ECR R25C, R25H Installation, Operation & Maintenance Manual

Page 1
TM
R25C/H
Packaged Terminal Air Conditioner (PTAC)
Packaged Terminal Heat Pump (PTHP)
Installation, Operation &
Maintenance Manual
Replacements for:
R25C - Climate Master/Friedrich ET,
Ice Cap RSet,
ECR International, Inc.
2201 Dwyer Avenue • Utica, New York 13501 Ph: 800.325.5279 • Web: retroaire.com
P/N 240010639 Rev. A [06/15/2014]
Page 2
TABLE OF CONTENTS
Receiving Information .....................................................................................................3
Important Safety Information ...........................................................................................4
R40C - Dimensional/Physical Data ....................................................................................5
Dimensional/Physical Data ............................................................................................... 6
General Product Information ............................................................................................7
Features ........................................................................................................................ 8
Installation Preparation ................................................................................................. 10
Installation .................................................................................................................. 11
Sequence of Operation .................................................................................................. 14
Final Inspection & Start-up ............................................................................................ 17
Maintenance ................................................................................................................ 24
Troubleshooting ............................................................................................................ 26
Performance Data ......................................................................................................... 27
Electrical Specications ................................................................................................. 28
AHRI Certied ™ is a
trademark of the Air-
Conditioning, Heating
and Refrigeration
Institute. These units are tested and rated in accordance with: AHRI
Standards 310/380
Information and specications outlined in this manual in effect at the
time of printing of this manual. ECR International reserves the right to
discontinue, change specications or system design at any time without
notice and without incurring any obligation, whatsoever.
The Right Fit for Comfort 2
UL-484
P/N 240010639, Rev. A [06/15/2014]
Page 3
RECEIVING INFORMATION
Shipping damage MUST be reported to the carrier IMMEDIATELY.
Examine exterior.
Remove cover and examine compressor and piping for signs of damage.
Inspection
Check shipment against bill of lading.
Verify equipment received as ordered.
Verify unit:
• Unit size and type correct per submittal sheet and job requirements?
Louver color correct, if special color specied?
• Voltage correct?
• Electric heat correct capacity, if used?
Inspect each component for damage. Concealed damage must be reported to carrier within 15 days of receipt of shipment.
Carrier must make proper notation on delivery
receipt of all damage identied and complete carrier
inspection report.
Purchaser must notify Manufacturer’s Service
department of all damage and is responsible for ling
any necessary claims with carrier.
General Information
Installation shall be completed by qualied agency.
this manual for future reference.
Installer, review this manual to verify unit has been installed correctly. Run unit for one complete cycle to verify proper function.
To obtain technical service or warranty assistance during or after installation, contact your local representative.
When calling for assistance, please have following information ready:
Model Number_________________________
Serial Number_________________________
Date of installation______________________
Retain
Customer Service : (800) 228-9364
3 Made in USA
P/N 240010639, Rev. A [06/15/2014]
Page 4
IMPORTANT SAFETY INFORMATION
All eld wiring shall conform to requirements of authority
having jurisdiction or in absence of such requirements:
• United States - National Electrical Code, ANSI/NFPA 70
• Canada - CSA C22.1 Canadian Electrical Code Part 1.
!
WARNING
Fire, and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
Become Familiar With Symbols Identifying Potential Hazards.
!
DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or serious injury.
!
WARNING
Tampering with PTAC/PTHP is dangerous and could result in death or serious injury. Do not modify or change this unit.
Safety Information
Installation by qualied personnel.
• Turn off electrical supply before servicing unit.
• Inspect all parts for damage prior to installation and start-up.
• Do not use unit if it has damaged wiring, is not working properly, or has been damaged or dropped.
• Connect to properly grounded electrical supply with proper voltage as stated on rating plate.
• Have proper over current protection (i.e. time delay fuse/HACR Breaker) as listed on Rating Plate.
• Connect unit to properly grounded electrical supply. Do not fail to properly ground this unit.
!
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates information which should be followed to ensure proper installation and operation.
The Right Fit for Comfort 4
P/N 240010639, Rev. A [06/15/2014]
Page 5
R25C - DIMENSIONAL/PHYSICAL DATA
Figure 1 R25C/R25H Dimensions - Inches (mm)
[523mm]
20.57in
[253mm]
9.96in
[381mm]
15.00in
[51mm]
2.00in
[485mm]
19.08in
[23mm]
.90in
[484mm]
19.06in
[65mm]
2.54in
[143mm]
5.63in
[692mm]
27.25in
5 Made in USA
P/N 240010639, Rev. A [06/15/2014]
Page 6
Figure 2 R25C/R25H Chassis
To use this format set your tiff output to
Print capture, 150dpi, C -Landscape, Scale to fit
for best results
Fresh Air Switch (FAS)
DIMENSIONAL/PHYSICAL DATA
Fan Speed
Switch (FSS)
Fan
Thermostat
Speed
Switch (FSS)
R25 Control
Unit
5 Position Terminal Block
Fan Cycle Switch (FCS)
R25 Base Unit
High Pressure Switch (HPS)
Line Cord
OPTIONAL: Hydronic NO/ NC Switch Valve
Orientation
Switch (VOS)
The Right Fit for Comfort 6
P/N 240010639, Rev. A [06/15/2014]
Page 7
GENERAL PRODUCT INFORMATION
Product Description
• Available in straight cooling (PTAC) or heat pump systems (PTHP).
• Heat pumps (PTHP) reduce energy costs and operate in mechanical heat mode down to outdoor temperature of 40°F (4.4°C). Below 40°F (4.4°C) heating is accomplished by an auxiliary heat option.
• Use R-410A refrigerant.
Include high-efciency rotary compressors, protected by a 5-year warranty.
Include enhanced high-efciency heat exchangers.
• Offer two fan speeds.
• Incorporate positive condensate re-evaporation to
improve efciency.
• Have optional motorized fresh-air feature with positive pressure seal.
• PTAC/PTHP units are available in nominal sizes of 9,000 Btuh, (2.6kW) 12,000 Btuh (3.5kW) or 15,000 Btuh (4.4kW).
• PTAC units (straight cooling only) are also available at 18,000 Btuh (5.3kW).
Energy Efciency Rating (EER) as high as 9.
Coefcient of performance (COP) ratings as high as
2.70 for heat pumps.
Standard Controls And Components
Construction
• 20-gauge galvanized steel construction of chassis.
Condenser bafe options to accommodate extended wall sleeve applications.
• Powder-coated condenser and evaporator drain pan.
• Foam strip seal for supply air duct.
• Weather strip insulation.
Air Systems
• Thermally-protected PSC type motors.
Air-stream surfaces insulated with 1/4" ber-glass or
1/8" (3.2 mm) Volara™.
• Forward-curved type indoor fan, directly mounted to motor shaft.
Unit mount controls include eld selection switch to control indoor fan by cycling with compressor operation or continuously with the unit.
Condensate Removal
• Outdoor fan incorporates condensate slinger ring. Condensate is thrown onto coil, where it evaporates, improving system performance.
• Thermostatic drain pan valve for condensate elimination when outdoor temperature drops below 60°F (15°C), heat pump units only.
– Controls
• Unit-mounted operating controls include thermostat, fan speed control, heat/cool switch, fan cycle switch, fresh air switch, if equipped.
7 Made in USA
P/N 240010639, Rev. A [06/15/2014]
• Ability to utilize 1-stage or 2-stage thermostat. 2 stage thermostat is capable of activating emergency heat if auxiliary heat source is available.
• Low ambient protection — see "Microprocessor control board" for details.
• Ability to control normally-open or normally-closed motor valve switch, available on hydronic heat units only. Order valve controls for 24V or line voltage.
• All hydronic heat units include molex plugs for connection of hydronic valve motor.
• Remote mount controls include fan speed control and fresh air switch, if equipped.
• All units are equipped with manual reset high pressure switch which prevents abnormal high pressure operation, increasing compressor reliability.
– Microprocessor Control Board
• Universal control board is used in straight cooling, electric resistance heat, hydronic heat, or cooling/ heat pump applications.
• Random start timer prevents multiple units from simultaneous startups after power interruption or on initial power-up.
• Fan purge — fan remains on for 60 seconds after
heat/cool is satised.
• Anti-short-cycle compressor protection prevents the compressor from rapid cycling, increases compressor reliability.
• Freeze-protection prevents evaporator coil freeze up, improving compressor reliability.
