ECR CM, CW, WM Installation, Operation & Maintenance Manual

Page 1
R-410A High Efciency Water Source Heat Pump
MODEL CM - Heat pump nominal capacities
e Right Fit for Comfort
8,000 12,000 15,000 Btuh
2.6 3.5 4.4 kW
MODEL CW - Straight cooling / heat pump nominal capacities
8,000 10,000 13,000 17,000 Btuh
2.6 3.5 4.4 5.3 kW
MODEL WM - Heat pump nominal capacities
9,000 12,000 15,000 Btuh
2.6 3.5 4.4 kW
Installation, Operation,
& Maintenance Manual
ECR International INC 2201 Dwyer Avenue Utica, NY 13501 e-mail: info@RetroAire.com
An ISO 9001-2000 Certified Company
CM
Replacement for: Freidrich and Climate Master "801" Series Water Source
WM
Replacement for: McQuay, Singer, or Climate Control WM Series Water Source
CW
New Construction
Replacement for: Freidrich and Climate Master CW and "800" Series Water Source
P/N 240008071, Rev. C [112309]
Page 2
Contents
Water Source Console Units
Installation, Operation, and Maintenance Manual
Read This First
Read This First 2-3
To the installer . . . . . . . . . . . . . . . . . 2
Inspection . . . . . . . . . . . . . . . . . . . 3
General precautions . . . . . . . . . . . . . . . 3
General Product Information 4-7
Product description . . . . . . . . . . . . . . . 4
Standard controls and components. . . . . . . . . . 4
Factory-installed options
Field-installed accessories . . . . . . . . . . . . . 4
CM Chassis . . . . . . . . . . . . . . . . . . . 5
CW Chassis . . . . . . . . . . . . . . . . . . . 5
WM Chassis (Left / Right). . . . . . . . . . . . . . 6
(consult the factory) . . . . . . . 4
Water Source Console Units Model Nomenclature 7
Features 8
Optional wall-mounted thermostats . . . . . . . . . 8
Preparing for the Installation of the Water Source Console Units 9
Electrical power connection . . . . . . . . . . . . 9
Remove the old chassis . . . . . . . . . . . . . . 9
Final Inspection & Start-up 14-19
Before operating the unit . . . . . . . . . . . . . 14
Start Up . . . . . . . . . . . . . . . . . . . . 15
Unit-mounted thermostat . . . . . . . . . . . . . 16
Remote-mounted thermostat . . . . . . . . . . . . 16
Straight cooling Water Source Console Units . . . . .16-17
Heat Pump Water Source Console Units . . . . . . .17-18
Auxillary heat option (Electric) . . . . . . . . . . . . 18
Auxillary heat option (Hydronic) . . . . . . . . . . 18
Maintenance & Troubleshooting 19-20
Monthly inspection and maintenance . . . . . . . . . 19
Seasonal start-up and maintenance. . . . . . . . .19-20
Troubleshooting . . . . . . . . . . . . . . . . 20
Performance Data 21
Electrical Specifications 22-25
Installation Instructions — CM 10
Installation Instructions — CW 11
Installation Instructions — WM (Left) 12
Installation Instructions — WM (Right) 13
To the installer
Retain this manual and warranty for future reference.
Before leaving the premises, review this manual to be sure the unit has been installed correctly and run the unit for one complete cycle to make sure it functions properly.
To obtain technical service or warranty assistance during or aer the installation of this unit, contact your local representative. Visit our web site www.retroaire.com for a local representative listing. For further assistance call 1-800-228-9364.
When calling for assistance, please have the following information ready:
Model Number___________________________________
NOTICE
e RetroAire™ Water Source Console Units are backed by EMI and ECR International and is tested and rated in ac­cordance with:
AHRI Standard 320
UL-484
Due to ongoing product development, product designs and specications may change without notice.
Please contact the factory for more information.
Serial Number____________________________________
Date of installation_________________________________
The Right Fit for Comfort 2 P/N 240008071, Rev. B [112309]
Page 3
Read This First (continued)
Water Source Console Units
Installation, Operation, and Maintenance Manual
Recognize this symbol as an indication of important safety information.
Inspection
Carefully check the shipment against the bill of lading.• Make sure correct chassis has been received (• as well as any op-
tions). Verify your equipment by using "model nomenclature" on •
page 7.
Verify unit:
Unit size and type correct per submial sheet and job requirements?• Voltage correct?•
Verify options (if any):
Capacity, electric heat, if used?• Hydronic coil included, if required? Piping located as required?• All other factory installed options installed, if any?• All eld installed options included, if any?•
Shipping damage MUST be reported to
the carrier IMMEDIATELY.
Examine the exterior.•
General precautions
DANGER
Electrical Supply
Carefully read the rating plate located on the front panel. e RetroAire replacement Water Source Console Units must:
Be properly connected• to electrical supply with the proper voltage as stated on the rating plate.
Be properly grounded• . Use the properly-sized over-current protection •
device as stated on the rating plate. (time-delay fuse/
HACR Breaker)
Do not modify the RetroAire replacement Water Source Console Units
Do not aempt to modify or change this unit in any way. Tam­pering with RetroAire replacement Water Source Console Units is dangerous and may result in serious injury or death. Tamper­ing voids all warranties.
Power Cord-Optional
e power cord sup ter Source Console Units should be checked before every use. Follow the instructions in the order listed on the device use the product if the cord fails the test. A damaged power supply cord must be replaced with a new cord from the manufacturer and not repaired. e use of extension cords is prohibited.
Failure to follow these instructions can result in a re, explo­sion or electrical shock causing property damage, personal injury or death.
WARNING — Safety instructions
plied with the RetroAire replacement Wa-
. Do not
Remove cover and examine • compressor and piping for signs of damage.
Inspect each component for damage.•
Concealed damage must be reported to the carrier • within 15 days of the receipt of the shipment.
e carrier must make proper notation on the delivery • receipt of all damage identied and complete a carrier inspection report.
e purchaser must notify ECR International’s Cus-• tomer Service department of all damage and is respon­sible for ling any necessary claims with the carrier.
Customer Service : (800) 228-9364
P/N 240008071, Rev. B [112309] 3 Made in USA
Save these instructions — this manual is intended as an aid to qualified service personnel for proper installation, operation, and maintenance of RetroAire replacement Water Source Console Units.
Read all instructions thoroughly and carefully before at­tempting installation or operation. Install or locate this unit only in accordance with these instructions. Use this unit only for its intended use as described in this manual.
Turn off the electrical supply before servicing the unit.
Water Source Console Units chassis are heavy. To avoid injury, use assistance when liing.
Do not use the unit if it has damaged wiring, is not working properly, or has been damaged or dropped.
Failure to follow these instructions may result in improper installa­tion, operation, service, or maintenance, possibly resulting in re, electrical shock, property damage, personal injury, or death.
Page 4
General Product Information
Water Source Console Units
Installation, Operation, and Maintenance Manual
Product description
All RetroAire Water Source Console Units units are available as heat pump systems. Model CW is available as a straight cool unit.
e Retroaire Water Source Console Units:
Use R-410A refrigerant.• Include high-eciency rotary compressors, protected by a 5-year •
warranty. Include enhanced, high-eciency heat exchangers.• Oer two fan speeds. • RetroAire Water Source Console Units ratings:• Water Source Console Units units are available in nominal sizes of •
8,000 Btuh (2.3kW), 9,000 Btuh (2.6kW), 10,000 Btuh (2.9kW), 12,000 Btuh (3.5kW), 13,000 Btuh (3.8kW), 15,000 Btuh (4.4kW) or 17,000 Btuh (4.9kW).
