ECOFOREST ecoGEO B3 3-12 kW, ecoGEO B3 5-22 kW, ecoGEO B1 3-12 kW, ecoGEO B1 T 5-22 kW, ecoGEO B2 3-12 kW Installation And User Manual

...
Page 1
ecoGEO
ecoGEO B1 3-12 kW ecoGEO B2 3-12 kW ecoGEO B3 3-12 kW ecoGEO B1 5-22 kW ecoGEO B2 5-22 kW
ecoGEO B3 5-22 kW ecoGEO B1 T 5-22 kW ecoGEO B2 T 5-22 kW ecoGEO B3 T 5-22 kW
ecoGEO C1 3-12 kW ecoGEO C2 3-12 kW ecoGEO C3 3-12 kW ecoGEO C1 5-22 kW ecoGEO C2 5-22 kW
ecoGEO C3 5-22 kW ecoGEO C1 T 5-22 kW ecoGEO C2 T 5-22 kW ecoGEO C3 T 5-22 kW
Installation and User Manual
Page 2
Table of Contens
1. GENERAL INFORMATION ..................................................................................................................... 4
2. SAFETY ISSUES .................................................................................................................................... 5
2.1. REFRIGERANT CIRCUIT....................................................................................................................... 5
2.2. HYDRAULIC CIRCUITS................................ ................................................................ ......................... 6
2.3. ELECTRICAL INSTALLATION ................................................................................................................. 7
3. HEAT PUMP OVERVIEW ....................................................................................................................... 7
3.1. MODEL IDENTIFICATION ...................................................................................................................... 7
3.2. OPERATING PRINCIPLES ..................................................................................................................... 8
3.3. DIMENSIONS AND CONNECTIONS ................................................................ ....................................... 11
3.4. MAIN COMPONENTS ......................................................................................................................... 13
3.5. REMOVING THE COVERS................................................................................................................... 19
4. USER MANUAL ................................................................................................................................... 26
4.1. FRONT PANEL OVERVIEW ................................................................................................................. 26
4.2. PROGRAMS .................................................................................................................................... 27
4.3. OPERATION SHEMES........................................................................................................................ 28
4.4. HOME SCREEN ................................................................................................................................ 28
4.5. USER MENU .................................................................................................................................... 30
4.6. INSTALLER MENU ............................................................................................................................. 35
5. TRANSPORT AND LOCATION ............................................................................................................ 41
5.1. TRANSPORT AND HANDLING .............................................................................................................. 42
5.2. RECOMMENDATIONS FOR LOCATION .................................................................................................. 42
5.3. SERVICE AREAS .............................................................................................................................. 43
6. HYDRAULIC INSTALLATION ................................ .............................................................................. 44
6.1. HEATING/COOLING CIRCUIT CONECTION ............................................................................................. 44
6.2. DHW TANK CONNECTION ................................................................................................................. 46
6.3. BRINE CIRCUIT CONNECTION............................................................................................................. 49
7. ELECTRICAL INSTALLATION ............................................................................................................. 53
7.1. POWER SUPPLY .............................................................................................................................. 54
7.2. ZONE 1 VALVE ................................................................................................................................ 55
7.3. EXTERNAL SHUNT GROUP FOR ZONE 2 ............................................................................................... 56
7.4. OUTDOOR TEMPERATURE PROBE ...................................................................................................... 57
7.5. TEMPERATURE PROBE AND LEGIONELLA PROTECTION ELECTRIC HEATER OF THE EXTERNAL DHW TANK ..... 58
7.6. BUFFER TANK TEMPERATURE PROBE ................................................................................................. 58
7.7. EXTERNAL ACTIVATION OF THE HEAT PUMP ........................................................................................ 58
7.8. POOL VALVE ................................................................................................................................... 59
8. INDOOR CONTROL DEVICES ............................................................................................................. 60
8.1. TH-TUNE INDOOR TERMINALS ........................................................................................................... 60
8.2. CONVENTIONAL RELAY THERMOSTATS ............................................................................................... 61
8.3. COMBINATION OF TH-TUNE INDOOR TERMINALS WITH CONVENTIONAL RELAY THERMOSTATS ................... 62
9. FILLING THE CIRCUITS ...................................................................................................................... 63
9.1. FILLING THE HEATING/COOLING CIRCUIT ............................................................................................. 63