• Low ambient lockout prevents compressor operation in outdoor temperatures less than 40°F (4.4°C). PTHP units supplied with unit-mounted control, Control causes automatic changeover to auxiliary heat, if installed.
• Test operation — all timers are temporarily suppressed to allow ease of testing or troubleshooting.
• Control board LED provides self-diagnostic troubleshooting codes, see "Sequence of operation."
Field-Installed Accessories
• Hydronic heat — coil assembly is shipped loose for
eld installation.
• Remote wall thermostat — digital 1-stage or 2-stage available.
• Wall sleeves, louvers, and cabinets
• Aquastat - delays fan start-up until coil reaches 100°F (38°C) to eliminate "cold" blow condition.
• Hydronic control valve , Water 2 way & 3 way
• Hydronic control valve, Steam 2 way
• Hydronic Isolation valve, 1/2 in Sweat Connection.
Page 8
FEATURES
Indoor Coil Freeze Protection (Standard)
Prevents indoor coil from freeze up in cooling mode.
Indoor coil freeze up can occur due to a dirty air lter,
restricted or poor air ow, low refrigerant charge or low
room or outdoor temperatures.
• This can cause compressor damage.
• Should freeze condition be detected, compressor and outdoor fan switch off for minimum of three minutes
until freeze condition is satised.
• During this time the indoor fan continues to run to aid in defrost process.
Condensate Removal (Standard)
RetroAire replacement unit, cooling operation, is designed to eliminate condensate by slinging it onto outdoor coil.
• Condensate drains through the bulkhead to the area near the outdoor fan.
• Unit as part of normal operation produces condensate and collects it in the unit's base pan. It is picked up there by the outdoor fan slinger ring and deposited onto
the condenser coil. This improves the unit’s efciency
by maintaining reduced refrigeration system pressures.
Base pan has overow notches. If too much condensate
is produced notches allow condensate to ow out of the
base pan and into the wall sleeve out of the building.
Anti-Short Cycle Timer (Standard)
Microprocessor control uses this timing to prevent compressor short-cycling.
• When the compressor cycles off on heating or cooling call, controller starts a 180-second timer.
• Compressor is not allowed to start until this time has elapsed.
• On initial power-up or after a power failure, this timing occurs after the random start timing.
Power Cord With Integral Safety Protection (Standard)
All PTAC/PTHP units rated 250V or less are equipped with power cord with integral safety protection as standard.
• Providing personal shock protection as well as arcing
and re prevention. Device is designed to sense any damage in line cord and disconnect power before a re
can occur.
• Tested in accordance with Underwriters Laboratories, cord set offers a unique “passive” operation, meaning unit does not require resetting if main power is interrupted.
Thermostatic Drain Pan Valve
(Standard On
Heat Pump Units)
Heat pump models (PTHP), condensate can accumulate in the outdoor drain pan during heat pump cycle.
• PTHP units include a thermostatic drain valve that opens when outdoor temperatures fall below 60°F (15°C).
When drain valve opens, condensate ows from the drain pan onto the bottom of the wall sleeve, and drains to the outside.
• Keeping the base pan free of condensate water, which could freeze during colder outdoor temperatures.
Random Start Feature (Standard)
Random start feature is initiated on initial power-up or after a power interruption.
• Controller adds a random time delay (from 5–120 seconds) on start-up, preventing compressor from starting.
• This staggers the start of multiple units in a single facility, preventing a large surge if all units started at the same time.
Heat Pump
• Heat pump units are “Limited Range” and should be equipped with back-up electric resistance or hydronic heat.
• Limited Range heat pumps are designed to operate when outdoor temperatures are between 70°F(21°C) and 40°F(4.4°C) and with maximum indoor temperature of 80°F(26.6°C).
• Unit is equipped with a reversing valve energized for cooling and de-energized in heating mode.
• Electric heating or hydronic heat will operate using onboard control logic below operating conditions of the heat pump.
The Right Fit for Comfort 8
P/N 240010639, Rev. A [06/15/2014]
Page 9
FEATURES
Hydronic Heating (Optional)
Hydronic heat package may be selected in lieu of electric heat. Heating operation is same as that of units with electric heat.
Aquastat Connection (Optional)
All replacement PTAC/PTHP's with hydronic heat are supplied with standard line volt Aquastat connection. Field installed Aquastat delays fan operation until hydronic coil reaches temperature of 100°F (38°C).
Motorized Fresh Air Damper (Optional)
Motorized fresh air damper allows fresh air into the space to be conditioned. When the Fresh Air switch is in "YES" position, damper door is open and allows fresh air into the space. This is only available when the indoor fan is on. When damper door switch is in the "NO" position, the damper door is closed and does not allow air in the space.
Optional Wall-Mounted Thermostats
PTAC/PTHP compatible thermostats.
• Manufacture offers single stage, cool/heat, thermostat that can be used in all RetroAire cooling, heating or heat pump applications.
• Thermostat has adjustable setpoint range of between 45°F(7°C) and 90°F(32°C).
• For heat pumps, manufacture offers a 2 stage heat/cool thermostat which allows for emergency heat.
Selecting A Thermostat
When selecting a thermostat for the PTAC/PTHP choose a single stage heat/cool, 24V thermostat.
Straight cooling with electric heat or hydronic heat (R10C — PTAC's) select a thermostat compatible with a cooling/ electric heat system. Thermostat should have “R”, “Y”, “W”, "C" and “G” terminals.
Heat Pump With Electric Heat (R__H - PTHPS)
Select a thermostat compatible with cooling/single-stage heat/heat pump system.
Thermostat should have "R", "Y", "O" and "G" terminals. RetroAire units are single stage heating only.
Electric heat and heat pump will not operate simultaneously.
9 Made in USA
P/N 240010639, Rev. A [06/15/2014]
Page 10
INSTALLATION PREPARATION
!
DANGER
Electrical shock hazard — Verify power to existing unit is disconnected before removing. Failure to do so will result in death or serious injury.
!
CAUTION
Moving parts can cause personal injury. Avoid contact with moving parts when testing or servicing the unit. Failure to follow these instructions could result in minor or moderate injury.
Verify existing wall sleeve/enclosure:
1.
RetroAire PTAC/PTHP's are to be used with metal wall sleeves.
2.
Existing front panels must be secured by screws that prevent contact with all parts.
3.
Minor dimensions of openings must not exceed ½ inch (12.5mm).
4.
Indoor air discharge grill must have dimensions not less than 26” x 4”. Grill must separate top surface of chassis from top surface of discharge grill by minimum of 1 in (25.4mm).
5.
For all models, outdoor openings must prevent contact of all moving parts by means of louvers or grills, with minor dimension not exceeding 1 in (25.4mm).
Electrical Power Connection
All wiring shall conform to requirements of authority having jurisdiction or in absence of such requirements:
• United States National Electrical Code, ANSI/NFPA 70
UL 1995 4th Addition.
• Canada CSA C22.1 Canadian Electrical Code Part 1.
Installer is responsible for ensuring units are installed in accordance with all applicable national and local codes.
UNITS RATED 208/230V — RetroAire unit is wired for 230v primary voltage from manufacture.
Transformer must be rewired by installer if job site voltage is 208V. Change transformer tap from orange to red. See wiring diagram for details.
1.
Verify RetroAire unit rating plate for circuit ampacity and required breaker or fuse size.
2.
Verify existing breaker or fuse is correct size. A. Replace breaker or fuse if incorrectly sized. B. Breakers must be type HACR only.
3.
Cord connected units — verify wall outlet is correct
rating. Outlet's blade conguration must match that of
cord supplied with RetroAire unit.
4.
Hard-wired units — verify power wiring is correctly
sized. Inspect existing wiring for deciencies, such as cuts or frayed wires. Replace any decient wiring if
found.
5.
Each unit must have separate branch circuit protected by fuse or breaker. Refer to unit rating plate for proper wire and breaker or fuse size. Use of extension cords is prohibited.
6.
DO NOT connect RetroAire unit to circuit with incorrectly sized overcurrent protection device.
7.
All cord-connected 265-volt units must be plugged into receptacles within unit subbase or chassis.
8.
Open power supply disconnect switch. Secure in open position during installation. Attach sign stating, "DO NOT TURN ON."
9.
On a plug and receptacle connection, unplug existing unit at the wall outlet. DO NOT plug in the new unit until installation is complete and start-up checklist has been completed.
