EDM Solution-16, Solution-16 Safecom Installation Manual

Solution-16/
Solution-16 Safecom
Installation Manual
ISSUE 2.20
This page has been included for you to cut out and insert into the spine
of the folder
MA880I
Solution-16/
Solution-16
Safecom
Installation
Manual
ISSUE 2.20
(61-2) 9672 1777
Solution-16/Solution-16 Safecom
Installation Manual
Copyright
This documentation is provided to suit
This installation manual includes programming locations to suit both Solution-16 (CC880/LP880) and the Solution­16 Safecom (SC8016) control panel. Locations that are only relevant when using the SC8016 are prefixed with the word Safecom.
1999 by Electronics Design & Manufacturing Pty Limited,
SYDNEY, AUSTRALIA
Document Part Number MA880I
Document Issue 2.20
Printed 7/05/2001
Solution-16 Control Panel (CC880/LP880 + SC8016)
Firmware Revision 1.10 - 2.06
Hardware Revision E - K
Copyright Notice
All rights reserved. No part of this publication may be reproduced, transmitted or stored in a retrieval system in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without the prior written permission of Electronics Design and Manufacturing Pty Limited.
Trademarks
Throughout this document trademark names may have been used. Rather than put a trademark symbol in every occurrence of a trademark name, we state that we are using the names only in an editorial fashion and to the benefit of the trademark owner with no intention of infringement of the trademark.
Notice of Liability
While every precaution has been taken in the preparation of this document, neither Electronics Design & Manufacturing Pty Limited nor any of its official representatives shall have any liability to any person or entity with respect to any liability, loss or damage caused or alleged to be caused directly or indirectly by the information contained in this book.
Electronics Design & Manufacturing Pty Limited reserves the right to make changes to features and specifications at any time without prior notification in the interest of ongoing product development and improvement.
Table Of Contents
INTRODUCTION................................................................................................................................ 13
INTRODUCTION ..............................................................................................................................................................14
QUICK START ..................................................................................................................................................................15
TELEPERMIT NOTE ........................................................................................................................................................16
PROGRAMMING................................................................................................................................ 17
PROGRAMMING ..............................................................................................................................................................18
PROGRAMMING WITH THE REMOTE CODEPAD .....................................................................................................19
PROGRAMMING WITH THE HAND HELD PROGRAMMER.....................................................................................20
PROGRAMMING USING THE PROGRAMMING KEY ................................................................................................21
PROGRAMMING VIA THE DTMF COMMAND MODULE..........................................................................................22
How To Establish A Communication Link With The Control Panel...........................................................................22
Programming The Control Panel Once A Communication Link Has Been Established ..............................................22
PROGRAMMING OPTION BITS .....................................................................................................................................22
INSTALLERS PROGRAMMING COMMANDS .............................................................................................................23
Command 958 - Enable/Disable Zone Status Mode ....................................................................................................23
Command 959 - Test Programming Key......................................................................................................................24
Command 960 - Exit Installer's Programming Mode...................................................................................................24
Command 961 - Reset Control Panel Back To Factory Default Settings.....................................................................24
Command 962 - Copy Control Panel Memory To Programming Key.........................................................................25
Command 963 - Copy From Programming Key To Control Panel..............................................................................25
Command 964 - Erase Programming Key....................................................................................................................26
Command 965 - Set Up Domestic Dialling Format .....................................................................................................27
Command 966 - Enable/Disable Automatic Stepping Of Locations............................................................................28
Command 999 - Display Software Version Number....................................................................................................28
Disable Factory Default...................................................................................................................................................29
DEFAULTING THE CONTROL PANEL .........................................................................................................................29
SYSTEM INDICATORS AND OPERATIONS................................................................................ 31
SYSTEM INDICATORS AND OPERATIONS.................................................................................................................32
The Codepad................................................................................................................................................................32
Zone Indicators ............................................................................................................................................................32
AWAY Indicator..........................................................................................................................................................32
STAY Indicator ...........................................................................................................................................................32
MAINS Indicator .........................................................................................................................................................33
FAULT Indicator .........................................................................................................................................................33
Audible Indicators........................................................................................................................................................33
LCD CODEPAD INDICATORS........................................................................................................................................34
SYSTEM OPERATIONS ...................................................................................................................................................35
Arming The System In AWAY Mode.............................................................................................................................35
Forced Arming.............................................................................................................................................................35
Disarming The System From AWAY Mode ...................................................................................................................35
Arming The System In STAY Mode 1............................................................................................................................36
Forced Arming.............................................................................................................................................................36
Disarming The System From STAY Mode 1..................................................................................................................37
Arming The System In STAY Mode 2............................................................................................................................38
Forced Arming.............................................................................................................................................................38
Disarming The System From STAY Mode 2..................................................................................................................39
Codepad Duress Alarm ...................................................................................................................................................40
Codepad Panic Alarm - Software Version 1.10 - 1.36 ....................................................................................................40
Codepad Panic Alarm - Software Version 1.37 Onwards ...............................................................................................40
Codepad Fire Alarm - Software Version 1.37 Onwards..................................................................................................40
Codepad Medical Alarm - Software Version 1.37 ..........................................................................................................40
Isolating Zones................................................................................................................................................................41
Standard Isolating ........................................................................................................................................................41
Code To Isolate............................................................................................................................................................41
Fault Analysis Mode .......................................................................................................................................................42
Fault Descriptions........................................................................................................................................................... 42
1 Low Battery.........................................................................................................................................................42
2 Date and Time..................................................................................................................................................... 42
3 Sensor Watch ......................................................................................................................................................42
4 Horn Speaker Monitor ........................................................................................................................................43
5 Telephone Line Fault ..........................................................................................................................................43
6 E2 Fault...............................................................................................................................................................43
7 Zone 16 In Alarm - Partitioned Systems Only ....................................................................................................43
8 Communication Failure....................................................................................................................................... 43
AC Mains Failure ........................................................................................................................................................43
SYSTEM FUNCTIONS........................................................................................................................45
SYSTEM FUNCTIONS .....................................................................................................................................................46
Installer Code Functions ................................................................................................................................................. 46
2 Set The Number Of Days Until The First Test Report........................................................................................ 46
3 Event Memory Recall Mode............................................................................................................................... 47
4 Walk Test Mode..................................................................................................................................................48
5 Satellite Siren Service Mode...............................................................................................................................48
7 Telephone Monitor Mode On and Off ................................................................................................................49
Master Code Functions ................................................................................................................................................... 50
0 Arming and Disarming All Areas At The Same Time - Partitioned Systems Only............................................. 50
1 Changing and Deleting User Codes ....................................................................................................................51
Auxiliary Codes...........................................................................................................................................................52
2 Programming Domestic Phone Numbers ............................................................................................................ 54
3 Event Memory Recall Mode............................................................................................................................... 55
4 Walk Test Mode..................................................................................................................................................56
5 Turning Outputs On and Off ...............................................................................................................................57
6 Setting The Date and Time .................................................................................................................................58
7 Turning Day Alarm On and Off (Software Version 1.10 Only).......................................................................... 58
8 Setting STAY Mode 2 Zones.............................................................................................................................. 59
User Code Functions - Partitioned Systems Only ...........................................................................................................60
0 Arming and Disarming All Areas At The Same Time - Partitioned Systems Only............................................. 60
Hold Down Functions.....................................................................................................................................................61
# Arm The System In AWAY Mode......................................................................................................................61
* Arm The System In STAY Mode 1.....................................................................................................................61
