Edwards Signaling 116EX Series AdaptaBeacon Installation Guide

STANCHION
116EX-S 1 1/4" HUB
Installation Instructions for 116EX Series AdaptaBeacon
Strobe Lights for Use in Hazardous Locations
PENDANT
CEILING
116EX-C 3/4" HUB
Figure 1. Mounting Options
116EX-P 3/4" HUB
116EX-C
116 SERIES HOUSING AND GLOBE
ASSEMBLY WITH GUARD
WALL
116EX-B 3/4" HUB
®
DescriptionDescription
Description
DescriptionDescription
The 116EX Series AdaptaBeacon strobe signaling appliances are intended for general utility signaling use. The strobes are UL and cUL listed for use in Class I, Division 1, Group C and D, Class I, Division 2, Group A, B, C and D, Class II, Division 1, Group E, F and G, Class II, Division 2, Group F and G, and Class III Division 1 and 2 hazardous locations with operating temperature codes per T able 2.
The strobes are UL and cUL Listed, as T ype 3R and 4X en­closures. Additionally, the 120V AC strobes are UL and cUL listed as Marine enclosures.
The strobe flashes a 360-degree beam of light approxi­mately 65 times per minute.
The 120V 50/60 Hz strobes are available in pendant, bracket, ceiling, or stanchion mount models (Figure 1).
InstallationInstallation
Installation
InstallationInstallation
WARNING
To reduce the risks of ignition of hazar dous atmo­spheres and shock, do not apply power to the unit until installation has been completed and unit is tightly assembled and secured.
b. Ceiling Mount Models (Figure 3): Mount the
catalog number 116EX-C, ceiling/wall mounting module, using appropriate hardware (not supplied) suitable for the mounting surface. Proceed to step
2.
c. Bracket Mount Models (Figure 4): Install the
catalog number 116EX-C ceiling/wall mounting module using appropriate hardware (not supplied) for the mounting surface. Install the catalog number 116EX-B wall mounting elbow to the wall box. Run the unit's wiring through the elbow to the wall box. Proceed to step 2.
d. Stanchion Mount Models (Figure 5): Install the
catalog number 116EX-S, stanchion mounting module, to the main housing. Run the unit's wires through the 1 1/4" conduit to the appropriate junction box. Install the unit on the conduit. Proceed to step 2.
2. Connect field earth ground wire to ground screw or earth ground via conduit system.
3. Using wire nuts, connect the incoming neutral or white wire to the unit's two neutral white wires and the incoming (+) or black wire to the unit's two (+) black wires. See Table 2 for required supply wire temperature ratings.
4. As appropriate, install the fixture on the mounting module.
Install this unit in accordance with the applicable require­ments in the latest edition of the National Electrical Code and Canadian Electrical Code.
1. Mount using the following applicable method. a. Pendant Mount Models (Figure 2): Install the
catalog number 116EX-P, pendant mounting module, to the main housing. Install explosion­proof hanger box (not supplied). Secure 3/4" (19 mm) NPT threaded conduit (not supplied) to the box. Install the unit on the conduit. Proceed to step 2.
WARNING
To reduce the risk of ignition of hazar dous atmo­spheres and shock, keep assembly tightly closed when circuits are energized.
5. Apply power to the unit and ensure proper function.
P/N 3100756 ISSUE 1 © 2004
6 3/4"
4"
4"
12"
12 3/4"
7 1/4"
Figure 2. Detail of Pendant Mounting Figure 3. Detail of Ceiling Mounting
MaintenanceMaintenance
Maintenance
MaintenanceMaintenance
Disassemble the unit as follows (Figure 6):
WARNING
To reduce the risk of ignition of hazardous atmo­spheres and shock, keep assembly tightly closed when circuits are energized.
5/16"
1"
13"
13 3/4"
7 1/4"
counterclockwise direction. Remove the ring and globe assembly .
3. Refer to Table 1 for the correct replacement catalog number and replace the necessary part.
4. T o replace, simply screw the unit on until it seats firmly onto its gasket. Tighten the unit another 1/8 to 1/4 turn. Tighten the setscrew .
5. Reinstall the guard, where applicable, and secure using the three supplied screws.
To reduce the risk of ignition of hazardous atmo­spheres and shock, disconnect from the supply and circuit and allow five (5) minutes for stored energy to dissipate before disassembling the unit.
1. Loosen the (3) guard screws and remove the guard.
2. Loosen the globe and ring assembly set screw. Insert a suitable tool into the notches in the globe and ring assembly and loosen the assembly by prying in a
6. After the unit is assembled, apply power and make sure the unit functions properly .
P/N 3100756 ISSUE 1