Edwards Signaling 105DHIST-FJ User Manual

Page 1
Installation Instructions for Cat. No. 105DHIST-FJ
Adverse Location Visual Signals
Description
The 105DHISTC-FJ (clear lens only) visual signal is a heavy duty, reliable, 8 Joule high intensity strobe that is both UL 1971 and CSFM listed for Special Application 20-30V DC Hearing Impaired indoor use in compatible fire alarm systems. See Figure 6 for light output patterns and Table 2 for operating current information.
Table 1. Hazardous Location Ratings
Cat. No. Class Division Group Operating Temperature
105DHIST*-FJ I 2 A, B, C, D T2A (280
I I 2 F, G T3B (165oC, 329oF)
I I I T3B (165
*Insert lens color: A - Amber, B - Blue, C - Clear, G - Green, M - Magenta, R - Red.
Installation
WARNING
To prevent electrical shock, do not connect power until instructed to do so.
Installation must be in accordance with local codes. The lens should be positioned up for outdoor applications.
1. Select a mounting configuration (Figure 5).
NOTE: When mounting using the Cat. No. 105BM mounting
bracket, the Cat. No. 105BX outlet box attachment must also be used as shown in Figure 1.
2. Pull field wiring into the mounting attachment.
3. Install the mounting attachment as follows:
WARNINGS
The 105BX junction box, 105BM mounting bracket and 105PM pipe mount attachments are non-conduc­tive plastic fixtures and do not provide earth-ground continuity when attached to metallic wiring systems.
Therefore
105DHIST series visual signals grounding is not required.
, they are intended for use with the
only
when earth-
These strobes, when assembled in accordance with installation instructions, constitute a UL listed Type 4X enclosure. They are designed for use in industrial applications or in applications where a Type 4X enclosure is required. For General Utility (non-fire alarm) use, all units are UL and cUL Listed for Marine and outdoor visual signaling applications. When assembled in accordance with these instructions, 105 Series visual signals are UL listed for use in Haz­ardous Locations with Operating Temperatures listed in Table 1.
For specification details, see Tables 2 - 3.
o
C, 536oF)
o
C, 329oF)
b. Cat. No. 105BM: Using the four supplied screws, secure
the mounting bracket to Cat. No. 105BX outlet box attachment as shown in Figure 1. Attach the adhesive backed gasket to the top of the 105BM mounting bracket, being careful to line up the holes in the gasket with the mounting holes in the outlet box.
c. Cat. No. 105PM: Install 3/4" (19 mm) conduit. Screw the
pipe mount attachment onto the 3/4" (19 mm) conduit. Attach the adhesive backed gasket to the top of the 105PM pipe mount attachment (Figure 3), being careful to line up the holes in the gasket with the mounting holes in the outlet box.
4. Attach the unit's wire leads to the field wiring as shown in Figure 4.
NOTE: It is not necessary to remove the lens from the Hi-
5. Secure the high intensity strobe base to the appropriate
6. Apply power and verify operability.
Intensity Strobe Base to install the 105DHIST series beacons. See Figures 1, 3 or 4.
mounting attachment using four screws (supplied) as shown in Figure 3.
The 105BX junction box, 105BM mounting bracket and 105PM pipe mount attachments metallic wiring systems end of a run.
a. Cat. No. 105BX: Screw the outlet box attachment to the
mounting surface (Figure 1) using two screws (not supplied) suitable for the surface. Attach the adhesive backed gasket to the top of the 105BX mounting box, being careful to line up the holes in the gasket with the mounting holes in the outlet box.
only
when installed at the
can
be used with
P/N 3100394 ISSUE 3 © 2003CHESHIRE, CT 203-699-3300 FAX 203-699-3365 (CUST. SERV.) 203-699-3078 (TECH SERV.)
Page 2
Maintenance
The lens should be periodically cleaned using a mild detergent and water on a soft, clean, lint-free cloth.
Light Source Replacement
WARNING
To prevent electrical shock, before starting work on units disconnect power and, for strobe modules wait 5 minutes for stored energy to dissipate.
1. Unscrew the lens from the base.
CAUTION
Do not touch the strobe tube or halogen bulb with bare fingers. Grasp the light source either by the base or using a soft, clean cloth.
2. For Strobe Tube Replacement:
a. Grasp the strobe tube by its base and pull straight up out
of the strobe tube socket (Figure 2).
b. Grasp the new strobe tube by the strobe tube base and
press into the strobe tube socket.
