Econ sens+, sens+ pro User Information

Article-No.: 222421 // Index: 0.6
User information – Please read first!
Introduction
Important Tests
All products undergo comprehensive safety and performance testing before they are shipped. Nevertheless, you must perform at least the following:
Please ensure that the device has survived transport without damage. Before you connect the device and switch it on, you must check the operating voltage
on the basis of the relevant technical data.
We assume no responsibility for parts that have been destroyed as a result of in­correct operating voltages!
econ sens+ page 1 of 4 EN
Article-No.: 222421 // Index: 0.6
Input voltage range
70 – 350 V AC (between U1,U2,U3 and N)
Power consumption
1.5 Watt max. (in Ethernet operation)
Power supply
direct (from measuring inputs U1 and U2)
Current range
0…400 / 1600 / 3200 A AC, depending on the model of coils
Conformity with
EN 61000-6-1 EN 61010-1
Storage temperature range
-20... +70°C
Operating temperature
-20... +55°C
Humidity
max. 80 % rel. air humidity, non-condensing
Equipment class
IP20
Terminal clamping torque
max. 2.5 Nm
Cable cross-section of terminals
0.15 – 4 mm²
Consumption measurement accuracy
+/- 1%
Area of application
Two, three and four-phase systems with arbi­trary load
Interfaces
Type S0-pulse:
Type RS485:
2 x S0-pulse output acc. to DIN EN 43864 1 x 100 BaseT-Ethernet (Webinterface, Modbus TCP/Modbus Gateway)
1 x RS485 (Sensbus, Modbus RTU) 1 x 100 BaseT-Ethernet (Webinterface, Modbus TCP/Modbus Gateway)
Technical data of the econ sens+ basic device
Delivery contents:
econ sens+ mounting rail assembly incl. current sensing coils  User information
Defects:
If the econ sens+ / econ sens+ pro does not start up properly once the operating voltage is applied and if the Log LED does not light up red, please re-disconnect the device from the supply voltage. If this does not remedy the defect you can find more information and sup­port at www.econ-solutions.de or contact us by e-mail (econ-sens@econ-solutions.de).
Safety information:
When working on the device, e.g. during service, disconnect the power! Installation may only be performed by appropriately trained technical staff!
econ sens+ page 2 of 4 EN
Article-No.: 222421 // Index: 0.6
Operation and installation
Connect the econ sens+ to the power supply as shown in Fig. 1. When installing the Rogowski coils please ensure that they are mounted in the correct direction, as depicted on the coils themselves.
Connect the econ sens+ / econ sens+ pro to your PC via the network cable. Enter the IP­address 192.168.0.1 in your web browser to access the econ sens+ / econ sens+ pro web interface. When the appliance to be measured is switched on, the measured data (voltage, current, output…) should be visible in the “Meter” menu.
For further assistance and troubleshooting information please consult the econ sens+ / econ sens+ pro user guide, which is available at www.econ-sens.com.
econ sens+ page 3 of 4 EN
Article-No.: 222421 // Index: 0.6
This documentation was created and checked with care; however we cannot assume responsibility for its complete accuracy.
econ solutions GmbH Rommelstraße 1 D-76227 Karlsruhe / Germany Phone +49 (0)7082-7919-201 Fax +49 (0)7082-7919-230
Warranty conditions
Warranty period
2 years as of delivery date.
Extent of warranty and handling of warranty claims
Malfunctions that are due to faulty workmanship and/or material defects will be fixed within the warranty period at no charge. Further claims, in particular any pertaining to secondary damage, are excluded.
In the event of a justified claim, please return the product to our attention. To make a war­ranty claim, please preferably enclose an accurate description of the malfunction and re­turn the product in its original packaging, insured and postage-free, to our attention.
Warranty exclusion
Damage and malfunctions that are caused by failure to comply with our user information as well as drop, shock, contamination or other abnormal handling are not covered by the war­ranty. Warranty claims expire if the product is not subjected to a safety and performance check as described in the “Important tests” section directly after it has been unpacked, or if abnormal interventions are performed or if the serial number is changed or rendered un­recognizable.
WEEE Directive
This product was produced in compliance with the EU directive 2002/96/EG on waste elec­trical and electronic equipment and the transposition thereof into the German Electrical and Electronic Equipment Act (ElektroG). Products that are no longer used can be returned to us, where they will be disposed of in a professional manner.
For further information please visit our homepage www.econ-solutions.de or contact us by e-mail (econ-sens@econ-solutions.de)
Karlsruhe, October 2013.
econ sens+ page 4 of 4 EN
Loading...