Econex VSB, VSA Series Series Manual

Page 1
Safety Shut-off Valves series VSB and VSA
Gas safety solenoid shut-off valve series VSB and VSA, ap­proved according to the norm EN 161 with product iden-
tication and manufactured according to regulation EU
2016/426, are suitable for the automatic control of gases
belonging to the rst, second and third family.
On request there are versions for biogas and air. These val-
ves, normally closed for continuous and cyclic operation, open by powering the coil and close quickly when there is
no tension.
TECHNICAL FEATURES
Valve body Brass OT-58 and die-cast aluminium
Pipe connections for valves with brass body Rp 3/8, Rp 1/2, Rp 3/4 according to EN 10226
Pipe connections for valves with aluminium body Rp 1/2÷ 2 according to EN10226
Pipe anged connections for valves with aluminium body DN 65 ÷ 200 PN16 according to ISO 7005
Inlet pressure 200 mbar, 360 mbar and 500 mbar
Opening/closing time on quick version < 1 second
Standard supply voltage 230V ac, 110V ac, 24V and 12V ac and dc
Frequency 50÷60 Hz, 50 Hz per 12V and 24V ac
Enclosure IP 65 - IEC 529
Supply voltage tolerance -15% - +10%
Duty cycle Continuous
Ambient temperature -20 / +60 °C
FEATURES
• Class A, Group 2 according to EN161
• Electromagnetic Compatibility – Directive 2004/108/CE
• Low voltage – Directive 2006/95/CE
• SIL 2 for single solenoid valves, if 2 valves are installed in series with tightness control, they reach SIL 3
• Quick and slow opening and quick closing
• Quiet operation
Poliammidic resin encapsulated coils and metallic frame for anged bodies
• Pressure test points at inlet by both sides
Accessories on request: by-pass, limit switch, manual max. ow adjustment
Page 2
SHUT-OFF VALVES SERIES VSB...
VSB = Safety shut-off valve in brass
Operation R = Quick
RP = Quick with max. ow adjustament
Max. pressure 2 = 200 mbar
Nominal diameter 10 = Rp 3/8
15 = Rp 1/2 20 = Rp 3/4
VSB R 2 15 C
Supply voltage
A = 24V ac/50 Hz B = 110V ac/50 - 60 Hz C = 230V ac/50 - 60 Hz
E = 24V dc F = 12V dc G = 12V ac / 50 Hz
Molle di taratura pressione
FLOW CHART
VN (m3/h)
Aria Air
Metano Methane
Gas di città Town gas
Propano Propane
Butano Butane
G.P.L. L.G.P.
dv=1
dv=0,64
dv=0,45
dv=1,56
dv=2,09
dv=1,70
Page 3
SHUT-OFF VALVES SERIES VSA... Rp 1/2 - 3/4 - 1
VSA = Safety shut-off valve in aluminium
Operation R = Quick
RP = Quick with max. ow adjustment L = Slow LP = Slow with max ow adjustment LSP = Slow with max ow adjustment + rapid stroke
Max. pressure
2 = 200 mbar 5 = 500 mbar
Nominal diameter
15 = Rp 1/2 20 = Rp 3/4 25 = Rp 1
Supply voltage
A = 24V ac/50 Hz B = 110V ac/50 - 60 Hz C = 230V ac/50 - 60 Hz
Other accessories BP = By-pass
I = signal lamp by valve feeding (in the connector) M = limit micro-switch F = Flanged (only for Rp 1) BK = Black cataphoresis
E = 24V dc F = 12V dc G = 12V ac/ 50 Hz
VSA R 2
FLOW CHART
15 C
BK
Page 4
SHUT-OFF VALVES SERIES VSA... Rp 1.1/4 - 1.1/2 -2
VSA = Safety shut-off valve in aluminium
Operation R = Quick
RP = Quick with max. ow adjustment L = Slow LP = Slow with max ow adjustment LSP = Slow with max ow adjustment + rapid stroke
Max. pressure 2 = 200 mbar
3 = 360 mbar 5 = 500 mbar
Nominal diameter 32 = Rp 1.1/4
40 = Rp 1.1/2 50 = Rp 2
Supply voltage
A = 24V ac 50 Hz B = 110V ac 50-60 Hz C = 230V ac 50-60 Hz E = 24V dc
Other accessories BP = By-pass
I = signal lamp by valve feeding (in the connector) M = limit micro-switch F = Flanged BK = Black cataphoresis
VSA R 3 40 E
FLOW CHART
BK
Page 5
SHUT- OFF VALVES SERIES VSA... FLANGED DN65÷DN200
VSA = Safety shut-off valve in aluminium
Operation R = Quick
RP = Quick with max. ow adjustment L = Slow LP = Slow with max ow adjustment LSP = Slow with max ow adjustment + rapid stroke
Max. pressure 3 = 360 mbar
Nominal diameter 65 = DN 65
80 = DN 80 100 = DN 100
125 = DN 125 150 = DN 150 200 = DN 200
Supply voltage
A = 24V ac 50 Hz B = 110V ac 50-60 Hz C = 230V ac 50-60 Hz E = 24V dc
Other accessories BP = By-pass
I = signal lamp by valve feeding (in the connector) M = limit micro-switch BK = Black cataphoresis
VSA R 3 80 E
FLOW CHART
BK
Page 6
DIMENSIONI
MODELS AND RATING
SERIES VSB... QUICK OPENING
An energy saving connector Green for valuable reduction of energy consumption is also available (3 VA).
