Fire & Life Safety
Notication Appliances
Overview
116DEGEX-FJ hazardous location strobes are life safety signaling
appliances designed for installation in hazardous environments.
Rigid specications and state-of-the-art technology provide for
high visual output and low maintenance. The 116DEGEX-FJ has
negligible in-rush current.
When pendant, wall or ceiling mounted, the 116DEGEX-FJ meets
or exceeds the requirements of UL 1971 Signaling Appliance for the
Hearing Impaired.
The 116DEGEX-FJ is intended for indoor use in UL listed compatible re alarm systems and other applications requiring electrical
supervision of signaling circuit eld wiring. Its strobe ashes a
360-degree beam of light approximately 65 times per minute with
a UL 1971 150 cd wall and ceiling light output. In Canada, the
116DEGEX-FJ is listed to ULC-S526-02 Visible Signal Device for Fire
Alarm Systems, suitable for indoor and outdoor applications.
When assembled with an available mounting option, the
116DEGEX-FJ is UL Listed for use in Class I, Division 1, Groups C and
D, Class I, Division 2, Groups A, B, C and D, Class II, Division 1, Group
E, F and G, Class II, Division 2, Group F and G, and Class III Division
1 and 2 hazardous locations. The strobe is UL and cUL Listed as a
Type 3R and 4X enclosure.
Standard Features
UL 1971 listed and ADA compliant for the hearing impaired
•
Negligible in-rush current
•
Approved for re alarm applications
•
Wall, ceiling or pendant mount
•
Diode polarized for use in electronically supervised circuits
•
High impact glass dome
•
65 ashes per minute
•
Can be synchronized
•
150 cd, wall or ceiling
•
Factory sealed - no external seals required
•
Quick connect - threads onto mounting module for easy instal-
•
lation
Epoxy powder coat for corrosion resistance
•
ULC-S526-02 listed for indoor and outdoor applications
•
Hazardous
Location Strobes
116DEGEX-FJ
Wall
Mount
Pendant
Mount
Ceiling
Mount
Data Sheet 518-21 Issue 1
Not to be used for installation purposes. Page 1 of 6
Application
NOTE: DC polarity of circuit shown in supervisory state (signal inactive). Circuit polarity to reverse to activate signal.
Electrical supervision requires wire run to be broken at each device.
Device for constant input voltage. Do not connect to “coded” or pulsating voltage.
From Power Source
or
Previous Signaling Device
End-of-Line Resistor,
when required with
supervised system
KEY:
Light symbol -
Wire nut symbol -
(+)
White
(+)
White
(+)
White
(+)
White
Black
(-)
Black
(-)
Black
(-)
Black
(-)
Series
116DEGEX
Series
(+)
(-)
116DEGEX
116DEGEX-FJ hazardous location strobes are designed for use in
compatible Edwards re alarm systems and other applications
requiring electrical supervision of signaling circuit eld wiring.
These strobes are suitable for many locations including mines, granaries, our mills, tankers, reneries, laboratories and other applications where environmental hazards may be present. 116DEGEX-FJ
strobes are particularly well-suited in areas of high noise levels
where standard bells or horns are not satisfactory.
When pendant, wall or ceiling mounted, 116DEGEX-FJ strobes are
ULC-S526-02 listed for indoor and outdoor applications and UL
1971 Listed (ADA compliant) for indoor visual signaling applications
in non-sleeping areas.
Wiring
For non-re alarm use, i.e., without eld wire supervision, installer can tie the two white leads together
and tie the two black leads together.
Notes:
1. DC Polarity of circuit shown in supervisory state (signal inactive). Circuit polarity to reverse to activate signal.
2. Electrical supervision requires wire run to be broken at each device.
3. Device for constant input voltage. Do not connect to “coded” or pulsating voltage.
4. For non-re alarm use, i.e., without eld wire supervision, the installer can tie the two white leads together and tie the two black leads together.
Hazardous Location Listings
Operating Temperature
Ambient
Temperature
40C (104F) 75C (167F) T2D (215C, 419F) T6 (85C, 185F) T4A (120C, 248F) T4A (120C, 248F)
55C (131F) 90C (194F) T2C (230C, 446F) T6 (85C, 185F) T4 (135C, 275F) T4 (135C, 275F)
65C (149F) 105C (221F) T2C (230C, 446F) T6 (85C, 185F) T3C (135C, 275F) T3C (135C, 275F)
Supply Wire
Temperature Marking
Class I, Div. 2
Groups A, B
Class I, Div. 1 & 2
Groups C, D
Class II, Div. 1
Groups E, F, G, & Class III
Not to be used for installation purposes. Page 2 of 6
Class II, Div. 2
Groups F, G, & Class III
Data Sheet 518-21 Issue 2