0 Arm The System In STAY Mode 2.....................................................................................................................61
1 Horn Speaker Test...............................................................................................................................................61
2 Bell Test.............................................................................................................................................................. 62
3 Strobe Test ..........................................................................................................................................................62
4 Turning Day Alarm On and Off (New - Software Version 1.20 Onwards)......................................................... 62
5 Fault Analysis Mode ........................................................................................................................................... 63
6 Initiate A Modem Call ........................................................................................................................................63
7 Reset Latching Outputs .......................................................................................................................................63
8 Codepad ID and Buzzer Tone Change................................................................................................................ 64
9 Initiate A Test Report..........................................................................................................................................64
REMOTE OPERATIONS ...................................................................................................................65
REMOTE OPERATIONS .................................................................................................................................................. 66
Remote Arming Via The Telephone ............................................................................................................................... 66
How To Remotely Arm Your System Via The Telephone.......................................................................................... 66
Operating The Control Panel Using The DTMF Command Module.............................................................................. 67
Operation - Software From Version 1.10 ....................................................................................................................67
Operation - Software From Version 1.20 ....................................................................................................................67
Upload/Download Via Alarm Link Software..................................................................................................................69
Direct Connect............................................................................................................................................................. 69
Remote Connect ..........................................................................................................................................................70
REPORTING FORMATS....................................................................................................................71
REPORTING FORMATS .................................................................................................................................................. 72
Contact ID Format ..........................................................................................................................................................72
Event Codes.................................................................................................................................................................... 73
Point ID Codes................................................................................................................................................................ 74
General Reporting Formats............................................................................................................................................. 75
Securitel ..........................................................................................................................................................................77
How To Program and Set Up Securitel........................................................................................................................77
Securitel and Partitioning................................................................................................................................................77
Domestic Reporting.........................................................................................................................................................78
Programming Domestic Reporting...............................................................................................................................78
Domestic Dialling Operation...........................................................................................................................................79
Acknowledge Domestic Dialling .................................................................................................................................79
Synthesised Voice Reporting ..........................................................................................................................................80
How To Set Up The Control Panel For Synthesised Voice Format.............................................................................80
How To Disable Synthesised Voice Dialling Using The Master Code........................................................................81
Synthesised Voice Dialling Operation.............................................................................................................................81
How To Acknowledge Synthesised Voice Dialling Without DTMF Command Module Fitted ..................................81
How To Acknowledge Synthesised Voice Dialling With DTMF Command Module Fitted .......................................81
Operation Of The Voice Module.....................................................................................................................................82
Recording The Voice Message ....................................................................................................................................82
Replay The Voice Message..........................................................................................................................................82
Connection Of The Voice Module...............................................................................................................................83
Basic Pager Format Reporting ........................................................................................................................................84
PET Alpha Pager Reporting............................................................................................................................................85
Programming and Hardware Requirements .................................................................................................................85
Telecom Access Telephone Numbers..........................................................................................................................85
PET Alpha Pager Messages.........................................................................................................................................86
PET Alpha Pager Password.............................................................................................................................................87
Converting ASCII Characters To Hexadecimal...........................................................................................................88
PET Alpha Pager ID Number..........................................................................................................................................88
Logging System Events Via Serial Printer ......................................................................................................................89
Printer Output Baud Rate ................................................................................................................................................89
BASE STATION INFORMATION.................................................................................................... 91
BASE STATION INFORMATION....................................................................................................................................92
How To Program A Phone Number.............................................................................................................................92
Primary Telephone Number ............................................................................................................................................92
Secondary Telephone Number........................................................................................................................................93
Callback Telephone Number...........................................................................................................................................93
Dialling Format ...............................................................................................................................................................93
Handshake Tone..............................................................................................................................................................94
Transmission Format.......................................................................................................................................................94
Transmission Speed.........................................................................................................................................................95
Subscriber ID Number ....................................................................................................................................................96
Ring Count ......................................................................................................................................................................96
Answering Machine Bypass.........................................................................................................................................96
ACCESS CODES ................................................................................................................................. 97
ACCESS CODES................................................................................................................................................................98
Installer Code ..................................................................................................................................................................98
User Codes ......................................................................................................................................................................98
User Code Priority .......................................................................................................................................................99
Auxiliary Codes.............................................................................................................................................................101
Auxiliary Code 1...........................................................................................................................................................101
Auxiliary Code 2...........................................................................................................................................................101
Code Retries..................................................................................................................................................................101
ZONE PROGRAMMING ................................................................................................................. 103
ZONE PROGRAMMING.................................................................................................................................................104
Zone Operating Information ......................................................................................................................................104
Zone Reporting Information ......................................................................................................................................104
Zone Defaults................................................................................................................................................................104
Zone Types....................................................................................................................................................................105
0 Instant Zone.......................................................................................................................................................105
1 Handover Zone ..................................................................................................................................................105
2 Delay-1 Zone.....................................................................................................................................................105
3 Delay-2 Zone.....................................................................................................................................................105
4 Delay-3 Zone.....................................................................................................................................................105
5 Delay-4 Zone.....................................................................................................................................................105
6 Instant Zone + Isolated In STAY Mode 1.........................................................................................................105
7 Handover Zone + Isolated In STAY Mode 1.................................................................................................... 105
8 Delay-1 Zone + Isolated In STAY Mode 1.......................................................................................................105
9 Delay-2 Zone + Isolated In STAY Mode 1.......................................................................................................106
10 Delay-3 Zone + Isolated In STAY Mode 1................................................................................................... 106
11 Delay-4 Zone + Isolated In STAY Mode 1................................................................................................... 106
12 24 Hour Burglary Zone................................................................................................................................. 106
13 24 Hour Fire Zone.........................................................................................................................................106
14 Chime Zone (Follow Me)..............................................................................................................................106
15 Zone Not Used.............................................................................................................................................. 106
Zone Options.................................................................................................................................................................107
