Edur LBU Series, VBU Series Operating Instructions Manual

Operating Instruction
Segmental Type Pumps
Please keep your Operating Instruction in a safe place!
Type
Serial No.
EDUR-Pumpenfabrik
Eduard Redlien GmbH & Co. KG
E-mail: info@edur.de · http://www.edur.de
Postfach 1949 · D-24018 Kiel
Tel. (+431) 689868 · Fax (+431) 6898800
2
Contents
1 Security 3
1.1 Identification of Safety Instructions in the Operating Manual 3
1.2 Qualification and Training of Operating Personnel 3
1.3 Hazards in the Event of Non-Compliance with the Safety Instructions 3
1.4 Compliance with Regulations Pertaining to Safety at Work 4
1.5 Safety Instructions relevant for Operation 4
1.6 Safety Instructions relevant for Maintenance, Inspection and Assembly Work 4
1.7 Unauthorized Alterations and Production of Spare Parts 4
1.8 Unauthorized Modes of Operation 4
2 Transport and Intermediate Storage 4
2.1 Transport 4
2.2 Intermediate Storage 5
2.2.1 Internal Preservation 5
2.2.2 Preservation Control 5
2.2.3 Removal of Preservation 5
3 Description 5
3.1 Design 5
3.2 Place of Operation 6
4 Mounting 6
4.1 Installation 6
4.2 Connected Loads 6
4.3 Direction 6
4.4 Coupling Protection 7
4.5 Piping 7
4.5.1 General Remarks 7
4.5.2 Suction Pipeline 7
4.5.3 Pressure Pipeline 7
4.5.4 Additional Connections 7
4.6 Low-Noise Installation 7
5 Starting Operation/ Stopping Operation 7
5.1 Preparations for Initial 7
5.2 Initial Starting 7
5.3 Restarting 8
5.4 Stopping Operation 8
6 Service/Maintenance 8
6.1 Supervision of Operation 8
6.1.1 Shaft Bearing 8
6.1.2 Mechanical Seal 8
6.1.3 Gland Packing 8
6.2 Maintance 9
6.2.1 Preparation 9
6.2.2 Dismounting 9
6.2.2.1 Pump 9
6.2.2.2 Dismounting of Mechanical Seal 9
6.2.2.3 Motor 9
6.2.3 Mounting 9
6.2.3.1 General Remarks 9
6.2.3.2 Mounting of the Motor 10
6.2.3.3 Replacing the Gland Packing 10
6.2.3.4 Mounting of Mechanical Seal 10
7 Disturbance 12
8 Pump View and List of Spare Parts 13
8.1 LBU 13
8.1 VBU 14
3
General
The most important operational data are mentioned on the type label. The sound pressure L depending on the nominal pump power input P will be seen from the diagram underneath.
Fig. Noise emission
The actual sound level ascertained at place of installation will possibly differ considerably from these values due to the operating conditions and the conditions of installation.
following VDI-guidelines 3743 sheet 1
pA
1 Security
This operating manual gives basic instructions which are to be observed during installation, operation and maintenance of the pump. it is therefore imperative that this manual be read by the responsible personnel/operator prior to assembly and commissioning. It is always to be kept available at the installation site.
It is not only the general safety instructions contained under this main heading safety that are to be observed but also the specific information provided under the other main headings.
1.1 Identification of Safety Instructions in the Operating Manual
Safety instructions given in this manual non-compliance with which would affect safety are identified by the following symbol:
or where electrical safety is involved, with
see DIN 4844-W9
Instructions non-compliance with which would give rise to malfunctioning of the machinery are identify by the word
CAUTION
It is imperative that signs affixed to the machine, e. g.
- arrow indicating the direction of rotation
- symbols indicating fluid connections
be observed and kept legible.
1.2 Qualification and Training of Operating Personnel
The personnel responsible for operation, maintenance, inspection and assembly must be adequately qualified. Scope of responsibility and supervision of the personnel must be exactly defined by the plant operator. If the staff does not have the necessary knowledge, they must be trained and instructed, which may be performed by the machine manufacturer or supplier on behalf of the plant operator. Moreover the plant operator is to make sure that the contents of the operating manual are fully understood by the personnel.
1.3 Hazards in the Event of Non-Compliance with the Safety Instructions
Non-compliance with the safety instructions may produce a risk to the personnel as well as to the environment and the machine and results in a loss of any right to claim damages.
