACs). There is space for three option modules. The available option modules include a Relay/City-Tie Module, a Dialer Module, and Remote Annunciator Driver Modules. Space for standby batteries is provided in the enclosure. Refer to the Appendix to select the proper battery for your application.
Table 1.1 - Base Panel Capacity
Base Panel
Accessory/Option
Module
Internal Batteries Two 12 V @ 4.5 AH
External Batteries 2400-BATBOX(R)
2 Zone Initiating Device Circuit
2400-2IDC (P/N 240457)
Relay/City-Tie Module
2400-RCT (P/N 240459)
Annunciator Driver Mast er
Module
2400-ADM (P/N 240461)
Dialer Module
2400-DL1 (P/N 240508)
Any Combination of 3, Max Any Combination of 2, Max
2412
Panel Capacity:
3 Option Modules
Two 12 V @ 6.5 AH
2 ea. P/N 12V10,
12 V @ 10 AH
2414
Panel Capacity:
2 Option Modules
Two 12 V @ 4.5 AH Two 12 V @ 6.5 AH
2400-BATBOX(R)
2 ea. P/N 12V10,
12 V @ 10 AH
2418
Panel Capacity:
3 Option Modules
Two 12 V @ 4.5 AH Two 12 V @ 6.5 AH
Four 6 V @ 8.0 AH
2400-BATBOX(R)
2 ea. P/N 12V10,
12 V @ 10 AH
0
Any Combination of 3, Max
2400-BPA Base Panel Class A (Style D/Z) Converter Module (P/N 46199-1072)
This Class A (Style D/Z) Base Panel Converter changes the base panel to Class A (Style D) Initiating Device Circuits and Class A (Style Z) Indicating Appliance Circuits. The Class A Base Panel Converter does NOT require any option module expansion spaces.
2
2400-2IDC Two Zone Initiating Device Circuit Module (P/N 240457)
This module provides two additional Class B (Style B) Initiating Device Circuits. Each circuit is provided with an
ENABLE/DISABLE switch and a tri-color LED. The module requires one option module expansion
space.
2400-IDCA Class A (Style D) IDC Converter Module (P/N 46199-1074)
This Class A (Style D) IDC Converter changes the two Class B (Style B) Initiating Device Circuits on a Two Zone Initiating Device Circuit Module to Class A (Style D) operation. The module does NOT require any option module expansion space.
2400-RCT Relay/City-Tie Module (P/N 240459)
The Relay/City-Tie Module is a configurable Normally-Open (N.O.) or Normally-Closed (N.C.) relay contact, which is configurable to operate on panel Alarm, Trouble, Supervisory, or Reset conditions. The Relay/City-Tie Module may be configured for, municipal box, reverse polarity, or dry contact operation. Relay contacts are rated for 24 VDC @ 1A. The module has a disconnect switch and an amber Trouble LED. The module requires one option module expansion space. Off premise power failure trouble signaling using this module has a 6 hour delay.
Table 1.2 - 2400-RCT Battery Standby Requirements
Feature 2412 2414 2418
Dialer Up to 60 Hrs. Up to 60 Hrs. Up to 60 Hrs.
Dry Contact (Shunt) Up to 60 Hrs. Up to 60 Hrs. Up to 60 Hrs.
Master Box Up to 60 Hrs. Up to 60 Hrs. Up to 60 Hrs.
Reverse Polarity Up to 60 Hrs. Up to 60 Hrs. Up to 60 Hrs.
NOTES:
1. Refer to battery calculations.
2. NFPA 72 requires 60 hours of stand by battery when connecting to an off premises monitoring location
DL1 Dialer (Digital Alarm Communicator Transmitter) (P/N 240508)
The DL1 dialer module is a Digital Alarm Communicator Transmitter (DACT) for transmitting alarm, supervisory and trouble information to a compatible Digital Alarm Communicator Receiver (DACR) via two dial-up telephone lines. The dialer supports 20 PPS 3/2 or 4/2 format for communicating between the panel and the DACR (see specifications). Both Dual Tone Multi Frequency (DTMF) and Pulse dialing are automatically supported. AC power failure reporting may be delayed. The dialer performs an automatic test call every 24 hours to verify communications between the fire alarm panel and the receiving equipment. Dialer module programming is performed with any standard tone dial(DTMF) telephone. All programming is password protected.