Pipe
Rp
3/8 200 9 3 55 90,5 37 0,6 VSBRP210C...
1/2 200 9 3 55 90,5 37 0,6 VSBRP215C...
3/4 200 9 3 55 90,5 37 0,6 VSBRP220C...
Max
pressure
(mbar)
Rating at
230 V
(VA)
Rating at
230 V with
Green conn.
(VA)
Dimensions
(mm)
A B C
Weight
(Kg)
Model
SERIES VSA….. QUICK / SLOW OPENING THREADED Rp 1/2, 3/4, 1
Pipe
Rp
1/2
3/4
1
Dimensions
Max
pressure
(mbar)
Rating at
230 V
(VA)
A
(mm)
B
Weight
(Kg)
Model
C
R RP L - LP/LSP
200 18
70 135 150 200 74 0,85
500 18 VSA 515C...
200 18
70 135 150 200 74 0,85
500 18 VSA 520C...
200 18
70 135 150 200 74 0,80
500 18 VSA 525C...
VSA 215C...
VSA 220C...
VSA 225C...
Page 7
Pipe
Rp
1.1/4
1.1/2
2
SERIES VSA… QUICK / SLOW OPENING THREADED Rp 1.1/4, 1.1/2, 2
Dimensions
Max
pressure
(mbar)
Rating at
230 V
(VA)
A
R RP L LP/LSP
200
360 210 225 285 285 3,6 VSA 332C...
500
200
360 210 225 285 285 3,6 VSA 340C...
500 210 285 285 285
200
360 235 235 295 295 VSA 350C...
500 235 235 295 295
89 / 25 160
89 / 25 160
89 / 25 160
185 200 260 260
185 200 260 260
210 225 288 288
(mm)
B
Weight
(Kg)
C
140
140
140 3,6
3,4 VSA 232C...
3,4 VSA 240C...
VSA 250C......
Model
SERIES VSA… QUICK / SLOW OPENING FLANGED
Dimensions
Pipe
DN
Max
pressure
(mbar)
Rating at
230 V
(VA)
A
R RP L LP/LSP
65
105 / 29
80 310 328 328 439 486 211 17,60 VSA 380C...
100
360
125 480 570 570 681 728 322 34,00 VSA 3125C...
124 / 36
150 480 570 570 681 728 552 45,00 VSA 3150C...
200 47 / 5 600* ---- 920 1162 1162 ---- 101,00 VSA 3200C...
290 321 321 432 480 211 17 VSA 365C...
350 389 389 500 547 254 29,60 VSA 3100C...
* Opening time 13 seconds ± 20%.
(mm)
B
Weight
(Kg)
C
Model
Page 8
WIRING INSTRUCTIONS
Installation, adjustment and maintenance of the valve must be carried out exclusively by skilled and authorized service
technicians
1. Before electric wiring, check that the main voltage matches with the power supply voltage stated on the product label.
2. Disconnect power before wiring.
3. By wiring connector, use terminals and cables as reported in the Instruction leaet in the package.
4. Connect the power supply to terminals 1 and 2 and the ground wire to terminal .
5. Using energy saving Green connector with 12 and 24 Vdc comply with polarity.
INSTALLATION AND OPERATING INSTRUCTIONS
1. Make sure that all operating data indicated on the safety shut-off valve label correspond to those of the system.
2. Before installing the safety shut-off valve, quit the gas supply and make sure that the pipeline is free from impurities. The pipeline must be vibration-free.
3. The ow direction indicated by the arrow on the valve body must be respected, facing towards the user appliance. The safety valve can be installed either horizontally or vertically, provided that the coil is not turned downwards.
4. When installing the safety shut-off valve in pipework do not use the coil as a lever, but use the correct wrench.
5. The sealing material must be applied to the external thread of the pipeline only and not to the internal thread of the safety shut­off valve.
ADJUSTMENT OF FLOW RATE - OPENING TIME AND RAPID STROKE
QUICK OPENING SLOW OPENING
1. Coil fastening nut
2. Flow rate adjustment
Unscrew the nut and spin the internal screw clockwise to reduce and counter clockwise to increase the ow rate.
1. Flow rate adjustment. Loosen screw A and rotate cylinder B to the desired position. Tighten screw A to x the position.
2. Opening time adjustment. Turn screw C clockwise to
reduce the opening time or turn counter clockwise to increa-
se values.
3. Rapid stroke adjustment.
All the reported data are subject to be changed without notice. from 180911
Econex s.r.l. - Via Francesco De Sanctis, 53 - I-20141 Milano Tel. +39 0289502912 - Fax +39 028463084 - www.econex.it - info@econex.it