Remove Old Chassis
1.
Disconnect power or unplug cord before proceeding.
2.
Remove front of the existing room enclosure to expose old chassis.
3.
Loosen any tie-down bolts or screws. Remove old chassis.
NOTICE
Dispose of old chassis following existing state and federal regulations.
4.
Inspect wall sleeve/cabinet for any rust, holes, or damage.
A. Clean wall sleeve of any dirt. B. Repair any damage. C. Ensure proper drainage of condensate or rainwater
to exterior of building.
5.
Remove or repair old weather seals. Note location for installation of any new seals.
6.
Check wall sleeve/cabinet to ensure all drain holes are open and:
A. Wall sleeve/enclosure is level left to right B. Back is pitched to outside by ½ in (12.5mm)
maximum.
7.
Before installing new chassis, inspect outdoor louver for minimum free area of 70% and remove any
obstructions. Obstructions restrict air ow over
condenser coil and may cause damage to the chassis.
8.
Follow the installation instructions on the following pages.
9.
DO NOT connect power to the unit or plug in the cord until instructions in this manual have been completed.
The Right Fit for Comfort 10
P/N 240010639, Rev. A [06/15/2014]
Page 11
INSTALLATION
Installation
1.
Verify existing wall thickness. Distance from condenser coil to outdoor louver varies with wall sleeve
depth. Units shipped with factory installed bafes.
Manufacturer offers alternate air bafe kits for unique
applications. Wall sleeve depth is required when
ordering to ensure proper bafe size.
2.
Install Bafes - Remove sets of bafes from the
kit bag supplied with unit. Install only one set of left
and right side bafes on the condenser coil. Complete
following steps:
Choose proper tting bafes for your application.
Verify selected bafes come in contact with outdoor
louver.
Verify bafes are directed inward toward center of coil.
See gure 3.
Secure bafes tightly into existing holes of condenser coil using provided screws.
3.
Install foam tape — Apply 1∕2” x 1∕2” open cell foam
strips to both weather angles, prevents outside air from entering around the chassis to the room from the
sides. See gure 4.
Install 1" x 1" open cell foam to back of unit above condenser coil. It is necessary to have a solid air seal between wall sleeve and chassis. Failure to do so will result in air leakage from outdoor to indoor causing system problems.
4.
Connecting optional hydronic coil controls. If
hydronic heat option has been ordered, eld install
the hydronic coil on the new unit. Coil with old unit can be located in subbase, under chassis in a special attachment, or above chassis in a special attachment. It is necessary to know where the coil is to be located and physical size of the coil so the new coil can be
veried if ordered for replacement. The new coil
should be installed in the same manner as the coil it is replacing. Hydronic coils are not factory installed and need to be ordered.
5.
Connecting accessory eld installed Aquastat. (If ordered)
A. Remove black jumper wire located on bottom panel
of control box. This is terminated with 2-position connector.
B. Cut jumper wire in the middle and splice the
Aquastat to jumper using 2 - crimp popcorns.
C. Place connector back into original location. Refer to
wiring diagram on unit for details.
6.
Secure chassis — Verify all seals are in the proper
locations, correct bafes are attached to the condenser coil, and in proper orientation. Slide unit into nal
position and tighten any tie down bolts or screws as necessary.
7.
Hard-wired units —
A. If unit is hard wired, follow instructions on
page 8to verify existing wiring and overcurrent protection.
B. Remove line cord wires from PTAC PTHP power
entrance terminals.
C. Route power supply wiring through a strain-
relief bushing. Connect leads to power entrance terminals.
D. Secure strain-relief clamp.
E. If wiring is through conduit, insert conduit through
control box knockout and secure in place.
F. DO NOT turn on power until completing
instructions in "Final Inspection and Startup" on page 17.
8.
DO NOT PLUG IN the line cord, if used. Follow instructions in "Final Inspection and Startup" page 17.
• Remove 2-position connector assembly from kit bag supplied with unit. This will have 2 yellow wires attached.
• Splice 2 yellow wires to valve motor using 2 - crimp popcorn.
• Connect this 2-position connector to 2-position connection located on bottom of control box panel.
11 Made in USA
P/N 240010639, Rev. A [06/15/2014]
Page 12
Figure 3 R25 Bafe Direction
INSTALLATION
Figure 4 - Foam Tape Installation
Bafes
Install 1/2" x 1/2" Foam Tape
The Right Fit for Comfort 12
P/N 240010639, Rev. A [06/15/2014]
Page 13
INSTALLATION
Installation
1.
Verify existing wall thickness. Distance from condenser coil to outdoor louver varies with wall sleeve
depth. Two sets of air bafes are included with each
unit to accommodate most installation requirements.
Manufacturer offers alternate air bafe kits for unique
applications. Wall sleeve depth is required when
ordering to ensure proper bafe size.
2.
Verify air supply alignment - Slide unit into wall sleeve. Supply duct on cooling chassis should line up with supply vent on room cabinet.
3.
Install Bafes - Slide unit out of wall sleeve.
Remove both sets of bafes from the kit bag supplied
with unit.
Install only one set of left and right side bafes on the
condenser coil. Complete following steps:
Choose proper tting bafes for your application.
Verify selected bafes come in contact with outdoor
louver.
Verify bafes are directed inward toward center of coil.
See gure 3.
Secure bafes tightly into existing holes of condenser coil using provided screws.
4.
Install Foam Tape — Apply 1∕2” x 1∕2” open
cell foam strips around supply air duct to ensure all conditioned air is delivered into the room. See Figure 15. Failure to do so results in recirculation of conditioned air around the cabinet causing unit to short cycle and coil to freeze.
Apply 1” x 1” open-cell foam strips to the weather angle to prevent outside air from entering around cooling chassis to the room from the sides and top of the cabinet. Install between wall sleeve and chassis.
See gure 4. Verify a solid air seal between the wall
sleeve and the chassis. Failure to do so will result in air leakage from outdoor to indoor causing system problems (example — coils freezing, short cycling, and constant running of unit).
5.
Connecting optional hydronic coil controls
If hydronic heat option has been ordered, eld install
the hydronic coil on the new unit. Coil with old unit can be located in subbase, under chassis in a special attachment, or above chassis in a special attachment. It is necessary to know where the coil is to be located and physical size of the coil so the new coil can be
veried if ordered for replacement. The new coil
should be installed in the same manner as the coil it is replacing. Hydronic coils are not factory installed and need to be ordered.
• Remove 2-position connector assembly from kit bag supplied with unit. This will have 2 yellow wires attached.
• Connect this 2-position connector to 2-position connection located on bottom of control box panel.
6.
Connecting accessory eld installed Aquastat.
(If ordered)
A. Remove black jumper wire located on bottom panel
of control box. This is terminated with 2-position connector.
B. Cut jumper wire in the middle and splice the
Aquastat to jumper using 2 - crimp popcorns.
C. Place connector back into original location. Refer to
wiring diagram on unit for details.
7.
Secure chassis — Verify all seals are in the proper
locations, correct bafes are attached to the condenser coil, and in proper orientation. Slide unit into nal
position and tighten any tie down bolts or screws as necessary.
8.
Hard-wired units —
A. If unit is hard wired, follow instructions on
page 8to verify existing wiring and overcurrent protection.
B. Remove line cord wires from PTAC PTHP power
entrance terminals.
C. Route power supply wiring through a strain-
relief bushing. Connect leads to power entrance terminals.
D. Secure strain-relief clamp.
E. If wiring is through conduit, insert conduit through
control box knockout and secure in place.
F. DO NOT turn on power until completing
instructions in "Final Inspection and Startup" on page 17.
9.
DO NOT PLUG IN the line cord, if used. Follow instructions in "Final Inspection and Startup" page 17.
13 Made in USA
P/N 240010639, Rev. A [06/15/2014]
Page 14
SEQUENCE OF OPERATION
Sequence of Operation
R_ _C units are straight cool, single stage air conditioners available with electric or hydronic heat.
R_ _H units are limited range, single stage heat pump. Mechanical compression heating (heat pump mode) is locked out at outdoor temperatures of approximately 35º F (1.7º C) and below. Below these ambient temperatures, auxiliary electric or hydronic heat will be used.
General
Microprocessor controlled unit. Thermostat and control connections are made to the control board.
Two conguration jumpers are located on the board. See
Figure 5.
• Straight Cool units R_ _C, locate jumper on outside two pins.
