ECR International 75, 100, 075 97gb, 100 97gb Installation, Operation & Maintenance Manual

CONDENSING
GAS BOILER
INSTALLATION,
OPERATION &
MAINTENANCE
MANUAL
H
P/N # 240008282, REV D [10/2010]
DIMENSIONS
FIGURE 1-1 Dimensions
(D)
Wall Hanging
Bracket
(D)
(B)
Vent Connection
Supply Water
Gas
Connection
(G)
(F)
Floor
(E)
Combustion Air
Return Water
(E)
User Interface
(A)
(B)
Size
075
/100
Width
(A)
22-1/16"
(560mm)
(H)
(I)
Condensate
Drain
Height
(B)
35-5/8"
(905mm)
Alternate Gas
Supply Water
Depth
(C)
16-3/16"
(411mm)
Connection
(F)
Alternate
(E)
Table 1 : Physical Data
Bracket
(D)
27-1/2"
(969mm)
Water Connections
Size
(E)
1-1/4"
NPT
Height
(F)
31-1/16"
(789mm)
(C)
Alternate
Return Water
(E)
Gas
Connection
(G)
1/2" NPT 7-1/2" 5"
Condensate Drain
(H) (I)
Weight
Shipping Unit
140 lb
(63.5 kg)
115 lb
(51.2 kg)
2
TABLE OF CONTENTS
1 - Introduction ............................................................................................................................... 4
2 - Important Safety Information .................................................................................................... 5
3 - Component Listing .....................................................................................................................6
4 - Locating Boiler .........................................................................................................................10
5 - Hydronic Piping ........................................................................................................................12
5.2 Special Conditions ................................................................................................................... 12
5.3 Safety Relief Valve and Air Vent .................................................................................................12
5.4 Trim Piping ............................................................................................................................. 13
5.5 System Piping ......................................................................................................................... 13
6 - Combustion Air And Vent Piping .............................................................................................. 18
6.2 Removal of Existing Boiler..........................................................................................................18
6.3 Materials ............................................................................................................................... 18
6.4 Pipe Installation ...................................................................................................................... 19
6.5 Termination ............................................................................................................................ 19
6.6 Condensate Piping ...................................................................................................................25
7 - Gas Supply Piping ....................................................................................................................26
8 - Electrical Connections .............................................................................................................. 28
8.2 Line Voltage Connections .......................................................................................................... 28
8.3 Low Voltage Connections .......................................................................................................... 28
9 - Start Up Procedure ...................................................................................................................30
10 - Operating Instructions ...........................................................................................................34
11 - General Maintenance And Cleaning ........................................................................................ 35
12 - Ratings And Capacities ...........................................................................................................38
13 - Trouble Shooting ....................................................................................................................39
14 - Wiring Diagram ......................................................................................................................56
15 - Glossary .................................................................................................................................58
Appendix A - Control Module ......................................................................................................... 60
1.1 Introduction ........................................................................................................................... 60
1.2 Operation ............................................................................................................................... 60
1.3 Status Indication ..................................................................................................................... 60
1.4 Sequence of Operation ............................................................................................................. 61
1.5 Theory of Operation ................................................................................................................. 63
3
1 - INTRODUCTION
1.1 Designated Use
Hot water heating boiler.• Indoor installation.• Closet or alcove installation.• Direct vent boiler.• For use with natural gas or liquefi ed petroleum gases
(LP/propane).
1.2 The unit MUST NOT:
• Directly heat potable water. Indirect heating is acceptable.
• Heat water with non-hydronic heating system chemicals present (example, swimming pool water).
Exceed 50 psig (344 kPa) system pressure.• Exceed 195°F (90.5°C) system design temperature.
1.3 Operational Features
Modulating: 20-100%.• Integral Dual Limit.• Integral Low Water Cutoff (with test button).• Outdoor Temperature Reset.
Integral Multiple Boiler Control.
4
!
This is the safety alert symbol. Symbol alerts you to potential personal injury hazards. Obey all safety messages following this symbol to avoid possible injury or death.
2.2
Become familiar with symbols identifying
potential hazards.
2 - IMPORTANT SAFETY INFORMATION
2.1 General
Boiler installation shall be completed by qualifi ed agency. See glossary for additional information.
WARNING
!
Fire, explosion, asphyxiation and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
2.2
Become familiar with symbols identifying
potential hazards.
This is the safety alert symbol. Symbol alerts you to potential personal injury hazards. Obey all safety messages following this symbol to avoid possible injury or death.
!
DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or serious injury
!
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
2.3 Installation shall conform to requirements of authority having jurisdiction or in absence of such requirements:
United States
• National Fuel Gas Code, ANSI Z223.1/NFPA 54
National Electrical Code, NFPA 70.
Canada
Natural Gas and Propane Installation Code, • CAN/CSA B149.1.
Canadian Electrical Code, Part I, Safety Standard • for Electrical Installations, CSA C22.1
2.4 Where required by authority having
jurisdiction, installation shall conform to Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
Additional manual reset low water cutoff may be required.
2.5 Requirements for Commonwealth of Massachusetts:
Boiler installation must conform to Commonwealth of Massachusetts code 248 CMR which includes but is not
limited to:
Installation by licensed plumber or gas fi tter.
.
!
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal injury.
5
Return Water From Heating System (In) 1-1/4" NPT
(see pages 7 & 8)
-
Connections supplied to con-
nection top and/or bottom of boiler.
Low Voltage Terminal Strip
(see pages 7 & 8)
- Connection of all low voltage wiring, including thermostat. See section
8.
Heat Exchanger Pump
Gas Shutoff Valve
- Fuel supply isolation
during servicing. See section 7
Combustion Air Blower
- Delivers proper quantity of combustion air, receives fuel from gas valve, mixes air and fuel sending mixture to burner for combustion.
Gas (Control) Valve
- Delivers proper quantity of fuel to Combustion Air Blower. See section 7.
High Temperature Supply Switch
Low Water Cutoff
Senses inadequate quantity of water. Turns off boiler before damage can occur (with test button).
8
Gas Connection
- Gas supply may be piped either through top or bottom of boiler. See section 7.
Control Module
3 - COMPONENT LISTING
3.1 Component Listing
User Interface
1.
regarding boiler condition. Allows adjustment of boiler operating parameters. NOTE: Does not replace thermostat used to control central heating space.
2.
Combustion Air Inlet (2" PVC)
Return Water From Heating System (In) 1-1/4"
3.
NPT
(see pages 7 & 8)
nection top and/or bottom of boiler.
Low Voltage Terminal Strip
4.
- Connection of all low voltage wiring, including thermostat. See section
Igniter
5.
Flame Sensor
6.
Sight Glass
7.
burner fl ame.
Burner
8.
(see page 8)
(see page 8)
(see Page 8) - Displays information
(see page 7 & 8)
-
Connections supplied to con-
(see pages 7 & 8)
8.
(see page 8)
(see page 8) - Permits observation of
Gas (Control) Valve
20.
proper quantity of fuel to Combustion Air Blower. See section 7.
High Temperature Supply Switch
21.
Low Water Cutoff
22.
quantity of water. Turns off boiler before damage can occur (with test button).
Safety Relief Valve
23.
Field installed. See section 5.
High Voltage Junction Box
24.
connection of 120V components. See section
Vent Connector (2" PVC)
25.
section 6.
Gas Connection
26.
piped either through top or bottom of boiler. See section 7.
Bracket for Optional Wall Mount
27.
Integral to boiler. Allows optional wall mounting when used with supplied wall mounting bracket. See section 4.
(see page 8)
(see page 8) --
(see page 8) - Factory supplied,
(see page 8) - For
(see pages 7 & 8) - See
(see page 7)
- Delivers
(see page 8)
Senses inadequate
8.
- Gas supply may be
(see page 7) -
Combustion Chamber
9.
Condensate Collector
10.
Return Temperature Sensor
11.
Drain Valve
12.
Heat Exchanger Ball Valve
13.
14.
Supply Water Outlet to Heating System (Out) 1-1/4"NPT (see pages 7 & 8) - Connections supplied
for connecting from either top or bottom of boiler. See section 5.
Vent Temperature Sensor
15.
Condensate Drain
16.
a liquid (condensate) as a by-product of combustion. Condensate must be piped to appropriate drain. See section 6.
Heat Exchanger Pump
17.
(see page 8)
(see page 8)
(see page 8)
(see page 8)
(see page 8)
(see page 8)
(see page 8) - Boiler produces
(see page 8)
Auxiliary Power Outlet
28.
outlet for condensate pump or service. Controlled by Service Switch (29)
Service Switch
29.
Air Vent
30.
Central Heating Pump Circuit Breaker
31.
5 amp circuit breaker protects control module.
Control Module
32.
Internal Access Panel
33.
upward then forward to access control module. Removable for access to internal components of boiler.
Central Heating Pump Relay
34.
Transformer
35.
water cutoff.
Pressure Switch
36.
(see page 7)
(see page 7)
(see page 9)
(see page 9) - Supplies 24V power to low
(not shown)
(see page 7) - Convenience
(see page 7)
(see page 9) - Gently pull
(see page 9)
Gas Shutoff Valve
18.
during servicing. See section 7
Combustion Air Blower
19.
proper quantity of combustion air, receives fuel from gas valve, mixes air and fuel sending mixture to burner for combustion.
(see page 8)
(see page 8)
- Fuel supply isolation
- Delivers
Test Port
37.
Combustion Analysis Test Port
38.
- (see page 8)
6
- (see page 8)
FIGURE 3-1 Boiler Components
LOW VOLTAGE
TERMINAL
STRIP
SAFETY
RELIEF
VALVE
AIR VENT
RETURN WATER
FROM HEATING
SYSTEM (IN)
HIGH VOLTAGE JUNCTION BOX
SUPPLY WATER TO
HEATING SYSTEM
(OUT)
GAS CONNECTION
SERVICE SWITCH
AUXILIARY POWER
OUTLET
CENTRAL HEATING
PUMP CIRCUIT BREAKER
BRACKET FOR
OPTIONAL WALL
MOUNT
LOW VOLTAGE
TERMINAL
STRIP
COMBUSTION
AIR INLET- 2" PVC
3 - COMPONENT LISTING
VENT
CONNECTOR - 2" PVC
HIGH VOLTAGE JUNCTION BOX
SAFETY
RELIEF
VALVE
AIR VENT
RETURN WATER
FROM HEATING
SYSTEM (IN)
BRACKET FOR
OPTIONAL WALL
MOUNT
SUPPLY WATER TO
HEATING SYSTEM
(OUT)
GAS CONNECTION
SERVICE SWITCH
AUXILIARY POWER
OUTLET
CENTRAL HEATING
PUMP CIRCUIT BREAKER
NOTE:
See Section 5-3
For Safety Relief
Valve Piping Instructions
7
3 - COMPONENT LISTING
LOW
VOLTAGE
TERMINAL
STRIP
HIGH VOLTAGE JUNCTION BOX
RETURN WATER
FROM HEATING
SYSTEM (IN)
1-1/4" NPT
IGNITER
SIGHT GLASS
HEAT EXCHANGER
BALL VALVE
CONDENSATE
DRAIN 1/2" PVC
GAS SHUTOFF
VALVE
LOW WATER
CUTOFF
COMBUSTION
AIR
BLOWER
COMBUSTION
CHAMBER
GAS (CONTROL)
VALVE
USER INTERFACE
RETURN WATER
FROM HEATING
SYSTEM (IN)
1-1/4" NPT
SUPPLY WATER TO
HEATING SYSTEM
(OUT) 1-1/4" NPT
HEAT EXCHANGER
PUMP
SAFETY RELIEF VALVE
COMBUSTION
ANALYSIS TEST
PORT
IN-LINE
PRESSURE
SWITCH
VAPOR
COLLECTOR
FIGURE 3-2 Boiler Components
HIGH VOLTAGE JUNCTION BOX
SAFETY RELIEF VALVE
NOTE:
See Section 5
For Piping
Instructions
LOW WATER
CUTOFF
HIGH TEMPERATURE
SUPPLY SWITCH
GAS (CONTROL)
VALVE
COMBUSTION
AIR
BLOWER
VENT CONNECTOR
(2" PVC)
USER INTERFACE
COMBUSTION
AIR INLET
2" PVC
RETURN WATER
FROM HEATING
SYSTEM (IN)
1-1/4" NPT
LOW
VOLTAGE
TERMINAL
STRIP
IGNITER
FLAME
SENSOR
SIGHT GLASS
TEST PORT
COMBUSTION
CHAMBER
GAS SHUTOFF
VALVE
(SHOWN IN OPEN
POSITION)
HEAT EXCHANGER
PUMP
CONDENSATE
DRAIN 1/2" PVC
VENT
TEMPERATURE
SENSOR
SUPPLY WATER TO
HEATING SYSTEM
(OUT) 1-1/4" NPT
HEAT EXCHANGER
BALL VALVE
DRAIN
VALVE
RETURN TEMPERATURE
SENSOR
IN-LINE
PRESSURE
SWITCH
VAPOR
COLLECTOR
COMBUSTION
ANALYSIS TEST
PORT
CONDENSATE
COLLECTOR
RETURN WATER
FROM HEATING
SYSTEM (IN)
1-1/4" NPT
8
Note: To open
Lift panel up
then pull forward
3 - COMPONENT LISTING
INTERNAL ACCESS
PANEL - CLOSED
CONTROL
MODULE
INTERNAL ACCESS
PANEL -OPEN
CENTRAL HEATING
PUMP RELAY
Control Module Fuse and holder
TRANSFORMER
9
4 - LOCATING BOILER
4.1 Boiler Location Considerations
Ambient room temperature always above 32°F (0°C) to • prevent freezing of liquid condensate.