Page 3
9.2. FILLING THE DHW COIL CIRCUIT ....................................................................................................... 63
9.3. FILLING THE BRINE CIRCUIT .............................................................................................................. 65
10. SETTINGS AND START UP ................................................................................................................. 67
10.1. SELECTING THE FRONT PANEL LANGUAGE .......................................................................................... 67
10.2. SELECTING THE HEAT PUMP MODEL ................................................................................................... 67
10.3. SOURCE SYSTEM SELECTION ............................................................................................................ 67
10.4. SELECTING THE WORKING SCHEME ................................................................................................... 67
10.5. SELECTING THE INDOOR CONTROL DEVICES ....................................................................................... 67
10.6. SETTING THE HEATING CURVE........................................................................................................... 68
10.7. EXPAMPLES OF HEATING CURVE ....................................................................................................... 73
10.8. DOMESTIC HOT WATER ON/OFF ...................................................................................................... 76
10.9. SWIMMING POOL ON/OFF .................................................................................................................. 76
10.10. DIGITAL INPUT SIGNAL ...................................................................................................................... 76
10.11. POWER LIMITATION AND SETTING PROTECTIONS ................................................................................. 76
10.12. TEMPERATURE PROBE CALIBRATION .................................................................................................. 77
10.13. FINAL INSPECTION AND START UP OF THE INSTALLATION ...................................................................... 77
11. IDENTIFYING PROBLEMS AND TROUBLESHOOTING ...................................................................... 79
11.1. ALARM LIST .................................................................................................................................... 79
11.2. COMFORT PROBLEMS ...................................................................................................................... 80
12. TECHNICAL SPECIFICATIONS ........................................................................................................... 81
12.1. TECNICAL DATA ............................................................................................................................... 81
12.2. INTERNAL SCHEMATICS OF THE HEAT PUMPS ...................................................................................... 83
12.3. ELECTRICAL PANEL CONECTIONS ...................................................................................................... 95
12.4. ECOGEO B1, B2, C1 AND C2 WIRING DIAGRAMS.............................................................................. 102
12.5. ECOGEO B3 AND C3 WIRING DIAGRAMS .......................................................................................... 107
12.6. LIMITATION ON THE HEAT PUMP THERMAL POWER ............................................................................. 112
12.7. LIMITATION OF THE HEAT PUMP ELECTRIC CONSUMPTION ................................................................... 116
12.8. OPERATING ENVELOPE OF THE HEAT PUMPS..................................................................................... 122
12.9. PRESSURE DROP IN HEAT EXCHANGERS .......................................................................................... 123
12.10. PERFORMANCE CURVES OF CIRCULATION PUMPS .............................................................................. 129
13. SPECIFIC INSTALLATION DETAILS FOR ECOGEO B HEAT PUMPS ............................................. 131
13.1. SUGGESTIONS FOR THE HEATING-COOLING CIRCUIT INSTALLATION...................................................... 131
13.2. DIRECT CONNECTION TO THE EMISSION SYSTEM ............................................................................... 132
13.3. BUFFER TANK INSTALLATIONS ......................................................................................................... 134
14. RECOMMENDED APPLICATIONS .................................................................................................... 135
14.1. COMPONENT LEGENDS .................................................................................................................. 135
14.2. INSTALLATION IN 1 ZONE FOR ECOGEO B1, B2, B3, C1, C2 AND C3.................................................. 136
14.3. INSTALLATION IN 1 ZONE WITH POOL FOR ECOGEO B1, B2, B3, C1, C2 AND C3 ................................. 139
14.4. INSTALLATION IN 1 ZONE WITH SEPARATE SYSTEMS FOR HEATING AND COOLING ECOGEO B3 AND C3 ... 142
14.5. INSTALLATION IN 2 ZONE FOR ECOGEO B1, B2, B3, C1, C2 AND C3.................................................. 145
14.6. INSTALLATION WITH INTERMEDIATE BUFFER TANK FOR ECOGEO B1 AND B1 ........................................ 149
14.7. INSTALLATION WITH INTERMEDIATE BUFFER TANK AND POOL FOR ECOGEO B3 .................................... 152
15. GUARANTEE ................................................................................................ ..................................... 155
16. DECLARATIONS OF CONFORMITY ................................................................................................. 158
Page 4
1. GENERAL INFORMATION
Thank you for purchasing the ECOFOREST ecoGEO heat pump. In this manual, you will find information about the installation, commissioning, maintenance and
troubleshooting of the equipment. It also includes useful information for the end user, such as navigating and adjusting parameters using the front panel.
