Installation Instructions for 108 Series Chameleon
Multi-Status Indicator
Description
The Edwards Chameleon Multi-Status Indicator is a UL and cUL
listed, multi-color LED signaling appliance. The enclosure is
Type 3R, 4X and IP65 rated.
The lights are available in 24V DC and 120V 50/60 Hz. They are
available in either red, blue and amber or red, green and amber.
A pipe mount kit, Cat. No. 102PMF (sold separately) and one of
three extension pipes (sold separately) allows the status indicator
to be raised above the mounting surface for increased visibility.
The lights are designed such that any one or all three lights can be
activated by either a PLC or contact closure. The first light activated will illuminate either steady or flashing (set by the internal
jumper). If a second light is activated, the Chameleon cycles
between the two colors. A third activation causes the Chameleon
to cycle between all three colors: red, amber and green or red,
amber and blue.
The Chameleon also features a multi-tone base module that allows the installer to select one of eight available tone options.
The selected tone can be operated as a fourth signal or used in
conjunction with any of the LED signals.
The Chameleon is also available with two shorter bases that are
used when a lower profile is desired: one for surface mounting and
one for pendant mounting. The shorter bases do not allow for use
of a tone module.
An additional light module can be used on the Chameleon. For
available lens modules and light sources, refer to Table 4.
PLC Compatibility
The electrical input characteristics for PLC compatible signals are
listed in Table 2. Signals with these characteristics may be directly connected to PLC output cards that do not exceed these
input characteristics.
Installation
Installation must be in accordance with the latest edition of the
National Electrical Code and other governing standards and codes
for standard installation.
WARNINGS
To prevent electrical shock, do not connect power
until instructed to do so.
To prevent abrasion of wiring insulation, ensure
that wire passage holes are adequately protected.
1.If using the 102PMF mounting kit, perform the following:
NOTE: All references below are to Figure 5.
a.Using the supplied gasket (D) as a guide, mark the four
mounting holes and the center clearance hole on an
appropriate surface.
b.Punch the four mounting holes. Punch the wiring
clearance hole in the mounting surface to be sufficiently
larger than that in the gasket to ensure the wiring
insulation is protected from abrasion by the gasket
(without interfering with the mounting screw holes), or
provide other appropriate wire insulation abrasion
protection as needed.
c.Screw the pipe extension (purchased separately) into the
mounting flange.
d.Ground the flange by pulling the ground wire through
the mounting surface clearance hole and center hole of
the gasket. Connect earth ground to the bottom of the
base mount flange using the ground screw (G) and wire
retention terminal cup washer (H).
e.Pull the remaining field wiring through center clearance
hole of mounting surface, center hole of the gasket, pipe
mount flange and extension pipe.
f.Align the mounting gasket (D) and flange (A) on the
panel. Secure using (4) #10-24 x 1" (25 mm) pan head
screws (B), (4) external tooth #10 star washers (E) and
(4) #10-24 hex nuts (F).
g.Mount the base as instructed below.
2.If not using the 102PMF mounting kit, install base on 3/4"
(19 mm) conduit (not supplied). Pull field wiring through
conduit entrance hole.
3.If not using the 102PMF mounting kit, mount using the
appropriate method below.
NOTE: For indoor applications, the base ma y be panel
mounted or conduit mounted. For NEMA3R, 4X, and
outdoor applications, it is recommended that either the
108IP or 108I series be used.
a.Cat. Series 108I Install base on 3/4" (19 mm) conduit
(not supplied). Pull field wiring through conduit entrance
hole.
b.Cat. Series 108IP Install base on 3/4" (19 mm) conduit
(not supplied). Pull field wiring through conduit entrance
hole.
c.Cat. Series 108ID Using the supplied mounting gasket
as a template, punch the four mounting holes. Punch the
wiring clearance hole in the mounting surface to be
sufficiently larger than that in the gasket to ensure the
wiring insulation is protected from abrasion by the gasket
(without interfering with the mounting screw holes), or
provide other appropriate wire insulation abrasion
protection as needed. Mount the base to the surface using
the (2) screws (supplied).
4.Connect field wiring.
a.Cat. Series 108I Connect field wiring to the terminal
block as shown in Figure 1.
Connect additional field wiring to the terminal block
mounted on the signal assembly as shown in Figure 2.