2400-ADM Four Circuit Annunciator Driver Master Module (P/N 240461)
The Four Circuit Remote Annunciator Driver Module is used to supervise and operate the connection to four individual alarm zone LEDs on a conventional zone annunciator. The -ADM is automatically configured for IDC zones 1 to 4. The Annunciator Driver Master Module requires one expansion module space in the enclosure.
3
2400-ADS Four Circuit Annunciator Driver Slave Module (P/N 240463)
The Four Circuit Remote Annunciator Driver Slave Module is used to supervise and operate the connection to four additional alarm zone LEDs on a conventional zone annunciator. The -ADS is automatically configured for IDC zones 5 to 8. The Remote Annunciator Driver Slave Module mounts on the 2400-ADM Master, module and does NOT require any expansion module space.
2400-RTU Remote Trouble Unit (P/N 46199-1076)
The 2400-RTU Remote Trouble Unit is a remote trouble annunciator which displays fire alarm normal and trouble conditions. The unit is provided with a power LED and an integral trouble buzzer. A trouble silence switch with ring-back is also provided.
2400-xZA Remote Zone Annunciators
The 2400-xZA Remote Zone Annunciators duplicate the control panels individual zone alarm LEDs at a location remote from the control panel. Model 2400-4ZA provides 4 zone LEDS, model 2400-8ZA provides 8 zone LEDs.
2400-RTUxZA Combination Remote Annunciators
The 2400-RTUxZA Remote Annunciators combine the features of the 2400-RTU and the 2400-xZA annunciators in a single package. Model 2400-RTU4ZA provides remote trouble annunciation and 4 zone LEDS, model 2400-RTU8ZA provides remote trouble annunciation and 8 zone LEDs.
Batteries are available in a variety of sizes to meet the 24 and 60 hour standby requirements, followed by 5 or 30 minutes in alarm. Table 1.1 shows the batteries suitable for each panel. Appendix 1 provides information on battery sizing.
4
2.0 APPLICATION
The 2412, 2414, and 2418 panels are suitable for small to medium size buildings, requiring from two to eight Initiating Device Circuits (IDCs), and two Indicating Appliance Circuits (IACs).
2.1 Fire Alarm System Limitations
Fire Alarm Systems provide the occupants of a facility with early warning of smoke and fire conditions. Fire alarm systems use a variety of components to meet the requirements of each installation. The fire alarm panel, automatic and manual detection devices, alarm annunciators, and the installation wiring are all factors in a reliable system. To maintain proper operation, fire codes require, and this manufacturer recommends preventive maintenance and testing on a routine basis by qualified personnel.
3.0 THEORY OF OPERATION
3.1 Initiating Device Circuits (IDCs)
The supervised IDCs operate with compatible smoke detectors (refer to Appendix) and normally-open alarm initiating devices. An IDC may be programmed as an Alarm, Waterflow/Supervisory, or Supervisory zone. Alarm zones may have verified or non-verified operation. Waterflow/Supervisory zones programmed with or without a 15 second retard period, also support a single supervisory input device with a
Wseries resistor. IDC circuits may take one of four operating states: Normal, Trouble, Alert, or Alarm.
1.1K Table 3.1 defines the states for the various IDC zone types.
Table 3.1 - IDC Operation
State of Operation
Zone Type Alarm
(Low Impedance)
Non-Verified
Alarm Zone
Verified Alarm Zone
with high impedance smoke detectors and N.O. contact devic es
Verified Alarm Zone
with smoke detectors
only
Waterflow/Supervisory
Zone
Waterflow/Supervisory
Zone with Retard
Supervisory Zone Supervisory Condition Supervisory Condition Normal Operation Trouble
Alarm after 15 seconds S upervisory Condition Normal Operation Trouble
Alarm Alarm Normal Operation Trouble
Alarm Verifying the Alarm Normal Operation Trouble
Verifying the Alarm Verifying the Alarm Normal Operation Trouble
Alarm Supervisory Condition Normal Operation T roubl e
(High Impedance)
Alert
Normal Open
WARNING! Do NOT put contact devices on Low Impedance Verified Circuits.
An active IDC defined as an Alarm or Waterflow Zone may be identified by a steady red zone LED. Active IDCs defined as supervisory zones may be identified by a rapid flashing amber zone LED.
