1 PREFACE.......................................................................................................3
2 CMU 200 SYSTEM.........................................................................................6
2.1 DESCRIPTION..................................................................................................................... 6
2.1.1 SOFTWARE...................................................................................................................... 6
2.1.2 HARDWARE...................................................................................................................... 6
3 DESCRIPTION...............................................................................................7
3.1 DESCRIPTION..................................................................................................................... 7
3.2 APPERANCE........................................................................................................................ 7
3.3 HARDWARE DESCRIPTION............................................................................................... 8
3.3.1 PORTS CONFIGURATION............................................................................................... 8
3.3.2 RS485 INTERFACE BOARD............................................................................................. 8
3.3.3 MULTIMODE FIBER OPTIC INTERFACE BOARD......................................................... 11
4 SCHEMATIC.................................................................................................13
5 INSTALLATION............................................................................................14
5.1 INSTALLATION.................................................................................................................. 14
6 COMMISSIONING & MAINTENACE..........................................................15
6.1 COMMISSIONING.............................................................................................................. 15
6.2 MAINTENANCE................................................................................................................. 15
7 TECHNICAL DATA......................................................................................16
8 DIMENSIONS...............................................................................................18
9 ORDERING...................................................................................................19
Page: Company: Device: Document: Code: Version: Date:
2 Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015
PREFACE

1 PREFACE

Liability statement
We have checked the contents of this manual to ensure that the descriptions of both hardware and software are as accurate as possible. However, deviations may occur so that no liability can be accepted for any errors or omissions contained in the information given.
The contents of this manual will be checked in periodical intervals, corrections will be made in the following editions.
We reserve the right to make technical improvements without notice.
Contact
If you have any questions or comments related to this product please contact us on:
Ediseja 21 d.o.o. Drenov Gric 175 1360 Vrhnika Slovenia – EU
Tel: 00 386 51 643 411, 051 643 411
Email: grega.flander@ediseja21.com
www.ediseja21.com
Copyright
Copyright © Ediseja 21, 2013. All rights reserved.
Explanation of the symbols
Read the instructions!
Device was tested with 2,5 kV AC voltage to check the device insulation.
Device ground terminal.
Waste Electrical and Electronic Equipment (WEEE) Directive 2002/96/EC; the affixed product label indicates that you must not discard this electrical/electronic product in domestic household waste.
Company: Device: Document: Code: Version: Date: Page:
Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015 3
Warnings
In this paper the following terms are used:
Danger
indicates that death, severe personal injury or substantial property damage will result if proper precautions are not taken.
Warning
indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken.
Caution
indicates that minor personal injury or property damage can result if proper precautions are not taken. This particularly applies to damage on or in the device itself.
General information
These paper contain the information that is necessary for the proper and safe operation of the described devices. This paper is intended for technically qualified personnel.
Warning!
Hazardous voltage is present inside the device during operation. Disregarding of safety rules can result in severe personal injury or property damage.
Only qualified personnel may work with described devices after being familiar with warnings and safety notices in this paper and other safety regulations.
Warning!
Device must operate completely assembled! Device must be used as described. No modifications of the device should be made.
Warning!
Do not open device while it is energized! Hazardous voltage is present inside the device. Disconnect all connectors before opening!
Page: Company: Device: Document: Code: Version: Date:
4 Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015
PREFACE
Warning!
If device is damaged disconnect it from power supply! Send it to the manufacturer for inspection.
Warning!
Connect to earth before attaching power supply!
Company: Device: Document: Code: Version: Date: Page:
Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015 5

2 CMU 200 SYSTEM

2.1 DESCRIPTION

Communication unit (CMU 200) is modular system of communication devices that can be used for various of tasks such as:
communication converter (for example 20 channels RS232 to Fiber Optic converter)
star coupler (for example RS232 to 39 fiber optic)
CMU 200 device is a couple of software and hardware. For different purposes, different software versions and different hardware configuration have been developed.

2.1.1 SOFTWARE

Software is application dependent and allows different hardware configurations. Software's task is switching between communication ports and allows almost any combination between them.