Approved for installation in closets and on combustible oors. Do not install boiler on carpeting.
Protection of gas ignition system components from • water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, condensate trap,
control replacement, etc.). Floor or wall mounting.
Wall must be plumb and capable of supporting boiler • weight plus 60 lbs (28 kg). See Table 1.
Floor must be level. Leveling feet allow adjustment • up to 1/4" (6 mm).
Wall mounting. See section 4.2.
Access to outdoors to meet minimum and maximum • pipe lengths for combustion air and vent piping. See section 6.
Disposal of condensate. See section 6.
TABLE 2: BOILER CLEARANCES
Dimension
Top (A) Left Side (B) Right Side (C) Front (D) Back (E)
Bottom (F)
Combustion Air/Vent piping
Hot Water Pip­ing
(1)
Required distances measured from boiler.
(2)
Service, proper operation clearance recommendation.
Combustible
Materials
0" (0 cm) 14" (36 cm)
6" (16 cm) 6" (16 cm)
0" (0 cm) 1½" (4 cm) 0" (0 cm) 6" (16 cm) 0" (0 cm) 0" (0 cm)
0" (0 cm)
0" (0 cm) 6" (16 cm)
½" (1.3 cm) 6" (16 cm)
(1)
Service
0" (0 cm) Floor
12" (32 cm) for
Bottom Piped
(1)(2)
Drainage of water (or water - antifreeze solution) during • boiler service or from safety relief valve discharge. See section 5.
Access to system water piping, gas supply, and electrical • service. See sections 5, 7 and 8.
Clearances to combustible materials and service • clearances. See Table 2 and fi gure 4-1.
Multiple Boilers can be placed side by side, back to back • or wall mounted.
FIGURE 4-1 Clearance to Combustible Materials
A
E
B
A
A
C
E
FLOOR FLOOR
D
10
B
C
4 - LOCATING BOILER
!
FIGURE 4-2 Wall Mount Bracket Engaged with Bracket on Boiler
Center brackets. Avoid
overhang on sides of wall
mount bracket.
4.2 Wall Mounting Option
Boiler can be wall mounted using wall mounting bracket included with unit.
Structure must be capable of supporting boiler weight • plus 60 lbs (28 kg). See Table 1, page 2.
Wall mount bracket has 4 slots allowing mounting on • two (2) wall studs spaced at 11½" to 16½" on center. See fi gure 4-2.
Boiler includes (4) 3/8" x 3" lag screws and (4) washers • for attaching wall mount bracket to wood studs. Field source appropriate fasteners for other wall constructions (masonry, concrete).
Attach wall mount bracket level on wall.• Boiler must engage with wall mount bracket. • Avoid overhang on sides of wall mount bracket. Verify
boiler bracket is centered on wall bracket. See fi gure 4-2.
4 Slots for attaching Wall
Mount Bracket to Studs
!
CAUTION
Boiler weight exceeds 115 pounds (51.2 kg). Do not lift boiler onto wall without assistance.
11
5 - HYDRONIC PIPING
5.1 General
Install piping in accordance with authority having jurisdiction.
NOTICE
Use two (2) wrenches when tightening and fi tting to pipe boiler's threaded fi ttings. Boiler's internal piping can be damaged if subjected to excessive torque.
Support system piping and safety relief valve discharge • piping. Boiler's internal piping and wall mount bracket can be damaged if subjected to excessive weight.
Size central heating pump (and domestic hot water pump, • if used) for system requirements only. Heat exchanger pump compensates for pressure drop through boiler internal piping and heat exchanger.
Thoroughly clean and fl ush system before connecting to boiler.
5.2 Special Conditions
System piping exposed to freezing conditions: Use • inhibited proplyene glycol solutions certifi ed by fl uid manufacturer for use with closed water heating system. Do not use automotive or ethylene glycol.
!
WARNING
Poison hazard. Ethylene glycol is toxic. Do not • use ethylene glycol.
Never use automotive or standard glycol antifreeze, • even ethylene glycol made for hydronic systems.
Ethylene glycol can attack gaskets and seals used • in hydronic systems.
Use only inhibited proplyene glycol solutions • certifi ed by fl uid manufacturer as acceptable for use with closed water heating system.
Thoroughly clean and fl ush any system that used glycol before installing new Boiler.
Provide user with Material Safety Data Sheet • (MSDS) on fl uid used.
NOTICE
Do not expose boiler and condensate piping to freezing temperatures.
Boiler installed above radiation level (or as required by • authority having jurisdiction). Integral low water cutoff provided in boiler. See page 6.
Boiler used in connection with refrigeration system. • Install piping in parallel with boiler, with appropriate valves to prevent chilled medium from entering boiler.
System piping connected to heating coils located in air • handling unit exposed to refrigerated air circulation. Install fl ow control valves or other automatic means to prevent gravity circulation of boiler water during cooling cycle.
5.3 Safety Relief Valve and Air Vent
NOTICE
Boiler rated at 50 psig (345 kPa) maximum allowable working pressure. Boiler provided with 30 psig (206 kPa) safety relief valve. Field source safety relief valve for system pressures greater than 30 psig (206 kPa). Temperature Pressure Gauge and Air Vent satisfactory for 30-50 psig (206-345 kPa) operation.
FIGURE 5-1 Safety Relief Valve & Air Vent
Safety Relief
Valve
3/4" NPT
Air Vent
3/4 NPT
90° Elbow
3/4" NPT
Close Nipple
3/4"F x 3/4"M
NPT Tee
Install safety relief valve and air vent using pipe fi ttings provided with boiler. See fi gure 5-1.
Install safety relief valve with spindle in vertical position.• Do not install shutoff valve between boiler and safety
relief valve.
3/4" x 1/4" NPT
90° Elbow
12
5 - HYDRONIC PIPING
!
WARNING
Burn and scald hazard. Safety relief valve could discharge steam or hot water during operation. Install discharge piping per these instructions.
FIGURE 5-2 Safety Relief Valve Discharge Piping
5.4 Trim Piping
Systems with automatic fi ll valves require back fl ow prevention device.
Install discharge piping from safety relief valve. See gure 5-2.
Use ¾" or larger pipe.• Use pipe suitable for temperatures of 375°F (191°C)
or greater. Individual boiler discharge piping shall be independent
of other discharge piping. Size and arrange discharge piping to avoid reducing
safety relief valve relieving capacity below minimum relief valve capacity stated on rating plate.
Run pipe as short and straight as possible to location • protecting user from scalding and properly drain piping.
Install union, if used, close to safety relief valve outlet.• Install elbow(s), if used, close to safety relief valve
outlet and downstream of union (if used). Terminate pipe with plain end (not threaded).
Supply and Return Piping
Check Local Codes
For Maximum
Distance To Floor
FIGURE 5-3 Temperature Pressure Gauge Installation
Temperature Pressure Gauge
shown at Optional Bottom
Supply Connection to Boiler
Supply - Select either top, bottom or both.• Return - Select either top, bottom, or both.• Use second temperature pressure gauge when piping
top and bottom. Install brass plug(s) provided with boiler in unused
tapping(s). Use provided sealant.
Temperature - Pressure Gauge. Install temperature • pressure gauge using nipple, bushing and tee provided with boiler. See fi gure 5-3.
5.5 System Piping
Single boiler system. See fi gures 5-4, 5-5, 5-6, 5-7 for general guidance. Additional considerations:
Control system designed for single central heating • pump. Installer responsible for integration of multiple central heating pumps.
Control system allows domestic hot water • prioritization. Function could be lost if central heating pump not directly connected to control
system.
Multiple boiler system. See fi gure 5-8 for general guidance. Additional considerations:
Control system requires equivalent water • temperatures entering each boiler to properly sequence and adjust system supply temperature.
Install multi boiler sensor kit. See "Parts, Kits & • Optional Accessories" manual for part number.
13
5 - HYDRONIC PIPING
NOTICE
Illustrations are meant to show system piping concept only. Installer responsible for all equipment and detailing required by authority having jurisdiction.
FIGURE 5-4 System Piping
System
Supply
System
Return
Piping Legend
FLOOR
Check Local Codes
For Maximum
Distance To Floor
14
5 - HYDRONIC PIPING
5-5 TWO-PIPE ZONED SYSTEM WITH VALVES
DHW Pump
CH/System
Pump
Heat exchanger
ball valve open
(as shipped)
3/8"/10mm
Open End
Wrench
5-6 TWO-PIPE ZONED SYSTEM WITH PUMPS
DHW Pump
Zone
Pump
Heat exchanger
ball valve open
(as shipped)
3/8"/10mm
Open End
Wrench
15
5 - HYDRONIC PIPING
5-7 SINGLE BOILER USING PRIMARY/SECONDAY PUMPING
12"/305mm Max. apart
CH/System
Pump
3/8"/10mm Open
End Wrench
12"/305mm Max. apart
Heat exchanger ball
valve open
Existing closely
spaced tees
in primary
system loop
Heat exchanger
ball valves closed
Limit length
to
5'/1.6 m
3/8"/10mm Open
End Wrench
16
5 - HYDRONIC PIPING
5-8 TYPICAL MULTIPLE BOILER PIPING - (See Multiple Boiler Guide)
DHW Pump
CH/
System
Pump
12"/305mm Max. apart
System
T emperature
Sensor
Size common piping
according to
maximum heat
capacity of
entire system
Up to 16
boilers
All heat exchanger
ball valves closed
3/8"/10mm Open
End Wrench
(See Multiple Boiler Guide)
17
6 - COMBUSTION AIR AND VENT PIPING
6.1 General
This boiler requires a dedicated direct vent system. Install combustion air and vent piping in accordance with these instructions, authority having jurisdiction,
and:
USA - National Fuel Gas Code, ANSI 223.1/NFPA 54.• Canada - Natural Gas and Propane Installation Code,
CAN/CSA B149.1
Vent connections serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure.
Install vent system in accordance with these instructions.
6.2 Removal of Existing Boiler From Common Vent System
When existing boiler is removed from common venting system, common venting system is likely to be too large for proper venting of appliances remaining connected to it.
After removal of existing boiler, following steps shall be followed with each appliance remaining connected to common venting system placed in operation, while other appliances remaining connected to common venting system are not in operation:
Seal any unused openings in common venting system.• Visually inspect venting system for proper size and
horizontal pitch. Determine there is no blockage or restrictions, leakage, corrosion and other defi ciencies which could cause an unsafe condition.
When practical, close all building doors, windows, and • all doors between space in which appliances remaining connected to common venting system are located and other spaces of building. Turn on clothes dryer and any appliance not connected to common venting system. Turn on exhaust fans, such as range hoods and bath­room exhaust so they will operate at maximum speed. Do not operate summer exhaust fan. Close fi replace dampers.
their previous condition of use. Any improper operation of common venting system
should be corrected so installation conforms with National Fuel Code, ANSI Z223.1/NFPA 54 and/or Natural Gas and Propane Installation Code, CAN/CSA B149.1. When re-sizing any portion of common venting system, com­mon venting system should be re-sized to approach minimum size as determined using appropriate tables in Chapter 13 of the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 and/or Natural Gas and Propane Installation
Code, CAN/CSA B149.1.
6.3 Materials
See Table 4
Table 3 - Combustion Air and Vent Piping Length
Combustion Air and Vent Pipe Equivalent
Length
2” Pipe 3” Pipe
Minimum 6 ft (1.8 m) 6 ft (1.8 m)
Maximum 60 ft (18.3 m) 100 ft (30.4 m)
1 - 90° elbow = 5 ft (1.6 m) 1 - 45° elbow = 3.5 ft (1.1 m) 1- 2" x 3" adapter = 0 ft (0 m)
Note: Concentric Vent Kit=5 ft (1.6m) equivalent length
For Example: Boiler can be installed on outside wall and vented with 1-90° elbow and 1 ft (0.30 m) of vent pipe.
Turn on appliance being inspected. Follow lighting • instructions. Adjust thermostat so appliances will operate continuously.
Test for spillage at draft hood relief opening after 5 • minutes of main burner operation. Use fl ame of match or candle, smoke from cigarette, cigar or pipe.
Determine each appliance remaining connected to • common venting system properly vents when tested as outlined above. Then return doors, windows, exhaust fans and any other gas-burning appliance to
18
6 - COMBUSTION AIR AND VENT PIPING
Table 4 - Combustion air and vent pipe fi ttings
must conform with the following:
Item Material Standards
PVC schedule 40 ANSI/ASTM D1785
PVC - DWV ANSI/ASTM D2665
CPVC schedule 40
Vent Pipe
and Fittings
Pipe
Cement/
Primer
IPEX is approved vent manufacturer in Canada listed • to ULC-S636.