5
When an IDC is programmed as a waterflow zone, the IACs DO NOT respond to the ALARM SIL ENCE switch or automatic alarm silence until the waterflow device is no longer active. Both an alarm initiating device and a supervisory contact may co-exist on the same circuit by putting a 1.1K supervisory contact. When the waterflow with retard option is programmed, a special algorithm samples the circuit repeatedly. If 66% of the samples taken in any 15 second period indicate a waterflow (shorted) condition, the circuit activates a waterflow alarm.
When an IDC is programmed as a verified zone and a smoke alarm is detected, the panel enters the Alarm Verification state. A twenty five second sequence in which the detector is reset, delayed, and restarted is initiated, as shown in Figure 3.1. If auxiliary power is programmed as resettable, it is de­energized for the reset period. Following the reset-delay-restart sequence, a 60 second verification window is opened. If the verifying zone should go into the Alert, Alarm, or Trouble conditions within the 60 second window as shown in Figure 3.2, the panel enters the alarm mode. If any other IDC on the panel goes into the alert or alarm state during the verification period, the panel immediately enters the alarm mode. Dry contact alarm initiating devices may be combined with High Impedance 2-wire smoke detectors on verified zones. The closing of a normally open dry contact alarm initiating device generates an Alarm state immediately, and the panel enters the alarm mode.
Initiating Device Circuit, Class A (Style D) Operation
To convert a Class B (Style B) IDC zone to a Class A (Style D) IDC zone, install a 2400-BPA Class A
in series with the
NOTE
2- Wire Relay Bases are NOT supported on Initiating Device Circuits (IDCs).
(Style D/Z) Converter on the base panel, or a 2400-IDCA Class A (Style D) Converter on the Two Zone IDC Module. The converters provides an alternate path to the zone module for all Initiating Devices in the event of a single wire break in an IDC.
6
Figure 3.1 - Unsustained Alarm Operation
Figure 3.2 - Verified Alarm Operation
7
3.2 Indicating Appliance Circuits (IACs)
Two supervised Indicating Appliance Circuits (IACs) operate using compatible 24 VDC (nominal) polarized signaling appliances. Each circuit is rated at nominal 24 VDC @ 2.5 Amps, with a total of 4.0 Amps available for both circuits. An IAC may be programmed as either silenceable or non-silenceable. Signal rate selection is independently programmable for each IAC as shown in Figure 3.3. Refer to the Appendix for compatible Indicating Appliances.
Figure 3.3 - IAC Signal Rates
IACs generate a trouble indication (slow flashing LED) when field wiring is open or shorted. In an open fault condition, the panel will attempt to energize the signal appliances (i.e., all appliances up to the circuit break will operate). An IAC with shorted field wiring will NOT operate in the event of an alarm. If an IAC develops a short during an alarm, the IAC will automatically shut off and continuously monitor the field wiring. When the fault is cleared, the IAC will re-energize. These actions protect the power supply and other panel components from damage caused by the short circuit.
Indicating Appliance Circuit, Class A (Style Z) Operation
To convert Class B IAC zones to Class A (Style Z) IAC zones, install a 2400-BPA Class A (Style D/Z) Converter Module on the base panel. The converter provides alternate paths to the base panel for both Indicating Appliance Circuits in the event of a single wire break in an IAC.
8
4.0 INSTALLATION
4.1 Codes and Standards
Install this panel in accordance with all applicable codes and standards to the satisfaction of the Authority Having Jurisdiction (AHJ). A partial list of codes and standards appears in the Appendix.
US Installations: For Class B (Style B/Y) circuits, the End-Of-Line resistor is installed on the last device. Canadian Installations: For Class B (Style B/Y) circuits, purchase End-Of-Line resistor plates separately
from your Distributor. Use the specified resistors and install in a separate electrical box in an accessible location beyond the last device on a circuit.
4.2 Site Storage
Remove backbox from top of carton. Place extra modules in panel carton and store safely in a dry location during rough-in, to avoid damage to electronic parts.
4.3 Drawing References
Table 4.1 lists the drawings that are included at the end of this manual.