• Heat Pump units R_ _H, locate jumper on inside two pins.
Heat Pump Conguration Jumper is a 3 pin jumper.
Second conguration jumper “TEST” allows for control’s
internal timers to be by-passed for test purposes. Placing jumper on two pins enables test mode.
Figure 5 - Control Board
TEST
Conguration
Jumper
LED
Indicator
Light
Heat
Pump
Conguration
Jumper
Table 1 - Status Codes
Status LED (Light Emitting Diode), LED1 is located on center of board. Series of blinks communicates board status. Between blink sequence is separation of approximately 2 seconds. See Table 1.
Initial Power-Up or Power Restoration
When power is applied to the unit, either for the rst time or after a power failure, board initializes itself.
• During initialization, LED1 is lit for approximately 5 seconds.
• Following initialization, a random start timer is initiated. Timer adds randomly selected 5-120 seconds to start-up sequence, reducing possibility of multiple units starting at same time.
• Once random start timer has expired, 180 second Anti-Short Cycle Timer is initiated and Processor
Board Trouble Code LED is set to blink a 2 ash code.
Timer prevents compressor from rapid cycling.
• After Anti-Short Cycle Timer expires, Processor Board Trouble Code LED is set to blink 1 blink Trouble Code,
indicating normal operation.
R_ _C / R_ _H; Cooling Operation
Unit Mount Controls
• With System Switch [SS] set to “Cool”, and Fan Cycle Switch [FCS] set to “On” (Continuous Fan Operation), indoor fan motor starts.
• If Fan Cycle Switch [FCS] is set to “Off” (Cycling Fan Operation), indoor fan motor starts with call for cooling from internal thermostat [T’stat].
The Right Fit for Comfort 14
Trouble Code
(Blinks)
1 2 3 4 5
Status
Normal Operation
Anti-Short Cycle Timer Active
Outdoor Coil Freeze Protection
Indoor Coil Freeze Protection
Simultaneous “Y” and “W” Call
P/N 240010639, Rev. A [06/15/2014]
Page 15
SEQUENCE OF OPERATION
• If equipped with Motorized Fresh Air Damper, and is active with Fresh Air Switch [FAS], damper will open with call for the indoor fan.
• If room temperature is below thermostat setting fan operation continues as noted.
• If room temperature is above thermostat setting, reversing valve is energized. Compressor and outdoor fan start provided Anti-Short Cycle Timer has timed out from initial power-up, power restoration or previous compressor on cycle. Operation will continue until room
temperature satises the thermostat.
• Once room temperature falls below set point by 3º F (2º C)compressor, outdoor fan motor and reversing valve will de-energize.
• If FCS is set to “Off”, indoor fan continues to operate for 60 seconds after compressor stops.
• If FCS is set to “On”, indoor fan continues to operate.
• As soon as the compressor is de-energized, Anti-Short Cycle Timer is initialized and prevents compressor from starting again for another 180 seconds.
• While Anti-Short Cycle Timer is active, Processor Board
Trouble Code LED is set to blink a 2 ash code.
• After Anti-Short Cycle Timer expires, Processor Board Trouble Code LED is set to blink 1 blink Trouble Code, indicating normal operation.
NOTE:
Remote-Mount Cooling Operation depends on features of wall-mounted thermostat. By default fan will cycle with call for cooling.
For thermostats with AUTO / ON fan switch, fan will run continuously if this is “ON” (Continuous Fan Operation).
Fan cycles with call for cooling if this is set to “AUTO” (Cycling Fan Operation).
In cooling, units will not start if indoor air temperature is 60º F (15.5º C) or below or outdoor temperature is below 40º F (4.5º C).
R_ _C / R_ _ H; Heating Operation
• With System Switch [SS] set to “Heat”, and Fan Cycle Switch [FCS] set to “On” (Continuous Fan Operation), indoor fan motor will start.
• If Fan Cycle Switch [FCS] is set to “Off” (Cycling Fan Operation), indoor fan motor will start with call for heating from the internal thermostat [T’stat].
• If equipped with Motorized Fresh Air Damper, and is active with Fresh Air Switch [FAS], damper opens with call for indoor fan.
• If room temperature is above thermostat setting fan operation continues as noted above.
• If room temperature is below thermostat setting, action of the unit will depend on outdoor temperature and freeze sensor status.
NOTE: Remote-Mount Heating Operation depends on features of wall-mounted thermostat. By default fan will cycle with call for Heating.
For thermostats with AUTO / ON fan switch, fan runs continuously if this is “ON” (Continuous Fan Operation).
Fan cycles with call for heating if this is set to “AUTO” (Cycling Fan Operation).
A. R_ _H; Mechanical Heating “Heat Pump"
• If outdoor coil temperature remains above 25º F (-4º C), compressor and outdoor fan start provided Anti-Short Cycle Timer has timed out from initial power-up, power restoration or previous compressor on cycle.
• Operation continues until room temperature
satises thermostat.
• Once room temperature rises above set point by 3º F (2º C), compressor and outdoor fan motor will de-energize.
• If FCS is set to “Off”, indoor fan continues to operate for 60 seconds after compressor stops.
• If FCS is set to “On”, indoor fan continues to operate.
• As soon as compressor is de-energized, Anti-Short Cycle Timer is initialized and prevents compressor from starting again for another 180 seconds.
• While Anti-Short Cycle Timer is active, Processor
Board Trouble Code LED is set to blink a 2 ash
code.
• After Anti-Short Cycle Timer expires, Processor
Board Trouble Code LED is set to ash 1 blink
Trouble Code, indicating normal operation.
B. R_ _H; Auxiliary Heating “Electric” or “Hydronic”
• If outdoor coil temperature falls to 25º F (-4º C) or below for 180 seconds at anytime during heating call, compressor and outdoor fan motor are de­energized and auxiliary heat is energized.
• Anti-Short Cycle Timer is initiated, prohibiting compressor operation for 180 seconds. Processor
Board Trouble Code LED ashes 3 blink Trouble
Code, indicating auxiliary heat operation.
• Heating operation with auxiliary heat continues until outdoor coil sensor reaches 50º F (10º C).
B.1 “Electric Heat”
A. System Switch [SS] set to “Heat”, and Fan
Cycle Switch [FCS] set to “On” (Continuous Fan Operation), indoor fan motor starts.
B. If Fan Cycle Switch [FCS] is set to “Off”
(Cycling Fan Operation), indoor fan motor starts with call for heating from internal thermostat [T’stat].
15 Made in USA
P/N 240010639, Rev. A [06/15/2014]
Page 16
SEQUENCE OF OPERATION
C. If unit is equipped with Motorized Fresh Air
Damper, and is activated with Fresh Air Switch [FAS], damper opens with call for indoor fan.
D. If room temperature is above thermostat
setting fan operation continues as noted above.
E. If room temperature is below thermostat
setting, electric heater is energized until room
temperature satises thermostat.
F. Once room temperature increases above set
point by 3º F (2º C), electric heaters are de­energize.
B.2 “Hydronic Heat”
A. If FCS is set to “On” (Continuous Fan
Operation) and unit has Aquastat, the indoor fan and fresh air motorized damper operation are controlled by the Aquastat.
B. If the Aquastat senses temperature of 80 ± 5º
F (26 ± 3º C) or below, the indoor fan shuts down and the motorized damper closes fresh air door.
C. With call for heat, signal from processor board
activates water or steam valve.
D. If unit is equipped with a eld installed
Aquastat [AS], the indoor fan start will be delayed until the hydronic coil reaches 100 ± 5 ºF (38 ± 3 ºC). The signal to the water or steam valve will continue until the room temperature rises above the set point by 3 ºF (2 ºC). If the FCS is set to “Off”, the indoor fan will continue to operate for 60 seconds or until the hydronic coil temperature as sensed by the Aquastat reaches 80 ± 5 ºF (26 ± 3
ºC), whichever occurs rst. If the FCS is set
to “On”, the indoor fan will de-energize if the Aquastat senses a temperature of 80 ± 5 ºF (26 ± 3 ºC) or below.
B.3 “Remote Wall Thermostat Controls”
Cooling and Heating operates identical to unit mount controls.
See remote controls manual for control details. Remote units do not use a system switch, or FCS.
The Right Fit for Comfort 16
P/N 240010639, Rev. A [06/15/2014]
Page 17
FINAL INSPECTION & START-UP
Before Operating The Unit
1.