NOTE: The tone module may be wired to sound independently
or in conjunction with an LED signal.
T o sound tone module independently , connect to separate
hot lead.
To sound tone module with a particular light source,
connect horn hot terminal to selected light terminal on
the terminal block.
b.Cat. Series 108IP or Cat. Series 108ID Using wire nuts,
connect 18" (457 mm) wire leads to field wiring. The
wire leads are marked as follows: Neutral, Red, Blue (for
models with Red, Amber and Blue LEDs) or Green (for
models with Red, Amber and Green LEDs), Amber, and
2nd Module.
5.If using a second module, install as follows (see Figure 4):
a.Loosen the captive screw in the cap and remove the cap
from the unit.
b.Pull the captive key in the second lens module into the
"out" position.
c.Place the second lens module on top of the first.
d.Push in the captive key to secure the lens module.
WARNING
To prevent leakage, ensure the magnifier ring on the
lens cover and the magnifier ring on the lens module
are aligned (Figure 4).
NOTE: When using LED light sources, ensure that the color of
the LED light source and the lens assembly match.
f.Place the lens assembly cover on the front of the lens
module and secure using two captive screws.
g.Replace the cap on top and secure the cap with the captive
screw.
6.If using the Cat. No. 108I, set the selected tone. See Table 3
and Figure 3.
7.Apply power to the unit and verify proper operation.
e.Insert the light source into board grooves at bottom of
lens module, ensuring that the four prongs on the PC
Maintenance
board are aligned with the plug located in the back of the
lens assembly.
The lens surfaces should be periodically dusted and cleaned with
a dry soft clean cloth to maintain optimum light visibility. If
necessary , the outside of the lens may be cleaned with water and a
mild detergent on a well rung-out, soft, clean cloth.
*Signifies lens module color (A - amber, B - blue, C - clear , G - green, R - red)
**Signifies lens and LED module color (A - amber, B - blue, G - green, R - red) NOTE: LED light sources must be used with the cooresponding color lens module
(e.g., a blue LED light source, 102LS-SLEDB-G1, must be used with a blue lens, 102LM-B).
***A non-halogen lamp, as listed, may be used in place of the halogen lamp.
#
At nominal operating voltage.
##
Projected lamp life based on manufacturer's calculated lamp life @ 65 fpm and 50% duty cycle.
###
Strobe tube life @ operating power to 75% efficiency .
##
7 1/4"
(184mm)
1/2"
(13mm)
3 5/8"
(92mm)
3 5/8"
(92mm)
3"
(76mm)
Cap
Magnifier
Ring
Board
Groove
Light Source
Assembly
Signal Base
Lens Module
Cover
(2) Captive
Screws
P/N 3100178 ISSUE 3
Figure 4. Dimensional Drawing (108I Series shown)
Page 5
C
(4) o-rings
(4) #10-24 x 1" (25 mm)
B
pan head screws
A
Cat. No. 102PMF
Pipe mount flange
H
Wire retention
terminal cup washer
G
#10-16 x 3/8"
Pan head, thread forming,
ground ( ) screw
D
Mounting gasket
F
#10-24 Hex nut
E
External tooth
#10 Star washer
Figure 5. Optional 102PMF Mounting Kit Assembly
P/N 3100178 ISSUE 3
Page 6
Installation Instructions for 108 Series Chameleon
DeviceNet Status Indicating Lighting System
Description
The Edwards Chameleon DeviceNet Status Indicating Lighting System is a unique audible-visual signaling device that
combines three LED visual and eight audible signals in one compact housing.
The Chameleon also features a multi-tone base module that contains eight tone options. The selected tones can be
operated as independent signals or used in conjunction with any of the LED signals.
All components of the Lighting System are UL listed subassemblies and cUL Listed. The enclosures are NEMA 3R, NEMA
4X and IP65 Rated. The unit has been tested by ODVA's authorized independent test lab and found to comply with
ODVA conformance test software.
The lens module contains a removable cover to allow for easy relamping. The lens module cover features a molded-in
gasket for weather tight reliability.
See Tables 1 and 2 for specification information.
Device Profile
Revision1.00
Firmware Revision1.00
The DeviceNet interface is in the unit's base which interfaces between the network and the modules.
The Chameleon DeviceNet Status Indicator is a slave device. It is a general purpose status indicator designed to indicate
the status of a machine or process.