IPEX System 636 Cements and Primers are approved • in Canada listed to ULC-S636.
SDR-21 & SDR-26 PVC ANSI/ASTM D2241
ABS-DWV ANSI/ASTM D2661
Schedule 40 ANSI/ASTM F628
PVC ANSI/ASTM D2564
CPVC ANSI/ASTM F493
Schedule 40 ABS ANSI/ASTM D2235
DO NOT USE CELLULAR (FOAM) CORE PIPE
!
WARNING
Use of cellular core PVC for venting fl ue gas could result in death, serious injury.
!
WARNING
Vent extending through exterior wall shall not terminate adjacent to wall or below building extensions such as eaves, balconies, parapets or decks. Failure to comply could result in death or serious injury.
ANSI/ASTM D1784/
F441
6.4 Pipe Installation
Minimum and maximum combustion air and vent pipe • lengths listed in Table (3). Pipe length counted from combustion air connector to termination.
Install fi eld-sourced 2" to 3" transition, if used, in vertical section at combustion air inlet and vent connector.
90° elbows equivalent to 5.0 ft (1.6 m). 45° elbows • equivalent to 3.5 ft (1.1 m). 2" to 3" transition has no equivalent length.
Slope vent pipes minimum 1/4" per foot (21 mm/m) • back toward boiler. Support horizontal sections to prevent sags capable of accumulating condensate.
Support piping in accordance with pipe manufacturer's • instruction and authority having jurisdiction. In absence of manufacturer's instruction use pipe hooks, pipe straps, brackets, or hangers of adequate and strength located at intervals of 4 ft (1.2m) or less. Allow for expansion/contraction of pipe.
Combustion air and vent piping must be air tight and • water tight.
Certifi ed vent system components must NOT be inter- changed with other vent systems or unlisted pipe/fi ttings.
Canadian installations only. All venting material, primer • and glue must be listed to ULC S636.
Canadian installations only. First 3 ft (0.9 m) of • plastic vent pipe from vent connector must be readily
accessible for visual inspection.
6.5 Termination
Terminate combustion air and vent pipes with fi ttings or concentric vent kit.
See "Parts, Kits and Optional Accessory" manual for • concentric vent kit part numbers.
Use horizontal pipe for vent and 90° elbow for • combustion air termination when using fi ttings.
Terminate combustion air and vent pipes in same • atmospheric pressure zone through exterior sidewall or roof.
Locate combustion air termination as far as possible • from swimming pool, swimming pool pump house, and other sources of airborne chlorine.
Locate combustion air and vent as required by authority • having jurisdiction.
19
6 - COMBUSTION AIR AND VENT PIPING
FIGURE 6-1
12" (30 cm)
Minimum
8" (21 cm)
Minimum
Vent Combustion
Air
12" (30 cm) US, 18" (46 cm)
Canada Minimum above
anticipated snow line
FIGURE 6-2
3" (8 cm)
Maximum
15" (38 cm)
Maximum
Roof Line
Roof
Terminations
y 3" (8 cm) Maximum horizontal separation between combustion air intake and vent of same appliance.
y 8" (21 cm) Minimum vertical separation between combustion air intake and vent of different appliances.
y 15" (38 cm) Maximum horizontal length of vent.
y Maximum vent/intake between different appliances 12" (30cm).
y Maximum allowable total vertical vent length with outside exposure equals 10 ft.(3.05m).
y Abandoned unused masonry chimney may be used as chase­way for combustion air and vent. Both combustion air and vent pipe must exit above top of chimney with clearances as shown in fi gure 6-1.
12" (30 cm)
Minimum from
overhang
See snow & ice
page 23
FIGURE 6-3
3" (8 cm) Maximum
separation
12" (30 cm) Separation
between bottom of
combustion air intake
and bottom of vent
Vent
Combustion Air
12" (30cm)
Minimum
separation
Side Wall
Terminations
y 3" (8 cm) Minimum horizontal separation between combustion air intake and vent terminations.
y 8" (21 cm) Minimum vertical separation between combustion air intake and vent terminations.
y 12" (30 cm) Separation between bottom of combustion air intake and bottom of vent.
y Multiple terminations as shown in 6-1, 6-2, and 6-3 must be minimum of 12” (30 cm) horizontally between vent of one termination and air intake of next appliance.
y Maximum allowable total outside exposure vent length equals 10 ft. (3.05m).
y Maintain a pitch of 1/2" per ft (0.15m/m) back to boiler to ensure proper condensate drainage for horizontal runs.
See snow & ice
page 23
Combustion Air
Vent
20
6 - COMBUSTION AIR AND VENT PIPING
FIGURE 6-4
1" (2.54cm) Maximum
1"(2.54cm) Maximum
Combustion
Vent
Air
NOTICE
Concentric termination kit reduces allowable intake/ vent piping length by 5' (1.5m) from that listed in installation instructions.
FIGURE 6-7
FIGURE 6-5
1" (2.54cm) Maximum
* See Note Below
Combustion
Air
*Must be less than 4" or greater than 24" Horizontal dis­tance between end bells of each air intake to prevent fl ue gas recirculation.
Note: Securing strap must be fi eld installed to prevent movement of termination kit in side wall
Roof overhang
12" (30cm) Minimum
36"(0.9m) Minimum
Maintain 12"(30cm) US
Vent
clearance above
(18"(46cm) Canada)
highest anticipated
clearance above highest
snow level or grade
anticipated snow level or
Maintain 12"
grade
OD 3½" ( OD 4½" (11.4cm) - 3" (7.6cm) kit
Combustion Air
Elbow fi eld supplied
** Note Overall length may be modifi ed by cutting or extending both combustion air and vent pipes. 12" is minimum allowable length and 60" is maximum allowable length for this dimension. SDR-26 PVC (D2241) only may be used for extending pipes. Do not use Schedule 40 PVC or use couplings to extend pipes. Dimension will change if intake/vent pipes are lengthened or shortened.
8.9cm)
- 2" (
5.0cm)
kit
2 or 3" (5.0 or 7.6cm) Diameter
PVC intake/combustion air
2" (
5.0cm)
46-3/4" (1.2 m)
Diameter = 41" Length (1.0m)
3" (7.6cm) Diameter = 47" Length (1.2m)
**See
Note
Combustion Air
Vent
1"(2.54cm) Maximum
21
6 - COMBUSTION AIR AND VENT PIPING
Concentric
Vent Roof
Termina-
tions
y Glue inner vent pipe to prevent recirculation.
y Maintain 12" (30 cm) US (18"(46 cm) Canada) minimum clearance above highest anticipated snow level. Maximum of 24"(0.61m) above roof.
y Support must be fi eld installed to secure termination kit to structure.
y Elbow, roof boot/fl ashing fi eld supplied.
y Allowed Wall/Roof thickness 1/2"-30" (1.2 - 76cm).
y Vertical concentric vent system can be installed in unused masonry chimney.
y Contact ECR Technical Support 800­325-5479, for questions regarding installation or use.
FIGURE 6-6
Combustion Air
Roof boot/fl ashing (fi eld supplied)
Note: Support must be fi eld installed to secure termination kit to structure
Vent
Vent
Maintain 12"(30cm) US
(18"(46cm) Canada)
clearance above highest
anticipated snow level
24" above roof
Support (fi eld supplied)
Combustion Air
22
6 - COMBUSTION AIR AND VENT PIPING
Forced Air
Inlet
12"
(30.5cm m)
Minimum
Less than 10' (3 m)
Minimum
Termination must be 12" (30.5 cm)
from or below doors,
windows or gravity
inlet.
Termination
Termination
3' (0.9 m) [If located within 10' (3 m) of forced air inlet]
Doors &
Windows
Condensate
Forced Air
Inlet
Combustion air and vent termination must be 12" (30.5 cm) from or below doors, windows or gravity inlet.
Vent gas may condense, forming moisture, may be corrosive. Protect building materials at vent from exhaust of vent gas.
Terminate venting system 3’ (0.9 m) above and 10' (3.0 m) from any forced air inlet (except boiler’s combustion air inlet).
3' (0.9 m)
Minimum
Grade, Snow
& Ice
"L"
Corner
Terminate vent system bottom, minimum 12"(300 mm) above highest anticipated snow level.
Avoid locations where snow may drift and block vent and combustion air. Ice or snow may cause boiler to shut down if vent or combustion air becomes obstructed.
Vent termination shall NO T be installed closer than 3' (0.9 m) from inside corner of “L” shaped structure.
23
Vegetation,
Plants &
Shrubs
Meters, Regulators, deck, porch
Walkways
6 - COMBUSTION AIR AND VENT PIPING
Keep vent termination 3’ minimum (0.9m) away from vegetation. Position termination where vent vapors will not damage plants/shrubs or air conditioning equipment.
Termination
Vent termination US only - 4’ (1.2 m), Canada - 6' (1.83m) horizontally from, no case above or below, electric meters, gas meters, regulators, and relief equipment, or under deck or porch.
3' (0.9 cm)
Minimum
Locate vent termination minimum 7' (2.1 m) above any public walkway, with consideration to condensate.
People or
Pets
Stones,
Balls,
Etc.
Vapors
Locate combustion air and vent termination to prevent accidental contact with people or pets.
Position combustion air and vent termination where it will NOT be damaged by foreign objects, such as stones, balls, etc.
Position termination where vent vapors are not objectionable.
7' (2.1 m)
Minimum
Position termination so it will not be
Eddy,
Flue
Gases
effected by wind eddy, air born leaves, snow, or recirculated vent gases. Give consideration to excessive wind and locate away from windward side of building.
Multiple
Family
Dwellings
24
Vent shall not terminate directly above paved sidewalk or paved driveway located between two single-family dwellings serving both dwellings.
6 - COMBUSTION AIR AND VENT PIPING
FIGURE 6-1 Condensate Drain
6.6 Condensate Piping
Use materials acceptable to authority having jurisdiction. • In absence of such authority:
USA - PVC or CPVC per ASTM D1785/D2845 Cement • or primer per ASME D2564 or F493.
Canada - CSA or ULC certifi ed PVC/CPVC pipe, ttings and cement.
Insert 1/2" (1.3 cm) PVC pipe through grommet in • chassis. See fi gure 6-1.
Attach PVC tee provided with boiler and fi eld sourced piping to condensate drain vertical tee on left side of boiler. See fi gure 6-1.
Slope condensate drain pipe minimum 1/4" per foot • (21mm/m) away from boiler.
Use condensate pump if boiler located below disposal • point. 120 VAC auxiliary power outlet can be used to power condensate pump.
Field source condensate neutralizing kit as required • by authority having jurisdiction or for environmentally
friendly condensate disposal.
PVC Tee (fi eld installed)
on condensate drain
pipe
25
!
7 - GAS SUPPLY PIPING
7-1 Gas Connection Knockout Plate at Bottom of Boiler
Bottom cover
for Optional Gas
Connection
7.1 General
7-2 Gas connection at Top of Boiler
Gas Connection Top
of Boiler
7-3 Bottom Gas Connection
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.• Do not touch any electrical switches; do not use
any phones in your building. Immediately call your gas supplier from
a neighbor’s phone. Follow gas supplier’s instructions.
If you cannot reach your gas supplier, call the fi re department.
Use piping materials and joining methods acceptable • to authority having jurisdiction. In absence of such requirements:
USA - National Fuel gas Code, ANSI Z223.1/NFPA 54• Canada - Natural Gas and Propane Installation Code,
CAN/CSA B149.1
Size and install gas piping system to provide suffi cient gas supply to meet maximum input at not less than minimum supply pressure. See Table 5.
Support piping with hooks straps, bands, brackets, • hangers, or building structure components to prevent or dampen excessive vibrations and prevent strain on gas connection. Boiler will not support piping weight.
Use thread (joint) compound (pipe dope) suitable for • liquefi ed petroleum gas.
Provide sediment trap up stream of gas valve.
Optional Bottom Gas
Connection
TABLE 5: GAS SUPPLY PRESSURE
SIZE
075/100 75,000
Maximum
Input (Btuh)
Note: See Glossary - Piping Table 16
7.2 Conversion Kit Instructions
See Gas Conversion Kit Instructions included with Boiler.
Natural Gas Propane
Min. Max. Min. Max.
3.0" w.c.
(0.7 kPa)
13.5" w.c. (3.3 kPa)
5.0" w.c. (1.2 kPa)
13.5" w.c. (3.4 kPa)
26
7 - GAS SUPPLY PIPING
!
DANGER
Fire Hazard. Do not use matches, candles, open ames, or other methods providing ignition source. Failure to comply will result in death or serious injury.
7.3 Near Boiler Gas Piping
Select top or bottom gas connection. To convert from
• top connection to bottom connection:
Remove bottom knockout by removing two (2)
• screws. See fi gure 7-1.
Disconnect gas connection by removing two (2)
• screws. See fi gure 7-2.
Relocate gas connection to bottom opening.
• Secure with two (2) screws. See fi gure 7-3.
Relocate knockout cover to top opening. Secure
• with two (2) screws. See fi gure 7-4.
Install fi eld sourced manual main shutoff valve and
• ground joint union. See fi gure 7-5.