In order to get the most benefit from your ecoGEO heat pump, please read this manual carefully before installing and commissioning the equipment. This manual should be kept for future reference.
The coGEO heat pumps are intended for serving heating-cooling systems and producing domestic hot water (DHW). Any other application of the equipment could result in injuries and/or property damage or equipment malfunction. The manufacturer will not be liable for any property damage and/or injuries resulting from the inappropriate use of the equipment.
The heat pump should be installed by an authorized installer following the applicable local regulations and in accordance with the installation instructions set outlined this manual.
NOTE
This manual applies to software version from V5.0 B79 onwards.
NOTE
Indicates a situation which could result in property damage or equipment malfunction. It may also
indicate whether the practice is the commendable for the equipment.
DANGER!
Indicates an imminent or potentially hazardous situation which, if not avoided, could result in death or
personal injury. It may also warn you about unsafe practices.
Page 5
2. SAFETY ISSUES
The indications outlined in this section cover important issues on your safety; please follow them carefully.
2.1. REFRIGERANT CIRCUIT
The refrigerant circuit uses R410A as working fluid. This refrigerant is eco-friendly, as it is chlorine-free and, therefore, does not contribute to ozone layer depletion. However, any action on the refrigerant circuit should be carried out by authorized personnel only and in accordance with the applicable local regulations and the instructions outlined in this manual.
TOXICITY
Under normal operating conditions, the coolant toxicity is nil. However, in spite of its low toxicity, it could result in personal injuries under unusual equipment operating conditions.
In its gaseous state, the refrigerant is denser than air, thus tending to accumulate in lower levels. If
the equipment is installed in a location where it is possible that refrigerant vapour accumulates at ground level, it should be well ventilated.
DANGER!
In the event of accidental refrigerant leakage, avoid touching the leaking area directly. Otherwise,
serious freezer burns could occur. The maximum operating pressure of the cooling circuit is 4.2 MPa (42 bar). Avoid touching the pipes, the compressor or other refrigerant circuit parts during or immediately after
operating the heat pump. These could be at high or low temperature, and touching them could result
in heat or freezer burns. If you need to touch these pieces, allow sufficient time for temperatures to
stabilize and use protective gloves to prevent injuries.
DANGER!
All installation and maintenance work must be performed by an authorized technician following the
indications outlined in this manual. An improper installation or misuse of the equipment could result in electrical shock, short circuits,
working fluid leakage, fire or other injuries and/or property damages. If you are unsure about the
equipment installation, maintenance or operation procedures, please contact your local dealer or
customer services for advice. If you detect unusual performance in the unit, please contact your local dealer or customer services
to resolve your concerns. This equipment must not be operated by persons suffering any type of physical, sensorial or
psychological disability, children or persons lacking the necessary experience or knowledge, unless
they have been given supervision or instruction concerning use by a person responsible for their
safety. During the installation, maintenance or commissioning of the heat pump, please always wear
appropriate personal protective equipment. Keep all plastic packaging bags away from children to prevent suffocation.
Page 6
Direct exposure of the refrigerant to flames produces toxic gas. However, this gas can be detected
by its smell in concentrations well below the allowable limit. If you detect an unusual smell, evacuate and ventilate the area until you are sure that the gas has been fully eliminated.
In the event of accidental refrigerant leakage, ventilate the area immediately. Anyone who has had contact with the refrigerant vapour should evacuate the area immediately and
breathe fresh air.
FLAMMABILITY
Under normal conditions, there is no risk of explosion or combustion of the refrigerant contained in the circuit.
SERVICING AND SCRAPPING In order to repair the refrigerant circuit, the coolant contained within should not be released to the atmosphere, but it should be recovered and destroyed in treatment plants intended for such purpose.
