FFZB1-ECO
TM
AUDIO DETECTOR
patent pending
Installation Manual & Users Guide
SPECIFICATIONS
Frequency: 2.4GHz Operating Temperature: 32°-120°F (0°-49°C)
Battery: One 3Vdc lithium CR123A (1550 mAh) Operating Humidity: 5-95% RH non condensing
Battery life: 4 years Supervisory signal interval: 27 min(approx.)
Detection distance: 6 in max Maximum current draw: 135mA during transmission
3rd Party Certifications: FCC, IC, ETL
OPERATION
The FireFighter™ sensor is designed to listen to the alarm sounder of any smoke detector. Once confirmed as an
alarm, it will transmit a signal to the alarm control panel which if connected to a central monitoring station, will
dispatch the fire department.
WARNING: This audio detector is intended only for use with smoke detectors but it does not detect the presence of
smoke, heat, or fire directly.
ATTENTION: Ce détecteur audio est uniquement destiné à une utilisation avec des détecteurs de fumée, mais il ne
détecte pas la présence de fumée, la chaleur ou le feu directement.
ENROLLING (see IMAGE: 1)
To enroll the sensor, set your panel into program mode. Refer to your specific alarm panel instruction manual for
details on these menus. Once in program mode, place the battery into the sensor and follow the instructions that
appear on the panel. When “Trip to Pair” appears on the screen, press the tamper button to complete the
enrollment process. See LED section below for more information on initial power up behavior.
NOTE: For best results, pair the device to your panel before installation.
MOUNTING (see IMAGE: 2 & 3)
Included with this device is a mounting bracket, hardware and double sided tape. To ensure proper operation
ensure the side of the device with the small holes is directly facing the sounder holes on the smoke detector.
Secure the mounting bracket to the wall or ceiling using the two mounting screws and double sided tape
provided, then secure the audio detector to the mounting bracket using the small screw provided. The
FireFighter™ must be mounting within 6 inches of the detector for optimal operation.
WARNING: Non-interconnected smoke detectors require an audio detector by each smoke detector sounder.
ATTENTION: Detecteurs de fumée non interconnectés nécessitent un détecteur audio par chaque sondeur
détecteur de fumée.
This equipment should be installed in accordance with Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72,
(National Fire Protection Association, Batterymarch Park, Quincy, MA 02269). Printed information describing proper
installation, operation, testing, maintenance, evacuation planning, and repair service is to be provided with this
equipment. Warning: Owner’s instruction notice: ’Not to be removed by anyone except occupant’.
Cet équipement doit être installé conformément au chapitre 2 du National Fire Alarm Code, ANSI / NFPA 72 (
National Fire Protection Association , Batterymarch Park , Quincy , MA 02269 ) . Les informations imprimées
décrivant l'installation , le fonctionnement , les tests , la maintenance , la planification de l'évacuation , et le service
de réparation doit être fournie avec cet équipement . Attention: l'instruction d'un préavis de propriétaire : “Ne pas
être éliminé par personne, sauf l'occupant”

TESTING (see IMAGE: 1)
LEARN BUTTON
TAMPER SWITCH
IMAGE 1: ENROLLING / TEST / TAMPER BUTTON
IMAGE 2: INSTALLATION DISTANCE
HOLES TO LINE
UP WITH EXISTING SMOKE
DETECTOR
To test the RF transmission from the mounted position you can generate a tamper by removing the cove. This will
send a signal to the control panel. To test the audio detection, press and hold the smoke detector test button. If
you are using zone type 16 (Fire with Verification) you must press and hold the smoke detector button for at least 30
seconds to ensure that FireFighter™ has had sufficient time to identify the smoke alarm pattern and lock into alarm.
Ensure the FireFighter™ cover is on and that you wear hearing protection.
NOTE: This system must be checked by a qualified technician at least once every three (3) years. Please test the unit once
per week to ensure proper functionality.
LED
The Firefighter™ is equipped with a multi-color LED. When a valid audio signal is heard the LED will turn red and
flash in sequence to the smoke detector sounder. When the Firefighter™ has determined the audio signal heard is
a valid alarm, the LED will turn solid red to indicate it has transmitted to the panel. On power up, the LED will stay
solid green for 2 seconds, then blink green 3 times every 5 seconds (approx.) when not enrolled with a panel.
REPLACING THE BATTERY
When the battery is low a signal will be sent to the control panel. To replace the battery:
1. Remove the top cover to reveal the battery. This will send a tamper signal to the control panel.
2. Replace with a Panasonic CR123A battery ensuring the + side of the battery faces as indicated on the device.
3. Re-attach the cover, you should hear a click when the cover engages properly.
WARNING: While the audio detector monitors its own battery, it does not monitor the battery in the smoke
detectors. Batteries should be changed as per the original smoke detector manufacturer’s instructions. Always test
the audio detector and smoke alarms after battery installation to confirm proper operation
ATTENTION: Bien que le détecteur audio surveille sa propre batterie, il ne contrôle pas la batterie dans les
détecteurs de fumée. Les piles doivent être changées selon les instructions du fabricant original de détecteur de
fumée. Toujours tester les détecteurs de fumée et alarmes audio après l'installation de la batterie pour confirmer
le bon fonctionnement.
REBOOTING AND RESETTING TO FACTORY DEFAULTS
In order to reboot the device, simply remove the battery and place it back in. Upon doing this, you should see the
green LED illuminate. See LED section for more information on LED behavior.
To reset the device to factory defaults use the following instructions:
1. Open case and remove battery from device.
2. Press and hold tamper switch.
3. Place battery back into the device while still holding the tamper switch.
4. When you see the green LED illuminate, release the tamper switch.