For example, non-compliance may involve the following hazards:
- Failure of important functions of the
machine/plant
- Failure of specified procedures of
maintenance and repair
- Exposure of people to electrical, mechanical
and chemical hazards
- Endangering the environment owing to
hazardous substances being released
see DIN 4844-W8
4
1.4 Compliance with Regulations Pertaining to Safety at Work
When operating the pump, the safety instructions contained in this manual, the relevant national accident prevention regulations and any other service and safety instructions issued by the plant operator are to be observed.
1.5 Safety Instructions relevant for Operation
-
If hot or cold machine components involve hazards, they must be guarded against accidental contact.
- Guards for moving parts (e.g. coupling)
must not be removed from the machine while in operation.
- Any leakage of hazardous (e.g. explosive,
toxic, hot) fluids (e.g. from the shaft seal) must be drained away so as to prevent any risk occurring to persons or the environment. Statutory regulations are to be complied with.
- Hazards resulting from electricity are to be
precluded (see, for example, the VDE Specifications and the bye-laws of the local power supply utilities).
1.6 Safety Instructions relevant for Maintenance, Inspection and Assembly Work
It shall be the plant operator's responsibility to ensure that all maintenance, inspection and assembly work is performed by authorized and qualified personnel who have adequately familiarized themselves with the subject matter by studying this manual in detail.
Any work on the machine shall only be performed when it is at a standstill, it being imperative that the procedure for shutting down the machine described in this manual be followed.
Pumps and pumps units which convey hazardous media must be decontaminated.
On completion of work all safety and protective facilities must be re-installed and made operative again.
Prior to restarting the machine, the instructions listed under Initial commissioning are to be observed.
Unauthorized Alterations and Production of Spare Parts Any modifications may be made to the machine only after consultation with the manufacturer. Using spare parts and accessories authorised by the manufacturer is in the interest of safety. Use of other parts may exempt the manufacturer from any liability.
1.7 Unauthorized Modes of Operation
The reliability of the machine delivered will be only guaranteed if it is used in the manner intended, in accordance with our order documentation, especially with the order confirmation. The limit values specified in the data sheet must under no circumstances be exceeded.
2 Transport and Intermediate Storage
2.1 Transport
When transporting the complete pump unit by crane, mount the ropes as shown in the figure.
The crane facility and the ropes must be of
CAUTION
for transport of the complete pump unit.
Fig. 2.1a Pumps of structural form V
sufficient capacity. The ring loop of the motor must not be used
Fig. 2.1b Pumps of structural form L
5
Fig. 2.1c Pumps of structural forms N, S and
N1-N9
Fig. 2.1d Pumps of structural form Z
CAUTION
and base plate are tightened at our works. Please take care that before setting into operation the screws have to be released by all means resp. in case of a transport again have to be tightened. In this regard also see section 4.1
For transport only the screws between foot of suction casing
2.2 Intermediate Storage
On delivery, all pumps are preserved. Thus, they can be stored for 6-12 months. If the storage time is longer or the pumps are not in operation, they must receive additional preservation on the inside. The preservation means (please consult us) depends on the used materials and conditions of operation. The storage room must be roofed and well ventilated. Avoid temperatures below zero and high humidity.
2.2.1 Internal Preservation
Close the suction branch securely. Fill the pump with the preservation means and slowly turn the rotor manually. Close the pressure branch securely.
2.2.2 Preservation Control
Check the filling level of the pump and turn the rotor by hand at regular intervals of 3 months. Refill preservation means, if necessary.
Fig. 2.1e Pumps of structural forms V1-V6, E1-E6,
E11-E16
Fig. 2.1f Pumps of structural forms
NVB(K)1-NVB(K)9, V1-V6, E1-E6, E11-E16, NuV25
2.2.3 Removal of Preservation
Prior to operation, the pump must be rinsed thoroughly. In the case of additional preservation, the preservation means on the inside must at first be removed.
3 Description
3.1 Design
Horizontal and vertical, single-stage or multi-stage ring section pumps, with or without an electric drive unit, on a common bed-plate or unit­construction pumps, available in different construction materials, sizes and with different shaft sealings. Self-priming pumps are provided with an inlet bend fitted at the suction branch.
6
3.2 Place of Operation
The pump unit must be freely accessible for the purpose of supervision, servicing, maintenance, mounting and dismounting. Avoid using it in corrosive and very dusty surroundings. The limiting values of the electric drive unit with regard to the insulation material class and the types of protection must be observed. For other drive units supplied, see the enclosed separate operating instructions.