1&2 Lockout Siren & Lockout Dialler..................................................................................................................107
4 Silent Alarm ......................................................................................................................................................107
8 Sensor Watch ....................................................................................................................................................108
Zone Pulse Count.......................................................................................................................................................... 108
Zone Pulse Count Handover .........................................................................................................................................109
Zone Pulse Count Time.................................................................................................................................................109
Day Alarm.....................................................................................................................................................................110
Day Alarm Resetting .................................................................................................................................................110
Day Alarm Latching ..................................................................................................................................................110
Day Alarm Operation - (Software Version 1.10)..........................................................................................................111
Day Alarm Operation - (Software Version 1.20 Onwards)...........................................................................................111
Day Alarm In Partitioning.............................................................................................................................................111
EOL Resistor Value...................................................................................................................................................... 112
SYSTEM STATUS INFORMATION...............................................................................................113
SYSTEM STATUS INFORMATION..............................................................................................................................114
Zone Bypass Reports (1-8) ...........................................................................................................................................114
Zone Bypass Reports(9-16) ..........................................................................................................................................114
Zone Trouble Report (1-8)............................................................................................................................................115
Zone Trouble Report (9-16)..........................................................................................................................................115
Codepad Duress............................................................................................................................................................ 116
Codepad Panic ..............................................................................................................................................................117
Access Denied...............................................................................................................................................................118
AC Fail..........................................................................................................................................................................118
Low Battery ..................................................................................................................................................................119
Program Altered Code ..................................................................................................................................................119
Sensor Watch................................................................................................................................................................ 120
Open/Close Reports For Area 1....................................................................................................................................120
Safecom RF Fail ...........................................................................................................................................................121
Safecom Telco Fail ....................................................................................................................................................... 121
Safecom RF Jamming ...................................................................................................................................................121
Test Reports.................................................................................................................................................................. 122
Test Report Options...................................................................................................................................................122
PROGRAMMABLE OUTPUTS.......................................................................................................123
PROGRAMMABLE OUTPUTS...................................................................................................................................... 124
Output Configurations...................................................................................................................................................125
Redirecting Outputs To The Codepad Buzzer .............................................................................................................. 126
Safecom Remote Operation Of Outputs........................................................................................................................126
Example ........................................................................................................................................................................ 126
OUTPUT EVENT TYPES ...............................................................................................................................................127
Output Polarity - (Software Version 1.20 - 1.40)..........................................................................................................134
0 Output Not Used ...............................................................................................................................................134
1 Normally Open, Going Low.............................................................................................................................. 134
2 Normally Open, Pulsing Low............................................................................................................................ 134
3 Normally Open, One Shot Low......................................................................................................................... 134
4 Normally Open, One Shot Low With Retrigger................................................................................................ 134
5 Normally Open, One Shot Low With Reset ......................................................................................................134
6 Normally Open, One Shot Low With Alarm.....................................................................................................134
7 Normally Open, Latching Low.........................................................................................................................134
8 Normally Low, Going Open.............................................................................................................................. 135
9 Normally Low, Pulsing Open............................................................................................................................ 135
10 Normally Low, One Shot Open.....................................................................................................................135
11 Normally Low, One Shot Open With Retrigger............................................................................................135
12 Normally Low, One Shot Open With Reset ..................................................................................................135
13 Normally Low, One Shot Open With Alarm.................................................................................................135
14 Normally Low, Latching Open......................................................................................................................135
Output Polarity - (Software Version 1.10 Only)............................................................................................................135
Timing Of Outputs ........................................................................................................................................................136
Pulsing Polarities...........................................................................................................................................................136
One Shot Polarities........................................................................................................................................................137
SYSTEM EVENT TIMERS.............................................................................................................. 139
SYSTEM EVENT TIMERS .............................................................................................................................................140
How To Program Entry/Exit Times...............................................................................................................................140
Entry Time.................................................................................................................................................................140
Entry Time 1 .................................................................................................................................................................140
Entry Time 2 .................................................................................................................................................................140
Entry Time 3 .................................................................................................................................................................140
Entry Time 4 .................................................................................................................................................................140
Exit Time.......................................................................................................................................................................141
Exit Time For AWAY Mode.........................................................................................................................................141
Exit Time For STAY Mode 1 .......................................................................................................................................141
Exit Time For STAY Mode 2 .......................................................................................................................................141
Entry Guard Time For STAY Mode .............................................................................................................................141
Codepad Lockout Time.................................................................................................................................................142
Sensor Watch Time.......................................................................................................................................................142
Safecom RF Jamming Delay .........................................................................................................................................142
Safecom RF Supervision Time......................................................................................................................................142
System Date...................................................................................................................................................................143
Setting The Date and Time ........................................................................................................................................143
Auto Arming Time ........................................................................................................................................................144
Auto Arming Pre-Alert Time ........................................................................................................................................144
Timed Output Pre-Alert Time .......................................................................................................................................145
Auto Operation Of The Timed Output ..........................................................................................................................145
Siren Run Time .............................................................................................................................................................145
Siren Sound Rate...........................................................................................................................................................146
Swinger Shutdown Count..............................................................................................................................................146
Swinger Shutdown Count For Siren..............................................................................................................................147
Swinger Shutdown Count For Dialler ...........................................................................................................................147
Ring Burst Time............................................................................................................................................................148
Ring Burst Time............................................................................................................................................................148
System Time..................................................................................................................................................................149
Setting The Date and Time ........................................................................................................................................149
OPTION BITS .................................................................................................................................... 151
OPTION BITS ..................................................................................................................................................................152
Dialler Options 1...........................................................................................................................................................152
Dialler Options 2...........................................................................................................................................................153
System Options 1...........................................................................................................................................................154
