Description
The 105 Series visual signals are heavy duty, reliable, UL, cUL (general utility), and CSFM Listed (miscellaneous device/control unit accessory) beacons which, when assembled in accordance with installation instructions, constitute a UL Listed Type 4X enclosure and are UL Listed for marine use. They are designed for use in industrial applications or in applications where a Type 4X enclosure is required. The signals are available in steady-on halogen, flashing halogen, 3 joule strobe, or 8 joule high intensity strobe.
When assembled in accordance with these instructions, the 105 Series visual signals are UL Listed for use in hazardous locations with operating temperatures as listed in Table 1.
These appliances are UL and cUL Listed for use in Class I, Division 2, Group A, B, C, and D, Class II, Division 2, Groups F and G, and Class III, Division 1 and 2 for hazardous or nonhazardous locations only.
For electrical specifications, see Table 2.
Installation
Installation must be in accordance with local codes. The lens should be positioned facing up for outdoor applications.
WARNINGS
• Explosion hazard. Substitution of any component may impair suitability for Class I, Division 2.
• Explosion hazard. Do not remove or replace lamps or plug-in modules unless power has been disconnected or the area is known to be free of ignitable concentrations of flammable gases or vapors.
• Explosion hazard. Do not disconnect while the circuit is live or unless the area is known to be free of ignitable concentrations.
• To reduce the risks of ignition of hazardous atmospheres and shock, do not apply power to the signal until installation has been completed and the signal is tightly assembled and secured.
• To prevent electrical shock, before starting work on signals disconnect the power. For strobe models wait 5 minutes for stored energy to dissipate.
• To avoid risk of injury, install the lens before energizing the signal and do not remove or insert the light source when the signal is energized.
WARNINGS (continued)
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• To reduce the risk of ignition of hazardous atmospheres and shock, keep the assembly tightly closed when circuits are energized.
Cautions
• The 105BX outlet box, 105BM mounting bracket, and 105PM pipe mount attachments are nonconductive plastic fixtures and do not provide earth-ground continuity when attached to metallic wiring systems. Therefore, they are intended for use with the 105XBRi series visual signals only when earth-grounding is not required.
• The 105BX outlet box, 105MB mounting bracket, and 105PM pipe mount attachments can be used with metallic wiring systems only when installed at the end of the run.
To install the device:
1. Select a mounting configuration (Figure 1).
Note: When mounting using the 105BM mounting bracket, the
105BX outlet box attachment must also be used as shown in Figure 2.
2. Pull the field wiring into the mounting attachment.
3. Install the mounting attachment as follows:
a. 105BX: Screw the outlet box attachment to the mounting
surface using two screws (not supplied) suitable for the surface. Attach the adhesive backed gasket to the top of the 105BX outlet box, being careful to line up the holes in the gasket with the mounting holes in the outlet box.
b. 105BM: Using the four supplied screws, secure the
mounting bracket to the 105BX outlet box attachment as shown in Figure 2. Attach the adhesive backed gasket to the top of the 105BM mounting bracket, being careful to line up the holes in the gasket with the mounting holes in the outlet box.
c. 105PM: Install 3/4 in. conduit. Screw the pipe mount
attachment onto the 3/4 in. conduit. Attach the adhesive backed gasket to the top of the 105PM pipe mount attachment, being careful to line up the holes in the gasket with the mounting holes in the outlet box.
Note: It is not necessary to remove the lens from the
hi-intensity strobe base to install the 105HIST Series beacons.
4. Mount the 105SINH, 105FINH, and 105ST Series as follows. Unscrew the gasketed base from the lens assembly as shown in Figure 3 and remove the clear gasket from around the base.
5. Secure the base to the appropriate mounting attachment using the four screws (supplied). Replace the clear gasket on the base with the flared, open end facing down.
6. Attach the signal wire leads to the field wiring as shown in Figure 5.
7. Ensuring that the light source is in place, screw the lens back on the base.
8. Mount the 105HIST Series as follows. Secure the hi-intensity strobe base to the appropriate mounting attachment using the four screws (supplied) as shown in Figure 4.
9. Apply power and verify operability.
P/N 3100290-EN • REV 04 • ISS 14JAN15 1 / 4
Page 2
Figure 1: Mounting configurations
105ST Series
Mounted on a 105PM pipe mount attachment
Mounted on a 105BX outlet box attachment
Mounted on a 105BM mounting bracket with the 105BX outlet box attachment
Mounting surface
Screws to mount 105BX to the mounting surface (2X)
Adhesive backed gasket
105-L Series lens
Countersunk screws to mount lens to 105BM, supplied (4X)
Gasket
Adhesive backed gasket
105BM mounting bracket
Screws to mount 105BM to 105BX, supplied (4X)
3/4 in. conduit nipple
105PM pipe mount attachment
Adhesive backed gasket
Gasket
Beacon base
105-L Series lens
Strobe tube
Strobe tube base
Strobe tube socket
Screws to mount lens to 105PM, supplied (4X)
105HI-L series lens
Hi-intensity strobe base
Adhesive backed gasket
105PM pipe mount attachment
3/4 in. conduit nipple
105SINH, 105FINH,
Figure 3: 105PM pipe mounting
105HIST Series
Figure 2: 105BM bracket mounting
Figure 4: 105HIST mounting
2 / 4 P/N 3100290-EN • REV 04 • ISS 14JAN15
Page 3
Figure 5: Wiring
Model number
105FINH* 105SINH* 105FINH* 105SINH*
105FINH* 105SINH*
Model number
105HIST* 105HIST*
105HIST*
105ST* 105ST* 105ST*
Model number
type
105SINH
umens,
105SINH
umens,
105SINH
umens,
105FINH
umens,
105FINH
umens,
105FINH
umens,
105ST
105ST
105ST
105HIST
105HIST
105HIST
* M
[1]
[
65 FPM and 50% duty cycle.
[3] Strobe tube life at operating power to 75% efficiency.