Table 4.1 - Drawing References
Subject Drawing Title
Assembly Details Ribbon Connectors Battery Interconnec t Base Panel Circuits IAC Wiring Diagram IAC Wire Chart Initiating Device Circuits IDC Wire Chart 2IDC Two Zone Initiating Devic e Ci rcuit Module INITIATING DEVICE CIRCUIT WIR IN G
Relay/City-Tie Module Applications. Connections and Jumper Sett i ngs
Remote Annunciators & Annunciator Driver Modules REMOTE ANNUNCIATORS 4-Wire Smoke Detectors Control Panel A p plications 2 Class A Wiring CONTROL PANEL
Panel Programming Instruc t i ons Panel Programming Panel Operations Panel Operatio n
Control Panel Inst allation 1 Control Panel Inst allation 2
Control Panel
Initiating Device Circuit Wirin g
or see the Installation S heet supplied with the Two Zone IDC Module
Relay/City Tie Module Control Panel A p plications 1
or see the Installation S heet supplied with the Relay/City-Tie Module
INITIATING DEVICE CIRCUIT WIRING
or see the Installation S heets supplied with the BPA Base Panel Class A Conv erter Module & IDCA, 2IDC Module Class A Converter
9
4.4 Installation Instructions
Mounting the Backbox
Install backbox per drawings Control Panel INSTALLATION 1 and Control Panel INSTALLATION 2. If a 2400- BATBOX Battery Cabinet is required, refer to the CONTROL PANEL APPLICATIONS 2 drawing for information.
Utility or Primary Power Circuit
NOTE
Install primary power conduit on lower left side or left bottom of backbox.
The panel requires a dedicated 120 VAC, 15A, 50/60 Hz branch circuit. Label the circuit breaker "Fire Alarm Control Panel." Within the fire alarm enclosure, route wire away from power limited circuit wiring.
WARNING
Do NOT apply power at this time.
System Control Wiring
1. Refer to the drawings at the end of this manual for circuit wiring diagrams and wire charts showing maximum wire runs and loading. Install system wiring using the wire type and gauge per the Authority Having Jurisdiction. Locate field wiring conduit on the upper sides and top of the backbox. At the panel, leave approximately 5’ (1.5 m) of wire available for dressing and termination. Pair and label wires according to zone and function. Do not mix power limited and non-power limited wiring in the same conduit.
2. Do not remove the factory installed test resistors from the panel at this time. The test resistors are used for panel testing in the next steps. Refer to the drawings provided with each initiating and signaling device for installation details. Install End-Of-Line resistors at the end of Class B circuits.
3. Use an ohm meter to check circuit continuity and verify that the wiring is free of shorts and ground faults, as follows:
Class B (Style B) IDC meter readings should show 4.7K Each wire should show an open to ground.
Class A (Style D) IDC meter readings should show a short between each set of outgoing and incoming wires, and an open between each side of the circuit.
Class B (Style Y) IAC meter readings should show 4.7K one direction and a short (polarized signals conducting) with the meter leads reversed. Each wire should show open to ground.
Class A (Style Z) IAC meter readings should show a short between each set of outgoing and incoming wires. Readings should show an open in one direction and a short (polarized signals conducting) with the meter leads reversed between each side of the circuit.
(EOL Resistor) between circuit pairs.
(EOL Resistor) between circuit pair in
10
Base Panel Assembly
CAUTION
The electronic components used in this system are sensitive to static electricity. Always
discharge any static buildup on your body by touching the panel enclosure before
handling any electronic components.
WARNING
The System Power Supply (the printed circuit board on the back of the Base Panel
Assembly) handles 170 VDC when powered. DO NOT handle this board with power on.
1. Remove the Base Panel Assembly from its anti-static carton.
2. Remove and place the anti-static foam packing on a flat work area.
3. Place the Base Panel Assembly Display face down on the foam packing. Leave the factory end-of-line
resistors in place on the base panel and expansion modules until making final connections.
Option Module Installation If your system requires no optional expansion modules, skip to the section entitled Base Panel Assembly Installation.
1. Refer to the CONTROL PANEL INSTALLATION 1 and CONTROL PANEL INSTALLATION 2 drawings.
2. Remove the Power Supply from the Base Panel Assembly to allow for first module installation.
3. Install Expansion Modules on the Base Panel Assembly from left to right (front view) starting with IDC Modules, Remote Annunciator Driver Modules, then the Relay/City-Tie Modules. Before installing
the ADM & ADS Annunciator Driver Modules, verify that all jumpers are installed. Before installing the RCT Relay/City-Tie Modules, verify that jumpers 1 & 2 are installed. Refer to RELAY/CITY-TIE & REMOTE ANNUNCIATOR drawings for additional jumper information.