Considering the fact that the R410A is a mixture, in the event of leakage, the extra refrigerant should be filled in liquid state. Filling the refrigerant in gaseous state alters its composition and might cause heat pump malfunctions.
Before dismantling the heat pump, the coolant should be recovered for disposal at a treatment plant, in accordance with the current regulations.
2.2. HYDRAULIC CIRCUITS
The installation and any further actions on the heating-cooling, brine and DHW circuits should be performed by authorized personnel only and in accordance with applicable local regulations and following the instructions provided in this manual.
DANGER!
Avoid touching the pipes, the compressor or other parts of the heating-cooling, brine and DHW
circuits during or immediately after operating the heat pump. These could be at high or low temperature, and touching them could result in burns from heat or cold. If you need to touch these parts, allow time for temperatures to stabilize and use protective gloves to prevent injuries.
Page 7
2.3. ELECTRICAL INSTALLATION
Any action carried out on the electrical installation of the equipment should be performed by an authorized installer and in accordance with the applicable local regulations and the instructions outlined in this manual.
3. HEAT PUMP OVERVIEW
3.1. MODEL IDENTIFICATION
The range of ecoGEO heat pumps is available in two models, ecoGEO B and ecoGEO C. The ecoGEO C heat pumps include a built-in DHW tank of 170 litres. The ecoGEO B heat pumps have only the heat pump module and the DHW tank should be installed separately. Each of this models are available in 9 different models, depending on the application, the heating output and the type el power supply, as described in Table 3.1.
ecoGEO B1 and C1 models provide heating and DHW non-simultaneously, using a 3-way valve. In addition, the ecoGEO B2 and C2 models provide passive cooling option, allowing moderate cooling to the housing with a minimum consumption of the heat pump (a consumption resulting from circulation pumps only). ecoGEO B3 and C3 models provide simultaneously DHW and climate control system through cycle reversal. Each one of the three versions is available for adjustable heating outputs within the ranges 3-12 kW and 5­22 kW, given the use of inverter compressors. 3-12 kW models are available only with single-phase power supply, while 5- 22 kW models are available with both single-phase and three-phase power supply.
DANGER!
Before carrying out any operation on the electrical panel, disconnect the power supply. When the upper front cover of the heat pump is removed, the electrical panel is exposed and its
components could be touched accidentally. During the installation and maintenance of the equipment, never leave the electrical panel unsupervised while exposed.
Avoid touching any component of the electrical panel with wet hands; otherwise, electric shocks may
occur.
Avoid touching any electrical component of the heat pump (including circulation pumps, valves,
legionella protection electric heater, etc.) either during or immediately after operating the equipment. Otherwise, fire or electric shocks may occur.
Avoid using water or other liquids for cleaning the heat pump; otherwise, fire or electrical shocks may
occur.
Page 8
Model
Heating
and DHW
Integrate
DHW tank
Free
cooling
Active
cooling
Heating
output (kW)
Power
supply
ecoGEO B1 3-12
3-12
Single-Phase
ecoGEO B2 3-12
3-12
Single-Phase
ecoGEO B3 3-12
3-12
Single-Phase
ecoGEO B1 5-22
5-22
Single-Phase
ecoGEO B2 5-22
5-22
Single-Phase
ecoGEO B3 5-22
5-22
Single-Phase
ecoGEO B1 T 5-22
5-22
Single-Phase
ecoGEO B2 T 5-22
5-22
Three-Phase
ecoGEO B3 T 5-22
5-22
Three-Phase
ecoGEO C1 3-12
3-12
Single-Phase
ecoGEO C2 3-12
3-12
Single-Phase
ecoGEO C3 3-12
3-12
Single-Phase
ecoGEO C1 5-22
5-22
Single-Phase
ecoGEO C2 5-22
5-22
Single-Phase
ecoGEO C3 5-22
5-22
Single-Phase
ecoGEO C1 T 5-22
5-22
Three-Phase
ecoGEO C2 T 5-22
5-22
Three-Phase
ecoGEO C3 T 5-22
5-22
Three-Phase
Table 3.1. Models available from the range of ecoGEO heat pumps.