Power to drive the LED light sources may be taken locally or from the DeviceNet Network. A standard open style 2 pin
connector is used to connect 24V DC @ 0.105A (max) or 120V AC @ 0.12A (max).
The unisolated physical layer contains DeviceNet required mis-wiring protection circuitry. A standard open style (unsealed) 5 pin connector is used to connect the Status Indicator to the DeviceNet bus. The current draw from the bus is
0.12A.
The Chameleon DeviceNet Status Indicator contains a preprogrammed microcontroller which implements the Group 2
pre-defined Master/Slave Connection Set. This allows for one Explicit Messaging Connection and one Poll Connection.
The objects (classes) supported are described in the next section. The Chameleon Status Indicator resets automatically
when DeviceNet power is applied.
Identity (1)Supports the reset service
Message Router (2)No effect
Devicenet (3)Configures port attributes
Assembly (4)I/O assembly for lamps
Connection (5)Establishes the number of connections
There is a single instance of the identity object for the Chameleon DeviceNet Status Indicator. No class attributes
are supported. All of the instance attributes are contained in rom and are gettable but not settable. The table
below shows the values.
Get Attribute Single0x0EAttribute ID
Reset0x050, 1
P/N 3100179 ISSUE 1PAGE 3
Page 9
2.2Message Router Object (Class ID = 2).
There is no externally visible interface to the Message Router Object.
2.3DeviceNet Object (Class ID = 3).
There is a single instance of the DeviceNet Object for the Chameleon DeviceNet Status Indicator.
DeviceNet Object Class Attributes:
ATTRIBUTEACCESSDATA
IDRULESNAMETYPEVALUE
1GetRevisionUint0x0002
DeviceNet Object Class Services:
SERVICESERVICE CODEPARAMETERS
Get Attribute Single0x0EAttribute ID
DeviceNet Object Instance Attributes:
ATTRIBUTEACCESSDATA
IDRULESNAMETYPEVALUE
1GetMacidUintDipswitch
2GetBaud rateUSINTDipswitch
3GetBOIBOOL0x01 Auto-Reset 0x00 Hold
4Get/SetBus off counterUSINT0x00 (Set) Value (Get)
5GetAllocation infoSTRUCTAllocate Serv
DeviceNet Object Instance Services:
SERVICESERVICE CODEPARAMETERS
Get Attribute Single0x0EAttribute ID
Set Attribute Single0x10Attribute ID
Allocate0x4BAllocation Choice Master MACID
Release0x4CRelease Choice
2.4Assembly Object (Class ID = 4)
There is a single instance of the Assembly Object for the Chameleon DeviceNet Status Indicator. No class attributes
or services are supported for the Assembly Class.
Assembly Object Instance Attributes:
ATTRACCESSDATA
IDRULESNAMETYPEVALUE
3Get/SetDataStructSee Sect 1.5
Assembly Object Instance Services:
SERVICESERVICE CODEPARAMETERS
Get Attribute Single0x0EAttribute ID
Set Attribute Single0x10Attribute ID
P/N 3100179 ISSUE 1PAGE 4
Page 10
2.5Connection Object (Class ID = 5).
There are two instances of the Connection object. Instance #1 is assigned to the Explicit Messaging Connection.
Instance #2 is assigned to the Polled I/O Connection. The following table shows the attributes and the predefined values where applicable. No class attributes are supported.
9Get/SetExpected packet rateUINTApplication dependent
10N/AN/AN/ANot used
11N/AN/AN/ANot used
12Get/SetWatchdog timeout actionUSINT(0x00 Default) 0, 1, 2
13GetProduced path lengthUINT0x0006
14GetProduced pathARRAY OF USINT20.04.24.01.30.03
15GetConsumed path lengthUINT0x0006
16GetConsumed pathARRAY of USINT20.04.24.01.30.03
Connection Object Services:
SERVICESERVICE CODEPARAMETERS
Get Attribute Single0x0EAttribute ID
Set Attribute Single0x10Attribute ID
P/N 3100179 ISSUE 1PAGE 5
Page 11
Installation
WARNING
To prevent electrical shock, do not connect power
until instructed to do so.