4 Mounting
4.1 Installation
The complete pump unit is generally mounted on a pedestal. The pedestal must be even and must have fasteners and a sufficient load capacity. Instead of the pump being secured by means of fasteners, the bed-plate of horizontal pumps or the suction casing of vertical pumps can be sealed in the pedestal by a depth of about 20 mm. The complete pump unit must be adjusted by means of a spirit level when it is being mounted on the pedestal. The levelling plates are to be installed between the bed-plate or suction casing and the pedestal as well as close to any existing fasteners. All levelling plates must be well set. The fasteners must be tightened steadily after the complete pump unit has been adjusted. In the case of self-priming pumps, the pipe bend must not be removed or distorted.
CAUTION
plate, the coupling must be checked thoroughly after the piping has been connected and the bed-plate secured. If necessary, pump and motor must be readjusted.
When checking the coupling and adjusting the unit, first loosen the pump footings and then retighten them but without stresses.
CAUTION
the suction casing must never be screwed to the bed-plate in order to avoid axial distortion.
Pump and motor are correctly adjusted if the distance between a straight-edge which is placed on the coupling halves and the relevant shaft is the same for the entire circumference of the shaft. The coupling rubber must have free motion of 1 to 2 mm between the coupling halves for the entire circumference on both sides (Fig. 4.1a).
Even if the pump unit is delivered completely mounted on the bed-
If the pump has two pump footings, the pump footing below
Fig. 4.1a Adjustment of the Coupling
The permissible axial and radial deviation measured at the front end and the circumference of the coupling is 0.1 mm. If this is not the case, the pump unit of the motor must be readjusted. Subsequently, the motor footing must also be tightened without stresses and the adjustment of the coupling must be checked once again.
CAUTION
shaft and shaft sealings.
Errors in adjustment can increase the load on the bearing,
4.2 Connected Loads
Work must only be executed when electricity is switched off. Make sure that the system cannot be powered on accidentally.
CAUTION
pumped liquid. The pump must by no means be operated without liquid!
The pump must be connected according to international national requirements as well as according to the requirements of the local mains system. Voltage and frequency must correspond to the winding of the electric drive. For details of the respective winding, see the type label. The motor must not be operated without motor protection facility. For motors with explosion protection, the range of temperature of the motor indicated on the type label must correspond to the range of the fuel gas.
Prior to connecting the pump to the power system, fill it with
4.3 Direction
Switch on the motor briefly in order to check the direction of rotation. The motor must not reach its operational speed. The direction of rotation must correspond to the arrow indicating the direction of rotation on top of the pump. If the direction of rotation is not correct, perform the relevant modifications at the phase-sequence.
7
4.4 Coupling Protection
The pump must not be operated if coupling protection is not fitted. If this
coupling protection is not supplied by the manufacturer, the operator of the pump must supply it himself.
4.5 Piping
4.5.1 General Remarks
The nominal widths of the pipes must be at least as wide as those of the pump connection joints. For adapters, use extension angles of 8°, if possible. The pipes must be gathered and secured right in front of the pump so that their weight does not affect the pump. The negative effects of variations in temperature and occurring oscillation may be reduced by installing a suitable bellow expansion joint (see section 4.6). Measuring equipment for supervision of the pump operation is required. Prior to operation, all parts in contact with liquids must be thoroughly cleaned.
4.5.2 Suction Pipeline
The suction pipeline must be as short as possible. Variations in diameter and additional piping must be kept to a minimum. The suction pipeline towards the pump must be rising, the inlet must be descending to prevent an air pocket from being formed. For non-self-priming pumps, installation of a foot valve into the suction pipeline is compulsory in order to avoid that, in case of a standstill, the pump and the suction pipeline run out of liquid during suction operation. Contamination of the pumped liquid is to be avoided by using a suction hose or a filter. By no means must air penetrate through the liquid level via the suction hose or dirt be whirled up from the liquid pool. Clean the suction hose and filter regularly. To close the suction pipeline in the case of mounting or maintenance work, a stop valve must be provided near the pump. The stop valve must not be used for adjustment and must be completely open during operation.
4.5.4 Additional Connections
For the position and dimension of required additional connections as e.g. for rinse, stop and quench liquid, refer to the labels supplied with the pump or to the drawings in the operating instructions. The rinse, stop and quench liquids must be checked at regular intervals. Connections for ventilation and release of the leakage liquid are also described in the drawings.