3. Ensure that the clear gasket is on the base with the flared, open end facing down. Screw the lens onto the base.
4. Apply power and verify operability.
Strobe tube
Strobe tube base
Strobe tube
socket
Figure 2. Strobe Tube Replacement
(4) Screws to mount lens to 105PM (supplied)
105HI-L Series Lens
Hi-Intensity Strobe Base
105-L Series Lens
Beacon Base
Gasket
(4) Screws to mount lens to 105BM (supplied)
105HI-L Series Lens
Hi-Intensity Strobe Base
Adhesive backed gasket
105BM Mounting Bracket
Adhesive backed gasket
(2) Screws to mount 105BX to the mounting surface
Mounting Surface
(4) Screws to mount 105BM to 105BX (supplied)
Figure 1. Mounting Cat. No. 105BM Mounting Bracket
Adhesive backed gasket
105PM Pipe Mount Attachment
3/4” (19 mm) Conduit Nipple
Figure 3. Securing the 105DHIST Series Beacon
to the 105PM Pipe Mount Attachment
P/N 3100394 ISSUE 3
Page 3
NOTE: DC polarity of circuit shown in supervisory state (signal inactive). Circuit polarity to reverse to activate signal. Electrical supervision requires wire run to be broken at each device. Device for constant input voltage. Do not connect to “coded” or pulsating voltage.
(-)
From Power Source
Previous Signaling Device
or
(+)
Red
105DHISTC-FJ 105DHISTC-FJ
Black
(-)
(+)
Red
Black
(-)
(+)
Red
Black
(-)
(+)
Red
Black
(-)
KEY:
Light symbol -
Wire nut symbol -
End-of-Line Resistor, when required with supervised system
(+)
NOTE: For non-fire alarm stand-alone use tie the two red leads together and tie the two black leads together.
Figure 4. Wiring Diagram for the 105DHIST-FJ Series
Table 2. 105DHIST-FJ Series Electrical Specifications
Operating Current* Initial Surge Inrush Current Repetitive Surge Current
Voltage** RMS Current (A) Mean Current (A) Current (A) Time (mS) Current (A) Time (mS)
20V DC 1.08 0.84 2.70 1.10 2.24 450 24V DC 0.95 0.69 2.97 1.13 2.21 400 28V DC 0.85 0.66 3.06 1.24 2.16 381 30V DC 0.83 0.64 3.14 1.27 2.14 360
*Use the operating current to establish the wire gauge and standby power requirements. Consult the control unit manufacturer to determine surge and peak current effects and maximum number of strobes on the system.
**CAUTION: To prevent damage to the visual signal's internal circuit and to assure its continued proper functioning, DO NOT operate the unit outside of the Special Application voltage range of 20-30V DC.
Mounted on a Cat. No. 105PM Pipe
Mount Attachment
Mounted on a Cat. No. 105BX Outlet
Box Attachment
Mounted on a Cat. No. 105BM
Mounting Bracket with the Cat. No. 105BX Outlet Box
Attachment
Figure 5. Mounting Configurations
105DHIST Series
P/N 3100394 ISSUE 3
Page 4
Product Light UL Limit as % of 0 axis rating
12 %
Intensity as %
of UL 0 axis
rating
Intensity
Angle
(Cd) 90 94.4 12 % 363 % 85 58.9 12 % 227 % 80 30.9 12 % 119 % 75 22.2 13 % 85 % 70 21.6 15 % 83 % 65 23.8 16 % 92 % 60 26.6 18 % 102 % 55 28.6 22 % 110 % 50 29.4 27 % 113 % 45 29.6 34 % 114 % 40 29.2 46 % 112 % 35 29.8 65 % 115 % 30 32.2 90 % 124 % 25 31.7 90 % 122 % 20 28.5 90 % 110 % 15 27.0 90 % 104 % 10 24.2 90 % 93 %
5 25.8 90 % 99 % 0 26.0 100 % 100 %
-5 25.8 90 % 99 %
-10 24.2 90 % 93 %
-15 27.0 90 % 104 %
-20 28.5 90 % 110 %
-25 31.7 90 % 122 %
-30 32.2 90 % 124 %
-35 29.8 65 % 115 %
-40 29.2 46 % 112 %
-45 29.6 34 % 114 %
-50 29.4 27 % 113 %
-55 28.6 22 % 110 %
-60 26.6 18 % 102 %
-65 23.8 16 % 92 %
-70 21.6 15 % 83 %
-75 22.2 13 % 85 %
-80 30.9 12 % 119 %
-85 58.9 12 % 227 %