7-4 Gas Connection Knockout Plate at Top of Boiler
Top of Boiler Cover for
Gas Connection
7-5 Manual Main Gas Shutoff Valve Outside Boiler Jacket
Manual Main Gas
Shutoff Valve
7.4 Leak Check Gas Piping
Pressure test boiler and gas connection before placing boiler in operation.
Pressure test over 1/2 psig (3.5 kPa). Disconnect
• boiler and its individual gas shutoff valve from gas supply system.
Pressure test at 1/2 psig (3.5 kPa) or less. Iso-
• late boiler from gas supply system by closing manual gas shutoff valve. See fi gure 7-6.
Locate leakage using gas detector, noncorrosive
• detection fl uid, or other leak detection method acceptable to authority having jurisdiction. Do not use matches, candles, open fl ames, or other methods providing ignition source.
Correct leaks immediately and retest.
Option: Gas
Connection May be
Located
At Bottom of Boiler
7-6 Gas Shutoff Valve
Gas shutoff valve
(shown in closed
position)
27
8 - ELECTRICAL CONNECTIONS
8.1 General
Electrically bond boiler to ground in accordance with requirements of authority having jurisdiction. Refer to:
USA- National Electrical Code, ANSI/NFPA 70.• Canada - Canadian Electrical Code, Part I, CSA C22.1: • Safety Standard for Electrical Installations.
8.2 Line Voltage Connections (Figure 8-1)
Boiler
Provide individual 120V, 15 amp circuit (recom-A. mended) with fused disconnect or service switch, as required by authority having jurisdiction.
Open High Voltage Junction Box (see Figures 3-1, B. 3-2) to access line voltage terminal strip.
Connect 120 VAC circuit to line voltage terminal C. strip 120 VAC L,N,G.
Central Heating Pump, if used.
Isolate pump from control module if pump FLA (Full A. Load Amps) exceeds 5 amps.
Connect pump to line voltage terminal strip CH B. PUMP L,N,G.
Domestic Hot Water Pump, if used.
Isolate pump from control module if pump FLA A. exceeds 1.0 amp.
Connect pump to line voltage terminal strip DHW B. PUMP L,N,G.
!
WARNING
Electrical shock hazard. Turn OFF electrical power supply at service panel before making electrical connections. Failure to do so could result in death or serious injury.
NOTICE
Wiring diagrams can be found in Section 14 of this Manual.
8-1 LINE VOLTAGE CONNECTIONS
8-2 LOW VOLTAGE CONNECTIONS
8.3 Low Voltage Connections (Figure 8-2)
User Interface Terminals
Factory wired to low voltage terminal plug USER A. INTERFACE terminals
Optional - Remote mount user interface for B. improved access.
Maximum wire length is 100 ft (30m) for 22 ga. C. wire, or 150 ft (45m) for 18 ga. wire.
Argus Link (Multiple boiler applications only)• Outdoor Sensor, if used.
Provided with boiler in accessory kit.A. Locate outdoor sensor to protect against wind and B.
direct sunlight. Mounting instructions provided with sensor.
Maximum wire length is 100 ft (30m) for 22 ga. C. wire, or 150 ft (45m) for 18 ga. wire.
Connect wires to low voltage terminal plug OUT-D. DOOR SENSOR terminals. Wires are interchangeable.
System Sensor (Multiple boiler applications only)
28
8 - ELECTRICAL CONNECTIONS
Domestic Hot Water (DHW) Thermostat, if used.
Use temperature control with dry contacts rated A. at 0.5 amps @ 120 VAC. Boiler control does not provide power to DHW temperature control.
IMPORTANT: Do not apply power to DHW T-T terminals. Dry contact only, use of isolation relay may be necessary.
Maximum wire length is 330 ft (100 m) 22 gauge B. wire.
Connect wires (interchangeable) to low voltage C. terminal plug DHW T-T terminals. Wires are
interchangeable.
Central Heating Thermostat
Use thermostat or boiler system control with dry A. contacts related 0.5 amps @ 120 VAC. Boiler control does not provide 24 VAC power to central heating thermostat.
Locate and install thermostat per manufacturer's B. instructions. Maximum wire length is 330 ft (100 m) for 22 ga. wire.
Connect wires to low voltage terminal plug CH T-T C. terminals. Wires are interchangeable.
NOTICE
29
9 - START UP PROCEDURE
9.1 Fill boiler with water and purge air
Fill boiler with potable water.• Fill boiler and system piping with water (or antifreeze-
• water solution, if used). See antifreeze information page 12. Purge air from boiler using air vent. Purge air from system piping.
Inspect system piping and boiler connections. Repair
• any leaks immediately.
9.2 Fill Condensate Trap with Water
Disconnect collet clip from elbow. See fi gure 9-1.
• Disconnect tubing below elbow.
• Pour about 1 cup (237ml) of water into condensate
• drain.
Reconnect tubing to elbow with collet clip. See Figure
• 9-1.
NOTICE
IMPORTANT: Condensate trap must be manually lled with water at initial start up.
9-1 Condensate Drain Assembly
1. Disconnect collet clip from hose barb and fi ll Condensate
trap with water.
2. Reconnect collet clip to hose barb before starting boiler.
30
9 - START UP PROCEDURE
e
9 -2 User Interface
-2 User Interfac
9.3 Program Boiler Control
Key Description
- Manual Lockout Reset
- Enter/Exit user menu
- Go to previous screen
- Select a menu item
- Confi rm new parameter value
- Scroll up to next menu item
- Increase value
- Scroll down to next menu item
- Decrease value
Boiler is factory programmed with following factory de­fault settings, Figure 9-3.
Parameters can be adjusted to suit particular application.
Detailed explanation of each can be found in Appendix A - Control Module.
List parameters in event of Control Module Failure to reprogram your settings.
Factory De-
9-3 Default Table
Control Parameter
Central Heating Setpoint
User
Menu
Installer
Menu
* List parameters in event of Control Module Failure to reprogram your settings.
Settings
Boiler
Confi guration
CH Settings
DHW Setpoint 180°F 82°C 104 - 195°F 40 - 91°C Temperature Units °F °F/°C Language English English/French Boiler Address 0 0-15 Low Water Cutoff Enabled Enable/Disabled Pump Mode 0 0 & 4 Service Reminder Status On ON/OFF Service Reminder Days 365 Days 1- 999 Days
CH Mode 1 0-3 Warm Weather Shutdown 70°F 21°C 35-100°F 2-38°C Reset Curve Design Temperature - Boiler 180°F 82°C 60-195°F 40-91°C Reset Curve Design Temperature - Outdoor 25°F -4°C -60-32°F -51-25°C Reset Curve Mild Weather Temperature - Boiler 70°F 21°C 35-120°F 2-49°C Reset Curve Mild Weather Temperature - Outdoor 70°F 21°C 35-85°F 2-29°C
Reset Curve Boiler Minimum Temperature 70°F 21°C 40-180°F 4-82°C Reset Curve Boiler Maximum Temperature 180° 82°C 80-195°F 27-91°C Boost Function Temperature 18°F 10°C 0-36°F 0-20°C Boost Function Time 20 Minutes 1-120 Maximum Power CH 100% 1-100% DHW Mode 0 0/2 DHW Maximum Priority Time 30 Minutes 1-60 minutes
fault Setting
Stan-
dard
140°F 60°C 104 - 195°F 40 - 91°C
Setting Range
Metric Standard Metric
*Actual
Parameter
Settings
31
9 - START UP PROCEDURE
9.4 Boiler Start-up and Operational Test
Verify air is purged from hydronic piping1. System test pumps - verify each pump is 2.
operational Verify gas piping3.
Confi rm pressure test. See section 7.3.
• Visually inspect piping to determine there are no
• open fi ttings or ends, and all valves at unused outlets are closed and plugged/capped.
Purge air from piping
• Check piping and connections for leaks
• immediately after gas is turned on. Shut off gas supply and make necessary repairs if leaks found.
Follow OPERATING INSTRUCTIONS to initiate boiler 4. operation. See section 10.
Inspect combustion air and vent piping. Verify pipe 5. is not leaking and terminations are unobstructed and vent gas discharge is not a nuisance or hazard.
Verify boiler functions.6. Inspect condensate disposal system. Verify 7.
condensate fl ows adequately and is disposed properly.
Check control module operation.8. Check fi eld-sourced limits, low water cutoffs, etc. 9.
per manufacturer's instructions.
Compare to boiler rating2.
Size Minimum Maximum
075 65 85 100 90.0 110
Adjust rate if needed using diagram 9-3 below.3.
NOTICE
Contact ECR Technical Support @ 800-325-5479 for additional information or assistance.
Check CO4. and 10.0%. See Figure 9-4 Combustion air analyzer port.
If CO
• 9-3.
If CO
Propane Gas
Most propane systems do not have fl ow meters.
Check CO1.
11.0%. If CO
• 9-3.
If CO
• 9-3.
. Natural gas should be between 8.5%
2
is low increase gas fl ow following fi gure
2
is high decrease gas following fi gure 9-3.
2
. Propane should be between 9.5% and
2
is low increase gas fl ow following fi gure
2
is high decrease gas fl ow following fi gure
2
9.5 Check Combustion
Natural Gas
Measure input. English units*1.
Turn off gas to all other appliances.
• Use ½, 1 or 2 cu ft dial on gas meter. Measure
• time required for one or more complete revolutions. Measure time for 1-2 minutes.
Calculate input.
Input (MBH) =
Example: Gas fl ow from Meter = 2 cu ft Measured time = 72 seconds
Rate (MBH) =
*Metric - See Glossary
3600 x cu ft seconds
3600 x 2 cu ft 72 seconds
= 100 MBH
9-3 Gas Valve
To increase gas fl ow turn 'throttle' left or counter
• clockwise .
To decrease gas fl ow turn 'throttle' right or
• clockwise .
Limit adjustment to one turn and retest.
1/4" FLAT HEAD SCREWDRIVER
MIN
OUT
32
9 - START UP PROCEDURE
NOTICE
Combustion analyzer port is provided. After use replace cover.
9-4 Combustion Analyzer Port
In-line Pressure Switch
Vapor Collector
Combustion Analyzer Port
Verify Burner, Proper Operation
Inspect burner ame through Sight Glass. See 1. gure 9-5.
Operate boiler through several heating cycles, 2. including domestic hot water, if used. Verify proper operation.
Reset control parameters to operating settings if 3. adjusted to allow startup and operation test.
Follow instructions TO TURN OFF GAS TO APPLIANCE 4. if boiler is not being placed into immediate operation.
Enter installer information on Warranty Registration 5. Card.
Gather all instructions, manuals, wiring diagrams, 6. warranty registration card and other supporting information. Review with user and/or affi x in conspicuous location adjacent to boiler.
9-5 Burner Flame
Burner
Flame
Flame
Look for BLUE fl ame
with slight YELLOW tips
evenly spaced around
burner
33
10 - OPERATING INSTRUCTIONS
!
FOR YOUR SAFETY READ BEFORE OPERATING
!
WARNING
If you do not follow these instructions exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
This appliance is equipped with an ignition device • which automatically lights burner. Do NOT try to
light this burner by hand.
Before operating smell all around appliance area • for gas. Be sure to smell next to fl oor because some gas is heavier than air and will settle to the oor.
Use only your hand to turn the gas shutoff • valve. Never use tools. If valve will not turn by
hand, do not try to repair it, call a qualifi ed ser- vice technician. Force or attempted repair may result in fi re or explosion.
Do not use this appliance if any part has • been under water. Immediately call a quali-
ed service technician to inspect appliance and to replace any part of control system and any gas control which has been under water.
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.• Do not touch any electrical switches; do not use
any phone in your building. Immediately call your gas supplier from a neigh-
bor’s phone. Follow the gas supplier’s instruc­tions.
If you cannot reach your gas supplier, call the fi re department.
10.2 TO TURN OFF GAS TO APPLIANCE
Set thermostat to lowest setting.• Turn "OFF" all electric power to appliance if service is
to be performed. Remove front jacket panel.• Turn gas shutoff valve handle clockwise to closed
position. Handle should be perpendicular to gas pipe. Replace front jacket panel.
10-1 Gas Shutoff Valve
10.1 OPERATING INSTRUCTIONS
Stop! Read Safety information above.
Set thermostat to lowest setting.• Turn " OFF" all electrical power to appliance. This appliance is equipped with an ignition device which
automatically lights the burner. Do not try to light
burner by hand!
Remove front jacket panel.• Turn gas shutoff valve clockwise to closed position.
Handle should be perpendicular to gas pipe. Wait 5 minutes for any gas to clear. Smell for gas,
including near fl oor. If you smell gas, STOP! Follow instructions on this page: “What To Do If You Smell Gas.” If you do not smell gas, go to next step.
Turn gas shutoff valve counter clockwise to the • open position. Handle should be parallel to gas pipe.
Replace front jacket panel.• Turn " ON" electrical power to appliance. Set thermostat to desired setting.• If the appliance will not operate, follow instructions TO
TURN OFF GAS TO APPLIANCE and call your service technician or gas supplier.
OPEN POSITION
CLOSED POSITION
34
11 - GENERAL MAINTENANCE AND CLEANING
!
!
DANGER
Before servicing, turn off electrical power to boiler at service switch. Close manual gas valve to turn gas supply OFF to boiler.
