Edwards Signaling 215-F6 User Manual

Page 1
www.ge-security.com/industrial
Warning! To avoid switch failure determine the actual load of the switch circuit and take steps to protect the switch from voltage spikes, current inrush and line/load capacitance using the following recommendations. If the installation instructions are not followed carefully, the switch may not work properly or fulfill its failsafe function, or it may fail prematurely.
1. Surges from coils, motors, contactors, solenoids and tungsten filaments must be considered.
2. Transient protection, such as back-to-back zener diodes (Transorb) or an RC network, is recommended for such loads to ensure that maximum ratings of the switch are not exceeded.
3. Line capacitance and load capacitance must be considered. An in-line resistor can be added to limit the inrush current.
4. The resistor can only be added in series with the last red wire just before the load.
5. The voltage drop and the power rating of the resistor must be considered.
Voltage drop = I • R
2
Watts = I ( I = maximum continuous current of the load)
• R
GuardSwitch™ Series 200
Patented Non-Contact Safety Interlock Switch
215-F6Y-16J 115-Y
215-F6
215-F6Y-06J 215-F6Y-12J
Dimensions
0.31"
0.79cm
0.63"
1.60cm
Figure 1
0.41"
1.04cm
0.22"
0.56cm
0.18"
0.46cm dia.
sensing face
sensing face
6.45cm
4.39cm
5.36cm
0.63"
1.60cm
2.54"
1.73"
2.11"
0.75"
1.91cm
0.19"
0.48cm
Installation
Use non-removable screws, bolts, or nuts to mount the switch and actuator. Do not over-torque mounting hardware.
2. Select a mounting location where the switch and actuator can be installed with their labels reading in the same direction. (See Figure 1.)
3. Mount the switch on the stationary frame of the machine and the actuator on the moveable guard, door or gate.
4. For best protection against operator defeat, mount with non-removeable screws, bolts, or nuts. (See accessories)
5. The switch and actuator must be mounted so that the actuator moves in one of the approved directions. (See Mounting Configuration, Figure 2.)
6. Parallel actuation is NOT recommended and may cause switch failure. An on/off/ on signal may result when the magnet passes by the switch rather than coming to rest in proximity to it. (See Mounting Configuration, Figure 2.)
7. When mounting on a hinged gate or door, mount the switch and actuator at least 6" away from the hinges so a more parallel movement is achieved.
8. The actuator can be mounted at a 90° rotation.
9. Keep the switch and actuator within the listed sense range (See Ordering/ Electrical Specifications).
10. Mounting on a ferrous (steel) material will reduce the sense range a minimum of 50%. A 1/4" nonferrous (plastic or aluminum) spacer installed under the actuator and switch will restore most of the lost gap.
11. When mounting a metal switch to an ungrounded machine, connect the ground lead to one of the switch mounting screws.
Page 2
Mounting Configurations
Figure 2
Perpendicular
Actuation
Door
Actuation
Rotated
Actuation
Parallel
Actuation
*
OK OK NO
* Actuation surface
Three configurations are appropriate for interlock applications. The parallel actuation can result in on/off/on signal if the actuator passes by the switch rather than coming to rest in proximity to it. This is NOT a recommended configuration for interlock applications.
Wiring for one FailSafe GuardSwitch
Add a 1/2 amp caused by inrush-currents, tampering, or excessive vibration.
Figure 3
fast-acting
fuse* in series to protect the switch from premature failure
OK
Wiring for two to ten FailSafe
GuardSwitches
Add a 1/2 amp
fast-acting
in series
fuse in series to protect the switch from premature failure
caused by inrush-currents, tampering, or excessive vibration.
Figure 4
Black
1/2A Fuse Required*
VAC/DC
Load
*
Use fast-acting Littlefuse 216, fast-acting Microfuse or
Red
White
fast-acting Pico II fuse up to 1/2 Amp.
FailSafe
GuardSwitch
Black
1/2A Fuse Required
VAC/DC
Load
*
Use fast-acting Littlefuse 216, fast-acting Microfuse or
Red
Black
Red
Black
Red
fast-acting Pico II fuse up to 1/2 Amp.
