Edwards Signaling 105XBRi User Manual

Page 1
Installation Instructions for Rebel ChameleonTM
105XBRi Series LED Multi-Status Indicator in
NEMA 4X Enclosures
Description
The 105XBRi Series Chameleon Multi-Status LED Indicator is a UL and cUL listed, multi-color LED signaling appliance which, when assembled in accordance with these installa­tion instructions, constitute a UL Listed Type 4X enclosure and are UL Listed for Marine Use. They are designed for use in industrial applications or in applications where a Type 4X enclosure is required. When assembled in accordance with these instructions, the 105XBRi series visual signals are UL Listed for use in Division 2 Hazardous Locations as described in Table 1.
The lights are available in 24V DC and 120V 50/60 Hz. They are available in either Red/Blue/Amber or Red/Green/Amber.
Edwards Signaling's NEW 105XBRi Multi-status Indicator is more "chameleon-like" than ever. With our new adaptive design - one device does it all. With a quick change to the new 105 Chameleon's dip switch settings, these exible multi-status indicators instantly adapt for use with or without control from an external PLC, PAC, or control relay. Now, regardless of the application you will have just the right device for the job with only half the inventory.
XTRA-SAFE Enabled
The Chameleon 105XBRi devices ship as standard with Edwards Signaling's XTRA-SAFETM Technology (patent pending) Enabled. XTRA-SAFE multi-status indicating devices employ patented combinations of color AND ash­rate to provide more denite status indication to those who are color-blind. With XTRA-SAFE, when Chameleon multi­status indicators are turned red, they pulse at a rate of 240 ashes per minute, further emphasizing the urgency which the color red typically connotes. When amber, these devices pulse at a "less urgent" rate of 120 ashes per minute. When Chameleon multi-status indicators are turned blue or green and no other colors are energized, the Chameleon devices remain "steady-on" and do not ash. Even in extreme cases where no color is perceived, ash-rate variation provides a redundant layer of visual indication.
Red: 240 FPM
Amber: 120 FPM
Green or Blue: 65 FPM
XTRA-SAFE Disabled
Externally Controlled
The Chameleon multi-status indicators can also be used in applications where they will be controlled "externally" us­ing a Programmable Logic Controller (PLC) or other such external controller. When externally controlled by a PLC, activation of colors and ash-rate are fully customizable, and can be programmatically determined. In applications, where multiple colors are activated simultaneously, the lights operate on a priority with red highest, amber second and blue or green, the lowest. Refer to Figure 1 (Applications WITH a separate PLC or Controller).Wire color corresponds with each indicated color.
Red wire = Red LED's
Yellow wire = Amber LED's
Blue with Green tracer wire = Green or Blue LED's
Table 1. Hazardous Location Ratings
Cat. No. Class Division Group Operating Temperature
105XBRiRGA24D 105XBRiRGA120A
105XBRiRBA24D 105XBRiRBA120A
http://www.edwardssignaling.com Phone: (800) 336-4206 Fax: (800) 454-2363
I 2 A, B, C, D T5 (100C, 212F)
II 2 F, G T5 (100C, 212F)
III T5 (100C, 212F)
I 2 A, B, C, D T6 (85C, 185F)
II 2 F, G T6 (85C, 185F)
III T6 (85C, 185F)
P/N 3101612 ISSUE 3
© 2010
Page 2
Electrical Specications
WARNING
To prevent electrical shock, ensure that power is turned off before installing the signal.
Catalog Number Electrical Specs
Red, Green, Amber
105XBRiRGA24D 24V DC, 0.150 A
105XBRiRGA120A 120V AC*, 0.100 A
Red, Blue, Amber
105XBRiRBA24D 24V DC, 0.150 A
105XBRiRBA120A 120V AC*, 0.100 A
* 120V AC 50/60 Hz
Installation
Installation must be in accordance with local codes. The lens should be positioned up for outdoor applications.
WARNINGS
The 105BX junction box, 105BM mounting bracket and 105PM pipe mount attachments are non-conductive plastic xtures and do not provide earth-ground continuity when attached to metallic wiring systems. Therefore, they are intended for use with the 105XBRi series visual signals only when earth-grounding is not required.
The 105BX junction box, 105MB mounting bracket and 105PM pipe mount attachments can be used with metallic wiring systems only when installed at the end of the run.
3. Install the mounting attachment as follows:
a. Cat. No. 105BX: Secure the outlet box attachment to
the mounting surface using two screws (not supplied) suitable for the surface. Attach the adhesive backed gasket to the top of the 105BX mounting box, being careful to line up the holes in the gasket with the mounting holes in the outlet box.
WARNING
To avoid risk of injury, install lens before energizing the unit and do not remove or insert light source when unit is energized.
WARNING - EXPLOSION HAZARD
Do not disconnect equipment unless power has been removed or the area is known to be non-hazardous.
WARNING
To prevent electrical shock, do not connect power until instructed to do so.
1. Select a mounting conguration (Figure 3).
NOTE: WhenmountingusingtheCat.No.105BM
mountingbracket,theCat.No.105BXoutlet boxattachmentmustalsobeusedasshownin Figure1.
2. Pu ll field wiring fro m conduit into the moun ting attachment.
Table 2. PLC Compatibility
Catalog Number
105XBRiRGA24D 24V DC 5 mA 150 mA 28.5 A / 65 μSeconds
105XBRiRBA24D
105XBRiRGA120A 120V AC 50/60 Hz 5 mA 100 mA 28.5 A / 212 μSeconds
105XBRiRBA120A
Operating
Voltage
Max. off state leak-
age current
b. Cat. No. 105BM: Using the four supplied screws,
secure the mounting bracket to Cat. No. 105BX outlet box attachment as shown in Figure 1. Attach the adhesive backed gasket to the top of the 105BM mounting bracket, being careful to line up the holes in the gasket with the mounting holes in the outlet box. Refer to Figure 1.
c. Cat. No. 105PM: Install 3/4" (19 mm) conduit.
