EDPAC Close Control 6, Close Control 12, Close Control 18 Installation, Operation & Maintenance Manual

Close Control
Small System Range
Chilled Water Units
Installation, Operation & Maintenance Manual 50/60Hz
2
Index
Description
Page
INSTALLATION
General
3
Mechanical Installation
4
Water and Drain Connections
5
General Engineering Data
6
Electrical Connections
7
OPERATION
General EC Fan910
Heating Operation
11
Cooling Operation
11
Dehumidification Control
12
Humidification Cycle
12
PGD Details
14
Alarms
15
MAINTENANCE
General
18
Common Components
18
Electric Panel – Inspection & Functional Tests
19
Steam Humidifier Canister Cleaning & Removal
20
Fault Finding Guide
21
Monthly Maintenance Inspection Check
23
Annual Maintenance Inspection Check
24
While every precaution has been taken to ensure accuracy and completeness in this manual, EDPAC assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Document reference E4.19-02-06-04
3
GENERAL
On receiving the equipment it should be checked to ensure that it is complete and in perfect condition. The carrier should be notified immediately, in writing, of any damage that might have been caused in transit.
HANDLING
Always keep the unit vertically upright and do not leave it out in the open. The unit can be moved with a pallet truck. If a forklift is being used ensure the forks extend beyond the pallet. Care should be taken not to damage the bottom of the unit. If a crane is being used to move the unit leave the packaging intact and place spreader bars across the top of the unit to prevent the slings causing damage. The unit should be moved as near as possible to the installation position before removing the cardboard packing and the pallet.
UNPACKING THE UNIT
1) Cut the three straps binding the unit taking care to avoid any backlash caused by their tightness.
2) Remove the lid.
3) The cardboard sleeve will then unravel itself revealing a plastic dust cover.
4) Remove dust cover. If it is a downflow model, to remove the front panels use the key attached to the sensor on the top of the unit.
5) Remove the two bolts securing the unit to the skid (19 mm spanner).
6) Manoeuvre the unit carefully from the pallet. If it is necessary, use rollers underneath the unit to locate it in its final position.
7) If the unit requires a plenum fix same before final positioning.
8) Ensure the unit is positioned on a level floor.
POSITIONING
Single Circuit Units. The Modular Range is built on a level base and its positioning is most important. The unit should be firmly supported on the floor itself or on an optional floorstand. Ensure that the unit is level in all directions as failure to do so will result in operational problems, particularly with regards to drainage. Care should be taken in manoeuvring the unit as the paintwork could be damaged. Use rollers where possible and apply pressure to the bottom of the unit for final positioning. Before final positioning ensure that inaccessible panels are correctly fitted and plenums are secured.
ATTACHING THE PLENUM
The plenum and unit are pre-drilled. At the time of installation remove the grilles from the plenum and secure the plenum internally by means of self tapping screws provided. Also secure to the back of the unit.
AIR COOLED CONDENSERS
Locate these as close to their final position as possible before uncrating. A full set of assembly instructions are attached to the unit. Headers and return bends are not to be used in the moving of the condenser. When locating the condenser ensure that it is in an open area with unrestricted airflow shaded from direct sunlight. Install in an environment free of debris to avoid the fins becoming blocked. Ensure that some form of vibration elimination is installed between the condenser legs and the roof of the building. Condensers are not to be ducted on either side. Where noise is critical in relation to the condenser make ensure that this is clearly specified at the time of order.
INSTALLATION
4
SERVICE ACCESS
Downflow Units
Service of a downflow unit can be generally completed from the front of the unit. To remove certain components from the unit it may be easier and quicker to have side access to assist in these operations. When positioned there should be a minimum clearance in front of the unit of 0.6m. If it is feasible, leave a distance of 0.6m at the side of the unit. Access to the back of the unit is not necessary. It is strongly recommended to leave a distance of 0.6m at both sides of the unit. There is a minimum distance of 150mm needed above the unit to allow removal of the filters.
Upflow Units
Unlike the downflow, side access is necessary for servicing the upflow. When installing ensure the left-hand side of the unit has access for the purpose of servicing, especially the motor. On the small frame the motor is actually mounted 'piggy-back' on the blower and on the mid and large frame the motor is located on the left-hand side of the blower Access to the back of the unit is not required. It is strongly recommended to leave a distance of 0.6m at both sides of the unit. The filters are located in the bottom front panel; a minimum distance of 1m is needed to allow the return air to enter the unit. Space above the unit will be determined by location. If a standard plenum is being installed the overall height of the unit is extended to 2380mm.
MECHANICAL INSTALLATION
SYSTEM APPLICATION
To achieve maximum performance and efficient energy usage following considerations should be given:
1) The room should be sealed effectively against air and vapour to minimise the loss and infiltration of uncontrolled humidity through concrete slab, walls, ceiling, roof, doors or any other opening or aperture.
2) Room location and orientation should be considered with regard to heat load and external variables should be reduced to a minimum.