Install unit per the instructions outlined in this manual and all applicable local and national codes.
2.
Verify electrical supply matches electrical requirements of the unit, and unit is properly grounded.
3.
Examine control box. Verify all wire connections are secure, and control board jumpers are in proper positions.
4.
Verify chassis is properly tted to wall sleeve and
securely mounted to surrounding framing.
5.
Verify chassis is level: Pour water into drain pan.
Verify it ows through the drain hoses to condenser
side of unit.
6.
Verify indoor blower wheels and outdoor fan blades are secured to their motor shafts, and rotate freely.
7.
Verify all sheet metal panels are in place and secure.
8.
Attach front panel to the existing cabinet enclosure.
9.
Verify nothing interferes with room discharge air or return air of units.
Examples:
Check for curtains or drapes that obstruct air ow. See gure 6 and gure 7.
Check for plush carpeting that can obstruct return air.
These types of obstructions can cause serious damage to the chassis.
Figure 6 - Proper Air Flow Diagram
Figure 7 - Restricted Air Flow Diagram
Any obstruction of supply air, including use of deector bafes, may cause condensate to form on louver or cabinet. See gure 7.
For optimum performance of your PTAC/PTHP, avoid
restricting the air ow. Position of curtains or drapes
over supply air grille may cause air to recirculate without cooling the room. Unit will short cycle and may cause
premature compressor failure. See gure 7.
17 Made in USA
P/N 240010639, Rev. A [06/15/2014]
Page 18
FINAL INSPECTION & START-UP
Electrical Connections
Installation and wiring shall be in accordance with requirements of authority having jurisdiction In absence of such requirements refer to:
• USA- National Electrical Code, ANSI/NFPA 70.
• Canada - Canadian Electrical Code, Part I, CSA C22.1: Safety Standard for Electrical Installations.
Units Rated 208/230V:
• RetroAire unit is wired for 230V primary voltage from manufacturer.
• Transformer must be rewired by installer if job site voltage is 208V.
• Change transformer tap from orange to red. See wiring diagram for details. Wiring diagramcan be found on
inside of control door.
Setting Control Board Jumpers
Control board has two sets of factory installed jumper pins: HP jumper and TEST jumper.
HP Jumper — selects heat pump or straight cooling. Pins determine whether unit operates as straight cooling or
as heat pump. See gures 8 and 9.
Jumper right pin to center pin for heat pump operation.
Jumper left pin to center pin for straight cooling operation.
TEST Jumper
— selects normal or test mode
Figure 8 - HP Jumper (selects heat pump or
straight cooling)
Heat Pump Mode
(Jumper center
& Bottom pins)
HP
Straight
Cool Mode
(Jumper center
HP
& Top pins)
Figure 9 - TEST jumper (selects normal or
test mode)
Normal operation
(pins not jumped)
Test mode
(pins jumped)
NOTICE
Do not leave unit operating with TEST jumper in TEST position.
Jumper is for testing only. See gures 8 and 10.
• When jumper pins are jumped together, all timers are eliminated (example — anti-short cycle, purge, etc.).
May be used for eld testing. Units are factory set with jumper on only one pin (normal operation position).
The Right Fit for Comfort 18
P/N 240010639, Rev. A [06/15/2014]
Page 19
FINAL INSPECTION & START-UP
Figure 10 TEST jumper (selects normal or
test mode)
TEST JUMPER
HEAT PUMP
JUMPER
19 Made in USA
P/N 240010639, Rev. A [06/15/2014]
Page 20
FINAL INSPECTION & START-UP
Start Up
1.
Verify unit is secure and level.
2.
Heat pump units only — Verify thermostatic drain pan valve is operating correctly. Valve should be closed if temperature is above 60° F and open if below 60°F.
3.
Test fresh air damper, if equipped, by setting damper door switch to "YES". Verify damper opens and allows fresh air to be moved into the space. Set damper door
switch to "NO". Verify ow of air into the space has
stopped. Fresh air is only available when indoor fan is operating.
4.
Verify HP jumper is set correctly for unit type, cooling
only or heat pump. See gure 7, page 9.
5.
Set TEST jumper to test mode, this disables time delays, including anti-short-cycle and purge times. See
gure 18, page 29.
6.
Verify unit is wired correctly, including requirements on page 10.
7.
Connect Electric power to unit.
8.
Turn unit on. Verify proper operation.
9.
Verify condensate removal: A. Pour water into base pan.
B. Place unit in cooling mode, with condenser fan
operating, verify water is picked up by slinger ring and thrown onto outdoor coil.
Compressor will not start until anti-short time period has elapsed.
On power-up, there are delays for control board initialization and random start timing. See Sequence of Operation Section, page 14.
Unit Mounted Thermostat
Figure 11 Typical Representation - Unit Mount
Control
THERMOSTAT KNOB
Do not rotate thermostat knob back and forth from heating to cooling.
This causes compressor to cycle on and off rapidly and will cause damage to the compressor.
Allow compressor to remain off for at least three minutes prior to restarting the unit.
Remote Mounted Thermostat
1.
Use thermostat to place PTAC/PTHP in COOL, HEAT, or OFF position. Test operation in all positions.
2.
If thermostat is tted with fan switch, set as desired
places the fan in either ON, OFF, or AUTO. Test operation in all positions.
3.
Check thermostat calibration for both heating and cooling operation.
1.
Use system switch to place PTAC/PTHP in COOL, HEAT, or OFF position. Test operation in all positions.
See gure 29.
2.
Use fan speed switch to place fan in LOW or HIGH speed. Test operation in both positions for heating and
cooling. See gure 11.
3.
Test operation of Fan Cycle switch, toggle switch on side of control box. Set switch to ON, continuous fan operation, or AUTO, cycling with thermostat, for both heating and cooling. Set switch in desired position.
4.
Rotate thermostat knob left to increase setpoint temperature, or right to decrease.
• Turning unit-mounted thermostat knob to far left produces the warmest room temperature.
• Turning thermostat knob all the way to the right produce coolest room temperature.
• Setting can be adjusted for personal comfort. See
gure 11.
The Right Fit for Comfort 20
P/N 240010639, Rev. A [06/15/2014]
Page 21
FINAL INSPECTION & START-UP
Straight Cooling PTAC's
Important Information
• Room temperature must be above 65°F (18°C) for compressor to operate in cooling mode on PTAC's with unit-mounted controllers.
• Room temperature must be below 85°F (29.4°C) to energize the heater on PTAC's with unit-mounted controllers.
• Room temperature must be below 85°F (29°C) for hydronic heater to operate on PTAC's with unit­mounted controllers. Hydronic valve is 24 Vac normally open valve. Should power be interrupted, valve will default to open position.
When unit is rst powered up, high humidity conditions may cause condensation to form on discharge grill. Keep doors and windows closed to reduce humidity allowing condensation to evaporate.
Cooling Cycle
1.
Place thermostat or system switch in COOL position.
2.
Adjust thermostat to cooler temperature until indoor fan starts running. Compressor and outdoor fan will
turn on and cold air will begin to ow from unit.
Allow unit to continue operating to cool the room and remove humidity.
3.
After unit starts and space gets cooler, adjust thermostat to warmer temperature until compressor cycles off.
4.
If a colder room temperature is desired, adjust thermostat to cooler temperature setting, turn compressor and both fans back on.
5.
If a warmer room temperature is desired, adjust thermostat to warmer temperature setting. Compressor and outdoor fan stop, indoor fan switches off after sixty-second purge time has elapsed.
6.
Place thermostat or system switch in OFF position. All operation will stop.
Heating Cycle — Electric Option
1.
Outdoor fan does not run during heating cycle.
2.
Place thermostat or system switch in HEAT position.
3.
Adjust thermostat for warmer temperature until indoor fan starts running and electric heater coil starts emitting heat.
4.
After unit starts running and space gets warmer, adjust thermostat to cooler temperature until electric heater turns off.
5.
If warmer room temperature is desired, adjust thermostat to warmer temperature setting, which will turn electric heater on.
6.
If cooler room temperature is desired, adjust thermostat to cooler temperature setting until electric heater turns off. Indoor fan will switch off after sixty­second purge time has elapsed.
7.
Place thermostat or system switch in OFF position. All operation will stop.
21 Made in USA
P/N 240010639, Rev. A [06/15/2014]
Heating Cycle — Hydronic Option Before Starting The unit:
• Verify motor valve is rated for correct voltage.
