Edwards Signaling 101 Series Catalog Page

VISUAL SIGNALS
FEATURES
> PLC compatible
> Seven gasketed modules:
steady-on or flashing incandescent steady-on or flashing halogen steady-on or flashing LED strobe
> Stackable in any combination or
color
> Base unit comes with 85 dB
pulsating horn
AdaptaLight
®
Stackable Beacon
PLC Compatible
101 Series
The Edwards AdaptaLight Stackable Beacon is a unique audible-
visual signaling device which can contain up to 5 light modules and
a pulsating horn in a single “stack.” It is for heavy duty use in
locations where visibility over longer distances is required. All
Beacon contains a pulsating horn rated at 85dB at 10 feet. The horn
can be operated as a sixth independent signal or in conjunction with
any one of the light modules.
The steady-on modules provide a constant visual signal. They are
ideal for start/stop functions, on/off process or continuous duty
visual signaling applications.
> Vibration resistant heavy duty
industrial design
> Module rearrangement requires
no wiring; screw terminals in base for field wiring
> 300,000 peak candlepower strobe
> Electrical interconnection
between units is through solid copper busses
AGENCY APPROVALS
> UL 1638 Listed
> cUL Listed
D-04
3-60
The flashing modules command immediate attention. They work
well as a warning signal when used with the steady-on module.
Applications include signaling of equipment malfunction.
The strobe modules are ideal for high ambient light areas. It can
effectively signal urgent status changes when used in conjunction
with the incandescent or LED light modules. The LED modules are
best for applications where long life (120,000 hours) is a
requirement.
The AdaptaLight can be surface or 1/2" (13mm) NPT conduit pipe
mounted in non-hazardous dust and weatherproof applications. For
indoor applications, it may be vertically mounted with lenses facing
either up or down. For weatherproof installation, the unit must be
mounted vertically with lenses facing up. May also be corner
mounted using the Cat. No. CBR, corner mount bracket, or wall
mounted, using the Cat. No. WBR, wall mount bracket. See
AdaptaBeacon Accessories page 3-118.
© Copyright 2004 Edwards
TECHNICAL INFORMATION
VISUAL SIGNALS
6"
(152 mm)
3 5/16"
(100 mm)
3/4"
(19 mm)
3 5/8"
(92 mm)
3 1/2"
(89 mm)
Module Nominal Flash Replacement Replacement Peak
Cat. No. Type Voltage Current Rate Horn Light Source Candlepower
101BS-E1 Base Unit w/Horn 12V
DC 0.05A (max) - 118-E1 - ­101BS-G1 with Horn 24V DC 0.05A (max) - 118-G1 - ­101BS-N5 (85 dB at 10 feet) 120V AC 50/60 Hz 0.05A (max) - 123A-N5 - -
(1)
101FIN*-E1 Flashing Incandescent 12V DC 1.0A 65 fpm - Industry Trade No. 94 101FINH*-G1 Flashing Halogen 24V DC 0.32A 65 fpm - 50LMP-9WH-D
(2)
101FINH*-N5 Flashing Halogen 120V AC 50/60 Hz 0.11A 65 fpm - 50LMP-12WH-D
(3)
2374
653 879
101FLED**-G1 Flashing LED 24V DC 0.065A 65 fpm - - color 101FLED**-N5 Flashing LED 120V AC 50/60 Hz 0.025A 65 fpm - - dependent
(1)
101SIN*-E1 Steady-on Incandescent 12V DC 1.0A - - Industry Trade No. 94 101SINH*-G1 Steady-on Halogen 24V DC 0.32A - - 50LMP-9WH-D
(2)
101SINH*-N5 Steady-on Halogen 120V AC 50/60 Hz 0.11A - - 50LMP-12WH-D
(3)
2374
653 876
101SLED**-G1 Steady-on LED 24V DC 0.065A - - - color 101SLED**-N5 Steady-on LED 120V AC 50/60 Hz 0.025A - - - dependent
101ST*-E1 Strobe 12V DC 0.5A 65 fpm - 91B-ST 101ST*-G1 Strobe 24V DC 0.3A 65 fpm - 91B-ST 101ST*-N5 Strobe 120V AC 50/60 Hz 0.12A 65 fpm - 91B-ST
*Insert lens color: R - red, A - amber, B - blue, G - green, M - magenta, C - clear **Insert lens and LED color: R - red, A - amber, B - blue, G - green
(1) Projected lamp life based on manufacturer's calculated lamp life at 65 fpm and 50% duty cycle is 1,520 hours. (2) Projected lamp life based on manufacturer's calculated lamp life at 65 fpm and 50% duty cycle is 15,000 hours. Can also be replaced with Industry Trade No. 1692. (3) Projected lamp life based on manufacturer's calculated lamp life at 65 fpm and 50% duty cycle is 25,000 hours. Can also be replaced with Industry Trade No. 15T7DC. (4) Strobe tube life at operating power to 75% efficiency is 3,000 hours.
(4)
(4)
(4)
300,000 300,000 300,000
SIGNAL INPUT LOAD CHARACTERISTICS*
Light Source Operating Max. off state Continuous on Surge (inrush/duration) Cat. No. Voltage leakage current (mA) Current (mA) Amps/milliseconds
101BS-G1 24V DC 25 50 2/1 101BS-N5 120V AC 25 50 2/1 101FINH( )-G1 24V DC 25 320 1.2/100 101FINH( )-N5 120V AC 25 110 1.15/8 101SINH( )-G1 24V DC 25 320 .36/1 101SINH( )-N5 120V AC 25 110 .5/8 101FLED( )-G1 24V DC 4 65 .07/1 101FLED( )-N5 120V AC 5 25 .09/8 101SLED( )-G1 24V DC 4 65 .07/1 101SLED( )-N5 120V AC 5 25 .09/8 101ST( )-G1 24V DC 1.5 300 0.33/1 101ST( )-N5 120V AC 5 120 2.1/1
*This device is PLC compatible and may be operated by PLCs with output characteristics that match the input load requirements of this signal.