3) The room should be kept at a positive pressure by introduction of pre-treated fresh air.
4) Low resistance to conditioned air distribution can be achieved by providing the maximum raised flooring height, minimum cable bunching and correct position of pipework (i.e. parallel to air flow).
5) Pipework that is not isolated or is fastened inadequately can transmit vibration along its full length.
Room Unit
Downflow Small System Unit
Service Access
600
Room Unit
Upflow Small System Unit
Service Access
600
600
5
CHILLED WATER UNITS
CHILLED WATER PIPING CONSIDERATIONS
Chilled water units are shipped with the flow and return pipes terminated with soft solder caps. The complete system is pressurised to 75psi with dry nitrogen. This pressure should be rechecked and discharged before caps are unsoldered. Supply and return pipes are clearly marked. Check the site piping to ensure that the flow is in the proper direction.
The maximum allowable static pressure for the chilled water circuit is 1000kPa. If static pressure exceeds 1000kPa special valves should be installed. Consideration of the minimum water temperature to be supplied from the chiller will determine if the need exists to insulate the supply and return lines.
It is recommended that isolating valves be field fitted on both flow and return lines from the unit for isolation and maintenance operations. Automatic air bleed valves should also be fitted in appropriate locations.
GENERAL ARRANGEMENT DRAWING
System Components
1. Evaporator Coil.
2. Balancing Valve
3. 3 Way Modulating Valve
4. Isolating Valves
Note: Item 4 is field fitted by others.
WATER AND DRAIN CONNECTIONS
WATER SUPPLY
Water is fed from the mains supply to the humidifier inlet solenoid valve. The connection to the solenoid valve is a 3/4” male connection. The feed water characteristics should comply with the following values:
In the case of high water pressure a pressure reducing valve calibrated to between 3 - 4 bar should be fitted. Inlet water temperature must not exceed 50oC. It is recommended to install a shut-off valve and a mechanical filter with the wire mesh size less than 50µm. The humidifier pan drain connection is a 22 mm female connection. The humidifier drain can be discharged into the standard drainage system via a rubber or plastic hose suitable for temperatures up to 100oC. The hose should have a minimum internal diameter of 22mm. A trap or vertical loop should be fitted in the tubing to prevent blow back or odours and ensure that the drain has a fall of not less than 1:50. Note: Do not feed demineralised water into the humidifier.
CONDENSATE DRAIN
Install a drain pipe from the base of the drainpan (typically a 1" female B.S.P. fitting). Insulating this drain pipe is not necessary. It is advised to fit a trap in this drainpipe. On a twin circuit unit there are knockouts on the side panels to route drain hoses through to a single outlet. Copper pipe should be used for drains on units with humidifiers. If the system is equipped with a condensate pump, install a check valve on the discharge line of the pump to prevent backfilling the pump reservoir.