Energy Eciency Rating(EER) in excess of 13. • Coecient of performance(COP) in excess of 4 for (heat pump •
models only)
Standard controls and components
Controls
Unit-mounted operating controls include thermostat, fan speed control • and heat/cool switch.
Remote mount controls include fan speed control.• High pressure switch.• Low Temperature/Low water ow cut out switch compressor lock •
out relay 4-Way reversing valve with solenoid activated by line voltage. Solenoid •
is energized for cooling mode. (Heat pump models only)
Factory-installed options (see model nomenclature p.7)
Voltage• Electric Heat/Hydronic Heat• Piping• Cabinet options• Pipe connection• Control•
Construction
20-gauge galvanized steel Water Source Console Units construc-• tion of chassis.
Powder-coated evaporator drain pan.• Foam strip seal for supply air duct.•
Air systems
Indoor fan motor is are thermally-protected PSC type. • Air-stream surfaces are insulated with ¹∕₄" ber-glass or ¹∕₈" (3.2 mm) •
Volara™. e indoor fan is a foward-curved type, directly mounted to the •
motor sha.
Field-installed accessories
Remote thermostat• Hydronic heat valves• Cabinets•
NOTICE
RetroAire units can be equipped with either unit-mounted or remote controlled thermostats. Specify when ordering.
The Right Fit for Comfort 4 P/N 240008071, Rev. B [112309]
Page 5
CM ChassisFigure 1
Water Source Console Units
Installation, Operation, and Maintenance Manual
High Volt
Connection
CONDITIONED AIR
Thermostat
Rating Plate
Fan Speed Switch (FSS)
System Switch (SS)
H20
IN
Wire Diagram
H20
OUT
Master
Slave
CW Chassis Figure 2
Optional
INLET AIR
High Volt
Connection
CONDITIONED AIR
Thermostat
Fan Speed Switch (FSS)
System Switch (SS)
Low Volt Program Relay
P/N 240008071, Rev. B [112309] 5 Made in USA
Rating Plate
H20
IN
Wire Diagram
H20
OUT
INLET AIR
Optional
Page 6
H20
Water Source Console Units
Installation, Operation, and Maintenance Manual
H20
OUT
IN
Rating Plate
INLET AIR
WM Chassis (Left)Figure 3
CONDITIONED AIR
Wire Diagram
Filter
SYSTEM SWITCH (SS)
FAN SPEED SWITCH (FSS)
THERMOSTAT
WM Chassis (Right)Figure 4
THERMOSTAT
FAN SPEED SWITCH (FSS)
SYSTEM SWITCH (SS)
Wire Diagram
INLET AIR
CONDITIONED AIR
Rating Plate
Filter
H20
IN
High Volt
Connection
H20
OUT
CONDENSATE
DRAIN STUB
The Right Fit for Comfort 6 P/N 240008071, Rev. B [112309]
Page 7
CM, CW, WM Model Nomenclature
Water Source Console Units
Installation, Operation, and Maintenance Manual
Model codingFigure 5
Position number:
1 2 43 5
Chassis coding
[verify with rating plate]
Product Series
[
series ]
CM
series ]
[
CW
series ]
[
WM
Straight cool or Heat Pump
[
= straight cooling (CW Series Only)]
C
H = heat pump unit ]
[
Refrigerant
G = 410A
Cooling Capacity (Btuh)
[
= 08,000 Btuh (CM and CW Series Only)]
08
09 = 09,000 Btuh (WM Series Only)]
[
10 = 10,000 Btuh (CW Series Only)]
[
= 12,000 Btuh (CM and WM Series Only)]
[
12
13 = 13,000 Btuh (CW Series Only)]
[
= 15,000 Btuh (CM and WM Series Only)]
[
15
= 17,000 Btuh (CW Series Only)]
[
17
Voltage
[
A = 115 V / 1 / 60 ] (CW Series Only)
[
D = 208/230 V / 1 / 60 ]
[
E = 265/277 V / 1 / 60 ]
Heat Options (230 Volts)
[
= No electric heat ]
0
[
2 = 2 kW electric heat ]
[
3 = 3 kW electric heat ]
[
4 = 4 kW electric heat ]
[
5 = 5 kW electric heat ]
[
6 = 1 Row Hydronic Coil N/C Valve (CWC Right Hand Pipe Only ]
[
7 = 1 Row Hydronic Coil N/O Valve (CWC Right Hand Pipe Only ]
Control Options
[ 0 = Unit Mount MCO]
1 = Unit Mount MCO Boiler less (Heat pump with Electric Heat Only]
[
2 = Unit Mount MCO with Disconnect Switch]
[
3 = Unit Mount MCO Boilerless (Heatpump with Elect Heat Only)]
[
4 = Unit Mount ACO]
[
5 = Unit Mount ACO Boilerless (Heat Pump with Elect Heat Only)]
[
6 = Unit Mount ACO with Disconnect Sw.]
[
7 = Unit Mount ACO Boilerless (Heat Pump with Elect Heat Only
[
and Disconnect Sw.)
P/N 240008071, Rev. B [112309] 7 Made in USA
]
7 8 9 10 11 12 13
6
Pipe Connections
[
= Sweat Connection]
0
1 = Female Pipe Thread]
[
2 = Male Pipe Thread]
[
3 = Ball Valve & Union]
[
4 = Sweat Connection with
[
Cupronickel Water Coil
5 = Female Pipe thread
[
with Cupronickel Water Coil
6 = Male Pipe thread with
[
Cupronickel Water Coil
7 = Ball Valve & Union with
[
Cupronickel Water Coil
Cabinet Options
[
= No Cabinet]
A
B = With Cabinet (CW Series Only)]
[
C = Cabinet with Locking Door (CW
[
Series Only
D = Front Air Intake (CW Series Only)]
[
Piping Options
[
= Left Hand Piping]
L
R = Right Hand Piping]
[
M = Left Mono Flow Piping]
[
N = Right Mono Flow Piping]
[
Control Options (Con't)
[
= Remote]
A
B = Remote Master / Slave]
[
C = Remote with Disconnect Sw.]
[
D = Remote Master / Slave with Disconnect Sw.]
[
E = Remote Boilerless (Heat Pump with Elect Heat Only)]
[
F = Remote Master / Slave Boilerless (Heat Pump with Elect Heat
[
Only)
G = Remote with Boilerless (Heat Pump with Elect Heat Only) and
[
Disconnect Sw.
H = Remote Master / Slave with Boilerless (Heat Pump with Elect Heat
[
Only) and Disconnect SW.
]
]
]
14
Design Revision
[
= Rev Level ]
A
Standard/Special
[
= standard ]
0
[
= special option ]
A-Z
Compressor Code
[
= Tech]
A
L = LG]
[
T = Toshiba]
[
]
15
]
]
]
]
Page 8
Features
Water Source Console Units
Installation, Operation, and Maintenance Manual
Indoor coil freeze protection (standard)
is feature will prevent the indoor coil from freeze up in the cooling mode.
Indoor coil freeze up can occur due to a dirty air lter, restricted • or poor air ow, low refrigerant charge or low room or coil water temperatures.
Low temperature water ow cut-out switch.• High pressure control.• Should a freeze condition be detected, the compressor will be •
switched o until the freeze condition is satised. During this time the indoor fan will continue to run to aid in the •
defrost process.