System Options 2...........................................................................................................................................................155
System Options 3...........................................................................................................................................................156
System Options 4...........................................................................................................................................................157
System Options 4...........................................................................................................................................................158
Consumer Options 1......................................................................................................................................................159
Consumer Options 1......................................................................................................................................................160
Consumer Options 2......................................................................................................................................................161
DTMF Command Module Options ...............................................................................................................................162
Expansion Board Type..................................................................................................................................................163
Expansion Board Type..................................................................................................................................................164
Telephone Line Fault Options.......................................................................................................................................166
Safecom Reporting Options ..........................................................................................................................................167
System Options 5...........................................................................................................................................................167
System Options 6...........................................................................................................................................................168
Carrier Sync Options.....................................................................................................................................................169
PARTITIONING ................................................................................................................................171
PARTITIONING .............................................................................................................................................................. 172
Master Partitioned Codepad Indicators.........................................................................................................................172
1 Zone Indicators ................................................................................................................................................. 172
2 Areas On/Off Indicators.................................................................................................................................... 172
3 Area Display Indicators.....................................................................................................................................172
4 Status Indicators................................................................................................................................................172
Operating Codepads In Partitioning..............................................................................................................................173
Operating From A "CP5 Area Addressable (CP500A)" Codepad.............................................................................173
Operating From A "CP5 Master Partitioned (CP500P)" Codepad............................................................................173
Securitel and Partitioning..............................................................................................................................................173
Questions To Be Considered When Partitioning ..........................................................................................................174
Open/Close Reports ...................................................................................................................................................... 175
Dialler Options 2...........................................................................................................................................................175
Open/Close Reports For Area 1....................................................................................................................................176
Open/Close Reports For Area 2....................................................................................................................................176
Open/Close Reports For Area 3....................................................................................................................................176
Open/Close Reports For Area 4....................................................................................................................................176
Subscriber ID Number For Area 1................................................................................................................................ 177
Subscriber ID Number For Area 2................................................................................................................................ 177
Subscriber ID Number For Area 3................................................................................................................................ 177
Subscriber ID Number For Area 4................................................................................................................................ 177
Zone Allocations........................................................................................................................................................... 178
Zone Allocations For Area 1.........................................................................................................................................178
Zone Allocations For Area 2.........................................................................................................................................178
Zone Allocations For Area 3.........................................................................................................................................179
Zone Allocations For Area 4.........................................................................................................................................179
User Code Allocations.................................................................................................................................................. 180
Setting Up and Programming Codepads For Partitioning............................................................................................. 181
Codepad Connections For Partitioning.........................................................................................................................182
OPTIONAL EQUIPMENT................................................................................................................185
Optional Equipment...................................................................................................................................................... 186
TERMINAL DEFINITIONS AND DESCRIPTIONS.....................................................................193
TERMINAL DEFINITIONS AND DESCRIPTIONS .....................................................................................................194
Solution-16 Wiring Diagram.........................................................................................................................................196
Eight Zone Expansion Board (CC885) - Fixed 3K3 EOL Resistors............................................................................. 197
Eight Zone Expansion Board (CC883) - Variable EOL Resistors ................................................................................ 197
Connections Of Split EOL Resistors For 16 Zone Operation .......................................................................................198
Eight Channel Open Collector Output Board (CC884).................................................................................................198
Connection For Momentary Or Latching Keyswitch .................................................................................................... 199
Connections For 25 Pin Logging Printer.......................................................................................................................199
Connections For 9 Pin Logging Printer.........................................................................................................................199
Solution-16 Component Overlay ..................................................................................................................................200
Solution-16 Safecom Interface...................................................................................................................................... 202
How To Install The BNC Fitting ..................................................................................................................................202
How To Mount The Radio............................................................................................................................................ 203
Mounting The Radio.....................................................................................................................................................203
Telecom Connection Diagrams.....................................................................................................................................204
APPENDICES .....................................................................................................................................205
APPENDIX A...................................................................................................................................................................206
Telephone Anti-Jamming ..........................................................................................................................................206
APPENDIX B...................................................................................................................................................................207
Test Reports Only When Armed ...............................................................................................................................207
SPECIFICATIONS.............................................................................................................................209
WARRANTY STATEMENT...........................................................................................................................................210
Specifications ............................................................................................................................................................210
Software Version Number.............................................................................................................................................210
PROGRAMMING SHEETS..............................................................................................................211
INDEX..................................................................................................................................................221
Introduction
14
Solution-16/Solution-16 Safecom Installation Manual
Introduction
Congratulations on selecting the Solution-16 control panel for your installation. So that you can obtain the most from your unit, we suggest that you take the time to read through this manual and familiarise yourself with the numerous outstanding operating and installation features of this control panel.
You will notice that in all aspects of planning, engineering, styling, operation, convenience and adaptability, we have sought to anticipate your every possible requirement. Programming simplicity and speed have been some of the major considerations and we believe that our objectives in this area have been more than satisfied.
This installation manual will explain all aspects of programming the final commissioning. All system parameters and options are detailed, however, suitability is left up to the individual. Every control panel can be tailored to meet all requirements quickly and easily. The programming simplicity will make your installation quick, accurate and rewarding each and every time.
The
Solution range of control panels has proven very popular amongst thousands of people throughout many countries
of the world, all who have various levels of technical aptitude and ability. We have tried to aim this installation manual to all levels of readers.
As the
Solution control panels have continued to advance over the years, they have become very powerful and extensive.
Some of its early first-time users have advanced to true "power users" and we need to address their needs too, while maintaining the simplicity of the manual and the product.
Solution-16 control panel from factory default to
ISSUE220.DOC Electronics Design & Manufacturing Pty Limited
Introduction 15
Quick Start
The following steps will enable you to use the Solution-16 control panel with the factory default values.
1. Connect the AC plug pack to the control panel.
All zone indicators on the remote codepad will illuminate momentarily and then extinguish. Check the operation of the overload LED (LD1) on the printed circuit board. In normal operation the LED will not illuminate. The MAINS indicator will remain on, as will the AWAY indicator. The system is now in the armed state.
2. The lead acid back-up battery should now be connected. The lead acid rechargeable back-up battery should be rated at 12v DC @ 6.5 Ah.
3. Enter the The control panel is now in the disarmed state. Programming of the control panel can now be accessed. Refer to the "Master Code Functions" on page 50 for more information. The factory default Master Code is
4. Enter the factory default The STAY and AWAY indicators will now flash simultaneously. Refer to "LOCATION 56 - 62" on page 98 for the locations of the factory default Installer Code. The factory default Installer Code is
5. Enter the Primary Telephone Number and the Secondary Telephone Number followed by the Subscriber ID Number.
6. If required, program the test reporting time and any other programming changes to be made; otherwise the
programmed factory default settings will be used.
7. Enter command will return to the disarmed state and is now ready for use.
8. Refer to page 42 for information on any system faults that may have occurred.
9. Using a Master Code set the date and time. Refer to "Master Code Functions" on page 50 for more information on
setting the date and time.
The factory default settings allow the control panel to communicate in Contact ID Format operating eight zones. For further information on the factory default settings, refer to the "Programming Sheets" on page 211 at the back of the installation manual. If sixteen zones are required, refer to "LOCATION 339" on page 112 for setting the split EOL resistor value or "LOCATION 672" to enable the zone expansion board if required on page 163.
followed by the button to disarm the system. The AWAY indicator will extinguish.