!
CAUTION
Label all wires prior to disconnection when servic­ing controls. Wiring errors can cause improper and dangerous operation.
NOTICE
Verify proper operation after servicing.
NOTICE
Perform regular service and maintenance by qualifi ed service agency at least once every 12 months to assure safe, trouble free operation and maximum effi ciency .
11-1 Sight Glass
11.1 Beginning of Each Heating Season
Check boiler area is free from combustible materials, • gasoline, and other fl ammable vapors and liquids.
Visually inspect combustion air and vent piping for • proper operation. Check for and remove any obstruction to fl ow of combustion air or vent gases. Immediately repair or replace pipe showing deterioration or leakage. Reassemble per instructions in section 6. Ensure proper reassembly and resealing of system.
Visually inspect condensate drain line for proper • operation. Checking for deteriorated or plugged condensate drain line. Verify condensate trap drains freely.
Visually inspect in-line pressure switch vapor trap for • water build-up. Drain condensate collector by removing bottom fi tting if water is detected. See Figure 9-4.
Test safety relief valve for proper operation. Refer to • valve manufacturer's instructions packaged with relief valve.
Examine fl ue passages in heat exchanger, burner, condensate lines, and cleaning (if necessary) by following instructions in “Annual Examination and Cleaning of Boiler
Components” in this section.
Sight Glass
Circulator pump and combustion air blower motor • furnished with boiler are permanently lubricated from factory and require no further lubrication. Lubricate eld sourced pumps and/or motors should be lubricated according to pump and/or motor manufacturer’s instruction.
Check following components are operating properly and • are free of blockages or obstructions:
air vent;• check venturi air inlet for blockage and clean as
required; check air hose is tight• supply, return, and fl ue temperature sensor clips
must be securely seated on pipes; Check boiler for any sign of leaks.
Check low water cutoff using user interface.
Check operation by pressing test button on low water • cutoff.
"Low Water" LED should illuminate and burner • should shut down.
Should get error message on User Interface • (E36).
Every 5 years remove low water cutoff. Reinstall • after cleaning.
Every 10 years replace low water cutoff.
Check fl ame signal with user interface. Should be 8 micro amps at 100%.
35
11 - GENERAL MAINTENANCE AND CLEANING
Visual inspection of fl ame through sight glass. Burner should be fully illuminated. See fi gure 9-5.
Check expansion tank.
11.2 Annual shut down procedure
Follow instructions “To Turn Off Gas To Appliance” unless boiler is also used to supply domestic hot water. See section 10.
Drain system completely and add antifreeze when • heating system is to remain out of service during freezing weather.
Drain condensate lines when boiler is to be exposed to • freezing temperatures.
!
WARNING
Following service procedures must be performed by qualifi ed service agent. Boiler owner shall not attempt these steps.
!
WARNING
Use gloves when handling refractory to avoid absorption of crystiline silica a potentially dangerous compound.
11-2 Blower Inlet Assembly
A
B
C
D
E
11.3 Annual Examination and Cleaning of Boiler Components
Obtain Burner Inspection Kit. See "Parts, Kits and • Optional Accessories" manual.
Before servicing, turn off electrical power to boiler at • service switch.
Follow instruction 'To Turn Off Gas to Appliance'. Close • main gas valve.
Visually inspect through sight glass verify no fl ame is present.
F
Burner Assembly
A Blower Inlet Housing
B Refractory C Burner
D Flame Sensor
E Igniter F Sight Glass * Inlet Gasket
* Not Shown
36
11 - GENERAL MAINTENANCE AND CLEANING
11-2 Condensate Collector
Condensate Collector
A Combustion Chamber B Condensate Collector C Condensate Drain
Examine fl ue passages by removing blower/burner assembly from heat exchanger.
Confi rm manual gas valve is closed. Disconnect fl ame sensor and igniter wires. Remove 2 screws and carefully remove igniter.
A
B
C
Remove 2 screws and carefully remove fl ame rod sensor.
Loosen and remove four nuts connecting fuel mixer • assembly to heat exchanger.
Entire gas train can be moved aside. Take precaution • to not kink fl exible gas hose.
Remove gasket and burner. It may be necessary to • unlatch both of the Heat Exchanger locking straps.
Clean burner using air hose directed into top of • burner opening. This will dislodge any debris build up in burner ports.
Remove four nuts holding condensate collector from • bottom of heat exchanger assembly. Also remove gasket.
Clean heat exchanger with low pressure water spray. • If this does not clean fi ns adequately, use fl exible handle nylon brush to loosen sediment and oxide on all accessible heating surfaces of heat exchanger. Take care not to get brush stuck in heat exchanger.
After brushing and rinsing, remove any remaining • loosened sediment using shop vacuum with snorkel attachment. Inspect burner for foreign matter in ame ports or inside burner. Foreign matter should be removed by blowing with compressed air or vacuuming. If burner cannot be cleaned, it must be replaced.
Reinstall refractory, burner holder, burner and • replace gasket (in that order). Position fuel mixer assembly over studs. Install four nuts and tighten. Reinstall igniter and igniter gasket and fasten with two screws. Replace gasket and condensate collector to bottom of heat exchanger assembly. Replace and tighten four nuts holding collector to heat exchanger assembly.
Connect igniter wires, and gas valve wires.
Visually inspect condensate trap. Remove any foreign • material visible in condensate lines as described below:
Inspect for sediment or blockage.
Flush out with water or vacuum.• Follow the instructions “Filling The Condensate Trap
With Water” section 9.1
Follow Boiler Start-up and Operational Test. See section
9.4.
.
37
12 - RATINGS AND CAPACITIES
TABLE 12-1: SEA LEVEL RATINGS
NATURAL AND PROPANE GASES
Size
075 100
(1)
1000 Btu/hr (British Thermal Units Per Hour)
(2)
Heating Capacity and AFUE (Annual Fuel Utilization Ef ciency) are based on DOE (Department of Energy) test
procedures.
(3)
Net I=B=R Ratings based on piping and pickup allowance of 1.15. Contact ECR Technical Support before selecting boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
Boiler Input Rate (MBH)
Maximum Minimum
75 15 69 60 97.0
100 20 91 79 97.0
(1)
12.1 Ratings and Capacities
Constructed and hydrostatically tested for maximum • allowable working pressure of 50 psig (pounds per square inch gauge) (345 kPa) in accordance with ASME Boiler and Pressure Vessel Code, Section IV, Rules for
Construction of Heating Boilers.
Ratings are for sea level applications. • US - Boiler derates input 4% for every 1000 feet (304
m) above an elevation of 2000 feet (610 m) above sea level.
Heating Capacity
(1)(2)
(MBH)
Net I=B=R Rating,
Water (MBH)
(1)(3)
AFUE
(2)
Canada - Boiler certifi ed for altitudes of 0-4500 feet (1350 m) above sea level. Contact Provincial authority having jurisdiction for installations above 4500 feet (1350 m) above sea level.
38
13 - TROUBLE SHOOTING
GO TO NEXT
PAGE
NO YES
Is User Interface Lit?
YES
NO
Power Switch Lamp Lit?
104Vac?
Is voltage at Service
Receptacle more than
YESNO
Display function?
Does User Interface
harness plugs are
Make sure all wire
properly pushed in.
NO
company
NO YES
Repair wiring or call utility
finger, remove and
reconnect all 7 plugs .
Release plug lock with
Check wiring from User
checking continuity of
Terminal Strip including
Interface to Low Voltage
YES
YESNO
NO
the wires. Does User
Interface Display work?
Remove User Interface
from base. Using Digital
present?
to 30 Vdc. Is voltage
Voltmeter check for 25
Replace Control Module Replace User Interface
NO
Is Lamp Lit?
YES
Turn on Boiler Switch.
YES
Hi-Voltage Terminal Box
Check for 120 Vac Inside
Turn off Circuit Breaker.
Check Circuit Breaker or
or Repair External Wiring
Emergency Disconnect Switch
and 120 Vac Wiring to Boiler. Fix
NO
Partially pull back ¼”
wire. Turn on Circuit
connectors on Boiler Switch.
Jump 1 & 2. Do not use bare
YES
Breaker. Is Power Lamp lit?
39
LWCO lamps lit?
YES NO
User Interface Display or
Replace Switch
13 - TROUBLE SHOOTING
x
p
p
p
p
p
p
_ _ _ _ _ _ F P _ _ _ _
Go to Page 41
Lockout Alarm Blocking Error E 3 5 Blocking Too Long Error False Flame Detect
_ _ _ _ _ _ _ _ _ _ _ _ Lockout Alarm Blocking Error E 3 6 Ignit Error Low Water Cutoff
_ _ _ _ _ _ _ _ _ _ _ _ Lockout Alarm Blocking Error E 4 0 GV Relay Error Return Temp
A 0 0
A 0 1
Go to Page 42
A 0 5
Go to Page 41
Go to Page 48
Go to Page 49
Go to Page 50
_ _ _ _ _ _ _ _ _ _ _ _
Lockout Alarm Blocking Error E 4 3
Replace Control Module
A 0 6
Safety Relay Error Various Text Messages
_ P _ _ _ _ _ _ _ _ _ _
A 0 8
Lockout Alarm Blocking Error E 4 4
Go to Page 43
Fan Error Phase Error
_ _ _ _ _ _ _ _ _ _ _ _ Lockout Alarm Blocking Error E 4 5
A 0 9 to A 1 4
lace Control
Re Module
Various Text Messages Net Freq Error
_ P _ _ _ _ _ _ _ _ _ _
A 1 5
Lockout Alarm Blocking Error E 4 6
Go to Page 44
Air SW Not Open Faulty Earth Error
_ _ _ _ _ _ _ _ _ _ _ _ Lockout Alarm Blocking Error E 4 7
Replace Control
A 1 6
Module
Varioius Text Various Text Messages
_ _ _ _ _ _ _ P _ _ _ _
A 1 7
Lockout Alarm Blocking Error E 5 1
Go to Page 46
Air SW Not Closed Supply Sens Open
_ _ _ _ _ _ _ P _ _ _ _
Go to Page 47
Lockout Alarm Blocking Error E 5 2
A 1 8
Max Temp Error Return Sens Open
_ _ _ _ _ _ _ P _ _ _ _ Lockout Alarm Blocking Error E 5 7
Replace Gas
A 2 0
Valve
Flame Out Too Late Flue Sens Shorted
_ _ _ _ _ _ _ P _ _ _ _ Lockout Alarm Blocking Error E 5 9
Replace Gas
A 2 1
Valve
Flame Error 1 Supply Sens Shorted
_ _ _ _ _ _ _ P _ _ _ _ Lockout Alarm Blocking Error E 6 0
A 2 2 A 2 3
lace Control
Re Module
Various Text Messages Return Sens Shorted
_ _ _ _ _ _ _ P _ _ _ _
A 2 4
Lockout Alarm Blocking Error E 6 5
Go to Page 48
3 Flame Failures Flue Sens Shorted
_ _ _ _ _ _ _ P _ _ _ _ Lockout Alarm Blocking Error E 6 6
A 2 7 to A 3 0
Re
lace Control
Module
Various Text Messages Reset Button Error
_ _ _ _ _ _ _ _ _ _ _ _ Blocking Error Blocking Error
E 3 1 to E 3 4
Replace Control Module
Various Text Messages Various Fan Error Te
E73 to E79
E 81, 88, 89
Re
lace Control
Module
Go to Page 50
Go to Page 51
Go to Page 52
lace Control
Re Module
Go to Page 52
Go to Page 53
Go to Page 54
Go to Page 54
Go to Page 55
Go to Page 55
Error clears in 1-2 minutes
Re
lace Control
Module
40
13 - TROUBLE SHOOTING
Enter Installer Menu, Boiler
Status. Scroll to most recent
Diagnose corrective action using
Lockout Alarm A 0 0
Blocking too long error
Lockout Alarm or Blocking Error.
_ _ _ _ _
appropriate Troubleshooting Tree.
to Control Module J13?
Is harness connected to Gas
Lockout Alarm A 0 5
GV relay error
Valve? Is harness connected
_ P _ _ _
NOYES
Connect harness
YES NO
and Control Module?
Valve. Does each wire have
Disconnect harness from Gas
continuity between Gas Valve
Replace harness
Replace Gas Valve
1.0 and 1.2 kohms?
Disconnect harness from
resistance across J13-3 and
Control Module J13. Measure
J13-4. Is resistance between
YES NO
Module
Replace Control
41
Check all wires, including
Igniter and Flame Sensor
leads. Check for proper and
connected?
board. Are all wires
tight connections to control
YES NO
13 - TROUBLE SHOOTING
Inspect the flue
way along the
sides of the baffle
near the coil for
Clear vent blockage
check for secure fit
Connect all wires and
Remove the gas
train including the
flue transition.
Remove the
burner and
blockages.
Is there any
apparent debris or
inspect.
Any sign of
obstruction of the
flue way?
damage to burner
surface?
YES NO
YES NO
Tree
Valve
Refer to the Gas
Troubleshooting
section
Refer to the Heat
Exchanger cleaning
Is this a new boiler on first
startup?
NO
YES
Is the Gas Shutoff
Valve closed?
propane gas?