• Most RetroAire units with unit mount controls will power a hydronic valve that is the same voltage as the unit (ex: a unit rated 208/230v will power a 208/230v).
• Switch is provided on control box to change from NO to NC.
• Verify wiring using wiring diagram, located on the unit,
and voltage application for the specic unit.
Other valve congurations and voltage options are available. Consult Technical Service if unit voltage does not match your valve application.
Starting the unit:
1.
Place thermostat or system switch in HEAT position.
2.
Adjust thermostat to warmer temperature.
3.
A signal from processor board will activate the water or steam valve.
4.
The motorized valve will open and allow hot water or steam to run through the coil.
5.
Indoor fans run, blowing air through the hydronic coil
6.
If the unit is equipped with an Aquastat, the indoor fan and motorized damper operation are delayed until the hydronic coil reaches 100 ± 5°F (38 ± 3°C).
7.
The signal to water or steam valve continues until room temperature rises above setpoint by 3°F (2°C).
8.
Once the area gets warmer, adjust thermostat to a cooler temperature. The hydronic valve closes and indoor fan switches off after sixty-second purge time has elapsed.
9.
If warmer room temperature is desired, adjust thermostat to warmer temperature setting, which opens the hydronic valve and turns on the indoor fan.
10.
If cooler room temperature is desired, adjust thermostat to cooler temperature setting. Hydronic valve closes and indoor fan switches off after sixty­second purge time has elapsed.
11.
Place thermostat or system switch in OFF position. All operation stops.
Testing Completion For Cooling-Only PTAC's
Operation testing is now complete. If TEST jumper was set to test mode verify it is set back to
normal operation. See gure 10, page 19.
NOTICE
Do not leave unit operating with TEST jumper in TEST position.
Page 22
FINAL INSPECTION & START-UP
Heat Pump PTHP's
Unit is equipped with reversing valve, energized for cooling and de-energized in heating mode.
Cooling Cycle — Heat Pump Units
1.
Place thermostat or system switch in COOL position.
2.
Adjust thermostat to cooler temperature until indoor fan starts running. Compressor and outdoor fan will
turn on and cold air begins to ow from the unit. Let
unit continue operating to cool the room and remove humidity.
3.
After the space gets cooler, adjust thermostat to warmer temperature until compressor cycles off.
4.
If colder room temperature is desired, adjust thermostat to cooler temperature setting, turning compressor and both fans back on.
5.
If warmer room temperature setting is desired, adjust thermostat to warmer temperature. Cooling mode ceases and compressor and outdoor fan stop. Indoor fan will switch off after sixty-second purge time has elapsed.
6.
Place thermostat or system switch in OFF position. All operation stops.
Heating Operation - Heat Pump Units — Outdoor Temperature Above 40°F (4°C)
Heat pump units are “Limited Range” equipped with back­up electric resistance heat. Limited Range heat pumps are designed to operate when outdoor temperatures are between 70°F (21°C)and 40°F (4°C) and with maximum indoor temperature of 85°F (29°C) .
When outdoor temperature falls below approximately 40°F (4°C) unit will switch from heat pump to electric resistance heat, or hydronic heat if optionally added.
Electric heat or hydronic heat will then remain as the heat source until the outdoor temperatures rise above 50°F (10°C).
RetroAire heat pumps (R_ _H) are single-stage heating units. Electric heat and heat pump will NOT operate simultaneously.
Room temperature must be below 85°F (29°C) for compressor to operate in heating mode on PTHP's with unit-mounted controllers.
5.
6.
Auxiliary Heating Operation — Heat Pump Units — Outdoor Temperature Below 40°F (4C°) — Electric
Option
Room temperature must be below 85°F(29°C) to energize heater on PTHP's with unit-mounted controllers.
1.
2.
3.
4.
5.
6.
Electric Heat Models
Manually reset limit switch if the limit switch opens and de-energizes the electric heat.
To reset switch:
If cooler room temperature is desired, adjust thermostat to cooler temperature setting. Heating mode stops and compressor and outdoor fan stop. Indoor fan will switch off after sixty-second purge time
has elapsed. Place thermostat or system switch in OFF position. All
operation stops.
Place thermostat or system switch in HEAT position. Adjust thermostat to warmer temperature until indoor fans start running and electric coil starts emitting heat. After space gets warmer, adjust thermostat to cooler temperature until electric heater turns off. If warmer room temperature is desired, adjust thermostat to warmer temperature setting, which will turn electric heater back on. If cooler room temperature is desired, adjust thermostat to cooler temperature setting until electric heater turns off. Indoor fan will switch off after sixty­second purge time has elapsed. Place thermostat or system switch in OFF position.
All operation stops.
• Turn power off
• Remove control box cover.
• Locate limit switch.
• Push reset button in, located on the face of the switch.
1.
Place thermostat or system switch in HEAT position.
2.
Adjust thermostat to warmer temperature setting until indoor fan starts running. Compressor and outdoor fan
will turn on and warm air will begin to ow from unit.
3.
After space gets warmer, adjust thermostat to cooler temperature until compressor cycles off.
4.
For warmer room temperature, adjust thermostat to warmer temperature setting, turning indoor, outdoor fans and compressor back on.
The Right Fit for Comfort 22
P/N 240010639, Rev. A [06/15/2014]
Page 23
FINAL INSPECTION & START-UP
Auxiliary Heating Operation — Heat Pump Units — Outdoor Temperature Below 40°F (4°C) — Hydronic
Option
Room temperature must be below 85°F (29°C) for hydronic heater to operate on PTHP's with unit-mounted controllers.
Hydronic valve is 24Vac normally open valve. Should power be lost to the unit, the valve will default to open position.
1.
Place thermostat or system switch in HEAT position.
2.
Adjust thermostat to warmer temperature.
The following occurs:
• Signal from processor board activates water or steam valve.
• Motorized valve opens and allows hot water or steam to run through coil.
• Indoor fans run, blowing air through hydronic coil
• If unit is equipped with an Aquastat, indoor fan and motorized damper operation is delayed until hydronic coil reaches 100 ± 5°F (38 ± 3°C).
• The signal to the water or steam valve will continue until the room temperature rises above the setpoint by 3°F (2°C).
• After space gets warmer, hydronic valve will close and indoor fan will switch off after sixty-second purge time has elapsed.
3.
After space gets warmer, temperature setting, indoor fan will switch off after sixty-second purge time has elapsed.
4.
If warmer room temperature is desired, adjust thermostat to a warmer temperature setting, which will open hydronic valve and turn on the indoor fan.
5.
If cooler room temperature is desired, adjust thermostat to cooler temperature setting. Hydronic valve will close and indoor fan will switch off after sixty-second purge time has elapsed.
6.
Place the thermostat or system switch in the OFF position. All operation stops.
Testing Completion For Heat Pumps
Operation testing is complete. If TEST jumper was set to test mode verify it is set back to
normal operation. See gure 11, page 19.
adjust thermostat to cooler
hydronic valve will close and
23 Made in USA
P/N 240010639, Rev. A [06/15/2014]
Page 24
MAINTENANCE
!
WARNING
Electrical shock hazard. Disconnect power to unit before servicing or accessing control compartment. Failure to do follow these instructions could result in death or serious injury.
NOTICE
Perform regular service and maintenance by
qualied service agency at least once every 12
months to assure safe, trouble free operation and
maximum efciency.
NOTICE
Verify proper operation after servicing.
Maintenance Schedule
Manufacturer recommends performing following inspections and maintenance on monthly basis. Units installed in harsh or dirty environments will require more frequent inspections and maintenance.
Disconnect power to unit and remove necessary access panels:
Clean or replace indoor air lter.
☐ Inspect chassis interior for rodent or insect infestation.
Clean if necessary.
Clean & ush condensate drain pan and chassis base pan.
☐ If applicable, verify condensate drain is functioning
properly.
☐ Inspect refrigeration tubing, especially braze joints, for
signs of refrigerant leaks (oil residue). Repair if necessary.
☐ Inspect indoor and outdoor coils. Verify dirt or debris
have not collected on ns. Clean if necessary. Take care not to damage coil ns when cleaning. Use n comb to straighten any bent ns.
☐ Examine control box. Verify all wire connections are
secure.
☐ Verify indoor blower wheels and outdoor fan blades are
secured to their motor shafts.