Characteristic
Minimum
Maximum
Feed Water Pressure
1 bar
10 bar
Electric Conductivity at 25oC
400 µS/cm
800 µS/cm
Impurity Size
-
0.1 mm
M
1
Chilled Water Flow
Chilled Water Return
1
2
3
4
4
6
GENERAL ENGINEERINGDATA
Model0612
18
Air Side Data
Air Volume
m3/hr
1,800
3,600
5,400
m3/s
0.5
1.0
1.5
External Static Pressure ESP
Pa7575
75
No. of Fans
No.11
1
Fan MotorkW0.55
1.10
1.50
Optional EC Plug Fan
Quantity
No.11
1
Fan Diameter
mm
450
450
450
Fan Motor
kW
1.0
1.0
1.0
Fan Absorbed Power
kW
0.3
0.5
0.9
Filter Data
Downflow Filter Size
mm
495 x 535
495 x 535
495 x 695
Downflow Filter Quantity
No.22
2
Upflow Filter Size
mm
775 x 300
775 x 300
775 x 460
Upflow Filter Quantity
No.11
1
Filter Depthmm100
100
100
Filter Efficiency
-G4G4
G4
Water Side Data
Control Valve Size
mm2025
25
Control Valve Kv
-
4.0
6.3
6.3
Chilled Water F&R Pipe Size
mm2228
28
Cooling Coil Data
Coil Face Area – DX and C. Water
m20.4
0.6
0.6
Coil Rows
No.44
4
Coil Drain Connection BSPF
inch11
1
Air Cooled Units
Discharge Line Pipe Size
mm1616
16
Liquid Line Pipe Size
mm1212
12
Condenser Conns. Inlet/Outlet 30°C
mm
22/16
22/16
28/22
Condenser Conns. Inlet/Outlet 35°C
mm
22/16
28/22
28/22
Condenser Conns. Inlet/Outlet 40°C
mm
22/16
28/22
35/28
Condenser Conns. Inlet/Outlet 45°C
mm
22/16
35/28
35/28
Condenser Conns. Inlet/Outlet 50°C
mm
28/22
35/28
35/28
Scroll Compressor – 50Hz
-
ZR34K
ZR61K
ZR81K
Scroll Compressor – 60Hz
-
ZR28K
ZR48K
ZR72K
Compressor Quantity
No.11
1
Noise Data
Free field SPL @ 3m
dBA5255
57
Optional Humidifier Data
Capacity
kg/hr22
3
Inlet Connection BSPM
inch11
1
Drain Connection BSPM
inch11
1
Water Feed Pressure
Bar
1-10
1-10
1-10
Water Feed Electrical Conductivity
μS
400 – 800
400 – 800
400 – 800
French Degrees Water Hardness
-
15-30
15-30
15-30
Optional Electric Reheat Data
Capacity - 400V/3Ph/50Hz
kW
7.5
7.5
9.6
Capacity - 220V/3Ph/60Hz
kW
7.5
7.5
9.6
Capacity - 380V/3Ph/60Hz
kW
6.8
6.8
8.7
Capacity - 460V/3Ph/60Hz
kW
10.0
10.0
12.8
No.of Stages
No.22
2
Notes
1. Indoor unit Free field SPL dBA levels are measured at 3m.
2. For correct installation pipe sizes refer to refrigerant and water pipe sizing tables.
7
400V/3PH/50Hz
Model
61218
Controls FLA
1.0
1.0
1.0
Fans FLA
1.5
2.7
3.6
Reheat FLA
10.9
10.9
13.9
Humidifier FLA
2.2
2.2
3.2
Max Unit FLA - Cooling only
2.5
3.7
4.6
Max Fuse FLA
10.0
10.0
10.0
Max Unit FLA - Cooling & Dehumidification
13.4
14.6
18.5
Max Fuse FLA
20.0
20.0
25.0
Max Unit FLA - Heating and Humidification
15.6
16.8
21.7
Max Fuse FLA
20.0
25.0
30.0
220V/3PH/60Hz
Model
61218
Controls FLA
1.0
1.0
1.0
Fans FLA
2.7
4.9
6.6
Reheat FLA
19.8
19.8
25.3
Humidifier FLA
4.0
4.0
5.8
Max Unit FLA - Cooling only
3.7
5.9
7.6
Max Fuse FLA
10.0
15.0
20.0
Max Unit FLA - Cooling & Dehumidification
23.5
25.7
32.9
Max Fuse FLA
30.0
35.0
45.0
Max Unit FLA - Heating and Humidification
27.5
29.7
38.7
Max Fuse FLA
35.0
40.0
50.0
Notes:
1. FLA = Full Load Amps.
2. Unit maximum FLA is the total of the components, which operate during maximum electrical load conditions.
3. Max FLA of Cooling only unit : FLA = Controls + Fans
4. Max FLA of unit with reheat only in dehumidification : FLA = Controls + Fans + Reheat.
5. Max FLA of units with heating & humidifiers : FLA = Controls + Fans + Reheat + Humidifier.
6. Max Fuse is the recommended value of the unit overcurrent protection device.
ELECTRICAL DETAILS – CHILLED WATER UNITS
8
380V/3PH/60Hz
Model
61218
Controls FLA
1.0
1.0
1.0
Fans FLA
1.6
2.9
3.8
Reheat FLA
10.3
10.3
13.2
Humidifier FLA
2.3
2.3
3.4
Max Unit FLA - Cooling only
2.6
3.9
4.8
Max Fuse FLA
10.0
10.0
10.0
Max Unit FLA - Cooling & Dehumidification
12.9
14.2
18.0
Max Fuse FLA
15.0
20.0
25.0
Max Unit FLA - Heating and Humidification
15.2
16.5
22.8
Max Fuse FLA
20.0
25.0
30.0
460V/3PH/60Hz
Model
61218
Controls FLA
1.0
1.0
1.0
Fans FLA
1.3
2.3
3.1
Reheat FLA
12.6
12.6
16.1
Humidifier FLA
1.9
1.9
2.8
Max Unit FLA - Cooling only
2.3
3.3
4.1
Max Fuse FLA
10.0
10.0
10.0
Max Unit FLA - Cooling & Dehumidification
14.9
15.9
20.2
Max Fuse FLA
20.0
20.0
25.0
Max Unit FLA - Heating and Humidification
16.8
19.2
23.0
Max Fuse FLA
20.0
25.0
30.0
Notes:
1. FLA = Full Load Amps.
2. Unit maximum FLA is the total of the components, which operate during maximum electrical load conditions.
3. Max FLA of Cooling only unit : FLA = Controls + Fans
4. Max FLA of unit with reheat only in dehumidification : FLA = Controls + Fans + Reheat.
5. Max FLA of units with heating & humidifiers : FLA = Controls + Fans + Reheat + Humidifier.
6. Max Fuse is the recommended value of the unit overcurrent protection device.
ELECTRICAL DETAILS – CHILLED WATER UNITS
Loading...
+ 16 hidden pages