4.6 Low-Noise Installation
A reduction in noise (Fig. 4.6a) can be achieved by isolating the pedestal (1) from the ground by means of an appropriate insulation board (2) and by using suitable bellow expansion joints between the piping and the pump. The pedestal (1) must not be secured to the ground or to the walls.
Fig. 4.6a Low-Noise Installation
Another possibility to reduce the noise is the use of oscillation absorbers. In this case, you need to install a frame under the base of the pump.
Bellow expansion joints must be checked regularly for brittle and cracks.
5 Starting Operation/ Stopping
Operation
5.1 Preparations for Initial
Prior to the start, the pump and the suction pipeline must be drained of air and be completely filled with the pumped liquid. The stop valve in the suction or inlet pipeline must be completely open, if there is one. For self-priming pumps, the pump must only be completely drained of air and filled with the pumped liquid.
4.5.3 Pressure Pipeline
For adjustment, repair and mounting of the pump, a stop valve is to be provided near the pressure joint.
5.2 Initial Starting
The pump must not be started until the outlet stop valve is closed so as to avoid overload of the motor. Immediately after reaching the operational speed, slowly open the stop valve of the pressure pipeline and adjust the operating point.
8
Until the liquid starts moving against atmospheric pressure, the hydrostatic pressure for self-priming pumps must not exceed 1 bar with reference to the difference in height between suction and outlet liquid level and to the density of the pumped liquid.
The pump must never be operated for a longer period if the outlet stop valve
damaged if the pumped liquid exceeds the permitted temperature.
is closed. The pump unit will be
5.3 Restarting
Do not restart the pump until the pump shaft stands still.
CAUTION
rotation of the pump. If this is the case, mechanical seals dependent on direction of rotation may be damaged.
Backflow of liquid must not result in a change of direction of
5.4 Stopping Operation
Close stop valve of the pressure pipeline. If there is a backflow stop and sufficient counter pressure in the pipeline, the stop valve can remain open. Switch off the motor and observe that it slows down smoothly. Close stop valve of the pressure pipeline. If the pumped liquid reaches temperatures below zero and/or if longer periods of standstill occur, the pump must be drained completely and be preserved (see section 2.2.1).
6 Service/Maintenance
6.1 Supervision of Operation
Ensure that the pump runs free of vibration and smoothly The pump must by no means be operated without liquid. There is only a minimal or invisible loss of leakage (steam) if the mechanical seals function correctly. Gland packings should drip slightly. Do not operate the pump for a longer period with a closed stop valve. The maximum permitted environmental temperature is 40oC. The storing temperature measured at the motor or pump casing may exceed the environmental temperature by 50oC. It must not exceed 90oC. Only operate the pump at a higher temperature with the manufacturer's approval.
We have to point out that an increased wear may occur in case of transport of abrasive / corrosive media.
CAUTION
components have to be checked regularly in order to detect wear in time - before a damage occurs. The intervals have to comply with the liquids to be pumped and initially have to be carried out more frequently, until perceptions about the progress of wear are attained.
Installed pumps must be powered on and off briefly once a week in order to guarantee that they are ready for operation.
In case of corrosive / abrasive media to be pumped pressurized
6.1.1 Shaft Bearing
Under normal operation conditions, replace the motor bearings after 20.000 hours of operation or at the latest after 2,5 years. In the case of bad operation conditions, as e.g. a high environmental temperature or a corrosive and dusty environment, the motor bearings must be checked at an earlier date and, if necessary, be replaced. Pump bearings with a lubrication device must be checked every 5000 hours of operation. Dirty bearings must be cleaned and filled with new lubricant. The free space in the bearing and casing should be filled by 30-50% with lubricant. Do not use resinous or acid lubricants. Its consistencies (NLGI grade) should correspond to a worked penetration of 265 to 295 mm/10. Lithium-base soap lubricants with a drop point of more than 185°C are to be used for pumped liquids which have a maximum temperature of 110°C. For pumped liquid with a higher temperature, use silicon lubricants with a lithium­base soap and with a drop point of more than 215°C. If necessary, the bearings can also be lubricated with lubricants of a different soap base. For this based on different soaps must not be mixed. The required re-lubrication periods must then be adapted to the type of lubricant used.