Power cord with integral safety protection (optional)
Water Source Console Units
have the option of a power cord
with internal safety protection.
Provides personal shock protection as well as arcing and re preven-• tion, e device is designed to sense any damage in the line cord and disconnect power before a re can occur.
Tested in accordance with Underwriters Laboratories, the cord set • also oers a unique “passive” operation, meaning the unit does not
require reseing if main power is interrupted.
Heat pump (optional)
Heat pumps are designed to operate when entering water temperature is between 60°F(16°C) to 90°F(33°C) and with a maximum indoor air temperature of 80°F(27°C). e unit is equipped with a reversing valve
that is energized for cooling and de-energized in heating mode.
Optional wall-mounted thermostats
Thermostats available from EMI
EMI oers a thermostat that is compatible with your Water Source Console Unit.
Select EMI part number 240008208 for the latest RetroAire price • list for this option. is is a single stage, cool/heat, thermostat that can be used in all RetroAire cooling, heating or heat pump applications.
The thermostat has an adjustable setpoint range of between • 45°F(7°C) and 90°F(32°C).
For heat pumps another option is EMI part number 240008209. • is is a 2 stage heat/cool thermostat which allows for emergency
heat.
Selecting a thermostat (by others)
When selecting a thermostat other than one oered by EMI, choose a single stage heat/cool, 24v thermostat.
Straight cooling with electric heat or hydronic heat
Select a thermostat that is compatible with a cooling/electric heat sys­tem. e thermostat should have “R”, “Y”, “W” and “G” terminals.
Heat pump
Select a thermostat that is compatible with a cooling/single-stage heat/heat pump system. e thermostat should have “R”, “ Y”, “ O” and “G” terminals. RetroAire units are single stage heating only.
Hydronic heating (optional)
An optional hydronic heat package may be selected in lieu of electric heat. Heating operation is essentially the same as that of units with
electric heat.
The Right Fit for Comfort 8 P/N 240008071, Rev. B [112309]
Page 9
Preparing for the Installation of the Water Source Console Units
Water Source Console Units
Installation, Operation, and Maintenance Manual
WARNING
Moving parts can cause personal injury. Avoid contact with moving parts when testing or servicing the unit.
e existing front panels must be secured by screws that prevent contact with all parts.
Minor dimensions of openings must not exceed ½ inch (12.5mm).
e indoor air discharge grill must have dimensions not less than 26” x 4”. e grill must separate the top surface of the chassis from the top surface of the discharge grill by a minimum of 1 in (25.4mm).
Electrical supply
Each unit must have a separate branch circuit protected by a fuse or breaker. Refer to the unit rating plate for the proper wire and breaker or fuse size. Use of extension cords is prohibited.
DO NOT connect the RetroAire unit to a circuit with an incorrectly-sized overcurrent-protection device.
All cord-connected 265-volt units must be plugged into recep­tacles within the unit subbase or chassis.
Electrical shock hazard — Before opening the existing unit:
Open the power supply disconnect switch. Secure it in an open position during installation. Aach a sign stating, "
TURN ON.
On a plug and receptacle connection, unplug the existing unit at the wall outlet. DO NOT plug in the new unit until installation is complete and the start-up checklist has been completed.
Failure to comply with the above could result in severe personal injury, death or substantial property damage.
"
DO NOT
NOTICE
All wiring should be in accordance with both the National Electric Code (NEC) and the local building codes.
Electrical power connection
Check the RetroAire unit rating plate for circuit ampacity and 1. required breaker or fuse size.
Verify that the existing breaker or fuse is the correct size.2.
Replace the breaker or fuse if incorrectly-sized.a. Breakers must be type HACR only.b.
Cord-connected units — verify that the wall outlet is the cor-3. rect rating. e outlet's blade conguration must match that of the cord supplied with the RetroAire unit.
Hard-wired units — verify that the power wiring is correctly 4. sized. Inspect the existing wiring for any deciencies, such as cuts or frayed wires. Replace such wiring if found. Refer to the units wire diagram for wire connections.
Remove the old chassis
Disconnect power or unplug cord before proceeding. 1. See WARNING at le.
Remove the cabinet from the old chassis.2. Disconnect water supply to coil.3. Disconnect condensate drain piping4. Remove any fasteners holding the old chassis to the sub base or 5.
wall and remove the chassis.
NOTICE
Dispose of the old chassis following existing state and federal regulations.
See the instructions for the specic RetroAire unit on the fol-1. lowing pages.
DO NOT2. connect power to the unit or plug in the cord until all instructions in this manual have been followed.
INSTALLATION
Put the new chassis in the same place where the old chassis 1. stood, and secure it to the subbase or wall as the older unit was secured.
Pipe the new chassis with the same hoses(check the hose for cracks 2. and/or brileness, replace with new hoses if any damage is found). If the unit is to be hard piped, there should be union between the unit and the hand shut o valve for service or removal of the unit. Connect condensate tube, and route to an adequate drain.
Plug the line cord into the receptacle. If hard wired; connect 3. power wiring to unit wires in the J-box.(See wiring diagram on unit). Wiring must be made in accordance with NEC and local codes.Follow the instructions on page 9 to verify existing wiring and overcurrent protection. Remove the line cord wires from the Water Source Console Units power entrance terminals. Route the power supply wiring through a strain-relief bushing and connect leads to the power entrance terminals. Secure the strain-relief clamp. (If wiring is through conduit, insert the conduit through the control box knockout and secure in place.) DO NOT turn on power until completing instructions in "Final Inspection and Startup" on page 14.
Open water valves. Bleed air from the water lines with the air 4. vent(if used) or by uncoupling the return water line allow any air to escape. If the water appears dirty the entire water system should be ushed with the proper cleaners to obtain a PH value of 7 or 8. Exercise caution if any sort of glycol(antifreeze) is be­ing used when cleaning the system. Be careful not to let this uid get on any carpeting ect. It is best to use trained personnel to do this type of work.
DO NOT PLUG IN the line cord, if in used condition5. . Follow instructions in "Final Inspection and Startup" on page 14.
P/N 240008071, Rev. B [112309] 9 Made in USA
Page 10
Installation Instructions — CM Chassis
Water Source Console Units
Installation, Operation, and Maintenance Manual
CM chassisFigure 6
J Box
High Volt
Connections
TOP
FRONT
Rating
Plate
Wire Diagram
Water Coil
Connections
H2O IN
H2O OUT
The Right Fit for Comfort 10 P/N 240008071, Rev. B [112309]
5/8" ID tube condensate
drain connection
Page 11
CW chassis Figure 7
Water Source Console Units
Installation, Operation, and Maintenance Manual
J Box
High Volt
Connections
INSTALLATION FOR NEW CONSTRUCTION
Installation Instructions — CW
FRONT
Rating Plate
TOP
Wire Diagram
Water Coil
Connections
P/N 240008071, Rev. B [112309] 11 Made in USA
5/8" ID tube Condensate
Drain Connection
Page 12
Installation Instructions — WM Left
Water Source Console Units
Installation, Operation, and Maintenance Manual
WM chassis Figure 8
TOP
FRONT
J Box
High Volt
Rating
Plate
Wire Diagram
Connections
Install 2" x ¹∕₂" foam tape
The Right Fit for Comfort 12 P/N 240008071, Rev. B [112309]
Water Coil
Connections
5/8" OD Pipe Condensate
Drain Connection
Page 13
Installation Instructions — WM Right
Water Source Console Units
Installation, Operation, and Maintenance Manual
WM Right chassis and installation kit contents Figure 9
TOP
FRONT
J Box
High Volt
Connections
Wire Diagram
Rating Plate
Water Coil
Connections
P/N 240008071, Rev. B [112309] 13 Made in USA
5/8" OD Pipe
Condensate
Drain
Connection
Page 14
Before operating the unit
Water Source Console Units
Installation, Operation, and Maintenance Manual
Read and understand the contents of this manual.