2580.
followed by the button to access the Installer's Programming Mode.
1234.
960 followed by the button to exit the Installer's Programming Mode. The control panel
Zone Number Zone Type
1
2, 3, 4, 5
6, 7 & 9 - 16
8
Delay-1 Handover Instant 24 Hour
Table 1: Zone Defaults
Electronics Design & Manufacturing Pty Limited ISSUE220.DOC
16
Solution-16/Solution-16 Safecom Installation Manual
Telepermit Note
The grant of a Telepermit for a device in no way indicates Telecom acceptance of responsibility for the correct operation of that device under all operating conditions.
This equipment shall not be used in any manner that could constitute a nuisance to other Telecom customers.
Immediately disconnect this equipment should it become physically damaged, and arrange for its disposal or repair.
The preferred method of dialling is to use DTMF tones as this is faster than pulse (Decadic) dialling. In some situations there may be difficulties with DTMF signalling as this control panel is not fully compatible with the Telecom Telephone Network. In this case you must use decadic dialling, and your control panel must be set up to record numbers using the following translation table as it does not implement the New Zealand "Reverse Dialling" standard.
Number to be dialled 0 1 2 3 4 5 6 7 8 9 Number to be programmed 9 8 7 6 5 4 3 2 1 0
Note that where DTMF dialling is used, the numbers should be entered normally.
The transmit level from this device is set as a fixed level and because of this there may be circumstances where the performance is less than optimal. Before reporting such occurrences as faults, please check the line with a standard telepermitted telephone.
ISSUE220.DOC Electronics Design & Manufacturing Pty Limited
Programming
18 Solution-16/Solution-16 Safecom Installation Manual
Programming
The programming options of this control panel are stored in a non-volatile EPROM. This memory will hold all the relevant configuration and user specific data even during a total power loss.
The data retention time is as long as ten years without power, therefore, no reprogramming will be required after powering the control panel down.
The data can be altered as many times as required without the need for any additional specialised equipment. This memory is laid out in numerous locations, each of which holds the data for a specific function.
In general, the entire programming sequence will consist of nominating the location number required and then entering or altering the data. You will repeat this procedure until all the data has been programmed to suit your requirements. The factory default settings have been selected for reporting in the Contact ID Format.
Note: 15 is the maximum value that can be programmed into any location.
There are two programming modes. The Installer's Programming Mode and the Operators Programming Mode. Both programming modes have individual access codes and these two codes must always be programmed differently. The Master Code, as well as being able to arm and disarm the system gives access to the Operators Programming Mode. The Installers Code only gives access to the Installer's Programming Mode and does NOT arm and disarm the system.
Programming of the
Solution-16 control panel can be carried out via any of the following five methods.
System Codepad
Hand Held Programmer (CC814)
Programming Key (CC891)
Alarm Link Upload/Download Software (CC816)
DTMF Command Module (CC886)
ISSUE220.DOC Electronics Design & Manufacturing Pty Limited
Programming 19
Programming With The Remote Codepad
The control panel must be in the disarmed state with no flashing zone alarm memories to access the Installer's Programming
Mode. This can be achieved by entering the
is
2580.
To access the Installer's Programming Mode, enter the
Installer Code is
1234. Three beeps will be heard and both the STAY and AWAY indicators will flash
simultaneously. If a long beep is heard, check the control panel for alarm memory. The combination of the MAINS and ZONE indicators will indicate the data stored in the first location of the Primary Telephone Number (LOCATION 000).
Data
Value
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Zone 1
Indicator
Zone 2
Indicator
Zone 3
Indicator
Table 2: Zone Indicators When Programming
Example
followed by the button. The factory default Master Code
followed by the button. The factory default
Zone 4
Indicator
Zone 5
Indicator
Zone 6
Indicator
Zone 7
Indicator
Zone 8
Indicator
 
MAINS
Indicator
     
To enter Installer's Programming Mode, enter the followed by the button. The factory default
Installer's Code is
1234. Two beeps will be heard and the codepad will display the current data stored in
"LOCATION 000".
To go to a particular location, enter the
required followed by the button. The data of the new
location will now be displayed.
To move to the next location, press the
button. This will step you to the next location and the data in that location
will be displayed via the ZONE indicators.
If you press the
change data at the current location, enter the new value (0-15) followed by the
button without previously entering a location number, the system will step back one location. To
button. This will store the new data
into the location and still leave you positioned at the same location.
To proceed to the next location, press the
button. The next locations data will now be displayed.
To exit the Installer's Programming Mode, enter command
960 followed by the button. Two beeps will be
heard and the system will return back to normal operation. Refer to "Installers Programming Commands" on page 23 for further information on commands that can be performed during access of the Installer's Programming Mode.
Electronics Design & Manufacturing Pty Limited ISSUE220.DOC
20 Solution-16/Solution-16 Safecom Installation Manual
Programming With The Hand Held Programmer
The Hand Held Programmer (CC814) has five, seven segment displays. The three on the left display the location number, and the two on the right display the data for that particular location.
To connect the hand held programmer, locate the connections marked PROGRAMMING KEY. This point can be found on the left hand side of the printed circuit board. Observe the triangular markings on the printed circuit board and line them up with the markings on the hand held programmers connecting socket.
When the hand held programmer is correctly plugged onto the printed circuit board, one beep will be heard and four centre bars on the hand held programmer will illuminate with either an 'A' or 'U' suffix to indicate the system is armed or unarmed. Only when the Installer's Programming Mode has been accessed will any numerals appear on the display.
Note: When connecting the hand held programmer to the control panel, make sure that the switch on the hand held
Example
To enter the Installer's Programming Mode, enter the followed by the # button. The factory default
Installers Code is stored in "LOCATION 000".
To move to a particular programming location, enter the new location will now be displayed.
To move to the next location press the now be displayed via the ZONE indicators.
If you press the
change data in the current location, enter the new value (0-15) followed by the the location and still leave you still positioned at the same location.
To proceed to the next location, press the
To exit the Installer's Programming Mode, enter command and the system will return back to normal operation. Refer to "Installers Programming Commands" on page 23 for further information on commands that can be performed during access of the Installer's Programming Mode.
programmer is in the EXT position and that no external programming key has been connected. Failing to do this may corrupt the control panel's memory. If this happens, the control panel will need to be returned to Electronics Design and Manufacturing Pty Limited where a service fee will be charged to unlock the control panel’s memory.