YES NO
Is this boiler to run with
YES NO
valves
Open gas shutoff
YESNO
Inspect Vent
System for
blockages.
YES NO
Is the vent system
clear?
Reset the boiler by
pressing the
‘Reset’ button.
When the boiler
tries to ignite, is
`
there a strong,
consistent spark
Disconnect the gas
evident throught
Does the boiler
valve electrical
harness and close
the gas shutoff
valve.
YES NO
the sight glass?
YES NO
ignite and stay
running?
With the ignition
lead connected to
the igniter, hold the
tip near the chassis
ground and attempt
ignition.
Remove the flame
rod and igniter rod
and inspect. Is
Is a spark observed
between the igniter
and ground?
there any
indication of
damage or debris
baked on?
Replace Burner
YES NO
Replace Control
YES NO
rod or igniter
Replace/clean flame
Is the propane gas orifice
Lockout Alarm A 0 1
Ignit error
_ P _ _ _
properly installed?
Install propane
Orifice
Enter the Installer
Menu and place
the boiler into test
mode in high fire.
Once the boiler
starts, go to the
boiler status
screen and
monitor the flame
signal.
Is the flame signal
greater than
8.0uA?
Check vent
YES NO
termination for
of wind effects
proper consideration
42
13 - TROUBLE SHOOTING
NO
operating?
YES
Is Combustion Air Blower
Lockout Alarm A 0 8
Fan error
_ _ _ _ _
NO
Are 3-wire and 4-wire
YES
harnesses connected to
Combustion Air Blower?
Connect harness
Disconnect harness from
NO
Is voltage 120 Vac ± 10%
Control Module J9. Measure
voltage between J9-2 and J9-3.
Air Blower
Replace Combustion
NO
YES
Module
Replace Control
NO
YES
Disconnect 3-wire harness
Measure continuity in each
from Combustion Air Blower.
wire. Continuity in each wire?
Replace harness
Air Blower
Replace Combustion
speed increase?
YES
Disconnect 4-wire harness
from Combustion Air Blower.
Does Combustion Air Blower
43
Replace harness
Disconnect harness from
Control Module J9. Continuity
(yellow, red, white, black)?
in each wire of 4-wire harness
YES NO
Module
Replace Control
13 - TROUBLE SHOOTING
Correct wiring
NO
Module
Replace Control
operating?
YES NO
Is Combustion Air Blower
Lockout Alarm A 1 5
Air SW not open
_ P _ _ _
YES NO
terminals (interchangeable)?
Air Pressure Switch NO and C
Are orange wires connected to
Air Pressure Switch.
Disconnect orange wires from
NO
YES
Combustion Air Blower?
Is 4-wire harness connected to
Connect harness
NO
terminals?
YES
Continuity across NO and C
NO
Disconnect harness from
between J16-2 and J16-3?
Control Module J16. Continuity
Switch
Replace Air Pressure
Replace wire(s)
YES
Replace harness
44
YES
and Control Module J9.
Disconnect 4-wire harness
Continuity in each wire?
from Combustion Air Blower
Air Blower
Replace Combustion
13 - TROUBLE SHOOTING
13-1 Differential Air Pressure Switch
Connect manometer to Air Pressure Switch tubing (see gure 13-2). Follow operating instructions to initiate boiler operation. Refer to Trouble Shooting Tree page 46.
!
DANGER
Test Port
Replace all test port caps. Failure to comply will result in death or serious injury.
Combustion
Analyzer Port
Differential Air Pressure Switch
Vinyl Tubing
Silicone Tubing
Vinyl Tubing
Tee
Vinyl Cap (Typ. 2)
Test Lines
-
+
Inclined Manometer
(Or Differential Pressure Gauge)
13-2 Test Port Locations
Test Port
In-line Pressure
Switch Vapor
Collector
Combustion
Analyzer Test Port
45
13 - TROUBLE SHOOTING
Connect harness
operating?
YES NO
Is Combustion Air Blower
Lockout Alarm A 1 7
Air SW not closed
_ P _ _ _
YES NO
Combustion Air Blower?
Is 3-wire harness connected to
in each wire?
YES NO
Control Module J9. Continuity
Are orange wires connected to
NC and C?
Air Pressure Switch terminals
Disconnect harness from
Disconnect 3-wire harness
from Combustion Air Blower.
NOYES
Connect wires
Replace wires
and J9-3. Is voltage
approximately 120 VAC?
Measure voltage between J9-2
Replace wires
Module
NOYES
Replace Control
Air Blower
Replace Combustion
See page 45
is each wire?
YES NO
Disconnect wires from Air
Pressure Switch. Disconnect
harness from J16. Continuity
46
Remove obstructions
YES NO
Is combustion air and vent
piping free of obstructions?
Connect manometer to Air
Pressure Switch tubing (see
INSTRUCTIONS to initiate
boiler operation. Is pressure
figure). Follow OPERATING
greater than 0.14" wc (35 Pa)?
Air Blower
NOYES
Replace Combustion
Switch
Replace Air Pressure
13 - TROUBLE SHOOTING
Replace Control
Module
2K to 1K ohms
2K to 3K ohms
3K to 9K ohms
°F°C Resistance
50 to 9010 to 32 9K to 24K ohms
Resistance Chart
90 to 130
150 to 200
130 to 150
and Control Module J13.
Temperature Supply Switch
Lockout Alarm A 1 8
Max Temp Error
Disconnect harness from High
_ _ _ _ _
NO
Switch 3?
YES
1? Continuity from J13-6 to
Continuity from J13-5 to Switch
Replace wire(s)
NO
YES
less than 185°F (91°C)?
Is supply water temperature
High Temperature Supply Switch
YES NO
Switch open (no continuity
Is High Temperature Supply
between terminals 1 and 3)?
Switch
Replace High
Temperature Supply
Replace High
Temperature Supply
YES NO
High Temperature Supply
Switch terminals 2 and 4?
Measure resistance across
Does resistance match supply
water temperature (see table)?
Module
32 to 54
Switch
54 to 66
66 to 94
47
Is High Temperature Supply
Switch open (no continuity
between terminals 1 and 3)?
Replace Control
YES NO
Switch
Replace High
Temperature Supply
13 - TROUBLE SHOOTING
clean and secure?
Inspect harness connection
Lockout Alarm A 2 4
3 flame failures
Flame Sensor. Is connection
_ P _ _ _
NO
YES
Replace Flame
Sensor or harness
NO
YES
free of contamination?
Remove Flame Sensor. Is rod
Clean or replace
Follow OPERATING
Flame Sensor
INSTRUCTIONS to initiate
boiler operation. Enter Installer
Menu, Boiler Status, Flame
Signal. Is flame signal greater
NO
than 3.7 uA?
YES
Replace Flame
Sensor and Burner
Module
Replace Control
Blocking Error E 3 5
False flame detect
_ P _ _ _
Module
NOYES
glass. Is flame present?
Inspect burner through sight
Replace Control
Turn Gas Shutoff
Valve clockwise to
closed position.
Follow instructions
TO APPLIANCE.
TO TURN OFF GAS
Replace Gas Valve.
48
13 - TROUBLE SHOOTING
NO
amber lamp lit?
NO
YES
Check Low Water Cutoff.
NO
YES
Is Green Power Lamp lit?
NO
YES
Is Harness plugged into Low Water Cutoff?
Is Black/White Harness plugged into 24 volt harness?
Is Blue/Yellow Harness plugged into 24 Vac Transformer?
Insert Harness
Disconnect Black/White
NO
Disconnect Blue/Yellow
harness from Transformer.
YES
Vac. Is 24 to 30 Vac present?
Using digital meter check for 24
Connect harness to
Harness?
YES
Is 120 Vac measured at
Harness from Transformer.
terminals 1 & 2?
Cutoff. Is 24 Vac at
harness from Low Water
Transformer. Disconnect
YES
Replace Main Harness
Replace Transformer
NO
Blocking Error E 3 6
Low Water Cutoff
_ _ _ _ _
Check Low Water Cutoff. Is
NO
Replace Low Water Cutoff Replace Harness
Insert Harness
Replace Harness
YES
system and refill.
Repair System Piping,
remove any remaining air in
Control Module J16?
Is harness plugged into
Harness OK?
YES NO
continuity if harness.
Low Water Cutoff and
Disconnect harness from
Control Module J16. Check
Replace Low Water Cutoff
49
13 - TROUBLE SHOOTING
Blocking Error E 4 4
_ P _ _ _
Phase error
Measure incoming power with
NOYES
VAC? Is 120 VAC (N)
volt meter. Is terminal 120
approximately 0 VAC?
VAC (L) approximately 120
Module
Replace Control
Correct field wiring
Blocking Error E 4 0
Return Temp
_ _ _ _ _
Is correct harness connected to
return sensor (2 Brown Wires)?
NOYES
Correct wiring
oriented properly?
Is Heat Exchanger Pump
YES NO
(Pump Arrow pointing down?)
Install Heat
proper orientation
Exchanger Pump in
Return Water Sensor.
Disconnect harness from
Measure resistance using
digital ohm meter. Is
resistance between 950 to
Sensor
Replace Return Water
33,000 ohms?
YES NO
Module
Replace Control
50
13 - TROUBLE SHOOTING
+/- 2%
Blocking Error E 4 5
Net frequency error
_ P _ _ _
and 61 Hz?
Is power supply between 59
NO
YES
stabilized power
Provide frequency
supply rated at 60 Hz
breaker
NO
Replace circuit
loose or faulty?
YES
Is power supply circuit breaker
NO
YES
Is field wiring loose or faulty?
Module
Replace Control
Correct wiring
51
13 - TROUBLE SHOOTING
Blocking Error E 5 1
Supply Sens Open
_ P _ _ _
NOYES
Module J5?
Water Sensor?
Is harness plugged into Supply
Is harness plugged into Control
Insert Harness
Disconnect J5 from Control
Module. Using digital meter
measure check continuity of
and Sensor. Continuity?
brown wires between Control
YES NO
Replace Wires
Using digital meter measure
resistance between Supply
of Sensor with digital meter.
Water Sensor terminals J5-11
and J5-3. Measure resistance
Estimate Sensor temperature.
Does it fall in the range of the
Resistance Chart?
YES NO
Water Sensor
Replace Supply
Module
Blocking Error E 4 6
Faulty ground
_ P _ _ _
conductor
Connect ground
YES NO
connected to High Voltage
Is field grounding conductor
Terminal Strip 120 VAC (G)?
Disconnect field wiring. Is
continuity between field wiring
Replace Control
conductor
NOYES
Correct faulty ground
10 ohms?
neutral and ground less than
Module
Replace Control
°F°C Resistance
Resistance Chart
Supply Water Sensor
3K to 9K ohms
50 to 9010 to 32 9K to 24K ohms
90 to 130
32 to 54
2K to 1K ohms
2K to 3K ohms
150 to 200
130 to 150
54 to 66
66 to 94
52
13 - TROUBLE SHOOTING
2K to 1K ohms
2K to 3K ohms
3K to 9K ohms
°F°C Resistance
50 to 9010 to 32 9K to 24K ohms
Resistance Chart
Return Temperature Sensor
90 to 130
32 to 54
150 to 200
130 to 150
54 to 66
66 to 94
Blocking Error E 5 2
Return Sens Open
_ P _ _ _
Module J5?
Temperature Sensor?
Is harness plugged into Return
Is harness plugged into Control
YES NO
Insert Harness
Continuity?
wires between Return
Temperature Sensor and
Check continuity of brown
Control Module J5-4 and J5-12
YES NO
Replace Wires
meter. Estimate Sensor
Measure Return Temperature
Sensor resistance with digital
temperature. Do temperature
ranges shown in chart?
and resistance fall within
Replace Return
Temperature Sensor
YES NO
Module
Replace Control
53
13 - TROUBLE SHOOTING
Replace wires
Switch 4?
High Temperature Supply
Blocking Error E 5 9
Supply Sensor Shorted
Disconnect wire harness from
_ P _ _ _
Switch. Measure resistance
across terminals 2 and 4. Do
NOYES
within ranges shown in chart?
temperature and resistance fall
Insert harness
J5-11 and Switch 2?
Disconnect J5 from Control
Module. Continuity between
Switch
Replace High
Temperature Supply
YES NO
Continuity between J5-3 and
Module
Replace Control
Resistance Chart
High Temperature Supply Switch
°F°C Resistance
3K to 9K ohms
50 to 9010 to 32 9K to 24K ohms
90 to 130
32 to 54
2K to 1K ohms
2K to 3K ohms
150 to 200
130 to 150
54 to 66
66 to 94
Blocking Error E 5 7
Flue sens open
_ P _ _ _
Is harness plugged into Vent
Temperature Sensor? Is
harness plugged into Control
NOYES
Module J5?
Replace wires
for each blue wire?
Temperature Sensor and
Disconnect harness from Vent
YES NO
Control Module J5. Continuity
Vent Temperature Sensor
Measure resistance across
54
match estimated flue
terminals. Does resistance
temperature (see table)?
YES NO
Replace Vent
Temperature Sensor
Module
Replace Control
Blocking Error E 6 5
Flue Sens Shorted
_ P _ _ _
13 - TROUBLE SHOOTING
NOYES
Does resistance match
Vent Temperature Sensor.