Install the unit per the instructions outlined in this manual and
all applicable local and national codes.
Ensure the electrical supply matches the electrical requirements
of the unit, and that the unit is properly grounded.
Examine control box. Ensure all wire connections are secure.
Verify that the chassis is properly ed to the cabinet and securely
mounted to the sub base or oor.
Make sure the chassis is level:
Pour water into the drain pan and make certain it ows from the
drain pan to the condensate drain
Final Inspection & Start-up
Any obstruction of supply air, including the use of deector baes, may cause condensate to form on the louver or cabinet (see Figure 10).
CAUTION
Proper air flow diagramFigure 10
Verify that indoor blower wheels are secured to the motor sha,
and rotate freely.
Ensure all sheet metal panels are in place and secure.
Aach the front panel to the existing cabinet enclosure.
Verify that nothing will interfere with the room discharge air or
the return air of the units. Examples:
Check for curtains or drapes that obstruct the air ow.•
See • Figure 10 and Figure 11.
Check for plush carpeting that can obstruct the return air.•
Items like these can cause serious damage to the chassis.•
To ensure optimum performance of your Water Source Console Unit, avoid restricting the air ow. e position of curtains or drapes over supply air grille may cause air to recirculate with­out cooling the room. e unit will short cycle and may cause premature compressor failure (see Figure 11).
Restricted air flow diagramFigure 11
The Right Fit for Comfort 14 P/N 240008071, Rev. B [112309]
Page 15
Final Inspection & Start-up (continued)
Water Source Console Units
Installation, Operation, and Maintenance Manual
Start Up
Use the procedure outlined below to initiate proper unit start up.
Adjust all hand water valves to the full open position, and turn 1. on the power to the units. (If when taking the old unit out you marked the position of the hand water valve handle put it back to that position rather than full open.)
Operate each unit in the cooling cycle first. Set thermostat 2. temperature lower than the room temperature and depress the "Cool" buon. e entering water temperature (EWT) should be at least 60°F(16°C). for start up. e unit will start discharging cool air almost instantly. Aer the unit has been running about 5 minutes check the temperature of the EWT and the leaving water temperature (LWT). e dierence should show a higher LWT by about 10-12°F(6-7°C). If you nd you have this dierence you also have the correct water ow. If the dierence is less then 10­12°F (6-7°C) you have too much water owing through the unit and if the dierence is higher then you don’t have enough water owing through the unit. You will have to adjust the hand water valve to get the temperature dierence needed.
Check the heating operation of the unit, turn the thermostat to 3. slightly above room temperature and depress the "Heat" buon. e compressor and fan will operate. Aer about 5 minutes of operation check the water temperature of the EWT & LWT. For correct water ow adjust the hand valves until the LWT is 6°F(3°C) less than the EWT.
Unit Mount ACO (Automatic change-over) with Fan Cycle 4. Switch (Optional): is option allows the operator of the CWC/ CWH/CMH to have the evaporator fan cycle or run continuously. With the switch in the cycling position the evaporator fan will only run when the unit is calling for heat or cooling. When the switch is in the “constant” position, the evaporator fan will run continuously unless the unit is physically turned o.
NOTE: ree factors determine the operating limits of RetroAire heat pump units:
1. Return air temperature
2. Water temperature
3. Ambient temperature
Whenever any one of these factors is at a minimum or maximum level, the other two factors must be at normal levels to ensure proper unit operation.
Operating Limits
WMH Operating Limits
Air & Water Limits
Min. Ambient Air 50(10) 50(10)
Rated Ambient Air 80(27) 70(21)
Max. Ambient Air 100(38) 85(30)
Mim. EAT 50(10) 70(21)
Rated EAT DB/WB 80/67(27/20) 60(16)
Max. EAT DB/WB 100/83(38/29) 80(27)
Water Limits Cooling
Min. EWT 60(16) 60(16)
Normal EWT 85(30) 70(21)
Max. EWT 95(35) 90(33)
CM/CW Operating Limits
Air & Water Limits Cooling
Rated *EAT DB/WB
Rated**EWT
Rated***LWT
Max.EWT
Max.EWT
Min.*EAT DB/WB
Min.*EWT
Water Limits Cooling
Min. EWT
Normal EWT
Max. EWT
(*'EAT' and Ambient Temp. Surrounding the unit are the same value)
°F
°F
°F
°F
°F
STARTING CONDITIONS
Unit will start and operate with entering air temperature(EAT) of 50°F(10°C) and entering water temperature(EWT) of 60°F(16°C) with both the air and water at the ow rates used in the ARI Stan­dard 320/86 rating test, for initial start up in winter. is is for start up only not long time running.
If the unit fails to operate, check the following:
Cooling
°F(°C)
°F(°C)
°F(°C)
°F
80/67(27/20) 70/60(21/16)
°F
°F
°F
°F
85(30) 70(21) 95(35) N/A
95/71(35/22) 80/67(27/20)
95(35) 90(33)
67/57(20/14) N/A
65(19) N/A
°F(°C)
60(16) 60(16) 85(30) 70(21) 95(35) 90(33)
Heating
Heating
Heating
Heating
°F(°C)
°F(°C)
°F(°C)
°F(°C)
P/N 240008071, Rev. B [112309] 15 Made in USA
a. Check the voltage and current. it should be in accordance with the electrical specications on the unit rating plate.
b. Look for wiring errors. check for loose terminals or wire nuts where wire connections have been made on both the line and low­voltage terminal boards.
c. Check for water leaks around hose swivel joints, If hard piped check all joints. Aer the unit is running check for leaks around the condensate drain hose and connection.
d. Ensure the High Pressure Switch (HPS) did not trip. Cycle the system switch o to reset the lockout relay.
Page 16
Final Inspection & Start-up (continued)
Water Source Console Units
Installation, Operation, and Maintenance Manual
Determine whether the fan operates during heating and cooling modes. If these checks fail to reveal a problem and the unit will not operate, contact a trained service technician for proper diagnosis or call the factory service department for assistance.
eUnit-mounted thermostat
Use the system switch to place the Water Source Console Units in 1. either the "COOL", "HEAT", or "OFF" position (see Figure 12). Test operation in all positions.
Use the fan speed switch places the fan in either LOW or HIGH 2. speed (see Figure 12). Test operation in both positions for heat­ing and cooling.
Test operation of the optional Fan Cycle switch (this is a toggle 3. switch on side of control box), with switch set at ON (continuous fan operation) or AUTO (cycling with thermostat) for both heat­ing and cooling. Set the switch in the desired position.
Rotate the thermostat knob counter clockwise to increase setpoint 4. temperature, or clockwise to decrease (see Figure 12). Turning the unit-mounted thermostat knob counter clockwise until it stops will produce the warmest room temperature, while turning it clockwise until it stops will produce the coolest. e seing can be adjusted for personal comfort.
Boilerless control operation-Optional
For Heat pump units with an optional Boilerless control and • electric heat, the heat pump and electric heat do not operate simultaneously.
e Boilerless control will monitor incoming water temperature • to the heat exchanger and when it drops below approximately 50°F the control will change from heat pump operation to electric heat.