Safety Message to Installers, Users, and Maintenance Personnel
The Chameleon DeviceNet Status Indicator must be installed in accordance with the latest edition of the National
Electrical Code and/or other applicable local regulations, by a trained and qualified electrician. The selection of the
mounting location, its controls and the routing of the wiring is to be accomplished under the direction of the facilities
engineer.
WARNING
To prevent electrical shock, do not connect to the
system when power is on.
NOTE: For NEMA 4X applications, it is recommended that the unit be conduit mounted vertically facing up.
1. If not using the optional 102PMF mounting kit, mount the base by installing on 3/4" (19 mm) conduit (not supplied).
Pull field wiring (if required) and DeviceNet wiring through the conduit entrance hole.
1. If using the 102PMF mounting kit, perform the following:
NOTE: All references below are to Figure 1.
a. Using the supplied gasket (D) as a guide, mark the four mounting holes and the center clearance hole on an
appropriate surface.
b. Punch the four mounting holes. Punch the wiring clearance hole in the mounting surface to be sufficiently
larger than that in the gasket to ensure the wiring insulation is protected from abrasion by the gasket (without
interfering with the mounting screw holes), or provide other appropriate wire insulation abrasion protection as
needed.
c.Screw the pipe extension (purchased separately) into the mounting flange.
d. Ground the flange by pulling the ground wire through the mounting surface clearance hole and center hole of
the gasket. Connect earth ground to the bottom of the base mount flange using the ground screw (G) and wire
retention terminal cup washer (H).
e. Pull the remaining field wiring through center clearance hole of mounting surface, center hole of the gasket,
pipe mount flange and extension pipe.
f.Align the mounting gasket (D) and flange (A) on the panel. Secure using (4) #10-24 x 1" (25 mm) pan head
screws (B), (4) external tooth #10 star washers (E) and (4) #10-24 hex nuts (F).
g. Mount the base as instructed below.
Network & Field Connections
CAUTION
Observe precautions for handling electrostatic
sensitive devices while handling printed cir cuit
boards.
P/N 3100179 ISSUE 1PAGE 6
Page 12
WARNING
To avoid electrical shock hazards, do not connect
wires when power is applied.
1. Make DeviceNet connections to the 5 position female terminal block plug as indicated in the below table. The 5
DeviceNet bus terminals are silkscreened near the terminals on the printed circuit board. Make connections as
follows:
2. A two (2) position screw terminal is provided to connect separate 24V DC light source operating power to the
Chameleon DeviceNet Status Indicator. The terminals for the 24V DC unit are labeled as "+" and "-". Make
connections as follows:
3. If it is desired to power the light sources from DeviceNet power, jumper (V+) and (V-) on the 5 position DeviceNet
terminal block to (+) and (-) respectively on the 2 position screw terminal.
Set DIPSWITCH S1 for the BAUD RATE and MAC ID required as follows:
Note the legend on the dipswitch for the sense of 0 and 1 (0 = OFF and 1 = ON)
SW1SW2SW3SW4SW5SW6SW7SW8
BAUD RATE - 125 Kbps00
BAUD RATE - 250 Kbps01
BAUD RATE - 500 Kbps10
BAUD RATE - 125 Kbps11
MAC ID 0000000
MAC ID 1000001
MAC ID 2000010
MAC ID 3000011
MAC ID 4000100
MAC ID 5000101
MAC ID 6000110
MAC ID 7000111
MAC ID 8001000
MAC ID 9001001
MAC ID 10 (0x0A)001010
MAC ID 11 (0x0B)001011
MAC ID 12 (0x0C)001100
MAC ID 13 (0x0D)001101
MAC ID 14 (0x0E)001110
MAC ID 15 (0x0F)001111
MAC ID 16 (0x10)010000
MAC ID 17 (0x11)010001
MAC ID 18 (0x12)010010
MAC ID 19 (0x13)010011
MAC ID 20 (0x14)010100
MAC ID 21 (0x15)010101