☐ Verify dirt or debris have not collected on indoor blower
wheels and outdoor fan blades. Use vacuum and soft brush to clean if necessary.
☐ Verify any ductwork connected to unit is secure and free
of air leaks.
ELECTRIC HEAT MODELS — in event the limit switch
opens and de-energizes the electric heat, limit switch
will need to be manually reset. See gure 12.
switch:
• Remove the control box cover.
• Locate the limit switch.
• Push in the reset button on the face of the switch.
To reset
Figure 12 - Manual Reset Limit Switch
Reset Button
*Note:
Button will pop out when limit switch opens. Push in to reset.
Seasonal Start-Up And Maintenance
Beginning of cooling and heating seasons, complete mechanical check should be performed and maintenance/ inspections performed as described below.
Disconnect power to unit and remove necessary access panels:
1.
Remove access panel. Visually inspect equipment. Look for obvious changes in unit such as damaged coils or evidence of extended wear on any moving parts.
2.
Check for unusual odors or leaks (examples: burnt motor windings, water, or refrigerant). Verify base pan is clean.
3.
Clean or replace return air lter as needed. Check lter
at least once month. Some environments may require more frequent replacement, depending on particulate in air stream.
4.
Inspect all electrical connections for frayed wires and poor connections.
5.
Check fan motors and blower assemblies. Verify screws and motor mounting hardware are tight.
6.
Centrifugal fan blades and blower cage brush and/or vacuum as necessary.
7.
Inspect both indoor and outdoor coils. Use n comb to straighten out any damaged ns.
NOTICE
Do not use solvent based cleaner to clean coils, some solvents will produce noxious odor when unit is in operation or may deteriorate components.
8.
Look for oil leaks or stains on or around all braze joints and refrigerant lines. Presence of oil here indicates potentially serious problem, such as refrigerant leak.
9.
Inspect and clean drain pan and drain line(s). Use of anti-fungicide tablet to keep condensate system free from bacterial contaminants is recommended.
10.
Verify unit is level for proper operation. Building and equipment may settle, causing shift in direction of
condensate ow. Verify weep holes along rear ange of
base pan are free of debris.
The Right Fit for Comfort 24
P/N 240010639, Rev. A [06/15/2014]
Page 25
MAINTENANCE
11.
Air leaks may make the conditioned area uncomfortably drafty or produce noises. Visually inspect foam gasket between wall and unit, taking note of separation between air inlet for condenser and condenser coil discharge. These two areas must be sealed off from each other. If you experience poor cooling operation or erratic operation, check for air recirculation at condenser coil.
12.
Replace access panels and reconnect electrical power.
Troubleshooting Sensors
1.
2.
Table 2 - Sensor Resistance Values
Heat Pump Units — Temporary Emergency
Heating Mode
Heat pump failure, control board can be forced into electric heat mode.
This is temporary solution until heat pump system can be repaired.
1.
Locate circuit board in control section of the unit.
2.
Locate terminals where outdoor sensor connects to the circuit board.
3.
Using small needle nose type pliers, disconnect one side of sensor from circuit board. A 2-stage thermostat will provide Emergency heat.
4.
This will appear to circuit board as outdoor coil freeze condition energizing the electric resistance heater on call for heat.
5.
See "Manual Reset Limit Switch" for resetting limit
switch if needed. See gure 12 page 24.
Figure 13 - Control Board Sensor Connections
See gure 31 for location of sensor connections to the
control board. If temperature response of indoor or outdoor sensor is not correct, disconnect sensor from control board and verify sensor resistance. Replace sensor if its resistance is not close to values in the table below.
@ Ambient
T e m p e r a t u r e
77 (25°C) 10.0 K
50 (10°C) 19.9 K
35 (1.6°C) 30.0 K
30 (-1.1°C) 34.4 K
Indoor Sensor Connections
Outdoor Sensor Connections
Resistance
25 Made in USA
P/N 240010639, Rev. A [06/15/2014]
Page 26
TROUBLESHOOTING
!
WARNING
Electrical shock hazard. Disconnect power to unit before servicing or accessing control compartment. Failure To follow these instructions could result in death or serious injury.
Symptom Suggestion
No heat or cooling Check to see if unit has power and if thermostat is satised. If
thermostat is not satised, call your installing contractor or service
contractor.
Thermostat calls for cooling, but cool air is not coming out of unit.
Light on circuit board is blinking.
Circuit board light is blinking 3 or 4 times, but there is no freeze condition.
Thermostat is satised, but fan
is still running.
Thermostat calls for heat, but no heat comes out of unit.
Thermostat calls for heat while in heat pump mode, but heated air is not coming out of unit.
• Check for continuity between thermostat and unit. Verify 24Vac is present across terminals C and R.
• Verify high pressure switch located in outdoor section has not been tripped. If tripped, press switch button to restart compressor.
• Note: If evaporator fan is operational and all of above suggested procedures have been followed, and there is still no cooling being supplied by unit, contact trained heating and cooling professional.
• Circuit board uses light for diagnostic purposes. Blinking codes are as follows:
1 blink = normal operation2 blinks = compressor lockout (ASCT — Anti-short cycle timer)3 blinks = outdoor freeze condition4 blinks = indoor freeze condition5 blinks = simultaneous Y and W call (Straight cool units only)
• Verify sensors have not been damaged. Remove sensor wires from control board and make resistance measurements, compare to following sensor resistances. Indoor and outdoor coil sensor wires are labeled, as is control board.
77°F = 10KOhms50°F = 19.9KOhms35°F = 30KOhms30°F = 34.4KOhms
If thermostat is set to auto mode, once thermostat is satised, fan will stay energized for extra 60 seconds to purge unit of excess cool or warm air in plenum.
• If thermostat fan switch is set to ON, fan will stay energized regardless
of whether thermostat is satised or not. Only way to turn fan off is to
turn unit off or turn thermostat fan switch to AUTO.
• Units equipped with electric heaters have temperature limit switch to prevent electric heater from reaching unsafe temperatures. If after calling for heating, heater is not energized, check for continuity across limit. If limit is open, replace with equivalent limit switch.
Verify unit has power or thermostat has been satised. If unit has power
and thermostat is satised, turn thermostat few degrees above room
temperature.
• While in heat pump mode, verify thermostat is not energizing O terminal. Retroaire units are designed to work in heat pump mode when 24Vac is present across Y and C. Verify heat pump jumper on control board is jumping two pins labeled “HP”. See control board jumper locations,
gure 13, Page 27.
• Verify there are no freeze conditions. Refer to blinking codes question above for more information.
Have qualied technician conduct troubleshooting
procedures.