Typical Representation of a Unit Mount ControlFigure 12
Remote-mounted thermostat
Use the thermostat to place the Water Source Console Unit in 1. either the "COOL", "HEAT", or " in all positions.
If the thermostat is ed with a2. the fan in either "ON", "OFF", or "AUTO". Test operation in all posi­tions.
Check thermostat calibration for both heating and cooling op-3. eration.
OFF"
position. Test operation
fan switch, set as desired places
Straight cooling Water Source Console Units
CAUTION
DO NOT rotate the thermostat knob back and forth from heating to cooling. is causes the compressor to cycle on and o rapidly and will cause damage to the compressor. Allow the compressor to remain o for at least three minutes prior to restarting the unit.
The Right Fit for Comfort 16 P/N 240008071, Rev. B [112309]
Cooling cycle
Place the thermostat or system switch in the COOL position.1. Adjust the thermostat to a cooler temperature until the indoor fan 2.
starts running. e compressor should then turn on and cold air will begin to ow from the unit. Let the unit continue operating to cool the room and remove humidity.
Aer the unit starts running and the space gets cooler, adjust the 3. thermostat to a warmer temperature until the compressor cycles o.
If a colder room temperature is desired, adjust the thermostat to a 4. cooler temperature seing, turning the compressor and fan back on.
If a warmer room temperature is desired, adjust the thermostat to 5. a warmer temperature seing, the compressor will stop.
Place the thermostat or system switch in the OFF position. 6. All operation should stop.
Page 17
Final Inspection & Start-up (continued)
Water Source Console Units
Installation, Operation, and Maintenance Manual
NOTICE
e room temperature must be above 65°F (18°C) for the com­pressor to operate in cooling mode on Water Source Console Units with unit-mounted controllers.
CAUTION
When the unit is rst powered up, high humidity conditions can cause condensation to form on the discharge grill. Keep doors and windows closed to reduce humidity and condensa­tion will evaporate.
Heating cycle electric option
Place the thermostat or system switch in the 1. HEAT position.
Adjust the thermostat for a warmer temperature until the indoor 2. fan starts running and the electric heater coil starts emiing heat.
Aer the unit starts running and the space gets warmer, adjust 3. the thermostat to a cooler temperature until the electric heater turns o.
If a warmer room temperature is desired, adjust the thermostat to 4. a warmer temperature seing, which will turn the electric heater back on.
If a cooler room temperature is desired, 5. to a cooler temperature seing e fan will stop.
Place the thermostat or system switch in the 6. OFF position. All operation should stop.
until the electric heater turns o.
adjust the thermostat
NOTICE
Room temperature must be below 85°F (29.4°C) to energize the heater controllers.
on Water Source Console Units with unit-mounted
Heating cycle — hydronic option
NOTICE
Make sure the motorized valve is rated for the correct voltage. Most RetroAire units with unit mount controls will power a hydronic valve that is the same voltage as the unit (ex: a unit rated 208/230V will power a 208/230V). Be sure to check the wiring diagram (located on the unit) and voltage application for the specic unit. Other valve congurations and voltage options are available. Consult Technical Service if the unit voltage does not match your valve application.
Place the 1.
Adjust the thermostat to a warmer temperature. 2. e following should then occur:
thermostat or
e motorized valve should open and allow hot water to run • through the coil.
system switch in the HEAT position.
e indoor fan will run, blowing air through the hydronic coil.• e signal to the water valve will continue until the room tem-•
perature rises above the setpoint by 3°F (2°C).
Aer the unit starts running and the area gets warmer, adjust the 3. thermostat to a cooler temperature, the hydronic valve will close and indoor fan will switch o .
If a warmer room temperature is desired, 4. a warmer temperature seing and turn on the indoor fan.
If a cooler room temperature is desired, a5. a cooler temperature seing and fan will stop.
Place the thermostat or system switch in the 6. OFF position. All operation should stop.
, which will open the hydronic valve
. e hydronic valve will again close
adjust the thermostat to
djust the thermostat to
NOTICE
Room temperature must be below 85°F(29°C) for the hydronic heater to operate.
Heat Pump Water Source Console Units
NOTICE
e unit is equipped with a reversing valve that is energized for cooling and de-energized in heating mode.
Cooling cycle — heat pump units
Place the thermostat or system switch in the 1. COOL position.
Adjust the thermostat to a cooler temperature until the indoor 2. fan starts running. e compressor will then turn on and cold air will begin to ow from the unit. Allow the unit continue operating to cool the room and remove humidity.
Aer the unit starts running and the space gets cooler, adjust the 3. thermostat to a warmer temperature until the compressor cycles o.
If a colder room temperature is desired, adjust the thermostat to a 4. cooler temperature seing, turning the compressor and fan back on.
If a warmer room temperature seing is desired, adjust the ther-5. mostat to a warmer temperature. e cooling mode will cease and the compressor and fan will stop.
Place the thermostat or system switch in the 6. OFF position. All operation should stop.
NOTICE
e room temperature must be above 65°F (29°C) for the com­pressor to operate in cooling mode on Water Source Console Units with unit-mounted co
Place system switch in the 7. OFF position. All operation should stop.
ntrollers
.
P/N 240008071, Rev. B [112309] 17 Made in USA
Page 18
Final Inspection & Start-up (continued)
Water Source Console Units
Installation, Operation, and Maintenance Manual
Heating operation — heat pump units — Enter­ing Water temperature above 60°F (16°C)
Place 1.
the thermostat or
Adjust the thermostat to a warmer temperature seing 2. Compressor and fan start running. from the unit.
Aer the unit starts running and the space gets warmer, adjust the 3. thermostat to a cooler temperature until the fan and compressor turn o.
For a warmer room temperature, 4. temperature
If a cooler room temperature is desired, 5. a cooler temperature seing compressor and fan will stop.
Room temperature must be below 85°F (29°C) sor to operate in heating mode on Water Source Console Units with unit-mounted co
Place the thermostat or system switch in the 6. OFF position. All operation should stop.
seing
Auxiliary heating operation — electric option
Place 1.
the thermostat or
Adjust the thermostat to a warmer temperature until the fan starts 2. running and the electric coil starts emiing heat.
Aer the unit starts running and the space gets warmer, adjust 3. the thermostat to a cooler temperature until the electric heater and fan turn o.
If a warmer room temperature is desired, adjust the thermostat to 4. a warmer temperature seing, which will turn the electric heater and fan back on.
If a cooler room temperature is desired, 5. to a cooler temperature turn o.
Place the thermostat or system switch in the 6. OFF position. All operation should stop.
system switch in the "HEAT" position.
until the
Warm air will begin to ow
adjust the thermostat to a warmer
turning the fan, and compressor back on
adjust the thermostat to
. e heating mode will cease and
NOTICE
for the compres-
ntrollers. .
system switch in the "HEAT" position.
adjust the thermostat
seing until the electric heater and fan
.
the
Auxiliary heating operation— hydronic option
Place 1.
the thermostat or
Adjust the thermostat to a warmer temperature. 2. e following should then occur:
e motorized valve should open and allow hot water to run • through the coil.
e indoor fan will run, blowing air through the hydronic coil •
e signal to the water valve will continue until the room tem-• perature rises above the setpoint by 3°F (2°C).
Aer the unit starts running and the space gets warmer, the • hydronic valve will close and the fan will turn o.