6.1.2 Mechanical Seal
The mechanical seals are maintenance-free. If leakages occur after a longer period of operation, replace the complete seal.
6.1.3 Gland Packing
Gland packings are low-maintenance parts and must leak slightly during operation. Do not tighten a gland packing after its first operation. Considerable leakage at the beginning disappears by itself. If greater leakages occur during operation, the gland lid or insert must be slightly tightened, however it must never be tightened at a slant.
9
It must be possible to rotate the slide slightly after having tightened the lid or insert. If tightening of the gland lid or insert results in the pump being heated excessively or if it is not possible to tighten the gland lid or insert any further, the gland packing must be replaced completely.
CAUTION
If the gland lid or insert is tightened too much the shaft will be damaged.
6.2 Maintenance
6.2.1 Preparation
In order to make sure that the pump cannot be started, separate the power cable from the motor. Secure the unit against accidental switch-on.
Close the stop valve of the pressure and suction pipelines. The pump casing must have reached the environmental temperature and be drained of liquid and pressure. In the case of pumps in unit-construction with mounting flange, the container must be drained completely.
6.2.2 Dismounting
By no means use force while dismounting the pump. Proceed as follows for the different pump types:
Unit-construction pumps:
- Separate the pump from the piping and any
additional connections
- Loosen the fasteners
Pumps with a motor on a common bed-plate:
- Separate the pump from the piping and any
additional connections
- Remove the coupling protection
- Loosen the pump from the bed-plate and
remove it from the motor
For fixed parts of the casings, impellers and couplings, use appropriate dismounting facilities. Impellers, which cannot easily be removed from the shaft, can be pushed back from the shaft by means of two hexagon screws.
6.2.2.1 Pump
The pump is always dismounted on the suction side and with the shaft in a horizontal position. Refer to enclosed drawings on page 13 to 14 (only pumps of structural forms LBU and VBU) or in the supplementary sheet for the dismounting sequence.
For unit-construction pumps, the pump and motor must not be separated for the axial fixing of the pump shaft. To prevent the partially mounted pump or the complete pump unit from tilting, put blocks as a mounting aid under the step casing and, if necessary, under the drive unit. Mark the position and sequence of the pump parts for later mounting.
6.2.2.2 Dismounting of Mechanical Seal
In order to replace the mechanical seal, the pump must be dismounted (s ee Fig. 6.2.2) first. After that the pump must be dismantled before the seal can be removed. Dismantle the pump in the sequence shown in the exploded view diagrams, pages 13 or 14. Remove impeller (230), casing (108,117), key (940.1) and the circlip (932), pull the delivery casing (107) off the shaft with the mechanical seal (433).
6.2.2.3 Motor
For vertical pumps and unit-construction pumps, it is not necessary to dismount the pump unit. The pump can remain in the piping. First, remove the coupling protection and loosen the hexagon screws of the coupling. After having loosened the hexagon screws at the motor flange, remove the motor from the pump. For pumps with a motor on a common bed-plate, first remove the coupling protection. Then, loosen the mounting screws of the motor and separate the motor from the pump.
6.2.3 Mounting
6.2.3.1 General Remarks
Prior to mounting, all parts must be cleaned thoroughly. Remove remaining parts of the seals. Slight scratches and grooves on the shaft near the shaft seal and on other sealing surfaces of the casings are to be polished with linen.
CAUTION
damage and replace them, if necessary. Mounting is effected in the reverse order of dismounting. Heat up the coupling joints of rigid couplings to approximately 250°C prior to mounting them onto the shaft.
In the case of flexible on the pump shaft must be tightened thoroughly
If this is not possible, replace the parts. Gaskets must always be renewed. Check O-rings for
couplings, the coupling half
10
by means of the shaft nut and/or the hexagon nut. If this is not observed, the bearings will be damaged.
The starting torques for the tie bolts and locking screws non lubricated condition are displayed in fig. 6.2.3.1a.
thread M 10 M 12 M 14 M16 M20 torque
Nm * for pumps with more than 4 tie bolts Abb. 6.2.3.1a Starting torque
30 40 50 110
70*
120
6.2.3.2 Mounting of the Motor
For initial mounting of motor and pumps with rigid coupling, first of all, remove the transport safeguards of the lantern or of the intermediate flange, then remove the motorside coupling half. Subsequently, put this part onto the motor shaft. This coupling half must be next to the motor shaft collar. Tighten screws, join motor and pump centrically without tilting them. Tighten screws between motor and lantern or intermediate flange and then coupling screws.