1234. Two beeps will be heard and the hand held programmers display will show the current data
followed by the # button. The data for the
# button. This will step you to the next location and the data in that location will
* button without previously entering a location number, the system will step back one location. To
* button. This will store the new data into
# button. The next locations data will now be displayed.
960 followed by the # button. Two beeps will be heard
Note: When using the hand held programmer, any reference in this manual made to the button should be
considered as the *
ISSUE220.DOC Electronics Design & Manufacturing Pty Limited
* button and the button considered as the #### button.
**
Programming 21
Programming Using The Programming Key
The Programming Key (CC891) is a unique device that will allow you to easily program your control panel. Inserting the programming key will automatically initiate a data transfer from the programming key to the control panel memory.
If you have a new programming key, you should first enter the Installer's Programming Mode, configure your control panel as per your requirements before inserting the programming key.
To connect the programming key, locate the connections marked PROGRAMMING KEY. This point can be found on the right hand side of the control panel. Observe the triangular markings on the printed circuit board and line them up with the markings on the programming key.
To copy the control panel's data into your new programming key, enter command to "Command 962 - Copy Control Panel Memory To Programming Key" on page 25 for further details.
Exit the Installer's Programming Mode by entering the command the activity LED to return to its normal state and then remove the programming key. This programming key will now become your standard data pattern for future programming of your control panels.
It should be noted that when entering the Installer's Programming Mode, inserting a programming key and then altering any location would cause a simultaneous update of not only the programming keys data, but also the control panel’s data. Therefore, you are not able to alter data in the programming key without the same location being altered in the control panel’s memory.
Note: Connecting a Programming Key (CC891) to the control panel when the programming keys memory is blank will
corrupt the control panel's memory unless the Installer's Programming Mode has been entered first. If this occurs, then the control panel will need to be returned to Electronics Design & Manufacturing Pty Limited where a service fee will be charged to unlock the control panel’s memory.
960 followed by the button, wait two seconds for
962 followed by the button. Refer
Electronics Design & Manufacturing Pty Limited ISSUE220.DOC
22 Solution-16/Solution-16 Safecom Installation Manual
Programming Via The DTMF Command Module
The DTMF Command Module (CC886) will allow you to operate and program your control panel remotely via the telephone line. Once a communications link has been established with the control panel, you will be able to perform any system functions using the codepad on a touch tone telephone for Master Code, User Code and Installer Code Functions as well as access into Installer's Programming Mode.
Below will give an example of making a connection to the control panel and changing the "Exit Time" for AWAY Mode to 26 seconds on a non-partitioned system. To connect to a system, which has been partitioned, refer to "Operating The Control Panel Using The DTMF Command Module" on page 67 for further information.
Example
How To Establish A Communication Link With The Control Panel
1. Dial the telephone number that the control panel has been connected to. When the control panel answers your call, you
will hear a short jingle.
2. After the jingle, press the 0 button on the telephone. You will now hear a second jingle and have established a
communication link with the control panel.
Programming The Control Panel Once A Communication Link Has Been Established
Once the connection has been established, enter your followed by the # button. Two beeps will be heard. If no
beeps are heard, enter a user code to disarm the system before entering the Installer's Code again.
After entering Installer's Programming Mode, follow the steps below to program the new "Exit Time " for AWAY Mode.
1. To go to "LOCATION 632", enter 632 followed by the # button.
2. Enter the value followed by the * button.
3. Press the # button to move to the next location.
4. Enter the value 1 followed by the * button.
5. Now enter command 960 followed by the # button to exit Installer's Programming Mode.
The exit time for AWAY Mode has now been programmed for 26 seconds.
To terminate the communication link with the control panel, press the
# button twice.
Programming Option Bits
When programming these locations you will notice that there are four alternatives per location. You may select one, two, three or all of these alternatives for each location, however, only one number is required to be programmed. This number is calculated by adding the option bit numbers together.
Example
If at "LOCATION 663" you want options 1, 2 and 4. Add the numbers together and the total is the number to be programmed. In this example, the number to be programmed is 7 (i.e. 1+2+4=7).
Option Description
1
2
4
8
Enable Dialler Reporting Functions Enable Remote Arming Via The Telephone Enable Upload/Download Terminate Alarm Link Session On Alarm
Table 3: Example - Programming Option Bits
ISSUE220.DOC Electronics Design & Manufacturing Pty Limited
Programming 23
Installers Programming Commands
There are several commands that can be invoked to perform various functions once the Installer's Programming Mode has been
entered. To invoke the command, enter the corresponding numerical code followed by the
Command Function
958
959
960
961
962
963
964
965
966
999
Enable and Disable Zone Status Mode Test Programming Key Exit Installer’s Programming Mode Reset Control Panel Back To Factory Default Settings Copy The Control Panel Memory To The Programming Key Copy The Programming Key Data To The Control Panel Erase Programming Key Set Up Domestic Dialling Format Enable and Disable Automatic Stepping Of Locations During Programming This Command Displays The Control Panel’s Software Version Number Only When
Using The Hand Held Programmer
Table 4: Installer's Programming Commands
Command 958 - Enable/Disable Zone Status Mode
This function enables and disables the zone status display mode. When using the hand held programmer, the zones will be displayed on the seven segment displays from left to right. If there is a dash illuminated on the display, the corresponding zone is unsealed and if the display is blank, the zone is sealed.
The third (or centre) display shows either the number 4 or the number 8. The number 4 constantly illuminated indicates that zones 1 - 4 are being displayed. The number 8 constantly illuminated indicates that zones 5 - 8 are being displayed. The number 4 flashing indicates zones 9 - 12 are being displayed. The number 8 flashing indicates that zones 13 - 16 are being displayed.
Pressing the it allows you to view the status of the zones directly at the control panel, saving you time and money.
How To Enable Zone Status Mode
1. Enter Installers Programming Mode.
2. Enter command 958 followed by the # button.
How To Disable Zone Status Mode
# button will toggle the display between the zones. This feature will prove to be very useful during installation as
Two beeps will be heard.
button
1. Enter command 958 followed by the # button.
Two beeps will be heard.
Example
A " - " in the display indicates the zone is triggered. A blank display indicates the zone is normal.
--4-- indicates that zones 1, 2, 3 and 4 are triggered.
A flashing "4" indicates zones 9, 10, 11 and 12 are being displayed.
-¤¤¤¤8¤¤¤¤- indicates that zones 5 and 8 are triggered.
A flashing "8" indicates zones 13 and 16 are being displayed.
Electronics Design & Manufacturing Pty Limited ISSUE220.DOC
24 Solution-16/Solution-16 Safecom Installation Manual
Command 959 - Test Programming Key
This command causes a test to be carried out on the programming key. This test is non destructive and any data in the programming key will remain intact after the test has been completed. One long beep indicates that the programming key has failed and three beeps indicate a successful test. If the programming key has been removed before the test has completed or the programming key has failed, the data in the programming key has become corrupt. Remember, do not remove the programming key while the activity LED is illuminated constantly or pulsing rapidly.