Aer the unit starts running and the space gets warmer, 3. thermostat to a cooler temperature seing, close and fan will turn o.
If a warmer room temperature is desired, 4. a warmer temperature seing and turn on the fan.
If a cooler room temperature is desired, adjust the thermostat to 5. a cooler temperature seing. e hydronic valve will close and fan will turn o.
Place the thermostat or system switch in the 6. OFF position. All operation should stop.
system switch in the "HEAT" position.
adjust the
the hydronic valve will
adjust the thermostat to
, which will open the hydronic valve
NOTICE
Room temperature must be below 85°F (29°C) for the hydronic heater to operate on Water Source Console Units with unit-mounted controllers. e hydronic valve is a 24Vac normally open valve. Should power be lost to the unit, the valve will default to the open position.
NOTICE
Room temperature must be below 85°F(29°C) to energize the heater
on Water Source Console Units with unit-mounted
controllers.
The Right Fit for Comfort 18 P/N 240008071, Rev. B [112309]
Page 19
Maintenance & Troubleshooting
Water Source Console Units
Installation, Operation, and Maintenance Manual
Monthly inspection and maintenance
DANGER
Electrical shock hazard — disconnect power to the RetroAire replacement Water Source Console Units before servicing or accessing the control compartment. Failure to do so could result in severe personal injury or death.
WARNING
It is illegal to discharge refrigerant into the atmosphere. Use proper reclaiming methods and equipment when servicing a RetroAire replacement Water Source Console Unit.
For optimum performance and reliability of your RetroAire replace­ment Water Source Console Unit, ECR International recommends performing the following inspections and maintenance on a monthly basis. Units that are installed in harsh or dirty environments will require more frequent inspections and maintenance.
Disconnect power to unit and remove necessary access panels.
Clean or replace the return air lter.
Clean or replace the return air lter as needed. Allowing dust to collect on the lter will cause the unit to lose eciency and eventually malfunction. Check the lter at least once a month. Some environments may require more frequent replacement, depending on particulate in the air stream.
If a new air lter is needed for your RetroAire replacement Water Source Console Unit, consult factory for availability and/or proper sizing.
Vacuum return air grille surface.
Inspect & clean the chassis interior for rodent or insect infestation.
Clean & ush condensate drain pan.
Ensure the condensate drain is functioning properly.
Inspect refrigeration tubing, especially braze joints, for signs of ☐ refrigerant leaks (oil residue). Repair if necessary.
Inspect coil. Ensure dirt or debris have not collected on the ns. ☐ Clean if necessary. Be careful not to damage coil ns when cleaning. Use a n comb to straighten any bent ns.
Examine control box. Ensure all wire connections are secure.
Ensure blower wheels are secured to their motor shas.
Ensure dirt or debris have not collected on the blower wheels . ☐ Use a vacuum and so brush to clean if necessary.
If the unit has a hydronic option installed, inspect piping, espe- ☐ cially braze joints, for signs of water leaks. Repair if necessary.
Clean the exterior of the cabinet as desired with a mild soap or ☐ household cleaner.
P/N 240008071, Rev. B [112309] 19 Made in USA
WARNING
NOTICE
In the event the limit switch opens and de-energizes the electric heat, ☐ the limit switch will need to be manually reset.
To reset switch:
Remove the control box cover. • Locate the limit switch. • Push in the reset buon on the face of the switch (see • Figure 13).
Figure 13 Manual Reset Limit Switch
Reset Button
*Note:
Button will pop out when limit switch opens. Push in to reset.
Seasonal start-up and maintenance
At the beginning of the cooling and heating seasons, a complete me­chanical check should be performed and maintenance/inspections performed as described below.
Disconnect power to unit and remove necessary access panels.
Perform the inspections and maintenance dened in "Monthly 1. start-up and maintenance."
Do a visual check of the equipment. Look for obvious changes in 2. the unit such as damaged coils or evidence of extended wear on any moving parts.
Check for unusual odors, oil leaks, or stains on or around the 3. coil and refrigerant lines. e presence of oil here may indicate a potentially serious problem such as a refrigerant leak (example
— burned motor windings, water, or reigerant).
Make sure the base pan is clean.4. Inspect all electrical connections.5. Look for frayed wires and poor
connections. Terminal ends that are loose will eventually fail, caus­ing a loss of performance or possible damage to equipment.
Check fan motor and blower assemblies. Some units may require 6. a drop of light oil to motors and/or bearing assemblies (look for oil cups). Ensure setscrews and motor mounting hardware are tight.
Brush and/or vacuum the centrifugal fan blades and blower cage 7. assemblies, as they must be clean to operate eciently.
If the unit has a hydronic option installed, inspect piping, espe-8. cially braze joints, for signs of water leaks. Repair if necessary.
Clean or replace the return air lter.9. Vacuum return air grille surface.10. Inspect & clean the chassis interior for rodent or insect infestation.11. Inspect coils. Use a n comb to straighten out any damaged ns. 12.
coils must be clean for proper operation.
ese
Page 20
Maintenance & Troubleshooting (continued)
Water Source Console Units
Installation, Operation, and Maintenance Manual
WARNING
Do not use a solvent-based cleaner to clean coils, as some solvents will produce a noxious odor when the unit is in operation.
Inspect and clean the drain pan and drain line(s). e use of an 13. anti-fungicide tablet to keep the condensate system free from bacterial contaminants is recommended.
Ensure the unit is level. Over time the building and equipment 14. may sele, causing a shi in the direction of the condensate ow.
Replace the access panels and reconnect the electrical power.15. Test the unit operation. 16.
Troubleshooting
WARNING
e troubleshooting procedures below should only be conducted by a qualied technician.
Symptom Suggestion
No heat or cooling Check to see if the unit has power and if the thermostat is satised. If the thermostat is not •
satised, call your installing contractor or service contractor.
e thermostat calls for cooling, but cool air is not coming out of the unit.
e thermostat calls for heat, but no heat comes out of the unit.
e thermostat calls for heat while in heat pump mode, but heated air is not coming out of the unit.
Check for continuity between the thermostat and the unit. Also make sure 24 Vac is present • across terminals C and R.
Ensure the water is owing through the water coil. Locate the high pressure switch reset • buon and push buon.
Some units are equipped with an • LCDI (Leakage Current Detection Interrupt) line cord. Make sure this line cord is reset by pressing the reset buon at the line cord plug.
Note: If the indoor fan is operational and all of the above suggested procedures have been • followed, and there is still no cooling being supplied by the unit, then contact a trained heating and cooling professional.
Check to see if the unit has power or if the thermostat has been satised. If the unit has • power and the thermostat is satised, set the thermostat a above room temperature.
Units equipped with electric heaters have a temperature limit switch to prevent the electric • heater from reaching unsafe temperatures. If aer calling for heating the heater is not ener­gized, check for continuity across the limit. If the limit is open, replace with an equivalent limit switch. Auto reset / Manual reset Switch.
If the unit is equipped with a LCDI Line Cord, Ensure it is not tripped. (See • Page 8 for information.)
While in heat pump mode, make sure the thermostat is not energizing the • O terminal. RetroAire units are designed to work in heat pump mode when 24Vac is present across Y and C.
Check to see if the unit has power or if the thermostat has been satised. If the unit has • power and the thermostat is satised, set the thermostat a above room temperature.