CAUTION
are connected and the motorside or pumpside coupling half has been installed incorrectly or not at all.
The inner parts of the pump will be damaged if motor and pump
6.2.3.3 Replacing the Gland Packing
Remove gland lid or insert and remove the old packing rings. Clean gland packing compartment of any remaining packing material. Insert new gland packing, ring by ring with staggered open butt joint, see Fig. 6.2.3.3a and slightly tighten it with gland lid or insert. No lubricant must touch the gland packing.
6.2.3.4 Mounting of Mechanical Seal
CAUTION
carefully and with precision.
Do not touch the surfaces of the seal. Do not damage the sealing parts. To facilitate the mounting, moisten elastomer with low-surface tension water.
The shape of spare mechanical seals may differ from those of the installed mechanical seal. However, the dimensions of the spare mechanical seal are the same and for that reason it can be replaced.
To avoid distortion of the counter-ring, mechanical seals with doubled PTFE-wrapped sealing O rings are additionally secured by a leading pin inside the casing. The pin must be removed when replacing the type of mechanical seals and when using a type with different O-ring material.
For details of the individual types of mechanical seals observe the following procedures.
When mounting the mechanical seals, you must proceed very
Mechanical seals and sealingparts with elastomer made of EP rubber must by no means come in contact with oil or grease.
Fig. 6.2.3.3a Gland packing
During the first hours of operation, watch out for any considerable increase in heat or leakage.
11
Observe the enclosed, separate mounting instructions for those types of mechanical seals which are not listed.
1. Stressed mechanical seal independent of
direction of rotation with elastomer bellows (fig. 6.2.3.4a)
Fig. 6.2.3.4a
Carefully press angle collar (1) together with counter ring (2) into the counter ring fit. Twist the rotating unit (3,4,5) onto the shaft as far as the counter ring. Put on supporting ring and mount circlip (932*) and/or push shaft sleeve for mechanical seal (516*) onto the shaft. For suction-side mechanical seals (only pumps of type Z), mount circlip (932.1*). Push rotating unit (5,4,3) on to the shaft up to the circlip (932.1*).
2. Stressed mechanical seal dependent on direction of rotation with conical springs (fig. 6.2.3.4b)
Fig. 6.2.3.4b
Insert O-Ring (1) into counter ring fit and carefully press counter ring (2) into it. Push mechanical seal (3) onto the shaft as far as the counter ring. Press O Ring (4) into the mechanical seal by means of the supporting ring. The pivot of the pressure spring (6) must be situated in the groove of the mechanical seal ring. Put on locking ring (7). Mount circlip (932*) and/or shaft sleeve for mechanical seal (516*). For suction-side mechanical seals (only pumps of type Z), mount circlip (932.1*). Push locking ring (7), pressure spring (6), supporting ring (5), O ring (4) and mechanical seal ring (3) separately onto the shaft.
*
see sectional drawing in the operating
instruction (only pumps of structural forms LBU and VBU) or sectional drawing in supplementary sheet.
12
7 Disturbance
Pump is blocked
Coupling fault
Heads too low
Rates of flow too low
Bearing temperature too high
Pump operates badly
Leakages at the casing
Overload of the drive
Shaft seal leaks badly
z z
z z z
z
z
z z
z
z z
z
z
z
z
z
z
1)
Please consult us
2)
Only pumps with lubricator
z z z
z z
z z z
z z
z z
z z z
z z
z z
z
z z
z z
To eliminate disturbance, the pump must have
CAUTION
reached the environmental temperature and must be drained of air and pressure.
The chart shows a list of potential errors and their possible causes. For errors which are not listed here or which have other reasons, please consult us.