-90 94.4
363 %
Wall Mount, Dome Horizontal, Vertical and Horizontal Viewing Plane
Intensity (Cd)
UL Rating
0o axis looking at
end of dome
UL 1971 Hearing Impaired: 26 cd wall rating
UL 1638 General Utility: 26 cd at 0o axis
90
85
80
100.0
90.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
10.0
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0.0
-55
-60
-65
-70
-75
-80
-85
-90
0
-5
-10
-15
-20
-25
-30
-35
-40
-45
-50
Product Light UL Limit as % of 0 axis rating
UL Limit as % of 0 axis rating
Intensity as %
of UL 0 axis
rating
Product Light Intensity as % of UL 0 axis rating
Intensity
Angle
(Cd) 90 0.8 3 % 85 0.8 3 % 80 1.8 7 % 75 3.7 16 % 70 4.7 19 % 65 6.9 29 % 60 7.5 31 % 55 7.7 32 % 50 8.2 34 % 45 9.5 39 % 40 11.4 48 % 35 14.1 59 % 30 14.8 62 % 25 19.0 79 % 20 21.6 90 % 15 22.1 92 % 10 30.8 129 %
5 58.8 245 %
0 94.2 100 % 393 %
-5 58.8 90 % 245 %
-10 30.8 90 % 129 %
-15 22.1 90 % 92 %
-20 21.6 90 % 90 %
-25 23.8 90 % 99 %
-30 26.6 90 % 111 %
-35 28.5 65 % 119 %
-40 29.4 46 % 122 %
-45 29.5 34 % 123 %
-50 29.1 27 % 121 %
-55 29.8 22 % 124 %
-60 32.2 18 % 134 %
-65 31.6 16 % 132 %
-70 29.2 15 % 122 %
-75 27.0 13 % 112 %
-80 24.2 12 % 101 %
-85 25.7 12 % 107 %
-90 26.0 12 % 108 %
Intensity
Angle
(Cd) 90 94.4 25 % 363 % 85 58.9 25 % 227 % 80 30.9 30 % 119 % 75 22.2 30 % 85 % 70 21.6 35 % 83 % 65 23.8 35 % 92 % 60 26.6 40 % 102 % 55 28.6 45 % 110 % 50 29.4 55 % 113 % 45 29.6 75 % 114 % 40 29.2 75 % 112 % 35 29.8 75 % 115 % 30 32.2 75 % 124 % 25 31.7 90 % 122 % 20 28.5 90 % 110 % 15 27.0 90 % 104 % 10 24.2 90 % 93 %
5 25.8 90 % 99 % 0 26.0 100 % 100 %
-5 25.8 90 % 99 %
-10 24.2 90 % 93 %
-15 27.0 90 % 104 %
-20 28.5 90 % 110 %
-25 31.7 90 % 122 %
-30 32.2 75 % 124 %
-35 29.8 75 % 115 %
-40 29.2 75 % 112 %
-45 29.6 75 % 114 %
-50 29.4 55 % 113 %
-55 28.6 45 % 110 %
-60 26.6 40 % 102 %
-65 23.8 35 % 92 %
-70 21.6 35 % 83 %
-75 22.2 30 % 85 %
-80 30.9 30 % 119 %
-85 58.9 25 % 227 %
-90 94.4 25 % 363 %
Wall Mount, Dome Down, Vertical Viewing Plane
Intensity of Horizontal plane is same as 0o angle of vertical, 360o around
90
85
100.0
90.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
10.0
0.0
o
0
axis looking at
Intensity (Cd)
UL Rating
side of dome
UL 1971 Hearing Impaired: 24 cd wall
UL 1638 General Utility: 94 cd at 0o axis
Ceiling Mount
Intensity (Cd)
UL Rating
-90
-85
0o axis looking at
end of dome
UL 1971 Hearing Impaired: 26 cd ceiling
100
90
80
70
60
50
40
30
20
10
0
-80
-75
-70
-65
-60
-55
-50
-45
-40
-35
-30
-25
-20
-15
-10
-5
-85
-
15
10
5
0
UL 1638 General Utility: 26 cd at 0o axis
Figure 6. Light Output Patterns for 105DHISTC-FJ (Unit with clear lens only)
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
-5
-10
-15
-20
-25
-30
-35
-40
-45
-50
-55
-60
-65
-70
-75
-80
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
P/N 3100394 ISSUE 3
Page 5
Table 3. Specifications
Cat. No. T VsgnitaRepy oltage Current
3.625”
(92 mm)
4.75”
(121 mm)
6.75”
(171 mm)
4.5”
(114 mm)
4.5”
(114 mm)
2.25”
(57 mm)
105PM Pipe Mount Attachment 105BM Mounting Bracket
*Insert lens color: A - Amber, B - Blue, C - Clear, G - Green, M - Magenta, R - Red.
1
Strobe tube life @ operating power to 75% eciency.
105DHIST*-FJ High Intensity 800,000 Peak Cd Table 2 Table 2
105BX Outlet Box Attachment
Mo dul e La mp
8 Joule Strobe 3,000 Hours
4.5”
(114 mm)
2”
(51 mm)
5.25”
(133 mm)
6”
(152 mm)
1
4.5”
(114 mm)
(use with 105BX)
4.5”
(114 mm)