Edwards Signaling 116DEGEX-FJ Catalog Page

Fire & Life Safety
Notication Appliances
Overview
116DEGEX-FJ hazardous location strobes are life safety signaling appliances designed for installation in hazardous environments. Rigid specications and state-of-the-art technology provide for high visual output and low maintenance. The 116DEGEX-FJ has negligible in-rush current.
When pendant, wall or ceiling mounted, the 116DEGEX-FJ meets or exceeds the requirements of UL 1971 Signaling Appliance for the Hearing Impaired.
The 116DEGEX-FJ is intended for indoor use in UL listed compat­ible re alarm systems and other applications requiring electrical supervision of signaling circuit eld wiring. Its strobe ashes a 360-degree beam of light approximately 65 times per minute with a UL 1971 150 cd wall and ceiling light output. In Canada, the 116DEGEX-FJ is listed to ULC-S526-02 Visible Signal Device for Fire Alarm Systems, suitable for indoor and outdoor applications.
When assembled with an available mounting option, the 116DEGEX-FJ is UL Listed for use in Class I, Division 1, Groups C and D, Class I, Division 2, Groups A, B, C and D, Class II, Division 1, Group E, F and G, Class II, Division 2, Group F and G, and Class III Division 1 and 2 hazardous locations. The strobe is UL and cUL Listed as a Type 3R and 4X enclosure.
Standard Features
UL 1971 listed and ADA compliant for the hearing impaired
Negligible in-rush current
Approved for re alarm applications
Wall, ceiling or pendant mount
Diode polarized for use in electronically supervised circuits
High impact glass dome
65 ashes per minute
Can be synchronized
150 cd, wall or ceiling
Factory sealed - no external seals required
Quick connect - threads onto mounting module for easy instal-
lation
Epoxy powder coat for corrosion resistance
ULC-S526-02 listed for indoor and outdoor applications
Hazardous Location Strobes
116DEGEX-FJ
Wall
Mount
Pendant
Mount
Ceiling Mount
Data Sheet 518-21 Issue 1
Not to be used for installation purposes. Page 1 of 6
Application
NOTE: DC polarity of circuit shown in supervisory state (signal inactive). Circuit polarity to reverse to activate signal.
Electrical supervision requires wire run to be broken at each device. Device for constant input voltage. Do not connect to “coded” or pulsating voltage.
From Power Source
or
Previous Signaling Device
End-of-Line Resistor, when required with supervised system
KEY:
Light symbol -
Wire nut symbol -
(+)
White
(+)
White
(+)
White
(+)
White
Black
(-)
Black
(-)
Black
(-)
Black
(-)
Series
116DEGEX
Series
(+)
(-)
116DEGEX
116DEGEX-FJ hazardous location strobes are designed for use in compatible Edwards re alarm systems and other applications requiring electrical supervision of signaling circuit eld wiring.
These strobes are suitable for many locations including mines, gra­naries, our mills, tankers, reneries, laboratories and other applica­tions where environmental hazards may be present. 116DEGEX-FJ
strobes are particularly well-suited in areas of high noise levels where standard bells or horns are not satisfactory.
When pendant, wall or ceiling mounted, 116DEGEX-FJ strobes are ULC-S526-02 listed for indoor and outdoor applications and UL 1971 Listed (ADA compliant) for indoor visual signaling applications in non-sleeping areas.
Wiring
For non-re alarm use, i.e., without eld wire supervision, installer can tie the two white leads together and tie the two black leads together.
Notes:
1. DC Polarity of circuit shown in supervisory state (signal inactive). Circuit polarity to reverse to activate signal.
2. Electrical supervision requires wire run to be broken at each device.
3. Device for constant input voltage. Do not connect to “coded” or pulsating voltage.
4. For non-re alarm use, i.e., without eld wire supervision, the installer can tie the two white leads together and tie the two black leads together.
Hazardous Location Listings
Operating Temperature
Ambient
Temperature
40C (104F) 75C (167F) T2D (215C, 419F) T6 (85C, 185F) T4A (120C, 248F) T4A (120C, 248F)
55C (131F) 90C (194F) T2C (230C, 446F) T6 (85C, 185F) T4 (135C, 275F) T4 (135C, 275F)
65C (149F) 105C (221F) T2C (230C, 446F) T6 (85C, 185F) T3C (135C, 275F) T3C (135C, 275F)
Supply Wire
Temperature Marking
Class I, Div. 2
Groups A, B
Class I, Div. 1 & 2
Groups C, D
Class II, Div. 1
Groups E, F, G, & Class III
Not to be used for installation purposes. Page 2 of 6
Class II, Div. 2
Groups F, G, & Class III
Data Sheet 518-21 Issue 2