Motor protection activated
Pump is becoming too hot
Cause Elimination
Pump and/or suction pipeline is not completely drained of air/filled
Suction level too high, NPSH value of the unit too high
z
Air inclusion in the pumped liquid too high
z
Formation of air bag in suction pipeline Change suction pipeline/attach drain valve
z
Direction of rotation incorrect Check and change phase sequence, if
Rates of flow too low Readjust operating point
z
Wear of inner parts Replace inner parts
Pump operates out of tolerance Readjust operating point
Shaft seal damaged Replace shaft seal
Stuffing box gland jammed or tightened too heavily Air entry through shaft sealing on suction side Speed too low Increase speed
Speed too high Reduce speed
Connecting screws, seals Tighten connecting screws, replace seals
Pump/motor not adjusted Replace defective parts, adjust pump/motor
Problems via piping Check pipe connections/pump
Insufficient, excessive or wrong lubrication grease Incorrect coupling gap Readjust motor
Defective bearing Replace bearing
Density/viscosity of pumped liquid higher than indicated in the order Motor protection unit set incorrectly or defective Impeller blocked Clean interior parts from particles and
Drain of air and fill
Completely open stop slide in the suction pipeline, check suction bag/footing valve, if necessary, increase liquid level, if necessary
Seal suction pipeline once again, check suction bag, increase liquid level, if necessary
necessary
Correct
Check liquid sealing or replace packing
1)
1)
fasteners/bearing distance of pipe clips, installation with oscillation absorbers Add, remove or change grease2)
1)
Check motor protection unit, replace it, if necessary
impurities
y
13
210 932.1 844
341 681 901.2 844.1 904
903
117108
920 nut
930/.1-.2 tooth lock washer
932/.1 circlip
940/.1 ke
When ordering spare parts, please
indicate serial no., type no. and
parts no. by all means.
904940 930.1 901.1
901.4
part no. designation 903 screwed plug
904 hexagon socket set screw
905 tie bolt
B
C
411 903 722554.1 901 930.2
part no. designation 554/.1 washer
592/.1 base
681 coupling guard
930
412
412 592 182 531 901.3
part no. designation 230 impeller
341 lantern
411 joint ring
722 intermediate flange
844/.1 disc type coupling
412 o-ring
433 mechanical seal
901/.1-.5 hexagon screw
531/.1 locking sleeve
545
A
930 531.1 412
A: Screwed plug G¼ for vent connection and pressure gauge connection
8 Pump View and List of Spare Parts
8.1 LBU
905 411 903 106 230 940.1 230 940.1 932 433 107 554 920 411
592.1 182.1901.5
part no. designation 106 suction casing
107 delivery casing
108 stage casing
117 endstage casing
182/.1 foot
B: Screwed plug G¼ for vent connection and pressure gauge connection
210 shaft
C: Screwed plug G¼ for drain
14
p
y
901.1930.1940 904
all means.
901.2 210 932.1 844 844.1 904
341 681
903
920 411
107 554
901.4
part no. designation 930/.1 tooth lock washer
932/.1 circlip
940/.1 key
930.2901554.1 722903411
When ordering spare parts, please
arts no. b
indicate serial no., type no. and
B
C
part no. designation 722 intermediate flange
844/.1 disc type coupling
901/.1-.3 hexagon screw
903 screwed plug
904 hexagon socket set screw
905 tie bolt
920 nut
412412
part no. designation 341 lantern
411 joint ring
412 o-ring
433 mechanical seal
554/.1 washer
230 230 433
412
681 coupling guard
905411
903 940.1 108 117940.1 932
106
545
C
part no. designation 106 suction casing
107 delivery casing
108 stage casing
8.2 VBU
117 endstage casing
B: Screwed plug G¼ for vent connection and pressure gauge connection
210 shaft
230 impeller
C: Screwed plug G¼ for drain
15
As defined by machinery directive 98/37/EC Annex II A
Declaration of Conformity
Herewith we declare that the pump unit supplied with mounted electric drive
complies with the following provisions applying to it
EC-machinery directive (98/37/EC, Annex I No. 1)
EC-low voltage directive (73/23/EEC)
Applied harmonized standards
EN 809 EN 953 EN 292-1 EN 60204-1 section 16 EN 292-2 EN 60034-5 EN 294
In case of a modification of the pump unit without being coordinated with us this declaration will not longer be valid.
i.A.
(QM-Supervisor)
1) other driving motor see separate declaration of c onformity
1)
As defined by machinery directive 98/37/EC, Annex II B
Herewith we declare that the pump supplied without driving motor is intended to be incorporated into machinery or assembled with other machinery to constitute machinery covered by this directive and must not be put into service until the machinery into which it is to be incorporated has been declared in conformity with the provisions of the directive, version 98/37/EC.
Applied harmonized standards
In case of a modification of the pump without being coordinated with us this declaration will not longer be valid.
i.A.
(QM-Supervisor)
Declaration by the manufacturer
EN 809 EN 292-1 EN 292-2
BE1 17102,8 / 071001
Loading...