How To Test The Programming Key
1. Enter Installer's Programming Mode.
2. Plug the programming key onto the pins marked PROGRAMMING KEY on the control panel.
3. Enter command 959 followed by the # button.
Two beeps will be heard and the programming key has now been tested.
4. Enter command 960 followed by the # button to exit the Installer's Programming Mode before removing the
programming key.
How To Test The Programming Key Using The Hand Held Programmer
1. Before connecting the hand held programmer, make sure that the switch on the hand held programmer is in the EXT
position.
2. Enter the Installer's Programming Mode.
3. Plug the programming key onto the pins marked EXTERNAL KEY on the hand held programmer.
4. Enter command 959 followed by the # button.
Two beeps will be heard and the programming key connected to the hand held programmer has now been tested.
5. Enter command 960 followed by the # button to exit the Installer's Programming Mode.
6. Leave the switch on the hand held programmer in the EXT position and disconnect the external programming key.
Command 960 - Exit Installer's Programming Mode
This command is used to exit the Installer's Programming Mode after you complete your programming alterations. This is
achieved by entering command normal. This command can be performed at any programming stage and from any location.
960 followed by the # button. Two beeps will be heard and the system will return to
Command 961 - Reset Control Panel Back To Factory Default Settings
This command will reset the control panel back to the factory default values. Refer to the values shown throughout this manual
or the “Programming Sheets” on page 211. This is achieved by entering the command Three beeps will be heard.
961 followed by the # button.
ISSUE220.DOC Electronics Design & Manufacturing Pty Limited
Programming 25
Command 962 - Copy Control Panel Memory To Programming Key
This command is used to copy the control panel memory to the programming key.
How To Copy The Control Panel Memory To The Programming Key
1. Enter Installer's Programming Mode.
2. Plug the programming key onto the pins marked PROGRAMMING KEY on the control panel.
3. Enter command 962 followed by the # button.
Two beeps will be heard and the control panel’s memory has now been copied into the programming key.
4. Enter command 960 followed by the # button to exit the Installer's Programming Mode.
5. Disconnect the programming key from the control panel.
How To Copy The Control Panel Memory To The Programming Key Using The Hand Held Programmer
1. Before connecting the hand held programmer to the control panel, make sure that the switch on the hand held programmer
is in the EXT position.
2. Enter the Installer's Programming Mode.
3. Plug the programming key onto the pins marked EXTERNAL KEY on the hand held programmer.
4. Enter command 962 followed by the # button.
Two beeps will be heard and the control panel's memory has now been copied into the programming key.
5. Enter command 960 followed by the # button to exit the Installer's Programming Mode.
6. Leave the switch on the hand held programmer in the EXT position and disconnect the programming key.
Command 963 - Copy From Programming Key To Control Panel
This command is used to copy data from the programming key to the control panel.
How To Copy The Programming Key Memory To The Control Panel
1. Enter Installer's Programming Mode.
2. Connect the programming key onto the pins marked PROGRAMMING KEY on the control panel.
3. Enter command 963 followed by the # button.
Two beeps will be heard and the programming key's data has now been copied to the control panel.
4. Enter command 960 followed by the # button to exit Installer's Programming Mode.
5. Now disconnect the programming key from the control panel.
How To Copy The Programming Key Memory To The Control Panel Using The Hand Held Programmer
1. Before connecting the hand held programmer to the control panel, make sure that the switch on the hand held programmer
is in the EXT position.
2. Enter the Installer's Programming Mode.
3. Plug the programming key onto the pins marked EXTERNAL KEY on the hand held programmer.
4. Enter command 963 followed by the # button.
Two beeps will be heard and the programming keys data will now be copied to the control panel.
5. Enter command 960 followed by the # button to exit the Installer's Programming Mode.
6. Leave the switch on the hand held programmer in the EXT position and disconnect the programming key.
Electronics Design & Manufacturing Pty Limited ISSUE220.DOC
26 Solution-16/Solution-16 Safecom Installation Manual
Command 964 - Erase Programming Key
This command erases all data from the programming key.
How To Erase The Programming Key
1. Enter the Installer's Programming Mode.
2. Connect the programming key onto the pins marked PROGRAMMING KEY on the control panel.
3. Enter command 964 followed by the # button.
4. Two beeps will be heard and the programming keys data has now been deleted.
5. Enter command 960 followed by the # button to exit the Installer's Programming Mode.
6. Now remove the programming key from the control panel.
How To Erase The Programming Key Using The Hand Held Programmer
1. Before connecting the hand held programmer to the control panel, make sure that the switch on the hand held programmer
is in the EXT position.
2. Enter the Installer's Programming Mode.
3. Plug the programming key onto the pins marked EXTERNAL KEY on the hand held programmer.
4. Enter command 964 followed by the # button.
Two beeps will be heard and the programming keys data has now been deleted.
5. Enter command 960 followed by the # button to exit Installer's Programming Mode.
6. Now disconnect the programming key from the hand held programmer.
ISSUE220.DOC Electronics Design & Manufacturing Pty Limited
Programming 27
Command 965 - Set Up Domestic Dialling Format
Command 965 has been added to make the set up of the Domestic Dialling Format a one step operation. Refer to page 78 for more information on "Domestic Reporting".
After Installer's Programming Mode has been accessed, enter command automatically set the following locations in bold below. No other locations will be altered when command 965 has been issued.
Location Description Setting
Location 49
Location 50
Location 52 - 55
Location 340 - 347
Location 348 - 355
Location 356 - 363
Location 364 - 371
Location 372 - 379
Location 380 - 387
Location 388 - 395
Location 396 - 403
Location 404 - 411
Location 412 - 419
Location 420 - 427
Location 428 - 435
Location 436 - 443
Location 444 - 451
Location 452 - 459
Location 460 - 467
Location 468 - 471
Location 472 - 475
Location 476 - 479
Location 480 - 483
Location 484 - 487
Location 488 - 491
Location 492 - 495
Location 496 - 499
Location 500 - 503
Location 504 - 505
Location 506 - 513
As you can see from the table above, all reporting other than zone alarms have been disabled. The handshake tone has been set for 1400 Hz tone acknowledgment and the Subscriber ID Number has been set for one identification beep. The zone reporting has been set so that any zone that triggers into alarm condition will only report when the alarm occurs, the zone restore report will not report as there is no separate indications for zone alarm reports and zone alarm restore reports.