2.1.2 HARDWARE

CMU 200 can handle up to 40 different interface boards. Currently available interface boards:
(non)isolated RS232
isolated RS485
Multimode Fiber Optic ST or SMA connectors
USB
ethernet (with one virtual com port)
power supply
There is possibility to use additional redundancy power supply.
Housing is made from inox and is intended for mount on standard 19"rack.
Page: Company: Device: Document: Code: Version: Date:
6 Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015
DESCRIPTION

3 DESCRIPTION

3.1 DESCRIPTION

Star coupler is communication device that transfer data from one (master) to more than one (slave) port.
This device contains 1 RS485 and 39 multimode fiber optic ports. Data is send from master port to all slave ports. On the other hand, data from either slave port is send to master port only.
Power supply voltage allows connection to all common station batteries. Additionaly it can be also connected to standard AC voltages.
This device is intended for use in cubicles and cabinets in all kinds of power production, transmission and distribution stations. It requires no maintenace. All normaly used connectors, switches and light indicators are accessed at the back side of the device. Two light indicators indicates power supply voltage, others indicate communication transfer.

3.2 APPERANCE

Company: Device: Document: Code: Version: Date: Page:
Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015 7
Picture 1: Front view

3.3 HARDWARE DESCRIPTION

3.3.1 PORTS CONFIGURATION

Port 1 2 3 4 5 6 7 8 9 10
Inter.
RS485 FO MM FO MM FO MM FO MM FO MM FO MM FO MM FO MM FO MM
Port 11 12 13 14 15 16 17 18 19 20
Inter.
FO MM FO MM FO MM FO MM FO MM FO MM FO MM FO MM FO MM FO MM
Port 21 22 23 24 25 26 27 28 29 30
Inter.
FO MM FO MM FO MM FO MM FO MM FO MM FO MM FO MM FO MM FO MM
Port 31 32 33 34 35 36 37 38 39 40
Inter.
FO MM FO MM FO MM FO MM FO MM FO MM FO MM FO MM FO MM FO MM

3.3.2 RS485 INTERFACE BOARD

Description
Single, galvanically isolated, half duplex, RS485 port with Phoenix 3 pin screw connector, with automatic switch to receive after end of transmission and with additional terminating and stabilizating resistors.
Hardware settings
For proper functioning of that board some settings must be done:
RS485 bus termination and stabilisation
baud rate
Page: Company: Device: Document: Code: Version: Date:
8 Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015
Picture 2: Back view
HARDWARE DESCRIPTION
RS485 bus termination and stabilisation
TERMINATION
At high transmission rates or long distance, RS485 bus termination is necessary.
The termination on RS485 bus must be set on both ends of the RS485 bus.
STABILISATION
Some device, to work properly, demands that RS485 must always be in known and valid state. That is, when + (positive) pin is more than 200 mV positive than – (negative) pin. Pins + and – are sometimes marked as A and B. In case that no device on RS485 bus is transmitting or in case of short circuit, there is no voltage difference between those pins and some device do not work correctly.
On this port board so called „true fail-safe“ RS485 chip is used so board works correctly without stabilisation at invalid RS485 bus state. But still switches for stabilisation are provided on port board.
The stabilization on RS485 bus may be set on one device only!
Switches at the lower side of connector:
Switch 4 5 6
Description
RS485 stabilisation RS485 termination RS485 stabilisation
Switches at the upper side of connector:
BAUD rate
BAUD rate Switch
Interface 5 Interface M Interface L 1 2 3
Company: Device: Document: Code: Version: Date: Page:
Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015 9
Picture 3: RS485 BUS schematic
BAUD rate Switch
19200 4800 300
OFF OFF OFF
38400 9600 600
OFF OFF ON
57600 19200 1200
OFF ON OFF
115200 38400 2400
ON OFF OFF
BAUD rate setting 19k2 (bps) is valid for all standard communication protocols, that do not request special timings. If special protocols (small request-respond time required) are used please note it in order.
NOTE! If there are problems with communication, try using higher speed setting. Some manufacturer have different markings for B and A line. Try to switch A and B wires. See
http://en.wikipedia.org/wiki/RS-485 for detailed information.
Connector pin table
MSTB 1 2 3
Description
GND - (A) + (B)
Page: Company: Device: Document: Code: Version: Date:
10 Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015
Picture 4: RS485 interface board appearance with switch settings
HARDWARE DESCRIPTION