NOTICE
The Right Fit for Comfort 26
P/N 240010639, Rev. A [06/15/2014]
Page 27
Table 3 R25 C/H Performance Data
PERFORMANCE DATA
Model
R60
R_ _C 09
R_ _H 09 8,400 (2.5) 2.68
R_ _C 12 11,400 (3.3)
R_ _H 12 11,600 (3.4) 8.33 10,600 (3.1) 2.62
R_ _C 15 14,000 (4.1)
R_ _H 15 13,500 (4.0) 7.92 12,600 (3.7) 2.57
Cooling
Btuh (kW) Btuh (kW) CFM (L/s) CFM (L/s) lbs (Kg)
9,000 (2.6) 0.74 8.98
Sensible
Heat
Ratio
0.65
0.63
EER
8.47 N/A N/A
7.92 N/A N/A
Heat Pump
N/A N/A
COP
Indoor Air
Flow
340 (160) 35 (17) 140 (64)
340 (160) 50 (24) 140 (64)
325 (153) 60 (28) 140 (64)
Fresh Air
Inlet
Flow
Shipping
Weight
27 Made in USA
P/N 240010639, Rev. A [06/15/2014]
Page 28
ELECTRICAL SPECIFICATIONS
Table 5 R25 - 9,000 BTU Electrical Specications
Power Supply
Volt 1–60
Compressor Fan Motor Electric Heat Unit Electrical Ratings
Volt Min RLA LRA FLA Hp
208/
230V
265V 240 3.32 18.8 0.8 0.8
197 4 22.2 0.8 0.08
Htr
Volt W HA TCA THA MCA MOCP Plug
#
0 N/A N/A N/A
208 1963 9.4 10.2 12.8 15
2
230 2400 10.4 11.2 13.14 15
208 2454 11.8 12.6 15.7
3
230 3000 13 13.8 17.3
208 2862 13.8 14.6 18.2
4
230 3500 15.2 16.0 20.0
208 4089 19.7 20.5 25.6
5
230 5000 21.7 22.5 28.2
0 N/A N/A N/A
265 3112 11.7 12.5 15.7
2
277 3400 12.3 13.1 16.3
3 265 3752 14.2 15 18.7
4 277 4100 14.8 15.6 19.5
5 N/A N/A N/A N/A N/A N/A N/A
4.8
4.12
N/A 5.8 15
20 6-20P
30 6-30P
N/A 5.0 15
20
6-15P
7-20P
Table 4 R25 - 12,000 BTU Electrical Specications
Power Supply
Volt 1–60
Volt Min RLA LRA FLA Hp
208/
230V
265V 240 4.6 20 0.8 0.125
197 5.6 29 0.8 0.125
Compressor Fan Motor Electric Heat Unit Electrical Ratings
Htr
Volt W HA TCA THA MCA MOCP Plug
#
0 N/A N/A N/A
208 1963 9.4 10.2 12.8 15
2
230 2400 10.4 11.2 14.0 15
208 2454 11.8 12.6 15.7
3
230 3000 13 13.8 17.3
208 2862 13.8 14.6 18.2
4
230 3500 15.2 16.0 20.0
208 4089 19.7 20.5 25.6
5
230 5000 21.7 22.5 28.2
0 N/A N/A N/A
265 3112 11.7 12.5 15.7
2
277 3400 12.3 13.1 16.3
265 3752 14.2 15 18.7
3
277 4100 14.8 15.6 19.5
5 N/A N/A N/A N/A N/A N/A N/A
N/A 7.8 15
6.4
N/A 6.6 15
5.4
6-15P
20 6-20P
30 6-30P
7-20P
20
The Right Fit for Comfort 28
P/N 240010639, Rev. A [06/15/2014]
Page 29
ELECTRICAL SPECIFICATIONS
Table 6 R25C - 15,000 BTU Electrical Specications
Power Supply
Volt 1–60
Compressor Fan Motor Electric Heat Unit Electrical Ratings
Volt Min RLA LRA FLA Hp
208/
230V
265V 240 6.0 28.0 0.8 0.125
197 7.4 33 0.8 0.125
Htr
Volt W HA TCA THA MCA MOCP Plug
#
0 N/A N/A N/A
208 1963 9.4 10.2 12.8 15
2
230 2400 10.4 11.2 14.0 15
208 2454 11.8 12.6 15.7
3
230 3000 13 13.8 17.3
208 2862 13.8 14.6 18.2
4
230 3500 15.2 16.0 20.0
208 4089 19.7 20.5 25.6
5
230 5000 21.7 22.5 28.2
0 N/A N/A N/A
265 3112 11.7 12.5 15.7
2
277 3400 12.3 13.1 16.3
265 3752 14.2 15 18.7
3
277 4100 14.8 15.6 19.5
5 N/A N/A N/A N/A N/A N/A N/A
N/A 10.1 15
8.2
N/A 8.3 15
6.8
6-15P
20 6-20P
30 6-30P
7-20P
20
Table 7 R25H - 15,000 BTU Electrical Specications
Power Supply
Volt 1–60
Volt Min RLA LRA FLA Hp
208/
230V
265V 240 5.6 28.0 0.8 0.125
197 6.6 33 0.8 0.125
Compressor Fan Motor Electric Heat Unit Electrical Ratings
Htr
Volt W HA TCA THA MCA MOCP Plug
#
0 N/A N/A N/A
208 1963 9.4 10.2 12.8 15
2
230 2400 10.4 11.2 14.0 15
208 2454 11.8 12.6 15.7
3
230 3000 13 13.8 17.3
208 2862 13.8 14.6 18.2
4
230 3500 15.2 16.0 20.0
208 4089 19.7 20.5 25.6
5
230 5000 21.7 22.5 28.2
0 N/A N/A N/A
265 3112 11.7 12.5 15.7
2
277 3400 12.3 13.1 16.3
265 3752 14.2 15 18.7
3
277 4100 14.8 15.6 19.5
5 N/A N/A N/A N/A N/A N/A N/A
N/A 9.1 15
7.4
N/A 7.8 15
6.4
6-15P
20 6-20P
30 6-30P
7-20P
20
29 Made in USA
P/N 240010639, Rev. A [06/15/2014]
Page 30
ELECTRICAL SPECIFICATIONS
LEGEND
RLA Rated Load Amps
FLA Full Load Amps
Hp Horse Power
W Watts
HA Heater Amps
TCA Total Cooling Amps
THA Total Heating Amps
MCA Minimum Circuit Amps
MOCP Maximum Over Current Protection
The Right Fit for Comfort 30
P/N 240010639, Rev. A [06/15/2014]
Page 31
LIMITED PRODUCT WARRANTY
RetroAire offers to the original purchaser/owner that under normal use and maintenance for comfort cooling and
conditioning applications, all RetroAire equipment will be free from defects in material and workmanship for a period of 12 months from the documented date of original installation or 18 months from the date of manufacture, if the documented date of original installation is not available. Unit compressors shall be free from defects in materials and workmanship under normal use and maintenance for a period 60 months from the documented date of original installation or 66 months from the date of manufacture, if the documented date of original installation is not available.
WHAT RETROAIRE WILL WARRANT:
ECR will provide a replacement for or, at the discretion of RetroAire, repair any functional component that proves to be defective in material or workmanship, under normal maintenance and operating conditions, within the prescribed warranty period. Said parts will be supplied via standard shipping; billed and then credited back, when the defective component is returned, at the sole discretion of RetroAire. However, the replacement cost shall NOT include labor or service costs to diagnose, remove, or install a warranty part, or return of defective materials, at the sole discretion of RetroAire.
WHAT RETROAIRE WILL NOT WARRANT:
Damages to or arising from: misapplication, improper installation or service; components not supplied or approved by RetroAire, including, without limitation, cabinetry, wall sleeves, louvers, internal components, equipment, or controls supplied by others; and lack of preventative maintenance such as, but not limited to, replacing air filters, general cleaning, clearing condensate drains, air flow adjustments; products manufactured or distributed by RetroAire but installed outside the United States and Canada; unauthorized alteration, application or improper operation; excessively corrosive installation environments; equipment usage during construction; shipping or handling.
RETROAIRE IS ALSO NOT RESPONSIBLE FOR:
Damages caused by faulty or interrupted power supply or electrical service; Damages caused by acts of God including, but not limited to, wind, hail, floods, lightning, earthquakes or other conditions beyond the control of RetroAire.
FURTHER LIMITATIONS:
All implied warranties of merchantability and/or fitness for any particular purpose are limited in duration to the period of the limited warranty. The rights and remedies provided herein are exclusive and constitute the entire contract. This limited warranty and any optional extended warranties are granted only to the original owner/user. This warranty becomes null and void if payment for the goods or product is in default. Warranty remedies may be withheld if the customer account is in arrears or default.
In no event shall RetroAire be liable (whether for breach of this limited warranty or contract, for strict liability for negligence, or otherwise), for any special, incidental, punitive or consequential damages, including, without limitation, damages for loss of profits, loss of goodwill, loss of time or convenience, loss of use of the product, the cost of a product rental, costs of gasoline, electricity, telephone, travel or lodging, or the loss of personal or commercial property, whether or not RetroAire has been advised of the possibility of any such damages.
In no event shall RetroAire’s obligations under this limited warranty exceed the purchase price of the product.
Any repairs performed under this limited warranty shall not in any way extend the statute of limitations for claims under this limited warranty.
No agent, representative or distributor of RetroAire has any authority to alter the terms of this limited warranty in any way.
For Service or Repair:
1) Contact the installing contractor
2) Call the nearest RetroAire sales rep/distributor
3) Call, E-Mail or write:
RetroAire, c/o ECR International, Inc., 2201 Dwyer Avenue, Utica, NY 13501, Ph: 1-800-325-5479
Fax: 1-866-432-7329, E-Mail: info@RetroAire.com, Web: www.RetroAire.com.
31 Made in USA
P/N 240009782 Rev B (9/2013)
P/N 240010639, Rev. A [06/15/2014]
Page 32
TM
ECR International, Inc.
2201 Dwyer Avenue • Utica, New York 13501 Phone: 1.800.325.5279 • Web: retroaire.com
P/N 240010xxx, Rev. A [05/12/2014]
Loading...