Edwards Signaling 116DEXSTC-FJ User Manual

Installation Instructions for 116DEXSTC-FJ AdaptaBeacon
Cheshire, CT 06410 203-699-3300 (Ph) 203-699-3365 (Cust. Serv. Fax) 203-699-3078 (Tech. Serv. Fax)
STANCHION
116EX-S 1 1/4" HUB
DescriptionDescription
Description
DescriptionDescription
The 116DEXSTC-FJ AdaptaBeacon is an in-rush current lim­ited strobe light. When pendant, wall or ceiling mounted, it is UL1971 Listed Signaling Appliance for the Hearing Impaired. Stanchion mount models are UL 1638 Listed for Private Mode Emergency Signaling. All models are CSFM Listed.
The strobe is intended for indoor use in UL listed compatiable fire alarm systems and other applications re­quiring electrical supervision of signaling circuit field wir­ing. This strobe flashes a 360-degree beam of light ap­proximately 65 times per minute with a UL 1971 60 cd wall and ceiling light output per Figure 7.
When assembled in accordance with these instructions, the 116DEXSTC-FJ visual strobe signal is UL Listed for use in Class I, Division 1, Groups C and D, Class I, Division 2, Groups A, B, C and D, Class II Division 1, Group E, F and G, Class II, Division 2, Group F and G, and Class III Division 1 and 2 hazardous locations with Operating Temperature Codes per the following chart. See Table 1 for Electrical Specifications.
This strobe is UL and cUL Listed as a T ype 3R and 4X enclo­sure. See Figure 1.
InstallationInstallation
Installation
InstallationInstallation
Install this unit in accordance with the applicable require­ments in the latest edition of the National Fire Alarm Code (NFPA 72), National Electrical Code (NFPA 70), and Cana­dian Electrical Code.
Fire Alarm Strobe Lights for Use in Hazardous Locations
CEILING
116EX-C 3/4" HUB
Figure 1. Mounting Options
WARNING
To reduce the risks of ignition of hazardous atmo­spheres and shock, do not apply power to the unit until installation has been completed and unit is tightly assembled and secured.
PENDANT
116EX-P 3/4" HUB
116EX-C
116 SERIES HOUSING AND GLOBE
ASSEMBLY WITH GUARD
WALL
116EX-B 3/4" HUB
a. Pendant Mount Models (Figure 2): Install the
catalog number 116EX-P, pendant mounting module, to the main housing. Install explosion­proof hanger box (not supplied). Secure 3/4" (19 mm) NPT threaded conduit (not supplied) to the box. Install the unit on the conduit. Proceed to step 2.
b. Ceiling Mount Models (Figure 3): Mount the
catalog number 116EX-C, ceiling/wall mounting module, using appropriate hardware (not supplied) suitable for the mounting surface. Proceed to step
2.
c. Bracket Mount Models (Figure 4): Install the
catalog number 116EX-C ceiling/wall mouting module using appropriate hardware (not supplied) for the mounting surface. Install the catalog number 116EX-B wall mounting elbow to the wall box. Run the unit's wiring through the elbow to the wall box. Proceed to step 2.
d. Stanchion Mount Models (Figure 5): Install the
catalog number 116EX-S, stanchion mounting module, to the main housing. Run the unit's wires through the 1 1/4" conduit to the appropriate junction box. Install the unit on the conduit. Proceed to step 2.
2. Connect field earth ground wire to ground screw or earth ground via conduit system.
3. Wire the unit in accordance with Figure 6. See Table 3 for required supply wire temperature ratings.
4. As appropriate, install the fixture on the mounting module.
WARNING
To reduce the risk of ignition of hazardous atmo­spheres and shock, keep assembly tightly closed when circuits are energized.
®
1. Mount using the following applicable method.
5. Apply power to the unit and ensure proper function.
P/N 3100759 ISSUE 1 © 2004
6 3/4"
1/4"
1 1/4"
Conduit
13 1/4"
12 3/4"
13 1/2"
4"
4"
12"
12 3/4"
5/16"
1"
7 1/4"
7 1/4"
Figure 2. Detail of Pendant Mounting Figure 3. Detail of Ceiling Mounting
12 9/16"
9 7/16"
16 1/16"
16 13/16"
6 3/4"
1"
4"
4"
5/16"
13"
13 3/4"
NOTE: Not for use as a Public Mode Fire Alarm
Signal
Figure 4. Detail of Wall Bracket Mounting Figure 5. Detail of Stanchion Mounting
NOTE: DC polarity of circuit shown in supervisory state (signal inactive). Circuit polarity to reverse to activate signal. Electrical supervision requires wire run to be broken at each device. Device for constant input voltage. Do not connect to “coded” or pulsating voltage.
(-)
(+)
(-)
(+)
White
Black
(-)
From Power Source
Previous Signaling Device
or
Series
116DEX
White
Black
Series
116DEX
(+)
White
Black
(-)
(+)
White
Black
(-)
KEY:
Light symbol -
Wire nut symbol -
End-of-Line Resistor, when required with supervised system
(+)
NOTE: For non-fire alarm use, i.e. without field wire supervision, installer can tie the two white leads
together and tie the two black leads together .