3.3.3 MULTIMODE FIBER OPTIC INTERFACE BOARD

Description
Single, full duplex, multimode, fiber optic port with ST connectors with positive or negative logic.
Hardware settings
For proper functioning of that board, optic logic must be set:
Fiber optic logic settings
Switch SW1 Light in idle state 1 2 3 4
Positive logic OFF
OFF ON OFF ON
Negative logic ON
ON OFF ON OFF
Company: Device: Document: Code: Version: Date: Page:
Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015 11
Picture 5: Data rate vs cable lenght
Page: Company: Device: Document: Code: Version: Date:
12 Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015
Picture 6: Multimode fiber optic interface board appearance
SCHEMATIC

4 SCHEMATIC

Company: Device: Document: Code: Version: Date: Page:
Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015 13
Picture 7: Schematic

5 INSTALLATION

5.1 INSTALLATION

Warning!
Hazardous voltage is present inside the device during operation. Disregarding of safety
rules can result in severe personal injury or property damage.
Only qualified personnel may work with described devices after being familiar with warnings and safety notices in this paper and other safety regulations.
Following instruction must be taken into consideration:
The device must be accessible to qualified personnel only.
The device is permitted to operate in enclosed housing or cabinet only.
The device location must be vibration-free.
The admisible operating temperature must be observed.
Check the device for damage at unpacking. If device is damaged it must not be installed but It should be send to the manufacturer for repair.
The device should not be opened.
The device should be mounted on 19" rack via 4x M6x10 mm screws
Attach ground wire before attaching power supply. Device must be grounded during operation!
Single core or stranded wire 0,5 – 2,5 mm2 must be used for power supply connection. If stranded wire is used ferrules must be used to prevent fraying. Recommended stripping lenght is 5 mm.
Protective earthing wire must be terminated with tinned copper ear terminal.
The prescribed bending radius of the optical fibre cables must be observed.
Page: Company: Device: Document: Code: Version: Date:
14 Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015
COMMISSIONING & MAINTENACE

6 COMMISSIONING & MAINTENACE

6.1 COMMISSIONING

Warning!
Hazardous voltage is present inside the device during operation. Disregarding of safety rules can result in severe personal injury or property damage.
Only qualified personnel may work with described device after being familiar with warnings and safety notices in this paper and other safety regulations.
Following instruction must be taken into consideration:
Device must operate completely assembled! Device must be used as described. No modifications of the device should be made.
Attach ground wire before attaching power supply. Device must be grounded during operation!
Check if the power supply voltage complies with device operation voltage.
Do not open device while it is energized! Hazardous voltage is present inside the device.
If single mode fiber optic interface is used, do not look into the laser beam.

6.2 MAINTENANCE

The device is maintenance-free. Disconnect power supply before cleaning it. Use moist cloth. Do not use liquids.
Company: Device: Document: Code: Version: Date: Page:
Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015 15