Measure Sensor resistance.
Disconnect wire harness from
estimated flue temperature?
Replace Vent
Temperature Sensor
in blue wires?
Disconnect harness from
Control Module J5. Continuity
YES NO
Replace wires
Module
°F°C Resistance
Resistance Chart
Vent Temperature Sensor
3K to 9K ohms
50 to 9010 to 32 9K to 24K ohms
90 to 130
32 to 54
2K to 1K ohms
2K to 3K ohms
150 to 200
130 to 150
54 to 66
66 to 94
Disconnect harness from
Blocking Error E 6 0
Return sens shorted
_ P _ _ _
Disconnect harness from
Control Module J5. Measure
less than 50 ohms?
YES NO
Measure resistance across
Return Temperature Sensor.
sensor terminals. Is resistance
Sensor
resistance between brown
wires at terminals J5-4 and J5-
Replace Control
NOYES
ohms?
12. Is resistance less than 50
Module
Replace Control
Replace wires
Replace Return Water
55
14.1 Connection Diagram
14 - WIRING DIAGRAM
56
14 - WIRING DIAGRAM
14.2 Schematic Diagram of Ladder Form
57
15 - GLOSSARY
ANSI - American National Standards Institute, Inc. oversees creation and maintenance of voluntary consensus standards, including ANSI Z21.13/CSA 4.9:
Gas-Fired Low Pressure Steam and Hot Water Boilers. ASTM - American Society for Testing and Materials.
ASTM International is one of largest voluntary standards development organizations in world trusted source for technical standards for materials, products, systems, and services. Known for their high technical quality and market relevancy, ASTM International standards have important role in information infrastructure that guides design, manufacturing and trade in the global economy.
AUTHORITY HAVING JURISDICTION - Individual or organization adopting and enforcing codes, rules, and by-laws governing various concerns of community. Commonly referred to as "fi nal authority" for any matters relating to LIFE SAFETY and BUILDING CONSTRUCTION
within a community. Btu - Abbreviation for British Thermal Unit. Quantity
of heat required to raise temperature of 1 pound of water1°F.
BURNER - Device for fi nal conveyance of gas or mixture of gas and air, to combustion zone.
COMBUSTION - Rapid oxidation of fuel gases accompanied by production of heat or heat and light. Complete combustion of fuel is possible only in presence of adequate supply of
Oxygen.
GAS PIPE SIZES
NATURAL GAS
Length of Pipe
- Ft.
20 92,000 190,000 350,000 625,000 40 63,000 130,000 245,000 445,000 60 50,000 105,000 195,000 365,000
Length of Pipe
- Ft.
20 131,000 216,000 189,000 393,000 40 90,000 145,000 129,000 267,000 60 72,000 121,000 103,000 217,000
Pipe Capacity - BTU Per Hour Input Includes Fittings
1/2” 3/4” 1” 1 1/4”
PROPANE GAS
Pipe Capacity - BTU Per Hour Input Includes Fittings
Copper Tubing
(Outside Diameter)
5/8” 3/4” 1/2” 3/4”
Iron Pipe
HIGH-VOLTAGE - Circuit involving potential of not more than 600 volts and having circuit characteristics in excess
of those of low-voltage circuit. IGNITER - Device utilizing electrical energy to ignite gas
at main burner. LEAK CHECK - Operation performed on gas piping system
to verify system does not leak. LOW WATER CUTOFF - Device constructed to automatically
cut off fuel supply when surface of water in boiler falls to lowest safe water level.
LOW-VOLTAGE - Circuit involving potential of not more than 30 volts.
COMBUSTIBLE MATERIAL - Materials made of or surfaced with wood, compressed paper, plant fi bers, or other materials capable of being ignited and burned. Such material shall be considered combustible even though
ame-proofed, fi re-retardant treated, or plastered. CONDENSATE - Liquid separated from fl ue gas due to
reduction in temperature.
For example: Gas Meter measures 0.1 cubic Meters in 100 seconds
DIRECT VENT BOILER - Boiler constructed and installed so all combustion air is derived directly from outdoors
and all vent gases are discharged to outdoors. DRAFT - Pressure difference causes gases or air to fl ow
through a chimney, vent , fl ue or appliance.
FLA - Full load amps. FLUE GASES - Products of combustion plus excess air in
appliance fl ues or heat exchanger.
METRIC GAS METERS
127,116 x cu meters
MBH
MBH
=
Seconds
127,116 x 0.1
=
100
= 127 MBH
PRESSURE TEST - Operation performed to verify gas tight integrity of gas piping following its installation or modifi cation.
PURGE - To free gas conduit of air or gas, or mixture of gas and air.
PURGE TIME - Period of time intended to allow for dissipation of any unburned gas or residual products of
combustion.
58
15 - GLOSSARY
QUALIFIED AGENCY - Any individual, fi rm, corporation, or company engaged in and responsible for:
Installation, testing, or replacement of gas piping, • or connection, installation, testing, repair or servicing of appliances and equipment.
Experienced in such work.• Familiar with all precautions required.• Complies with all requirements of authority having
jurisdiction.
SAFETY RELIEF VALVE - Valve designed to relieve pressure in hot water supply system when pressure
exceeds pressure capability of equipment. SAFETY SHUTOFF DEVICE - Device that will shut off gas
supply to controlled burner in event source of ignition fails.
SEDIMENT TRAP - Gas piping arrangement designed to collect any liquid or solid contaminant before reaching gas valve.
VENT - Passageway used to convey fl ue gases from appliance vent connector to outdoors.
VENTING SYSTEM - Continuous open passageway from of appliance vent connector to outdoors for purpose of removing fl ue or vent gases.
59
APPENDIX A - CONTROL MODULE
Op
l
e
1.1 Introduction
Boiler is equipped with programmable electronic control and user interface module.
1.2 Operation
Display: 4x20 character LCD screen to show boiler • status.
Function Keys
Key Description
- Manual Lockout Reset
- Enter/Exit user menu
- Go to previous screen
- Select a menu item
- Confi rm new parameter value
- Scroll up to next menu item
- Increase value
- Scroll down to next menu item
- Decrease value
Operation with LCD character display module
eration with LCD character display modu
1.3 Status Indication
The following status screens can be displayed:
Boiler Status Indicator
F = Flame Detected
SERVICE Reminder
P = Central Heating System pump On B = Combustion Air Blower On S = Safety Relay Check G = Gas Valve Open D = DHW Pump On
Combustion Air Blower Speed Indicator
Service Reminder Indica Boiler in Standby Mode
Boiler Supply Water Temperature Indicator.
tor
Boiler Running in Central Heat mode
Boiler Running in DHW mode
Lockout Alarm Indicator
Error code and short text de­scription is displayed Press 'Reset" key for manual reset.
Blocking Error in DHW
Error code and short text description is displayed Boiler automatically returns to Standby Mode when condition is eliminated.
60
1.4 Sequence of Operation
Operational State User Interface Display Explanation
APPENDIX A - CONTROL MODULE
No
Heat
Demand?
Yes
DHW CH
Pump on
Supply
Temperature
<Setpoint?
Yes
Air Pressure
Switch Open?
No
No
Lockout
Error
A15
Standby: No Demand
Boiler operates in standby mode until demand for Central Heat (CH) or Domestic Hot Water (DHW) is detected.
CH or DHW pump is turned based on type of heating demand.
(CH call is illustrated)
Control Module compares supply temperature to set point. Boiler proceeds to ignition if supply temperature is less than set point.
Air Pressure Switch is checked for open circuit before energizing Combustion Air Blower
Closed Air Pressure Switch during this stage will result in Lockout Error.
Yes
Combustion
Air Blower
On
Air Pressure
Switch
Closed?
Yes
15 Second
Prepurge
Ignition
Sparking
After 2 seconds
No
After
3
Trials
Lockout
Error
A17
Combustion Air Blower is energized to prove fl ow though Combustion and Vent Systems.
Air Pressure Switch is checked for closed circuit.
Open Air Pressure Switch during this stage will result in Lockout Error after 3 trials.
Combustion Air Blower speed modulates to prepurge setting for 15 seconds.
Sparking initiated sequence.
61
1.4 Sequence of Operation
Operational State User Interface Display Explanation
After 2 seconds
Flame
Detected?
No
Gas Valve Energized
Yes
Lockout
Error A21
5 Ignition
Lockout A01
APPENDIX A - CONTROL MODULE
If fl ame detected before Gas Valve opens during ignition boiler will lockout.
Please refer to troubleshooting guide.
Note:
trials,
then
Gas Valve energized to deliver air/fuel to burner.
After 3 seconds
Flame
Detected?
Yes
Heat Demand
Met?
No
No
Simultaneous
DHW + CH
Demand?
Yes
DHW
Priority
Mode
No
See Max DHW
Priority Time
30 second
post purge
Yes
Setting
If fl ame undetected after 3 seconds boiler will de-energize Gas Valve and enter post purge mode for 30 seconds.
Ignition attempted 5 times before lockout.
Boiler will run provided all operational and safety devices are within limits
Refer to for more information. Control module adjusts fi ring rate
according to heating demand. When Boiler detects demand met, will enter post purge mode then standby mode.
If simultaneous demand for Central Heat and DHW, boiler will enter DHW Priority Mode.
Priority mode limits amount of time boiler can run in DHW mode to meet CH demand.
Max DHW Priority Time setting deter­mines maximum time allowed for DHW heating mode.
Please refer to section Appendix A section
1.5 for more information.
62
1.5 Theory of Operation
MENU
Bo i l e r S t a t us
Se t t i ngs
Cascade St a tus
BO I L ER STAT US
Supp l y 14 0 °F
Re t u r n 12 0 ° F
DHW S t a t Op e n
BO I L ER STAT US
Sys t em N.C .
Flue 132°F
Ou t doo r 36 ° F
BO I L ER STAT US
Bo i l e r Pump O f f
CH / Sy s t em P ump O f f
DHW P ump O f f
BO I L ER STAT US
Cur r en t Supp l y
Set point 160 ° F
St andby : No Dema n d
75° F
APPENDIX A - CONTROL MODULE
STANDBY
User Menu
User Menu
User Interface Display
Explanation
Boiler operates in standby mode until demand for Central Heat (CH) or Domestic Hot Water (DHW) is detected.
User Menu can be accessed by pressing ‘Menu’ key on user interface.
Installer Menu can be accessed by simultaneously holding ‘Menu’ and ‘Enter’ keys for 5 seconds.
User Menu structure includes:
‘Boiler Status’ submenu– User can monitor general boiler • status parameters such as sensor temperatures and pump operation.
‘Settings’ submenu – User can view CH , adjust DHW • supply water set points and also select control language.
‘Cascade Status’ submenu – Boiler set to function as • part of multiple boiler installation; submenu used to view runtime parameters. See Multiple Boiler Manual.
Boiler Status
Supply Temperature set point displayed. If boiler running in CH mode, CH set point displayed. Note:
While running in Outdoor Reset mode, this value may • change in proportion with the outdoor temperature.
If the boiler is running in DHW mode, the DHW supply set • point is displayed.
Several boiler runtime parameters can be viewed while in ‘Boiler Status’ submenu.
Operational status of pump system also shown. Information available during all states of boiler operation.
Sensor values with troubleshooting tree used to diagnose typical problems.
63
SETT I NGS
Cen t r a l He a t i ng
Se t po i n t
°F
SETT I NGS
DHW S e t p o i n t
°F
SETT I NGS
Cha nge
Tempera t ure Un i t s
Fahrenhe i t ° F
SETT I NGS
Cha nge
Language
Eng l i sh
APPENDIX A - CONTROL MODULE
User Interface Display
Setting Range: 104° F to 195° F (40° C to 91° C) Default Value: 140° F (60° C)
Settings
Explanation
Adjust CH set point to hydronic system design while in Operating in CH Mode = 0 (CH with Thermostat) or 3 (Perma­nent Demand).
In CH Mode = 1 (CH with Thermostat and Outdoor Reset) or 2 (CH with Full Outdoor Reset). Display will change to ‘OD Reset Setpoint’ and cannot be changed. Controller calculates set point based on outdoor temperature.
Note:
For explanation of available CH heating modes, refer to
‘CH Mode’ section located in ‘CH Settings’ submenu.
DHW set point determines supply water temperature set point while operating in DHW mode.
Setting Range: 104° F to 195° F (40° C to 91° C) Default Value: 180° F (82° C)
User interface temperature unit of measure is selected using ‘Change Temperature Units’ screen.
Fahrenheit and Celsius available.
Select user interface language using ‘Change Language’ screen. English and French are available.
64
INSTALLER MENU
Bo i l e r S t a t us
Bo i l e r Con f i g
CH Se t t i ng s
DHW S e t t i n g s
Cascade Set t i ngs
System Test
STA T U S
Fa n S p e ed
Ac t u a l 4000RPM
L ow P owe r 1560RPM
STA T U S
Fa n S p e ed
I g n i t i on 3500RPM
H i P ower 5725RPM
STA T U S
Fl ame
Signa l 07.2uA
Fa i l ures 2
APPENDIX A - CONTROL MODULE
User Interface Display
Installer Menu
Installer Menu
Explanation
The Installer Menu structure includes:
‘Boiler Status’ submenu – User monitors detailed boiler • status parameters such as fl ame signal, fan speeds and stored error codes.