P/N 3100759 ISSUE 1
Figure 6. Wiring Diagram
MaintenanceMaintenance
Maintenance
MaintenanceMaintenance
Disassemble the unit as follows (Figure 8):
2. Loosen the globe and ring assembly set screw . Insert a suitable tool into the notches in the globe and ring assembly and loosen the assembly by prying in a counterclockwise direction. Remove the ring and globe assembly .
WARNING
T o reduce the risk of ignition of hazardous atmo­spheres and shock, keep assembly tightly closed when circuits are energized.
T o reduce the risk of ignition of hazardous atmo­spheres and shock, disconnect from the supply and circuit and allow five (5) minutes for stored energy to dissipate before disassembling the unit.
1. Loosen the (3) guard screws and remove the guard.
T able 1. 116DEXSTC-FJ AdaptaBeacon Strobe Light
Electrical Specifications
Voltage Designation* Current (A)**
Regulated 24V DC 0.802 Regulated 24V FWR 1.140
CAUTION: To prevent damage to the signal circuit and to otherwise assure continued proper functioning, DO NOT operate the unit outside of the Regulated 24V DC/FWR voltage range of 16 - 33V DC/V FWR.
*The designation Regulated 24 refers to the voltage range of 16
- 33 volts. **The Max RMS Operating Current is defined as the current rating over the entire voltage range.
3. Refer to Table 2 for the correct replacement catalog number and replace the necessary part.
4. T o replace, simply screw the unit on until it seats firmly onto its gasket. Tighten the unit another 1/8 to 1/4 turn. Tighten the setscrew .
5. Reinstall the guard, where applicable, and secure using the three supplied screws.
6. After the unit is assembled, apply power and make sure the unit functions properly .
Max RMS Operating
T able 2. 116DEXSTC-FJ
Description Number Ratings Size Rate Replacement
Housing Less 116DEXSTC-FJ 16 - 33V DC N/A Approx. 92-ST Mounting Module 0.802/1.104A 65 fpm
Ceiling/Wall 116EX-C N/A 3/4" NPT N/A N/A Mounting Module
Pendant 116EX-P N / A 3/4" NPT N/A N/A Mounting Module
Stanchion 116EX-S N/A 1 1/4" NPT N/A N/A Mounting Module
Wall Bracket 116EX-W N/A N/A N/A N/ A Mounting Elbow
Catalog Electrical Conduit Flash Strobe Tube
T able 3. Ratings
Operating Temperature
Amb ient Supply Wire Class I, Div. 2 Class I, Div. 1 & 2 Class II & III, Div. 1 Class II & III, Div. 2
Temp. Temp. Marking Groups A, B Groups C, D Groups E, F, G Group F, G
40°C 75°C T2D (215°C) T6 (85°C) T4A (120°C) T4A (120°C) 55°C 90°C T2C (230°C) T6 (85°C) T4 (135°C) T4 (135°C)
P/N 3100759 ISSUE 1
WALL
BRACKET
MOUNTING
ANGLE
(DEGREES)
zero 100% 100%
590%90% 10 90% 90% 15 90% 90% 20 90% 90% 25 90% 90% 30 90% 75% 35 65% 75% 40 46% 75% 45 34% 75% 50 27% 55% 55 22% 45% 60 18% 40% 65 16% 35% 70 15% 35% 75 13% 30% 80 12% 30% 85 12% 25% 90 12% 25%
Compound
45
UL1971 REQUIRED
DISPERSION AS % OF CD
RATING
VERTICAL
PLANE
HORIZONTAL
PLANE
24%
Effective Candela Light Output for Wall Bracket Mount
Vertical Plane
(Zero degree angle at side of globe)
-90
-85
-80
-75
-70
-65
-60
-55
-50
-45
-40
-35
-30
-25
-20
-15
-10
-5 0 degrees 5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
TYPICAL CD UL REQUIRED CD
FOR 35 RATING
130 120 110 100
90 80 70 60 50 40 30 20 10
0
UL 1971 Hearing Impaired: 60 cd wall
CEILING
MOUNTING
ANGLE
(DEGREES)
0 100%
590% 10 90% 15 90% 20 90% 25 90% 30 75% 35 75% 40 75% 45 75% 50 55% 55 45% 60 40% 65 35% 70 35% 75 30% 80 30% 85 25% 90 25%
Compound 45 24%
UL1971
REQUIRED X & Y PLANE DISPERSION AS % OF CD
RATING
Effective Candela Light Output for Ceiling Mount
X & Y Planes
(Zero degree angle at bottom of of globe)
180
140
170
165
160
155
150
145
140
135
130
125
120
115
110
105
100
95 90 85
80
75
70
65
60
55
50
45
40
35
30
25
130 120 110 100
20
15
10
175
170
165
160
155
150
145
140
90 80 70 60 50 40 30 20 10
0
5
TYPICAL CD UL REQUIRED CD
FOR 55 RATING
20
15
10
5
25
135
130
50
45
40
35
30
125
120
115
110
105
100
95 90 85
80
75
70
65
60
55
UL 1971 Hearing Impaired: 60 cd ceiling
P/N 3100759 ISSUE 1
degrees 0
Figure 7. Light Output Patterns for 116DEXSTC-FJ
Strobe Tube
Globe & Ring Assembly
Guard
CAUTION: Wait 5 minutes for strobe energy to dissipate
prior to disassembly.
Figure 8. Disassembly of the 116DEXSTC-FJ AdaptaBeacon