VISUAL SIGNALS
Compaxx® Series
Strobes
PLC Compatible
Type 4X
FEATURES
> Type 4X Enclosure
> Two Mounting Configurations -
Surface and Conduit
> 175,000 peak candela
> 12 inch (305mm) wire leads
> Black Impact Resistant
Polycarbonate ABS Blend Base
> Five Lens Colors
> Available in Quantity Packaging (6)
AGENCY APPROVALS
> UL 1638 Listed
> cUL Listed
> UL Listed Type 4X
114
The Edwards 114 Series Strobes are designed for applications in
industrial, commercial, and institutional applications where reliable
and distinctive visual indication is required. The 114 Series is ideal
for process control as well as vehicular applications such as tow
motors. The strobe units provide a bright visual indication by utiliz-
ing a linear strobe tube inside a shatter resistant polycarbonate
fresnel lens.
Suitable for indoor or outdoor installation. When mounted outdoors
the unit should be mounted with the lens facing up. Two mounting
configurations are available:
(†)
ST Series
• The 114S, a surface mount version that utilizes a mounting
gasket and locknut to provide a secure surface attachment and
seal
• The 114P, a pipe mount version for mounting on 1/2" (13mm)
NPT conduit.
SPECIFICATIONS
> Replaceable Linear Strobe Tube
Powered at 1.75 Joules
> 12 to 48 VDC, 120V AC or 240V AC
Operation
D-04
3-104
Edwards strobe lights are particularly effective in high noise areas
where ear protection must be worn and audible signals may not be
heard or understood. They can advise personnel in manufacturing,
process control and warehouse areas when an operation is starting
or stopping or a vehicle is moving. They are also often used to sig-
nal equipment malfunction and to warn personnel that they are en-
tering restricted areas.
† Insert "S" for surface mount, "P" for pipe mount
© Copyright 2004 Edwards
VISUAL SIGNALS
TECHNICAL INFORMATION
3 7/8"
Gasket (provided in the 114S
for surface mounting)
Internally threaded in the 114P
for 1/2" (13mm)pipe mounting
3 1/4"
(82.6mm)
Lens Replacement Strobe Peak Electrical
Cat. No. Co lor Lens Cat. No. Tube Candlepower Ratings Mounting
114SSTA-EK** Am
ber 104-LA 114-ST 175,000 24V DC Surface
114SSTB-EK** Blue 104-LB 1,500 hr* 0.350 Amps Surface
114SSTC-EK** Clear 104-LC Surface
114SSTG-EK** Green 104-LG Surface
114SSTR-EK** Red 104-LR Surface
114PSTA-EK** Amber 104-LA 114-ST 175,000 24V DC 1/2" NPT Pipe
114PSTB-EK** Blue 104-LB 1,500 hr* 0.350 Amps 1/2" NPT Pipe
114PSTC-EK** Clear 104-LC 1/2" NPT Pipe
114PSTG-EK** Green 104-LG 1/2" NPT Pipe
114PSTR-EK** Red 104-LR 1/2" NPT Pipe
114SSTA-N5** Amber 104-LA 114-ST 175,000 120V AC 50/60 Hz Surface
114SSTB-N5** Blue 104-LB 1,500 hr* 0.10 Amps Surface
114SSTC-N5** Clear 104-LC Surface
114SSTG-N5** Green 104-LG Surface
114SSTR-N5** Red 104-LR Surface
114PSTA-N5** Amber 104-LA 114-ST 175,000 120V AC 50/60 Hz 1/2" NPT Pipe
114PSTB-N5** Blue 104-LB 1,500 hr* 0.1 Amps 1/2" NPT Pipe
114PSTC-N5** Clear 104-LC 1/2" NPT Pipe
114PSTG-N5** Green 104-LG 1/2" NPT Pipe
114PSTR-N5** Red 104-LR 1/2" NPT Pipe
114SSTA-R5** Amber 104-LA 114-ST 175,000 120V AC 50/60 Hz Surface
114SSTB-R5** Blue 104-LB 1,500 hr* 0.10 Amps Surface
114SSTC-R5** Clear 104-LC Surface
114SSTG-R5** Green 104-LG Surface
114SSTR-R5** Red 104-LR Surface
114PSTA-R5** Amber 104-LA 114-ST 175,000 120V AC 50/60 Hz 1/2" NPT Pipe
114PSTB-R5** Blue 104-LB 1,500 hr* 0.1 Amps 1/2" NPT Pipe
114PSTC-R5** Clear 104-LC 1/2" NPT Pipe
114PSTG-R5** Green 104-LG 1/2" NPT Pipe
114PSTR-R5** Red 104-LR 1/2" NPT Pipe
*Calculated strobe tube life at operating power to 75% efficiency.
** For package quantities of 6 strobes add "-6" to the catalog number. e.g. 114SSTA-EK-6
(98.4mm)
Locknut - 1.3625" O.D. (provided
in the 114S for surface mounting)
SIGNAL INPUT LOAD CHARACTERISTICS***
Operating Max. off state Continuous on Surge (inrush/duration)
Cat. No. Voltage leakage current (mA) Current (mA) Amps/milliseconds
114-EK Series 24V DC 7 350 .45/.02
***This device is PLC compatible and may be operated by PLCs with output characteristics that match the input load requirements of this signal.
© Copyright 2004 Edwards
D-04
3-105