MAC ID 22 (0x16)010110
MAC ID 23 (0x17)010111
MAC ID 24 (0x18)011000
MAC ID 25 (0x19)011001
MAC ID 26 (0x1A)011010
MAC ID 27 (0x1B)011011
MAC ID 28 (0x1C)011100
MAC ID 29 (0x1D)011101
MAC ID 30 (0x1E)011110
P/N 3100179 ISSUE 1PAGE 8
Page 14
SW1SW2SW3SW4SW5SW6SW7SW8
MAC ID 31 (0x1F)011111
MAC ID 32 (0x20)100000
MAC ID 33 (0x21)100001
MAC ID 34 (0x22)100010
MAC ID 35 (0x23)100011
MAC ID 36 (0x24)100100
MAC ID 37 (0x25)100101
MAC ID 38 (0x26)100110
MAC ID 39 (0x27)100111
MAC ID 40 (0x28)101000
MAC ID 41 (0x29)101001
MAC ID 42 (0x2A)101010
MAC ID 43 (0x2B)101011
MAC ID 44 (0x2C)101100
MAC ID 45 (0x2D)101101
MAC ID 46 (0x2E)101110
MAC ID 47 (0x2F)101111
MAC ID 48 (0x30)110000
MAC ID 49 (0x31)110001
MAC ID 50 (0x32)110010
MAC ID 51 (0x33)110011
MAC ID 52 (0x34)110100
MAC ID 53 (0x35)110101
MAC ID 54 (0x36)110110
MAC ID 55 (0x37)110111
MAC ID 56 (0x38)111000
MAC ID 57 (0x39)111001
MAC ID 58 (0x3A)111010
MAC ID 59 (0x3B)111011
MAC ID 60 (0x3C)111100
MAC ID 61 (0x3D)111101
MAC ID 62 (0x3E)111110
MAC ID 63 (0x3F)111111
4. Connect the five position female connector on the tone module to the upper set of male pins in the Chameleon
DeviceNet Status Indicator. Set the selected tone in accordance with the table below. Set the third Byte (Data Byte
2) in accordance with the table below in order to access the required tone. "X" is the "Don't Care" State.
Switch Settings*
ToneBit3Bit2Bit1Bit0
Tone Off0XXX
Stutter Beep1000
Continuous1001
3 Pulse Horn1010
Rapid Siren1011
Hi/Lo1100
Fast Whoop1101
Yeow1110
Beep1111
*1 is ON. 0 is OFF.
P/N 3100179 ISSUE 1PAGE 9
Page 15
5. Install the front cover or the optional multi-tone module by tightening the two captive front screws.
6. Test the Chameleon DeviceNet Status Indicator to ensure that it operates as intended.
To test the device for functionality the unit must be connected to a DeviceNet network via the five (5) pin connector.
Turn on the network power supply and local power (if so configured) for the lamps. All lamps will flash
instantaneously (some lamps may not be visible) as the unit checks for proper lamp operation. The value of the
data byte in the master poll will be displayed on the lamps until it is changed by subsequent poll command. The
pre-defined poll connection has consume size of three (3) bytes, and a produce size of three (3) bytes. When all the
connections are released the lamps will display the last poll command data before release of the connection.
7. The following is an Output Data Byte example
Byte 2
0000 1 001
Set
Tone
On
Set
Tone
Value 1
Byte 1
000 00001
Set
Flash
Rate =
8OFPM
Set
LED1 to
Flashing
8. The following is an Input Data Byte example:
Byte 2
0000 1001
Sounder is
ON with
Tone
Value 1
Byte 1
XXX 00011
Lamp 2
was ON
before last poll
command
Byte 0
XXX 00001
LED 1 is
burned
out or
missing
Maintenance
The lens surfaces should be periodically dusted and cleaned with a dry soft clean cloth to maintain optimum light
visibility. If necessary, the outside of the lens may be cleaned with water and a mild detergent on a well rung out soft
clean cloth.
Table 1. Chameleon DeviceNet Status Indicator Specifications
ElectricalLamp Life
Catalog No.Ratings(Hours)
108-DN-RGA-G124V DC, 0.105 A100,000
108-DN-RBA-G1
108-DN-RGA-N5120V AC, 0.12A100,000
108-DN-RBA-N5
Table 2. Pertinent DeviceNet Specifications
Operating DeviceNet Bus Current0.12A
Current Draw supplied by separate power supply (per Light Module)DC: 0.062 to 0.320A
AC: 0.022 to 0.120A
In-Rush Current supplied by separate power supply (per Light Module)DC: 1.2A
AC: 0.5A
Flash Rate (selectable via second data byte of POLL command)45, 60 or 80 fpm
Operating Temperature32F to 158F (0C to 70C)
P/N 3100179 ISSUE 1PAGE 10
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.