Description
Edwards 125 Class Beacons are UL and cUL listed signaling appliances rated for NEMA 4X applications. Two versions of incandescent beacons are available: Flashing (125INCF) and Steady-on (125INCS). Both types can be either surface or conduit mounted.
Electrical Specications
GRAY BASE BLACK BASE
Catalog Number Catalog Number Voltage Current
Flashing Incandescent
125INCF*24D 125INCF*24DB 24V DC 0.610A
125INCF*120A 125INCF*120AB 120V AC 50/60 Hz 0.510A
Steady-On Incandescent
125INCS*24D 125INCS*24DB 24V DC 0.610A
125INCS*120A 125INCS*120AB 120V AC 50/60 Hz 0.510A
*Letter in this position designates lens color: A - amber, B - blue, C - clear, G - green, or R - red
Mechanical Specications
Panel Mounting (Figure 2)
Note: When panel mounting the beacon, the surface and
construction details of the panel must be taken into consideration in order to ensure that the integrity of the outdoor, NEMA 4X rating is fully maintained. Installer should evaluate.
1. Place the mounting gasket (supplied) over the hole in the panel and route the signal wires through the gasket and the hole in the panel.
2. Insert the base through the hole in the panel and screw the locking nut (supplied), with the raised locking edge facing the mounting surface, onto the base to secure the beacon.
3. Using wire nuts (not supplied), connect the signal's wire leads as shown in Figure 2. Polarity must be observed.
Maintenance
WARNINGS
To prevent electrical shock, ensure power is turned off before installation or maintenance.
Outdoor Locations
Temperature Ratings ...........-31F to +150F (-35C to +66C)
Installation
WARNING
To prevent electrical shock, ensure that power is turned off before installing the signal.
Conduit Mounting (Figure 1)
1. Thread the 18" (45.7 cm) signal wire leads through 1/2" conduit into an approved conduit outlet box.
2. Thread the conduit onto the base of the signal.
3. Using wire nuts (not supplied), connect the signal's wire leads as shown in Figure 1. Polarity must be observed for DC models. For AC models, polarity is not important.
To avoid risk of injury, install lens before energizing.
Cleaning
To maintain optimum light visibility, the exterior lens surfaces should be periodically cleaned with a soft clean cloth us­ing water and a mild detergent. Disconnect power before cleaning.
Light Source Replacement
1. Conduit Mounted Modules: Disconnect wiring and, if necessary, unscrew base from conduit (Figure 1).
Panel Mounted Modules: Disconnect wiring and
remove locking nut that secures the base to the panel (Figure 2).
2. Remove screws that secure the lens to the base from bottom of base and remove lens.
3. Unplug lamp and replace with appropriate new lamp (as specied in Table 1 - Replacement Parts). Reattach lens to base and fasten with screws removed in step 2.
http://www.edwardssignaling.com Phone: (800) 336-4206 Fax: (800) 454-2363
P/N 3101757 ISSUE 3
© 2010
125 Class Visual Indicator
3/4” NPT external (shown) 1/2” NPT internal Conduit (not supplied)
18” Wire Leads
DC units; Red positive (+) AC units; Black Hot
DC units; Black negative (-) AC units; White neutral
Locking Nut -
1.3625" OD (supplied)
Control panel
(enclosure)
125 Class Visual Indicator
Gasket (supplied)
18” Wire Leads
Wire Nuts (Not Supplied)
Power Source Wires
Figure 2. Panel Mounting
Wire nuts (not supplied)
Connect leads to Power Source
Figure 1. Conduit Mounting (3/4" Shown)
Catalog Number (gray base)
Catalog Number (black base)
Flashing Incandescent
125INCF*24D 125INCF*24DB
125INCF*120A 125INCF*120AB Industry Trade 15T7DC
Steady-On Incandescent
125INCS*24D 125INCS*24DB
125INCS*120A 125INCS*120AB Industry Trade 15T7DC
*Letter in this position indicates lens color: A - Amber, B - Blue, C - Clear, G - Green, R - Red.
Table 1. Replacement Parts
Replacement
Lens Replacement Lamp
125L*
125L*
Lens
Incandescent Lamp
Lamp Socket
O-Ring (in groove) (supplied)
Base
(4) Screws securiing lens to base
Figure 3. Lamp Replacement
Industry Trade 1692
Industry Trade 1692
Table 2. Programming Logic Controller (PLC) Compatibility: PLC Output to meet following product input parameters
Operating voltage
Cat. No.*
(Volts)
125INCF24D 24V DC 25 25 0.68A 7A exp decaying
125INCF120A 120V AC 50/60 Hz 25 25 0.3A / 8 ms 0.8A exp decaying
125INCS24D 24V DC 25 25 2.5A / 60 ms 7A exp decaying
125INCS120A 120V AC 50/60 Hz 25 25 0.5A / 8 ms 0.8A exp decaying
*PLC compatibility applies to models with any lens color and with either a gray or black base.
P/N 3101757 ISSUE 3
Max. off state leak-
age current (mA)
Continuous on
current (mA)
Repetitive
Surge
Surge
(inrush/duration)