NOTE
The Dialer Module MUST be installed in position number 3 or higher to prevent
mechanical interference with other system components.
Do NOT connect the Dialer Modules ribbon cable to the adjacent module until the rest of the system has been installed and tested.
4. Insert all ribbon connectors (except the Dialer Module) into the adjacent socket, and re-install the Power Supply on the back of the Base Panel Assembly. The Dialer Module will be connected later.
5. For Class A (Style D/Z) circuits, install the 2400-BPA Class A Converter modules on the back of the Base Panel Board and 2400-IDCA on the back of the IDC Expansion Modules. Refer to CONTROL PANEL INSTALLATION 1, CONTROL PANEL INSTALLATION 2, and INITIATING DEVICE CIRCUIT drawings.
Base Panel Assembly Installation
11
1. Refer to the CONTROL PANEL INSTALLATION 1 or CONTROL PANEL INSTALLATION 2 drawings. If a 2400-BATBOX Battery Cabinet is required, refer to the CONTROL PANEL APPLICATIONS 2 drawing for information.
2. Lift wiring up and away from the backbox, and install the Base Panel Assembly using the four quick fasteners. Do not connect control circuit wiring at this time.
3. Install the panel door and make the ground connection (green wire) from the power supply to the middle door mounting stud.
WARNING
Batteries can deliver extremely high currents. To prevent serious burns caused by short
circuiting the battery, remove all jewelry before handling.
4. Place the batteries in the lower right area of the backbox. If using the external battery cabinet, put the batteries in the battery cabinet.
5. Interconnect the cells per the CONTROL PANEL INSTALLATION 1 or CONTROL PANEL INSTALLATION 2 drawings. If a Battery Cabinet is being used, refer to the CONTROL PANEL APPLICATIONS 2 drawing for information. Connect panel battery leads at this time. Observe polarity: Red =
positive (+); Black = negative (-)
CAUTION
Observe polarity. Red is positive(+), Black is negative(-). A non-replaceable fuse
protects the system from damage caused by a reversed battery connection.
Power Up
1. Verify that all factory installed end-of-line resistors are still in place, all -ADM & -ADS module jumpers are all installed, and -RCT module jumpers 1 & 2 are installed.
2. Connect primary power wires: Line, Neutral, and Ground to the input terminals of the power supply.
3. Energize AC power to the system. When you first apply power to the system it will follow an
initialization procedure. This procedure programs all connected IDCs as non-verified alarm inputs and identifies the configuration of all output modules (it can take up to 15 seconds). You will see zone LEDs turning on and off in sequence and communication LEDs (lower edge of expansion module boards) flashing. Allow the system to complete this procedure before touching any controls. At the end of the process, all LEDs except the Power On LED should be off. If the system trouble LED is on and the trouble signal is sounding, refer to the trouble shooting procedures in this manual. If module LEDs remain on steady, refer to the Programming section for additional information.
4 Install the lower protective plastic barrier over the high voltage terminals. Make sure to install this
cover strip. It protects you from the high voltage input terminals and traces on the power supply printed circuit board.
Programming the Panel
1. Remove the Common Control insert card, reverse it, and then return it to its panel location. The Common Control switches are now labeled for programming functions.
2. Refer to Table 5.1 for panel default operations and the PANEL PROGRAMMING drawing for programming information. For Dialer Module programming, refer to the DIALER MODULE drawing
12
3. Fill-in the Panel Configuration & Programming Worksheets (located in the Appendix) and program the panel for the desired operation. Save the Panel Configuration Worksheets for future reference.
4. Remove, label, and re-insert the IDC, Relay/City-Tie, and Anunciator Driver Module insert cards. Use the Panel Configuration Worksheets in this manual to assist in labeling. Reverse the Base Panel insert card to display Fire Alarm Control functions.
Panel Function Testing
1. Test panel operations by shorting (Alarm) or opening (Trouble) the factory installed End-Of-Line resistors.
2. To activate IDC circuits which combine high impedance smoke detectors and contact devices, or supervisory signal operation of a waterflow/supervisory circuit, use a 1.2K End-Of-Line resistor.
3. Remove the End-Of-Line resistor to verify proper trouble response.
4. Reset the panel, allowing 20 seconds for the panel to return to normal.
IDC & IAC Field Wiring Connections
1. Refer to the CONTROL PANEL INSTALLATION, initiating device circuit wiring, control panel applications 1, & control panel applications 2 drawings for wiring details.
