Cheshire, CT 06410 203-699-3300 (Ph)
203-699-3365 (Cust. Serv. Fax)
203-699-3078 (Tech. Serv. Fax)
Installation Instructions for 1500 Series
Door Holder Extension Kits
Description
The Edwards 1500 Series Door Holder Extension Kits are used
where it is desired to hold doors open and where a standoff distance between the magnet assembly and the armature base is required. The extension rod kit can be used with Edwards 1504,
1505, 1508 and 1509 Series Door Holders. Parts from these door
holders are used with the extension kits to form a complete unit.
Specifications
Model Number Extension Range
1500-1 1 1/2" (38 mm) Fixed
1500-2 2" (51 mm) Fixed
1500-7 6.37 - 8.00" (162 - 203 mm)
1500-12 8.37 - 12" (213 - 305 mm)
Installation
WARNING
The extension kits project a significant distance from
the doors they are mounted on and should, therefore,
be mounted as high as possible to preclude interference or personal injury .
1. Install the extension kit as follows.
a. Remove the #10-32 x 1 1/2" (38 mm) armature securing
screw and remove the catch plate from the armature base
(Figure 1).
c. Insert the extension rod into the armature base and secure
with #10-32 x 1 1/2" (38 mm) armature securing screw
(Figures 1 - 3).
d. Insert spherical bushings (supplied) and flat washers
(supplied with 1500-7 and 1500-12 only) into the
extension rod assembly as shown in Figure 2 or Figure 3,
as applicable. Secure catch plate in extension rod using
#10-32UNF x 1" (25 mm) securing screw (Figure 2).
e. For adjustable units only, adjust the extension length by
loosening the knurled locking nut, extending the rod to
the desired length and retightening the knurled locking
nut (Figure 2).
NOTE: Proper alignment of the catch plate and the
electromagnet helps ensure sufficient holding force.
f. Align the catch plate with the electromagnet by moving
the extension arm up or down and back or forth while
simultaenously adjusting the catch plate against the
magnet. There should be no gap between the catch plate
and the magnet.
g. After the desired extension length and contact alignment
have been achieved, perform the following (Figure 2):
1. Using a 5/32" (4 mm) Allen Wrench (supplied), lock
the extension arm into position by tightening the
armature securing screw (Figure 2). Do not
overtighten.
h. Perform an operational check of the Electromagnetic
Door Holder as outlined in the installation instruction
provided with the door holder.
2. For more detailed information on installation of the door
holders, see the instructions supplied with the door holder.
b . Insert spherical bushings (removed in Step 1.a) as shown
in Figure 2 or Figure 3 as applicable. If bushings are
damaged, replace with bushings supplied with the door
holder extension kit.
Figure 1. Armature Base Assembly
P/N 3100331 ISSUE 2 © 2004
#10-32 x 1 1/2” (38 mm)
Armature Securing Screw
(supplied with door hol der )
Armature Base (supp lied with door holder)
(2) Spherical B ushings
(supplied)
Extension Tube
Assembly
#10-32 UNF x 1“ (25 mm)
Screw (supplied)
Knurled Locking Nu t
#10-32 UNF x 1" (25 mm)
Screw (supplied)
(2) Spherical Bushings
(supplied)
(2) Flat Washers
(supplied)
#10-32 UNF Nut
(supplied)
(supplied with door ho lder)
Catch Plate
Figure 2. Extension Rod Assembly (Adjustable 1500-7 and 1500-12 Model)
Catch Plate
(supplied with door holder)
(2) Spherical Bushings
(supplied)
#10-32 x 1 1/2" (38 mm)
Armature Securing Screw
(supplied with door holder)
P/N 3100331 ISSUE 2
#10-32 UNF Nut
Extension
(supplied)
Assembly
(2) Spherical Bushings
(supplied)
Armature Base
(supplied with door holder)
Figure 3. Extension Rod Assembly (Adjustable 1500-1 and 1500-2 Model)