The Right Fit for Comfort 20 P/N 240008071, Rev. B [112309]
Page 21
Performance DataTable 1
Water Source Console Units
Installation, Operation, and Maintenance Manual
Voltage Model
CMHG08 9,400 (2.7) 13.2 10,200 (3.0) 3.9 350 (165) 140 (64)
CMHG12 12,900 (3.8) 12.9 13,100 (3.8) 4.2 450 (212) 140 (64)
CWHG08 9,400 (2.7) 13.2 10,200 (3.0) 3.9 350 (165) 150 (68)
CWCG08 9,400 (2.7) 13.2 N/A N/A 350 (165) 150 (68)
115V
208/230V
CWHG10 13,000 (3.8) 12.9 13,100 (3.8) 4.2 400 (189) 160 (73)
CWCG10 13,000 (3.8) 12.9 N/A N/A 400 (189) 160 (73)
CWHG13 17,500 (5.1) 11.9 19,500 (5.7) 3.7 450 (212) 165 (75)
CWCG13 17,500 (5.1) 11.9 N/A N/A 450 (212) 165 (75)
WMHG09 9,200 (2.7) 12.9 10,000 (3.0) 3.8 350 (165) 150 (68)
WMHG12 12,400 (3.6) 13.1 13,600 (4.0) 4.1 450 (212) 160 (73)
CMHG08 9,400 (2.7) 13.2 10,200 (3.0) 3.9 350 (165) 140 (64)
CMHG12 12,900 (3.8) 12.9 13,100 (3.8) 4.2 450 (212) 140 (64)
CMHG15 18,200 (5.3) 12.9 18,300 (5.4) 3.9 500 (236) 150 (68)
CWHG08 9,400 (2.7) 13.2 10,200 (3.0) 3.9 350 (165) 150 (68)
CWCG08 9,400 (2.7) 13.2 N/A N/A 350 (165) 150 (68)
CWHG10 13,000 (3.8) 12.9 13,100 (3.8) 4.2 400 (189) 160 (73)
CWHG10 13,000 (3.8) 12.9 N/A N/A 400 (189 160 (73)
CWHG13 17,500 (5.1) 11.9 19,500 (5.7) 3.7 450 (212) 165 (75)
CWCG13 17,500 (5.1) 11.9 N/A N/A 450 (212) 165 (75)
CWHG17 19,300 (5.6) 13.6 19,400 (5.7) 3.8 500 (236) 170 (77)
CWCG17 19,300 (5.6) 13.6 N/A N/A 500 (236) 170 (77)
PERFORMANCE DATA CM / CW / WM **
Cooling Heat Pump
Btuh (kW) EER Btuh (kW) COP
Indoor Airflow
CFM (L/S)
Shipping
Weight
Lbs (Kg)
**Cooling ­ ID EAT 80°F (26.7°C) DB/67°F (19.4°C)WB EWT 85°F (29.4°C)
**Heating ­ ID EAT 70°F (21.1°C) DB EWT 70° (21.1°C)
WMHG09 9,200 (2.7) 12.9 10,000 (3.0) 3.8 350 (165) 150 (68)
WMHG12 12,400 (3.6) 13.1 13,600 (4.0) 4.1 450 (212) 160 (73)
WMHG15 17,500 (5.1) 11.9 19,500 (5.7) 3.7 550 (260) 170 (77)
CMHG08 N/A N/A N/A N/A N/A N/A
CMHG12 12,900 (3.8) 12.9 13,100 (3.8) 4.2 450 (212) 140 (64)
CMHG15 18,200 (5.3) 12.9 18,300 (5.4) 3.9 500 (236) 150 (68)
CWHG08 N/A N/A N/A N/A N/A N/A
CWCG08 N/A N/A N/A N/A N/A N/A
CWHG10 13,000 (3.8) 12.9 13,100 (3.8) 4.2 400 (189) 160 (73)
265V
P/N 240008071, Rev. B [112309] 21 Made in USA
CWCG10 13,000 (3.8) 12.9 N/A N/A 400 (189 160 (73)
CWHG13 17,500 (5.1) 11.9 19,500 (5.7) 3.7 450 (212) 165 (75)
CWCG13 17,500 (5.1) 11.9 N/A N/A 450 (212) 165 (75)
CWHG17 N/A N/A N/A N/A N/A N/A
CWCG17 N/A N/A N/A N/A N/A N/A
WMHG09 N/A N/A N/A N/A N/A N/A
WMHG12 12,400 (3.6) 13.1 13,600 (4.0) 4.1 450 (212) 160 (73)
WMHG15 17,500 (5.1) 11.9 19,500 (5.7) 3.7 550 (260) 170 (77)
Page 22
Electrical Specifications
Water Source Console Units
Installation, Operation, and Maintenance Manual
IMPORTANT
Due to ongoing product development, designs, specications, and performance are subject to change without notice. Please consult the factory for further information.
CW / CM - 8,000 BTU Table 2 electrical specifications
Power Supply
Volt — 1–60
Volt Min RLA LRA FLA Hp Htr # Volt W HA TCA THA MCA MOCP Plug
115V 104 7.5 47 1.4 0.09 N/A N/A N/A N/A 8.9 N/A 10.8 15 5-15P
208/ 230V
265V 240 N/A N/A 0.67 0.08
Compressor
197 3.9 20 0.6 0.08
Indoor Fan
Motor
Electric Heat Unit Electrical Ratings
0 N/A N/A N/A
208 1636 7.9 8.5 10.4
2
230 2000 8.7 9.3 11.5
208 2454 11.8 12.4 15.3
3
230 3000 13.0 13.6 16.9
208 3271 15.7 16.3 20.3
4
230 4000 17.4 18 22.3
208 4089 19.7 20.3 25.2
5
230 5000 21.7 22.3 27.8
0 N/A N/A N/A
2 265 2655 10 10.7 13.2 15
3 265 3983 15 15.7 19.5 20
4 265 5310 20 20.7 25.7 30 7-30P
5 N/A N/A N/A N/A N/A N/A N/A
N/A 5.5 15 6–15P
4.5
N/A N/A N/A N/A
0.7
15 6–15P
20 6–20P
25 6-30P
30 6-30P
7-20P
WM - 9,000 BTU Table 3 electrical specifications
265V Not Available
at this time
Power Supply
Volt — 1–60
Volt Min RLA LRA FLA Hp Htr # Volt W HA TCA THA MCA MOCP Plug
115V 104 7.5 47 1.4 0.09 0 N/A N/A N/A 8.9 N/A 10.8 15 5-15P
208/ 230V
265V 240 N/A N/A 0.67 0.08
Compressor
197 3.9 20 0.6 0.08
Indoor Fan
Motor
The Right Fit for Comfort 22 P/N 240008071, Rev. B [112309]
Electric Heat Unit Electrical Ratings
0 N/A N/A N/A
208 1636 7.9 8.5 10.4
2
230 2000 8.7 9.3 11.5
208 2454 11.8 12.4 15.3
3
230 3000 13 13.6 16.9
0 N/A N/A N/A
2 265 2655 10.0 10.7 13.2
3 265 3983 15.0 15.7 19.5 20 7-20P
N/A 5.5 15 6–15P
4.5
N/A 7.1
N/A
15 6–15P
20 6–20P
15 7-20P
265V Not Available
at this time
Page 23
Electrical Specifications
Water Source Console Units
Installation, Operation, and Maintenance Manual
IMPORTANT
Due to ongoing product development, designs, specications, and performance are subject to change without notice. Please consult the factory for further information.