FailSafe
GuardSwitch
FailSafe
GuardSwitch
FailSafe
GuardSwitch
White
White
White
GE Security Industrial
GuardSwitchTM Series 200 www.ge-security.com/industrial
Page 3
Testing
After mounting the switch and actuator, test the switch for proper operation. Test with circuit disconnected from source and load. For multiple switches in series, test one switch at a time with all other guard doors closed. Then:
1. Hook the black and white leads of the switch to an Ohmmeter. Move the gate or door open and closed several times slowly. At all times the meter should read O.L. or “open.”
2. Hook the Ohmmeter to the black and red leads of the switch. Move the door or gate open and closed. The meters should read O.L. when the actuator is away and it should read less than 1 Ohm when the actuator is in range.
3. Hook the Ohmmeter to the white and red leads of the switch. Move the door or gate open and closed. The meter should read 11–14 ohms when the actuator is away and it should read O.L. when the actuator is in range.
Wiring
1. After the switch and actuator have been mounted and tested, wire the FailSafe GuardSwitch
2. For wiring 2 to 10 FailSafe GuardSwitches 10 switches in a series).
3. Failure to install in-line fuse voids warranty.
as shown in Figure 3.
in series, see Figure 4. (Do not exceed
General Specifications
Enclosure Nylon 6/6
Temperature Range -40°F to 150°F (-40°C to 65°C)
Environmental Hermetically Sealed Contact Switch
Encapsulated in Polyurethane
NEMA Rating 1, 2, 3, 4, 4X, 5, 6, 12
Protection Class IP 67
Response Time 5 msec
Life Cycles 100,000 Under Full Load;
Up to 200,000,000 Under Dry Circuit
Lead Types/O.D. Jacketed (J) 18/3 AWG/0.24” (0.62cm)
UL/CSA All Models
Note: The 215 has a patented “watch-dog” circuit which, when switch failure occurs,
the fused watch-dog circuit will draw 2.5 Amps. The voltage supply must have a current capacity of 2.5 Amps. This results in an open, fail-safe condition.
Tr oubleshooting
If the in-line fuse blows or the GuardSwitch™ remains open:
1. Check the application for premature failure caused by inrush-currents, tampering, excessive vibration and misalignment.
2. Disconnect all three wires of GuardSwitch™ and test according to testing instructions, steps 1-3.
3. If the GuardSwitch
4. Replace the in-line fuse if blown.
fails any of the three tests, it must be replaced.
File E 115761
LR89176
GE Security Industrial
GuardSwitchTM Series 200 www.ge-security.com/industrial
Page 4
Accessories
PART NUMBER TAMPER PROOF SCREWS & SCREWDRIVER
1954 #8 x 1-1/2"L Tampruf Roundhead Screw
1955 Tampruf® Screwdriver
1956 Tampruf® 1/4" Drive Bit for #6 and #8 Screws
Ordering/Electrical Specifications
PART CONTACT NUMBER CONFIG. AC/DC Max. (AC/DC) (AC/DC) RESISTANCE NOMINAL NOMINAL FAILURE Max. NOMINAL
215-F6Y-06J N.O. 12W/VA 0.5A 24±4V 0.5 Ohms 0.7"(1.8cm) 1.8"(4.6cm) 2.5"(6.8cm) 6'(1.8m) 215-F6Y-12J N.O. 12W/VA 0.5A 24±4V 0.5 Ohms 0.7"(1.8cm) 1.8"(4.6cm) 2.5"(6.8cm) 12'(3.6m) 215-F6Y-16J N.O. 12W/VA 0.5A 24±4V 0.5 Ohms 0.7"(1.8cm) 1.8"4.6cm) 2.5"(6.8cm) 16'(4.8m)
115Y Actuator Only Included with all switches unless otherwise noted.
Warning— Each electrical rating is an individual maximum and cannot be exceeded!
1
Configuration with actuator away from the switch
2
Proximity of ferrous materials usually reduces sense range — typically by 50%. The shape and type of material cause a wide diversity of effects. Testing is required to determine actual sense range for specific applications.
1
LOAD RATING SWITCH CURRENT VOLTAGE RANGE CONTACT SENSE RANGE
2
BREAK RANGE BREAK AT LEAD LENGTH
GE Security
Industrial
©2004 GE Security Industrial. GE Security Industrial reserves the right to change specifications without notice. I-3919-0404 12946 Rev C
www.ge-security.com/industrial
12345 SW Leveton Drive Tualatin, OR 97062 Phone: 800-247-9447 Fax: 503-691-7563