105HI-L lens
Hi-intensity strobe base
Wire nuts (not supplied)
-G1
-N5
-R5
* Lens color: A = Amber, B = Blue, C = Clear, G = Green, M = Magenta, R = Red.
Table 2: Electrical specifications
Class Division Group Operating
I 2 A, B, C, D T2B (260˚C, 500˚F)
-N5
-R5
II 2 F, G T4 (135˚C, 275˚F)
III T4 (135˚C, 275˚F)
-EK I 2 A, B, C, D T2C (230˚C, 446˚F)
II 2 F, G T4 (135˚C, 275˚F)
III T4 (135˚C, 275˚F)
I 2 A, B, C, D T3 (200˚C, 392˚F)
II 2 F, G T4A (120˚C, 248˚F)
III T4A (120˚C, 248˚F)
Module
Lamp ratings Voltage Current
temperature
Maintenance
WARNING: Shock hazard. To prevent electrical shock, before starting
work on signals disconnect the power. For strobe models wait 5 minutes for stored energy to dissipate.
Caution: Do not touch the strobe tube or halogen bulb with bare
fingers. Grasp the light source either by the base or using a soft, clean cloth.
The lens should be periodically cleaned using a mild detergent and water on a soft, clean, lint-free cloth.
To replace the light source:
1. Unscrew the lens from the base.
2. For halogen bulb replacement:
a. While pressing down on the bulb, turn and then pull straight up
and out of the socket.
b. Insert the new halogen bulb into the socket, press down and
turn until the bulb is locked into place.
3. For strobe tube replacement:
a. Grasp the strobe tube by its base and pull straight up out of
the strobe tube socket (Figure 3).
b. Grasp the new strobe tube by the strobe tube base and press
into the strobe tube socket.
4. Screw the lens onto the base.
5. Apply power and verify operability.
Specifications
Table 1: Hazardous location ratings
P/N 3100290-EN • REV 04 • ISS 14JAN15 3 / 4
Class Division Group Operating
I 2 A, B, C, D T3 (200˚C, 392˚F),
-G1
-G1
II 2 F, G T4A (120˚C, 248˚F)
-G5 III T4A (120˚C, 248˚F)
-G5
I 2 A, B, C, D T2A (280˚C, 536˚F),
-N5
-N5
II 2 F, G T4 (135˚C, 275˚F)
III T4 (135˚C, 275˚F)
temperature
*-G1 Steady-on
halogen
*-G5 Steady-on
halogen
*-N5 Steady-on
halogen
*-G1 Flashing
halogen
*-G5 Flashing
halogen
*-N5 Flashing
halogen
*-G1 3 joule
strobe
*-N5 3 joule
strobe
*-R5 3 joule
strobe
*-EK High-
intensity 8 joule strobe
*-N5 High-
intensity 8 joule strobe
*-R5 High-
intensity 8 joule strobe
Lens color: A = Amber, B = Blue, C = Clear, G = Green,
= Magenta, R = Red.
At nominal operating voltage.
2] Projected lamp life based on manufacturer's calculated lamp life at
20 W, 226 l 20,000 hours [1][2]
20 W, 226 l
20,000 hours [1][2]
25 W, 175 l 20,000 hours [1][2]
20 W, 226 l 20,000 hours [1][2]
20 W, 226 l 20,000 hours [1][2]
25 W, 175 l 20,000 hours [1][2]
300,000 peak candela, 3,000 hours [3]
300,000 peak candela, 3,000 hours [3]
300,000 peak candela, 3,000 hours [3]
800,000 peak candela, 3,000 hours [3]
800,000 peak candela, 3,000 hours [3]
800,000 peak candela, 3,000 hours [3]
24 VDC 0.8 A
24 V,
60 Hz
120 V, 60 Hz
24 VDC 0.8 A
24 V, 60 Hz
120V, 60 Hz
24 VDC 0.3 A
120 V, 60 Hz
240 V, 60 Hz
12 VDC
24 VDC 48 VDC
120 V, 60 Hz
240 V, 60 Hz
0.8 A
0.2 A
0.8 A
0.2 A
0.1 A
0.02 A
1.2 A
0.8 A
0.38 A
0.1 A
0.05 A
Page 4
Table 3: Dimensions
Model
105 105ST models
105
105PM pipe mount attachment
105BX outlet box attachment
105BM mounting bracket (use with 105BX)
Ratings
3.625 in.
(92 mm)
4.375 in.
(111 mm)
4.625 in.
(117 mm)
4.5 in.
(114 mm)
3.625 in.
(92 mm)
4.5 in.
(114 mm)
4.75 in.
(121 mm)
6.75 in.
(171 mm)
4.5 in.
(114 mm)
2.25 in.
(57 mm)
4.5 in.
(114 mm)
2 in.
(51 mm)
5.25 in.
(133 mm)
6 in.
(152 mm)
5 in.
(127 mm)
4.5 in.
(114 mm)
Dimensions
SINH, 105FINH,
HIST models
Regulatory information
ANSI/ISA 12.12.01
CSA C22.2 No. 205 CSA C22.2 No. 213 UL 1638 UL and cUL Listed Type 4X enclosure
Contact information
For contact information, see www.edwardssignaling.com.
© 2015 UTC Fire & Security Americas Corporation, Inc.
All rights reserved.
4 / 4 P/N 3100290-EN • REV 04 • ISS 14JAN15
Loading...