CW - Cooling Capacity 10,000Table 4 electrical specifications
Power Supply
Volt — 1–60
Volt Min RLA LRA FLA Hp Htr # Volt W HA TCA THA MCA MOCP Plug
115V 104 9.9 53 1.4 0.09 N/A N/A N/A N/A 11.3 N/A 13.8 20 5-15P
208/ 230V
265V 240 N/A N/A 0.67 0.08
Compressor
197 5.2 27 0.60 0.08
Indoor Fan
Motor
Electric Heat Unit Electrical Ratings
0 N/A N/A N/A
208 1636 7.9 8.5 10.4
2
230 2000 8.7 9.3 11.5
208 2454 11.8 12.4 15.3
3
230 3000 13 13.6 16.9
208 3271 15.7 16.3 20.3
4
230 4000 17.4 18.0 22.3
208 4089 19.7 20.3 25.2
5
230 5000 21.7 22.3 27.8
0 N/A N/A N/A
2 265 2655 10 10.7 13.2
3 265 3983 15 15.7 19.5 20
4 265 5310 20 20.7 25.7 30 7-30P
N/A 7.1 15 6–15P
5.8
N/A 8.9
7.4
15 6–15P
20 6–20P
25 6-30P
30 6-30P
15
7-20P
CM / WM - Cooling Capacity 12,000Table 5 electrical specifications
Power Supply
Volt — 1–60
Volt Min RLA LRA FLA Hp Htr # Volt W HA TCA THA MCA MOCP Plug
115V 104 9.9 53 1.4 0.09 N/A N/A N/A N/A 11.3 N/A 13.8 20 5-15P
208/
230V
Models
CM &
WM
208/
230V
Model
CM only
265V 240 4.6 20 0.67 0.08
Compressor
197 5.2 27 0.6 0.08
Indoor Fan
Motor
Electric Heat Unit Electrical Ratings
0 N/A N/A N/A
208 1636 7.9 8.5 10.4
2
230 2000 8.7 9.3 11.5
208 2454 11.8 12.4 15.3
3
230 3000 13 13.6 16.9
208 3271 15.7 16.3 20.3
4
230 4000 17.4 18 22.3
208 4089 19.7 20.3 25.2
5
230 5000 21.7 22.3 27.8
0 N/A N/A N/A
2 265 2655 10 10.7 13.2 15
3 265 3983 15 15.7 19.5 20
4 265 5310 20 20.7 25.7 30 7-30P
N/A 7.1 15 6–15P
5.8
N/A 6.4 15 7-20P
5.3
15 6–15P
20 6–20P
25 6-30P
30 6-30P
7-20P
P/N 240008071, Rev. B [112309] 23 Made in USA
Page 24
Electrical Specifications
Water Source Console Units
Installation, Operation, and Maintenance Manual
IMPORTANT
Due to ongoing product development, designs, specications, and performance are subject to change without notice. Please consult the factory for further information.
CW - Cooling Capacity 13,000Table 6 electrical specifications
Power Supply
Volt — 1–60
Volt Min RLA LRA FLA Hp Htr # Volt W HA TC A THA MCA MOCP Plug
115V 104 10.8 53 1.4 0.09 N/A N/A N/A N/A 13.8 N/A 16.5 25 5-20P
208/ 230V
265V 240 6.0 28 0.67 0.08
Compressor
197 7.4 33 0.6 0.08
Indoor Fan
Motor
Electric Heat Unit Electrical Ratings
0 N/A N/A N/A
208 1636 7.9 8.5 10.4
2
230 2000 8.7 9.3 11.5
208 2454 11.8 12.4 15.3
3
230 3000 13 13.6 16.9
208 3271 15.7 16.3 20.3
4
230 4000 17.4 18.0 22.3
208 4089 19.7 20.3 25.2
5
230 5000 21.7 22.3 27.8
0 N/A N/A N/A
2 265 2655 10 10.7 13.2
3 265 3983 15 15.7 19.5 20
4 265 5310 20 20.7 25.7 30 7-30P
N/A 9.9 15 6–15P
8.0
N/A 8.2
6.7
15 6–15P
20 6–20P
25 6-30P
30 6-30P
15
7-20P
CM / WM - Cooling Capacity 15,000Table 7 electrical specifications
Power Supply
Volt — 1–60
Volt Min RLA LRA FLA Hp Htr # Volt W HA TCA THA MCA MOCP Plug
208/ 230V
Models
CM &
WM
208/
230V
Model
CM only
265V 240 6.0 28 0.67 0.08
Compressor
197 7.4 33 0.6 0.08
Indoor Fan
Motor
Electric Heat Unit Electrical Ratings
0 N/A N/A N/A
208 1636 7.9 8.5 10.4
2
230 2000 8.7 9.3 11.5
208 2454 11.8 12.4 15.3
3
230 3000 13.0 13.6 16.9
208 3271 15.7 16.3 20.3
4
230 4000 17.4 18.0 22.3
208 4089 19.7 20.3 25.2
5
230 5000 21.7 22.3 27.8
0 N/A N/A N/A
2 265 2655 10 10.7 13.2 15
3 265 3983 15 15.7 19.5 20
4 265 5310 20 20.7 25.7 30 7-30P
N/A 9.9 15 6–15P
8.0
N/A 8.2 15 7-20P
6.7
15 6–15P
20 6–20P
25 6-30P
30 6-30P
7-20P
The Right Fit for Comfort 24 P/N 240008071, Rev. B [112309]
Page 25
Electrical Specifications
Water Source Console Units
Installation, Operation, and Maintenance Manual
IMPORTANT
Due to ongoing product development, designs, specications, and performance are subject to change without notice. Please consult the factory for further information.
CW - Cooling Capacity 17,000Table 8 electrical specifications
Power Supply
Volt — 1–60
Volt Min RLA LRA FLA Hp Htr # Volt W HA TC A THA MCA MOCP Plug
208/ 230V
265V 240 N/A N/A 0.67 0.08
Compressor
197 8.3 44 0.6 0.08
Indoor Fan
Motor
Electric Heat Unit Electrical Ratings
0 N/A N/A N/A
208 1636 7.9 8.5 10.4
2
230 2000 8.7 9.3 11.5
208 2454 11.8 12.4 15.3
3
230 3000 13.0 13.6 16.9
208 3271 15.7 16.3 20.3
4
230 4000 17.4 18.0 22.3
208 4089 19.7 20.3 25.2
5
230 5000 21.7 22.3 27.8
0 N/A N/A N/A
3 265 3983 15 15.7 19.5 20
4 265 5310 20 20.7 25.7 30 7-30P
N/A 11.0 15 6–15P
8.9
N/A 8.9
7.4
15 6–15P
20 6–20P
25 6-30P
30 6-30P
15
7-20P2 265 2655 10 10.7 13.2
NEMA Specifications Non / Locking / ReceptaclesFigure 14
265V Not Available
at this time
P/N 240008071, Rev. B [112309] 25 Made in USA
Page 26
Notes
Water Source Console Units
Installation, Operation, and Maintenance Manual
The Right Fit for Comfort 26 P/N 240008071, Rev. B [112309]
Page 27
Notes
Water Source Console Units
Installation, Operation, and Maintenance Manual
P/N 240008071, Rev. B [112309] 27 Made in USA
Page 28
ECR International LLC 2201 Dwyer Avenue Utica, NY 13501 e-mail: info@RetroAire.com
An ISO 9001-2000 Certified Company
The Right Fit for Comfort 28 P/N 240008071, Rev. B [112309]