‘Boiler Confi g’ submenu – Modifi es general boiler settings.
‘CH Settings’ submenu – Modifi es advanced Central Heating settings including outdoor reset curve parameters and boost function.
‘DHW Settings’ – Modifi es Domestic hot Water control settings such as DHW priority time.
‘Cascade Settings’ - Refer to Multiple Boiler Manual.
‘System Test’ – Tool aids setup of boiler installation or • diagnosis of common problems.
Boiler Status
Combustion air Blower provides airfl ow through Combustion and Vent systems.
Fan speed status screen indicates actual and operational fan speeds in RPM, high, low and ignition power speed settings.
Settings are for information only to aid in troubleshooting.
Boiler equipped with ionization rod to detect presence of combustion using fl ame rectifi cation method. When fl ame is present, fl ame ionization rod measures small DC offset current across fl ame to ground (i.e. burner surface).
‘Flame’ screen in ‘Boiler Status’ submenu displays information regarding fl ame ionization system; for information only and used in diagnosing combustion problems. See troubleshooting guide.
65
APPENDIX A - CONTROL MODULE
STA T U S
Ign i t i on At tempts
Su c c e s ful 4267
Fa i led 21
User Interface Display
Installer Menu
Explanation
Control module logs successful and failed ignition attempts. Information accessed in ‘Ignition Attempts’ Screen as shown.
Ignition attempts are stored in non-volatile memory and are retained in event of power failure.
Figure A-1 Typical Ignition Cycle
Boiler Status
Following control features are implemented to ensure safe and reliable operation of Combustion System:
False Flame Detection
Re-ignition
Intermittent Operation
Flame out too late
Safety relay test
UL3563 High Limit Tempera­ture Device
If fl ame is detected at end of pre-spark period (Ignit_0) than lockout will occur.
If at end of safety period no fl ame detected control will go to post-purge removing unburned gas. Re-ignition attempt started following same cycle. Number of re-ignition attempts limited to 4 after which lockout occurs.
Boiler can be fi ring continuously for 24 hours. Burner switched off and restart sequence follows.
If fl ame detected after post purge lockout follows.
In Safety ON/OFF state correct operation of safety relay is proved before ignition.
Boiler comes equipped with UL353 approved temperature high limit device.
Gas Valve de-energized when supply temperature exceeds 203°F lockout follows.
66
STA T U S
Bo i l e r Run T ime
CH 320HR
DHW 145HR
STA T U S # E3 9
2H r s t o prev . Block
Low Water Cutoff
STA T U S #A01
13H r s t o prev . Lock
Igni t ion Error
BO I L E R C ONF I G
Add r e s s Se l e c t i o n :
Bo i l e r Address: 0
BO I L E R C ONF I G
LOW WA T ER CUTOFF
Disabled
APPENDIX A - CONTROL MODULE
User Interface Display
Boiler Status
Explanation
Boiler stores information regarding total CH and DHW run time in hours.
Data stored in non-volatile memory and retained in event of power failure.
Boiler logs last 16 blocking errors and 16 lockout errors in non-volatile memory. Information retained in event of power failure.
Most recent blocking error code and its text description displayed with elapsed time in hours since logged.
Optional Computer interface Kit purchased separately to view extended error code history
‘Address Selection” screen used to set boiler position in multiple boiler cascade installation. Refer to Multiple Boiler Installation Manual.
Default setting of ‘0’ indicates boiler is operating in single boiler mode.
Boiler Confi guration
Boiler incorporates integrated Low Water Cutoff device (LWCO) that disables boiler when low water condition exists. LWCO device located at high point of internal Heat Exchanger loop to detect low water condition.
Detection of low water condition will result in blocking error; boiler will automatically resume normal operation when proper water level returns. Refer to Troubleshooting Guide.
LWCO device can be disabled for diagnostic purposes or where applicable code permits.
67
BO I L E R C ONF I G
Pump Mo de MODE : 0
CH o r C H&DHW
BO I L E R C ONF I G
SE R V I C E REMI NDER
Sta tus On
R em i n d er 365 days
APPENDIX A - CONTROL MODULE
User Interface Display
Explanation
Two pump modes are available:
Pump Mode = 0 ‘CH or CH&DHW’
1.
In this mode either the CH or DHW pump terminal is • energized depending on the type of demand (CH or DHW).
CH and DHW pumps are never energized at the same time.
In the case of a simultaneous call for both CH and DHW, • the energized pump depends on whether the boiler is currently supplying the CH or DHW demand. Refer to DHW Priority settings below.
This is typical of a hydronic system design with separate CH • and DHW Pumps.
Pump Mode = 4 ‘System Pump’
2.
In this mode only one external system pump is installed in • the hydronic system. This pump will energize independent of the type of demand (CH or DHW).
Boiler Confi guration
Connect this pump to the CH/System Pump electrical • terminal block. See page 56 for diagram.
The DHW pump terminal does not function.
This is typical of a hydronic system design which utilizes • zone valves for all CH zones and an DHW indirect tank.
Note:
Pump Mode selection depends on electrical and • hydronic system design. Please refer to sections 5 and 8 for recommended hydronic piping and electrical confi gurations.
Internal heat exchanger pump is energized anytime • demand exists regardless of Pump Mode setting or type of demand (CH or DHW).
'Service Reminder’ feature allows the installer to enable or disable a service reminder notifi cation on the User Interface at a predefi ned interval .
Service reminder does not affect operation of boiler in any way. It is only a reminder to End User that routine preventative maintenance is required by qualifi ed service technician.
Allowed Range: 1 to 999 days
68
CH SETT I NGS
CH mo d e MODE:1
CH w i t h thermosta t
APPENDIX A - CONTROL MODULE
User Interface Display
CH Settings
Explanation
4. Central Heating (CH) modes available:
CH Mode = 0 ‘CH with Thermostat’
Boiler will attempt to satisfy CH demand while CH • thermostat input is closed.
Boiler will modulate its fi ring rate to maintain CH set point and match system heat load.
CH set point adjusted in ‘Settings’ submenu under ‘User • Menu’
CH Mode = 1 ‘CH with Thermostat and Outdoor Reset’
Boiler will attempt to satisfy CH demand when CH • thermostat input is closed. Boiler will modulate its fi ring rate to maintain CH set point and match system heat load. CH set point calculated as function of outdoor
temperature using outdoor reset curve. See Figure A-2
• CH Mode = 2 ‘CH with Full Outdoor Reset’
Boiler will permanently attempt to satisfy CH • demand.
CH thermostat input is ignored.• CH set point calculated as function of outdoor • temperature using outdoor reset curve. See Figure A-2
CH Mode = 3 ‘CH with Permanent Demand’
Boiler will permanently attempt to satisfy CH • demand.
CH thermostat input is ignored.• CH set point is adjusted in ‘Settings’ submenu under • ‘User Menu’
Note:
• Once CH demand is satisfi ed (i.e. CH thermostat opens or boiler determines its minimum fi ring rate exceeds system heating load):
Burner shuts off, boiler enters post purge.• CH pump continues to run for 30 seconds.• Control will wait until Anti-cycle time of 180 seconds
elapses before boiler fi res again. Prevents short- cycling.
• The internal heat exchanger pump is energized anytime demand exists regardless of Pump Mode setting or type of demand (CH or DHW).
69
CH SETT I NGS
Wa rm We at her
Shut down Temp
70°F
CH SETT I NGS
Reset Curve Design
Bo i l e r 180°F
Ou t d o o r 25 °F
CH SETT I NGS
R.Curve Mild Weath.
Bo i l e r 70°F
Ou t d o o r 70 °F
CH SETT INGS
Rese t Curve
Bo i l e r Mi n 070 °F
Bo i l e r Max 180°F
APPENDIX A - CONTROL MODULE
User Interface Display
Allowed Range: 35°F to 100°F (2°C to 38°C) Default Setting: 70°F (21°C)
A
Allowed Boiler Range: 60°F to 195°F (40° C to 91°C)
Default Boiler Setting:180° F (82°C)
B
Allowed Boiler Range: 35°F to 120 F (2°C to 49°C) Default Boiler Setting: 70°F (21°C)
Allowed Outdoor Range: 35°F to 85°F (2°C to 29°C) Default Outdoor Setting: 70°F (21°C)
CH Settings
Explanation
If outdoor temperature is greater than Warm Weather Shutdown Temperature, demand for CH blocked and pumps stopped.
Boiler capable of operating in Outdoor Reset Mode when included Outdoor Sensor is connected and proper CH Mode selected.
If CH Mode = 1, ‘Outdoor Temperature Reset with Thermo­stat’ or 2, ‘Full Outdoor Reset’ boiler will adjust CH set point proportional to outdoor temperature as defi ned by Outdoor Reset Curve below.
Outdoor reset curve adjusted by modifying Design and Mild Weather reference temperatures. See points A & B of Reset Curve below.
Calculated CH set point always limited between ‘Reset Curve Boiler Minimum/Maximum’ temperatures. See points C & D of Reset Curve below.
Figure A-2 Outdoor Reset Curve
A
D
Allowed Min. Range: 40°F to 180°F (4°C to 82°C) Default Min. Setting: 70°F (21°C)
Allowed Max. Range: 80°F to 195°F (27°C to 91° C) Default Max. Setting: 180°F (82°C)
C
D
B
C
Note:
Modes only function when outdoor temperature sensor • connected.
If ‘Open’ outdoor sensor detected CH set point equal to • ‘Boiler Reset Curve Design’ temperature.
Outdoor temperature used for CH set point calculation • measured once a minute and averaged with previous measurement to compensate for rapid outdoor temperature variations.
70
CH SETT I NGS
Boos t F unct ion
Temp 10°F
Time 20min
CH SETT I NGS
Max imum Power CH
Ma x 100%
DHW S E T T I NGS
DHW m o d e MODE : 1
DHW s t o r e w i t h
se n s o r
APPENDIX A - CONTROL MODULE
User Interface Display
CH Settings
Explanation
Outdoor reset boost function increases CH set point by increment (‘Temp’) if CH demand continues beyond pre-set time limit (‘Time’).
CH set point will continue to increase until set point reaches 195°F / 91°C
Allowable Temperature Increment: 0..36 °F (0..20 °C) Default Temperature increment: 18 °F (10 °C)
Allowable Time Delay: 1..120 minutes Default Time Delay: 20 minutes
Maximum boiler power in CH mode limited by adjusting ‘Maximum Power CH’ setting. Boiler will not exceed this value while operating in CH Mode.
Allowable Range: 1..100% Default Setting: 100%
Two DHW modes are available
DHW Mode = 0 ‘No DHW
DHW Mode is disabled• The DHW thermostat input is ignored and the DHW
pump is not used.
DHW Settings
DHW Mode = 2 ‘DHW Store with Thermostat’ Boiler reacts to DHW demand when DHW thermostat
input closes. Boiler modulates to meet DHW demand similar to CH
Mode except DHW set point is used. DHW set point set in Settings’ submenu found in 'User Menu’.
Simultaneous CH & DHW demands handled using DHW • Priority Timing. See ‘DHW Maximum Priority Time’ setting below.
Note:
Outdoor reset function disabled while operating in DHW • Mode. Typical when using a DHW indirect storage tank.• After DHW demand satisfi ed, boiler enters post purge
mode and DHW pump continues to run for 15 seconds.
71
DHW S E T T I NGS
DH W m a x . p r i o r i t y
time
30min
SYSTEM TEST
Set t e s t power
Of f
SYSTEM TEST
Bo i l e r Pump Of f
CH \ Sy s t em Pump Of f
DHW P ump Of f
APPENDIX A - CONTROL MODULE
User Interface Display
Allowed Range: 1 to 60 Minutes
DHW Settings
Default Setting: 30 Minutes
Explanation
Maximum time boiler operates in DHW mode limited by DHW Maximum Priority Time Setting.
Priority timer starts when both CH and DHW demand is present. Boiler will switch from DHW back to CH operation after Maximum Priority Time has elapsed.
CH demand then has priority until Maximum Priority Time has elapsed.
Process repeats until either CH or DHW demand satisfi ed.
System test can be activated via installer menu for testing system at fi xed power rates.
Boiler can be started without CH or DHW demand being present. System Test has priority over any system demand while test mode activated.
System test mode automatically ends after 30 minutes boiler resumes normal operation.
The following modes are available:
System Test
Disabled• Low power - Burner starts. After ignition period has
nished the burner stays at low power Ignition power - Burner starts. Stays at ignition power• High power - Burner starts. After ignition period has nished burner stays at high power.
Note:
!
WARNING
Before running system test modes, check if hydronic • system capable of dissipating heat.
Both heat exchanger and CH pumps are activated • during system test only.
During System Test Mode, boiler will run at fi xed power rates until supply water temperature is 93°C/195°F
All other safety functions remain active while in • System Test Mode.
72
73
74
75
CONDENSING
GAS BOILER
ECR International, Inc. 2201 Dwyer Ave. Utica, NY 13501
www.ecrinternational.com
Loading...