Note: From Software Version 1.30, Command 965 disables zone restore reports.
Handshake Tone Transmission Format Subscriber ID Number Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 Bypass Reports Trouble Reports Codepad Duress Codepad Panic Codepad Tamper AC Fail Low Battery Program Altered Sensor Watch Open/Close Reports Test Report Time
Table 5: Command 965 Defaults
965 followed by the # button. This will
2 (1400 Hz) 11 (Domestic Dialling) 0, 0, 0, 1 2, 0, 0, 0, 0, 3, 0, 1 (Delay-1) 1, 0, 0, 0, 0, 3, 0, 1 (Handover) 1, 0, 0, 0, 0, 3, 0, 1 (Handover) 1, 0, 0, 0, 0, 3, 0, 1 (Handover) 1, 0, 0, 0, 0, 3, 0, 1 (Handover) 0, 0, 0, 0, 0, 3, 0, 1 (Instant) 0, 0, 0, 0, 0, 3, 0, 1 (Instant) 12, 0, 0, 0, 0, 3, 3, 1 (24 Hour Burglary) 0, 0, 0, 0, 0, 3, 0, 1 (Instant) 0, 0, 0, 0, 0, 3, 0, 1 (Instant) 0, 0, 0, 0, 0, 3, 0, 1 (Instant) 0, 0, 0, 0, 0, 3, 0, 1 (Instant) 0, 0, 0, 0, 0, 3, 0, 1 (Instant) 0, 0, 0, 0, 0, 3, 0, 1 (Instant) 0, 0, 0, 0, 0, 3, 0, 1 (Instant) 0, 0, 0, 0, 0, 3, 0, 1 (Instant) 0, 0, 0, 0 (Not Used)
0, 0, 0, 0 (Not Used) 0, 0, 0, 0 (Not Used) 0, 0, 0, 0 (Not Used) 0, 0, 0, 0 (Not Used) 0, 0, 0, 0 (Not Used) 0, 0, 0, 0 (Not Used) 0, 0, 0, 0 (Not Used) 0, 0, 0, 0 (Not Used) 0, 0 (Not Used)
0, 0, 0, 0, 0, 0, 9, 0 (Not Used)
Electronics Design & Manufacturing Pty Limited ISSUE220.DOC
28 Solution-16/Solution-16 Safecom Installation Manual
Command 966 - Enable/Disable Automatic Stepping Of Locations
This command enables or disables the automatic stepping of locations while programming. When enabled via the hand held programmer, the decimal point of the left most display will reflect the mode of operation.
If the decimal point is illuminated then auto step mode is active. An automatic increment of the location being programmed will
occur as soon as the
If the decimal point is extinguished, the auto step mode is disabled. The next programming location will need to be manually
selected by pressing the programming successive locations.
How To Enable Automatic Stepping Of Locations
1. Enter command 966 followed by the # button.
Two beeps will be heard.
How To Disable Automatic Stepping Of Locations
1. Enter command 966 followed by the # button.
Two beeps will be heard.
Example
(Auto Step Enabled) To enter the Primary Telephone Number "02 pause 9 672 1055" with auto step enabled (i.e. Decimal point illuminated).
Press
0 followed by the # button.
(This will position you at "LOCATION 000" being the start of the Primary Telephone Number).
* button is pressed positioning you at the next location ready for programming.
# button. As you can see from the examples below, auto step mode is a very useful feature when
+ * + 2 + * + + * + 9 + * + 6 + * + 7 + * + 2 +
* + 1 + * +
+ * + 5 + * + 5 + * + 0 + *
Example
(Auto Step Disabled) To enter the Primary Telephone Number "02 pause 9 672 1055" with auto step disabled (i.e. Decimal point extinguished).
Press
0 followed by the # button.
(This will position you at "LOCATION 000" being the start of the Primary Telephone Number).
+ * + # + 2 + * + # + + * + # + 9 + * + # + 6 +
* + # + 7 + * + # + 2 + * + # + 1 + * + # +
+ * +
# + 5 + * + # + 5 + * + # + 0 + *
Command 999 - Display Software Version Number
This command will display the control panel's software version number. This command can only be used with the hand held programmer.
Enter command
heard. Press the
999 followed by the # button to display the control panel's software version number. Two beeps will be
# button to exit this command.
ISSUE220.DOC Electronics Design & Manufacturing Pty Limited
Programming 29
Disable Factory Default
LOCATION 900 0
The system has a feature that prevents the control panel from being manually defaulted via the default button or by using a programming key.
Any number between 0-14 programmed into this location will allow defaulting of the control panel. If 15 has been programmed into this location, defaulting of the control panel will not operate and the Installer Code MUST be used for further programming of the control panel.
If the Installer Code is not known, the control panel will need to be returned to your EDM Distributor for exchange. A nominal fee applies for this service.
Warning: Electronics Design and Manufacturing Pty Limited does not recommend the use of this feature.
If this option is required, a special programming procedure has been introduced to eliminate any possibility of accidentally setting this option. The default button on the PCB must be held down while programming this location.
How To Prevent Manual Defaulting Of The Control Panel
1. Plug the hand held programmer to the pins provided on the PCB.
2. Disarm the system.
3. Access Installer's Programming Mode.
4. Go to "LOCATION 900".
5. Hold down the default button.
6. Program a 15 into "LOCATION 900".
7. Release the default button.
8. Exit Installer's Programming Mode.
Defaulting The Control Panel
If the Solution-16 control panel does not have "LOCATION 900" programmed as 15, follow the procedure outlined below to successfully default the control panel back to the factory default settings.
How To Default The Control Panel
1. Disconnect the AC mains and backup battery from the control panel.
2. Hold down and continue to hold down the DEFAULT button located at the top of the printed circuit board.
3. Reconnect the AC mains to the control panel.
4. After reconnecting the AC mains, wait for 3-5 seconds before releasing the DEFAULT button.
You will hear the dialler seize relay (RL2) on the control panel click once and two beeps will be heard on the remote codepad. The control panel will now need to be disarmed by using the default Master Code 2580.
The control panel has now been successfully defaulted back to the factory default settings.
Note: If following the above procedure to default the control panel and you hear the dialler seize relay (RL2) click four
times, defaulting the control panel has been disabled. The control panel will need to be returned to Electronics Design and Manufacturing Pty Limited for exchange where a service fee will be charged to unlock the control panel's memory.
Electronics Design & Manufacturing Pty Limited ISSUE220.DOC
30 Solution-16/Solution-16 Safecom Installation Manual
ISSUE220.DOC Electronics Design & Manufacturing Pty Limited
Loading...
+ 200 hidden pages