7 TECHNICAL DATA

Power supply
Rated voltage
HAC
230 V AC, +10 %, -10 %
220 V DC, +10 %, -10 %
MDC
110 V DC, +10 %, -10 %
Rated current
HAC
0,3 A
MDC
0,5 A
Fuse (internal)
6,3 A T
Power supply indicator
green LEDs marked Power 1 and Power 2
oltage dips
20 ms
Connector type
screw type „MSTB“ Phoenix 8pin
Wire crossection
0,5 – 2,5 mm
2
Communication port RS485 (interface type 48x)
Type
RS485
Direction
half duplex
Speed
Interface type 5 19200 - 115200 BAUD
Interface type M 4800 - 38400 BAUD
Interface type L 300 - 2400 BAUD
Number of ports
1
Distance
up to 1200 m
Isolation
1000 V DC
Connector type
„MSTB“ Phoenix 3pin
Termination
120 Ohm
Max number of devices
on BUS
32
Communication port Multimode Fiber Optic (interface type FOx)
Type
multimode fiber optic
Wave lenght
820 nm
Fiber size
50/125 μm, 62,5/125 μm, 100/140 μm, 200 μm
Optical output power
-18 dB
Reciver sensitivity
-24 dB
Laser class
I (IEC 60825-1)
Page: Company: Device: Document: Code: Version: Date:
16 Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015
TECHNICAL DATA
Communication port Multimode Fiber Optic (interface type FOx)
Direction
full duplex
Speed
up to 230 k BAUD
Input
1 receiver (grey connector)
Output
1 transmitter (white connector)
Logic
light ON or OFF in idle state set by switch
(see table)
Number of ports
1
Distance
up to 500 m
Connector type
ST
* slowest interface defines device's maximum speed
Device
Weight
6 kg
Dimensions
(see picture)
(W) (H) (D)
19" rack 3U (133 mm) 154 mm + connectors
Temperature range
0 °C to +55 °C
Humidity operating
up to 95 % (noncondensing)
Enclosure
Material inox
IP 20
Mount type
4x M6 screw 19" rack
Class
I
Overvoltage category
II
Communication indicator
Receiveing yellow LED marked Rx
Tranmitting green LED marked Tx
Company: Device: Document: Code: Version: Date: Page:
Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015 17

8 DIMENSIONS

Page: Company: Device: Document: Code: Version: Date:
18 Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015
Picture 8: Dimensions
ORDERING

9 ORDERING

ORDERING NUMBER: CMU 200 / c . c . c . c . c . c . c - c . c
(enclosure width: 19“, height: 3U, depth: 154 mm)
Power supply :
single 230 V AC, 220 V DC power supply .................................................................. HACx1
double 230 V AC, 220 V DC power supply ................................................................. HACx2
single 110 V DC power supply ................................................................................... MDCx1
double 110 V DC power supply .................................................................................. MDCx2
Interfaces:
RS232 nonisolated, Rx & Tx support ............................................................................. 232 x n
RS232 isolated, Rx & Tx support .................................................................................... 23I x n
RS232 nonisolated, Rx, Tx, CTS & RTS support .......................................................... 23R x n
RS232 isolated, Rx, Tx, CTS & RTS support ................................................................. 2RI x n
RS485 isolated, half duplex (19200-115200 baud) ........................................................ 485 x n
RS485 isolated, half duplex (38400 - 4800 baud) ..........................................................48M x n
RS485 isolated, half duplex (300-2400 baud) ................................................................ 48L x n
FO multimode ST .......................................................................................................... FOT x n
FO multimode SMA ....................................................................................................... FOA x n
Ethernet (one virtual com port) ...................................................................................... ETH x n
n ... number of interfaces - maximum number of interfaces in CMU 200 is 40! Each 23R and 2RI interface must be treated as two interfaces!
Function:
three ports star coupler (up to 13 groups) .................................................................................... 2
1 on 1 converter (up to 20 groups) …............................................................................................ 7
40 port star coupler (1 master, up to 39 slaves) .......................................................................... 12
39 port star coupler (2 masters to 4 slaves (3 groups), 2 masters to 5 slaves (3 groups) .......... 15
40 port star coupler (1 master to 9 slaves, up to 4 groups) ......................................................... 18
For other functions please contact us.
Software Version:
software version ................................................................................................................. leave empty
Example: CMU 200 / HACx2 . 232x3 . FOTx27 - 18 is 1x RS232 to 9x fiber optic, 3 groups star coupler with
- two 230 V AC power supply
- 3 RS232 interfaces
- 27 fiber optic interfaces with ST connector
Additional accessories (order if needed):
- power supply cable with „schuko“ plug, 2 m
- RS232 cable to PC (state the lenght up 15 m)
- fiber optic cables (state the lenght)
Company: Device: Document: Code: Version: Date: Page:
Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015 19
Contact:
Ediseja 21, razvoj elektronskih naprav, d.o.o.
Drenov Gric 175 1360 Vrhnika Slovenia – EU
Tel: 00 386 51 643 411, 051 643 411 grega.flander@ediseja21.com
www.ediseja21.com
Page: Company: Device: Document: Code: Version: Date:
20 Ediseja 21 CMU200/XXXx2.485x1.FOTx39 User manual CMUMU203 V1 28.05.2015
Loading...