STANCHION
116EX-S 1 1/4" HUB
Installation Instructions for 116DEXMST Series
AdaptaBeacon® Supervised 16 - 33V DC Strobes for
CEILING
116EX-C 3/4" HUB
Figure 1. Mounting Options
Use in Hazardous Locations
PENDANT
116EX-P 3/4" HUB
116EX-C
116 SERIES HOUSING AND GLOBE
ASSEMBLY WITH GUARD
WALL
116EX-B 3/4" HUB
DescriptionDescription
Description
DescriptionDescription
The 116DEXMST*-FJ DC strobe AdaptaBeacon signaling appliances are heavy duty diode-polarized strobe lights intended for use in general utility signaling (non-fire alarm)
applications requiring electrical supervision of signaling
circuit field wiring. The strobes are UL and cUL listed for
use in Class I, Division 1, Group C and D, Class I, Division 2,
Group A, B, C and D, Class II, Division 1, Group E, F and G,
Class II, Division 2, Group F and G, and Class III Division 1
and 2 hazardous locations with operating temperature
codes per following chart.
The strobes are UL and cUL Listed, as Type 3R, 4X, and
Marine enclosures.
The strobe flashes a 360-degree beam of light approximately 65 times per minute.
The strobes are available in pendant, bracket, ceiling, or
stanchion mount models (Figure 1).
InstallationInstallation
Installation
InstallationInstallation
WARNING
To reduce the risks of ignition of hazardous atmospheres and shock, do not apply power to the unit
until installation has been completed and unit is
tightly assembled and secured.
Install this unit in accordance with the applicable requirements in the latest edition of the National Electrical Code
and Canadian Electrical Code.
1. Mount using the following applicable method.
a. Pendant Mount Models (Figure 2): Install the
catalog number 116EX-P, pendant mounting
module, to the main housing. Install explosionproof hanger box (not supplied). Secure 3/4" (19
mm) NPT threaded conduit (not supplied) to the
box. Install the unit on the conduit. Proceed to
step 2.
b. Ceiling Mount Models (Figure 3): Mount the
catalog number 116EX-C, ceiling/wall mounting
module, using appropriate hardware (not supplied)
suitable for the mounting surface. Proceed to step
2.
c. Bracket Mount Models (Figure 4): Install the
catalog number 116EX-C ceiilng/wall mounting
module using appropriate hardware (not supplied)
for the mounting surface. Install the catalog
number 116EX-B wall mounting elbow to the wall
box. Run the unit's wiring through the elbow to
the wall box. Proceed to step 2.
d. Stanchion Mount Models (Figure 5): Install the
catalog number 116EX-S, stanchion mounting
module, to the main housing. Run the unit's wires
through the 1 1/4" conduit to the appropriate
junction box. Install the unit on the conduit.
Proceed to step 2.
2. Connect field earth ground wire to ground screw or
earth ground via conduit system.
3. Wire the unit in accordance with Figure 6. See Table
2 for required supply wire temperature ratings.
4. As appropriate, install the fixture on the mounting
module.
WARNING
To reduce the risk of ignition of hazardous atmospheres and shock, keep assembly tightly closed
when circuits are energized.
5. Apply power to the unit and ensure proper function.
P/N 3100758 ISSUE 1 © 2004
6 3/4"
1/4"
1 1/4"
Conduit
13 1/4"
12 3/4"
13 1/2"
4"
4"
12"
12 3/4"
5/16"
1"
13"
13 3/4"
7 1/4"
7 1/4"
Figure 2. Detail of Pendant Mounting Figure 3. Detail of Ceiling Mounting
12 9/16"
9 7/16"
16 1/16"
16 13/16"
6 3/4"
1"
4"
4"
5/16"
Figure 4. Detail of Wall Bracket Mounting Figure 5. Detail of Stanchion Mounting
NOTE: DC polarity of circuit shown in supervisory state (signal inactive). Circuit polarity to reverse to activate signal.
Electrical supervision requires wire run to be broken at each device.
Device for constant input voltage. Do not connect to “coded” or pulsating voltage.
(-)
(+)
(-)
(+)
White
Black
(-)
From Power Source
or
Previous Signaling Device
Series
116DEX
White
Black
Series
116DEX
(+)
White
Black
(-)
(+)
White
Black
(-)
KEY:
Light symbol -
Wire nut symbol -
End-of-Line Resistor,
when required with
supervised system
(+)
NOTE: For use without field wire supervision installer can tie the two white leads together and tie the two
black leads together .
P/N 3100758 ISSUE 1
Figure 6. Wiring Diagram