6
STANDARD FEATURES
Cabinet
The cabinet frames shall be constructed of formed 2.0 mm
Zintec steel sections. Paint finish is Epoxy Powder Coated with
an “Orange Peel” textured finish. Interior panels to be
manufactured from galvanised steel in all cases. Exterior
panels are to be as cabinet except in 1.2 mm Zintec. Paint
Colour to be RAL 9018. The front panels shall be fastened to
the frame using quarter turn fasteners. Side panels shall be
secured to the frame using chrome plated screws. All panels
shall be flush fitting, sealed to the frame sections with closed
cell foam and insulated with a non-shedding material, which
shall be non-combustible, when tested in accordance with B.S.
476 Part 6 and 7. The units shall be fully accessible and
serviceable from the front.
Cooling Coil
The cooling coils shall be multi-row constructed from 10mm
O/D copper tubes with aluminium fins. Large surface areas
shall ensure high sensible heat ratios and low airside pressure
drops, resulting in reduced fan power requirements and noise
levels. All DX coils shall be tested to 25 bar.
DX Units
Each unit shall have 2 independent refrigerant circuits, each
with a liquid distributor, expansion valve, sight glass and filter
drier.
Fans
Large, low speed, double inlet, double width fans with forward
curved impellers and “sealed for life” self-aligning bearings
shall be used to minimize noise levels. Fans are belt driven. All
units have twin fans on a common shaft. The fan/motor
assembly is on a separate isolated deck.
Twin Belts
Twin grooved pulleys and twin belts giving a fixed speed are
provided for each fan assembly.
Motors
The motor shall comply with IP55 TEFC insulated to Class F.
Filtration
The filters shall be 100mm thick disposable pleated panel filter
rated G4 in accordance with EN779. They shall be fitted in the
return air stream and be accessible from the front of a Upflow
unit and the top of a Downflow unit.
Compressors
Compressors shall be high efficiency hermetically sealed scroll
type. Back seating service/isolating valve, high and low
pressure switches, motor overload protection and crankcase
heaters shall be provided. The compressors shall be mounted
on resilient neoprene mountings for vibration isolation.
Electrical Panel
The electrical panel shall be constructed and assembled in
compliance with IEC standards with all components VDE
approved. All sub circuits are protected by MCB’s. The high
and low voltage sections shall be segregated and all high
voltage electrical components shall be touch safe.
Electric Heaters
Electric heaters shall have stainless steel sheathed elements
with stainless steel finning, balanced over three phases and
rated to operate at black heat. Control shall be in two stages.
Protection is by a high temperature safety cut-out stat. The stat
shall be a capillary type mounted in the airstream resettable
from the control section of the electrical panel.
Humidification
The humidifier shall be of the electrode-boiler type. Features
shall include selectable steam output and microprocessor
control with alarms and diagnostic facilities. The humidifier
control system shall allow the use of a wide range of mains
water conditions namely: inlet mains water pressure of 1-10
bar, total hardness of 15-30 French degrees & water inlet
electrical conductivity of 400-800 micro siemens. Unit shall
optimize drain down frequency for maximum operational
economy.
Microprocessor Controls
All units shall be fitted as standard with the latest Delta range
of DIN rail mounted Microprocessor Controls. The Control
System utilizes a main Microprocessor Interface Board
equipped with a set of terminals necessary to connect the Board
to the controlled devices (e.g. valves, compressors, fans,
reheats, sensors and humidifiers). All software is permanently
stored in flash RAM and is therefore protected even in the event
of a power failure. Unit software is uploaded to the
Microprocessor using a RAM key or personal computer. On
multi-unit sites this quickens unit commissioning. The software
can also be easily changed or upgraded on site by qualified
service personnel.
The Microprocessor based Terminal Unit is complete with a 4
line x 20 character backlit LCD Display, keypad and LED
Indicators allowing the user to easily set the main control
parameters (set-points, differentials and alarm thresholds) and
carry out the main working operations (on/off and displaying
controlled variables).
Main features of controller are :
Status: The display shall indicate current temperature, current
humidity, temperature & humidity set points, cooling status,
heating status, humidification status & dehumidification status.
GUIDE SPECIFICATIONS