2. Dress all wires to allow "hinging" the Base Panel Assembly on the left by dressing your connections from right to left. This allows you to rotate the Base Panel Assembly out of the enclosure for access to system modules, facilitating additions or changes.
3. Leaving the system powered up, install the IDC & IAC circuits one at a time. The system will go into Trouble mode. Remember to remove the factory installed End-of-Line resistor from the panel or module terminals.)
4. Use the
5. Connect the appropriate field wiring, observing circuit polarity. If the wiring is correct, the trouble condition will clear (Trouble LED and amber Zone LED turn off).
TROUBLE SILENCE switch to silence the Trouble signal.
Wresistor in parallel with the
2400-DL1 Dialer Panel and Field Wiring Connections
To eliminate excessive calls to the Central Monitoring Station, the Dialer Module panel connection (ribbon cable) and programming should be performed after the balance of the panel has been tested and verified operational.
1. Verify the Central Monitoring Station (CMS) is properly programmed and ready for connection.
2. Refer to the
3a. Dress all wiring to allow "hinging" the Base Panel Assembly on the right by dressing your connections
from right to left. This allows you to rotate the Base Panel Assembly out of the enclosure for access to system modules, facilitating additions or changes.
3b. Fasten the dialer module to the panel assembly with the screws and standoffs provided. 3c. Fasten the bus interface adapter to the rear of the dialer, using the screws provided. 3d. Connect the ribbon cable to the next module in line. The system and dialer module will indicate trouble
conditions.
4a. Set the panels program switch to program mode (UP), and push the RESET switch. 4b. Wait for the Power LED to flash, then return the program switch to normal mode (down). This process
installs the Dialer Module in the panels data base. The panel will remain in trouble until the dialer is properly wired and programmed.
DIALER drawing and DACR technical manual for wiring and programming details.
CAUTION
13
The telephone jacks must be installed by an authorized representative of the telephone company. Phone lines must be loop start on the public switched network. PBX, ground start, and party lines are not acceptable
5. Using the supplied 7Ft. (2.13 M) phone jack extension cables, connect J1 & J2 to the RJ31X, or RJ38X (CA31A or CA38A in Canada) telephone jacks. A protective grommet is supplied for the enclosure knockout. The telephone jacks must be installed by an authorized representative of the telephone company. The phone lines must be loop start on the public switched network. PBX, ground start, and party lines are not acceptable.
6. With system powered up, program the dialer as shown in the drawing. A new dialer module will remain in disabled until completely programmed. Use the TROUBLE SILENCE switch to silence the Trouble signal.
7. If the telephone lines are wired properly and the panel is programmed correctly, the trouble condition will clear (panel and module trouble LEDs turn off), when the dialer is enabled.
8. Activate and open all IDCs and IACs, verifying proper reception at the CMS.
9. Verify that failure of the primary signal path (phone line connected to J1) results in a trouble signal being transmitted via the secondary signal path (phone line connected to J2) within 4 minutes.
10. Verify that failure of the secondary signal path (phone line connected to J2) results in a trouble signal being transmitted via the primary signal path (phone line connected to J1) within 4 minutes.
NOTE
If a DL1 Dialer Module is installed, it will introduce a panel trouble until programmed.
NOTE
The Dialer Module will be disabled, with the LED double flashing amber until both
phone numbers and both site ID numbers are set. Pressing the disconnect switch will
have no effect.
WARNING
The DL1 Dialer Module requires separate programming in order to operate.
Refer to the DIALER MODULE Drawing.
14
2400-ADM & 2400-ADS Field Wiring Connections
1. Refer to the REMOTE ANUNCIATOR drawing for wiring details.
2. Dress all wires to allow "hinging" the Base Panel Assembly on the left by dressing your connections from right to left. This allows you to rotate the Base Panel Assembly out of the enclosure for access to system modules, facilitating additions or changes.
3. Leaving the system powered up, connect the (+)24 VDC wire from the annunciator to the (+) Auxiliary Power terminal.
4. Connect the NO (Normally Open) and NC (Normally Closed) wires from the annunciator to the NO and NC trouble relay contacts on the control panel. Install a jumper between the trouble relay common terminal and the (-) Auxiliary Power terminal.