Screw the pipe mount attachment onto the 3/4" (19 mm) conduit. Attach the adhesive backed gasket to the top of the 105PM pipe mount attachment, being careful to line up the holes in the gasket with the mounting holes in the outlet box as shown in Figure
2.
4. Mount 105XBRi Series as follows. Unscrew the gasketed base from the lens assembly as shown in Figures 1 and 2 and remove the clear gasket from around the base.
5. Secure the base to the appropriate mounting attachment using four screws (supplied). Replace the clear gasket on the base with the ared, open end facing down.
Continuous on
current Surge (inrush/duration)
P/N 3101612 ISSUE 3
Page 3
105-LC Lens
(4) Countersunk screws to mount lens to 105BM (supplied)
Gasket
Adhesive backed gasket
105BM Mounting Bracket
(4) Screws to mount 105BM to 105BX (supplied)
Adhesive backed gasket
(2) Screws to mount 105BX to the mounting surface
Mounting Surface
105BX Outlet Box Attachment
105-LC Lens
Figure 1. Mounting Cat. No. 105BM Mounting Bracket
Mounted on a Cat. No. 105PM Pipe
Mount Attachment
Mounted on a Cat. No. 105BX Outlet Box
Attachment
LED Light Source
OFF
1
2
OFF
Dipswitch
Beacon Base
Gasket
Adhesive backed gasket
105PM Pipe Mount Attachment
3/4" (19 mm) conduit nipple
ON
ON
Figure 2. Securing the Beacon to the Mounting Attachment
(Pipe Mount Attachment shown)
Mounted on a Cat. No. 105BM Mounting
Bracket with the
Cat. No. 105BX Outlet Box
Attachment
Figure 3. Mounting Congurations
Table 3. Replacement Parts
Catalog Number Replacement Lens Replacement Lamp
105XBRiRBA24D
105XBRiRGA24D
105XBRiRBA120A
105XBRiRGA120A
*Median LED Life (L70) based on manufacturer's projections. Refer to http://www.philipslumileds.com/pdfs/WP15.pdf.
105-LC The 148,000 hour** lamp is
permanently installed.
105-LC
The 148,000 hour** lamp is
permanently installed.
P/N 3101612 ISSUE 3
Page 4
6. Wire the beacon as follows (Figure 5).
b. Set dipswitches for desired options (Figure 4)
a. For AC models: There are four 24" wire leads: white
(AC neutral), red (for activation of red LEDs), blue with green tracer (for activation of green or blue LEDs-­depending on the model) and amber (for activation of amber LEDs). Using wire nuts, connect white lead to AC neutral and connect each of the other three leads to AC hot (120V AC) source.
b. For DC models: There are four 24" wire leads: black
(DC -), red (for activation of red LEDs), blue with green tracer (for activation of green or blue LEDs-­depending on the model), and amber (for activation of amber LEDs). Using wire nuts, connect black lead to DC - and connect each of the other three leads to DC + (24V DC) source.
7. The 105XBRi Multi-Status indicator is shipped with XTRA-SAFETM Technology Enabled. The unit offers two other eld selectable options: (1) for applications without a separate PLC or controller with the XTRA-SAFETM Technology disabled or (2) for applications with a separate PLC or controller. For more information on the features, refer to the description. For settings, refer to Figure 4.
- Appli cations wit hout a separate PLC or Controller - XTRA-SAFE Technology Disabled: Set dipswitch SW1 to the OFF position and SW2 to the ON position.
XTRA-SAFE Disabled
- Applications with a separate PLC or Controller - Set dipswitches SW1 and SW2 to the OFF position.
With a PLC or other External Controller
XTRA-SAFE Enabled
a. Unscrew the lens from the bottom of base (Figures 1
and 2) and remove lens.
Applications WITHOUT a PLC or Controller* ­XTRA-SAFE Technology Enabled (Factory Default)
*It is generally recommended that both dipswitches, SW1 and SW2, be set to OFF for applications using an external Programmable Logic Controller (PLC) or other external controller. A PLC or controller, how­ever, can be used with any of the shown configurations.
8. Ensuring that the light source is in place, screw the lens back on the base.
9. Apply power and verify operability.
Applications WITHOUT a PLC or Controller* ­XTRA-SAFE Technology Disabled
Applications WITH a PLC or Controller*
P/N 3101612 ISSUE 3
Figure 4. Dipswitch Settings
Page 5
Maintenance
WARNING
To avoid risk of injury, install lens before energizing the unit.
WARNING
To prevent electrical shock, disconnect power before removing the lens.
Cleaning
The module lens exterior surfaces should be periodically cleaned with a soft clean cloth using water and a mild deter­gent to maintain optimum light visibility. Disconnect power before cleaning.
Lens Replacement
1. Unscrew the lens from the bottom of base (Figures 1 and
2) and remove lens.
2. Ensuring that the light source is in place, screw the lens back on the base.
Blue with Green tracer
(DC + or AC hot for Blue or Green
LED activation (depending on model))
Figure 5. Wiring the 105XBRI Chameleon Series
105-LC Lens
Black (DC -) or White (AC neutral)
Red (DC + or AC hot for Red LED activation)
Amber (DC + or AC hot for Amber LED activation)
Wire Nuts (not supplied)
Power source wires
(2) Screws to mount 105BX to the mounting surface
Mounting Surface
P/N 3101612 ISSUE 3
Loading...