5. Install all supervision jumpers
6. Connect the ADM & ADS LED circuits one at a time by removing the corresponding supervision jumper.
7. Use the
TROUBLE SILENCE switch to silence the Trouble signal.
8. Connect the appropriate field LED wiring. If the wiring is correct, the trouble condition will clear (Trouble LED and amber Zone LED turn off).
2400-RCT Field Wiring Connections
1. Refer to the RELAY/ CITY-TIE drawing and receiving station technical manual for wiring details.
2. Dress all wires to allow "hinging" the Base Panel Assembly on the left by dressing your connections from right to left. This allows you to rotate the Base Panel Assembly out of the enclosure for access to system modules, facilitating additions or changes.
3. Use the
TROUBLE SILENCE switch to silence the Trouble signal, if sounding.
4. Connect the appropriate field wiring, observing circuit polarity. If the supervised wiring is correct, the trouble condition will clear (Trouble LED and amber Zone LED turn off).
Field Wiring Trouble (Also refer to Troubleshooting)
1. Clear any wiring faults as you install the field wiring. When a fault on a Class B circuit is cleared, the panel will automatically return to the Normal mode. When a fault on a Class A circuit is cleared, the panel must be manually reset to return it to the Normal mode.
2. If an IAC is shorted (or a signal appliance connection is reversed) or open, the circuit will continue to display trouble. If an IAC has a ground fault, the trouble signal will resound and the Ground Fault LED will turn on. If an IDC has a short, the zone LED will change to red and the system will go into Alarm mode (delayed 25 seconds if the circuit is programmed as a Low Impedance verified smoke detector circuit). If an IDC has a ground fault, the trouble signal will resound and the Ground Fault LED will turn on.
3. Continue to complete supervised circuit connections one at a time using the panel to verify proper wiring.
4. Connect ancillary circuits and remote monitoring and remote annunciator circuits per installation drawings in this manual.
5. Test each circuit for proper function by putting the system into Alarm, Supervisory, or Trouble modes. Refer to Operating the Panel for a description of testing procedures.
15
5.0 PROGRAMMING
Panel Configuration Worksheets may be found at the end of this manual. These worksheets should be filled out prior to programming the panel, and saved with this manual should further programming be required at a later date. Refer to the
PANEL PROGRAMMING drawing during the programming process.
The reverse side of the base panel identification labels are programming templates. Remove, reverse, and re-insert the template labels as a programming aid. Dialer programming is covered in section 5.6.
CAUTION
The panel MUST be reprogrammed whenever permanently adding (or removing) option
modules to (from) the system. Replacing a module with another module of the same type does
NOT require reprogramming.
DO NOT DISCONNECT AC POWER WHI L E IN THE PROGRAMMING MO DE!
The panel is shipped from the factory with the default configuration denoted by in Table 5.1. The panel defaults may be re-programmed any time during the programming sequence by simultaneously pressing the
TROUBLE SILENCE and RESET switches for one second, which also returns you to the start of the
programming process. The programming step (of the panel being programmed) is indicated by the flash phase of the green Power LED. The program variable and flash phase is indicated in Table 5.2.
Table 5.1 - Programmable Features
= Default
Initiating Device Circuit (IDC)
1 Non-Verified Alarm 2 Verified High Impedance Detec tor w/Contact Device (See Not e) 3 Verified Low Impedance Detector Only 4 Supervisory 5 Waterflow & Supervisory 6 Waterflow w/retard & Supervi sory
Indicating Appliance Circuit (IAC)
1 Affected by Alarm Si l ence Features 2 Not affected by Alarm S i l ence Features
IAC Signal Rates
1 Continuous 2 March Time @ 120 SPM 3 Temporal 3-3-3 4 Continuous ON for 10 Seconds., 5 S econds. OFF 5 March Time ON for 10 Seconds., 5 Seconds. OFF
Alarm Silence Inhibit Timer
1 No Timer 2 One Minute Inhibit 3 Two Minute Inhibit 4 Three Minute Inhibit
Automatic Signal Silence Timer
1 No Timer 2 10 Minutes to Silence 3 20 Minutes to Silence 4 30 Minutes to Silence
Auxiliary Power Reset
1 Auxiliary Power NOT Reset 2 Auxiliary Power Reset
NOTE: Do Not use this option. High Impedance detectors are not presently available.
16
Loading...
+ 55 hidden pages