ACCESSORIES The following accessories are supplied with the heat pump:
Part
Quantity
Heat pump Installation and User Manual
1
th-Tune Installation and User Manual
1
1" strainer
2
Rubber gasket kit
1
th-Tune indoor terminal
1
Outdoor temperature probe
1
Temperature sensor for external tank
2
Table 3.2. Accessories included with ecoGEO heat pump.
3.2. OPERATING PRINCIPLES
ecoGEO geothermal heat pumps are designed for conditioning (heating and cooling) and providing DHW all­year round with simple installation and guaranteeing maximum energy efficiency at all times.
Installations with geothermal heat pumps consist of three main circuits (refrigerant circuit, brine circuit and heating-cooling circuit), in which thermal energy is carried between the ground and the building by using several fluids (refrigerant, antifreeze mixture and water). These circuits use different fluids; therefore, the transfer of thermal energy from one fluid to another is done by heat exchangers, where fluid at the highest temperature transfers heat to the fluid at the lowest temperature without mixing.
Page 9
No
Description
No
Description
1
Heat pump
7
Evaporator
2
Ground source system
8
Condenser
3
Heating-cooling system
9
Compressor
4
Brine circuit
10
Expansion valve
5
Refrigerant circuit
11
Brine circulation pump
6
Heating-cooling circuit
12
Heating-cooling circulation pump
Figure 3.1. Geothermal heat pump schematic.
The operating modes provided by the different technologies included in the ecoGEO geothermal heat pumps are outlined below.
HEATING MODE During the normal operating cycle, heat pumps draw energy from the ground for producing hot water in
the heating system. Its operation can be split into four sub-processes which are repeated on a cyclical basis.
The antifreeze mixture is successively circulated by a circulation pump through an ground source system, where it absorbs heat from the ground, and the evaporator, where it transfers heat to the fluid in
1
2
3
Page 10
the refrigerant circuit. The refrigerant in the evaporator is at low pressure and temperature, and it vaporizes as a result of the heat absorbed by the antifreeze mixture.
The refrigerant vapour coming from the evaporator is suctioned by the variable-speed inverter compressor, where its pressure and temperature increase (hot gas) in order to meet the actual heating demand.
The hot gas coming from the compressor is led to the condenser, where it transfers heat to the water in the heating system. As a result of this heat transfer, the refrigerant gas cools down and condenses into liquid form.
The refrigerant in liquid state is led back to the evaporator through the electronic expansion valve, which accurately controls the re-circulated refrigerant flow rate based on the heating system requirements. At the same time, while passing through the electronic expansion valve, the pressure and the temperature of the coolant decrease in order to attend again the condition to absorb heat from the antifreeze mixture in the evaporator.
FREE COOLING MODE (ECOGEO B2 AND C2 MODELS ONLY) The heat pump is supplied with an extra heat exchanger which allows direct heat exchange between the brine in the ground source system and the water in the cooling system, so the refrigerant circuit is not used. By using this operating mode, the compressor remains off and the cooling and brine circuits are derived to the free cooling heat exchanger through two 3-way valves. Thus, the equipment supplies fresh water to the cooling system, obtained from the energy exchange with the brine system, all with the sole use of circulation pumps.
This technology allows to air-condition dwelling (or commercial premises) all-year round in temperate regions, where temperatures during warmer months do not reach excessively high values. It is worth mentioning that, in the FREE COOLING mode, energy consumption is very low due to the high efficiency of circulation pumps.
ACTIVE COOLING MODE (ECOGEO B3 AND C3 MODELS ONLY) Active cooling consists of reversing the operating cycle of the heat pump's refrigerant circuit through a 4-
way valve. This means that the normal cycle condenser becomes the reversed cycle evaporator, and vice versa. In this operating mode, the fluid in the cooling system (water) draws heat from the dwelling and transfers it to the refrigerant in the evaporator; whereas the antifreeze mixture absorbs heat from the refrigerant in the condenser and transfers it to the ground. This operating mode is called active cooling by cycle reversing.
This technology provides year-round air-condition for housing (or commercial premises) even in regions where temperatures reach high values during warmer months.
DHW MODE The production of domestic hot water (DHW) is performed by two different technologies, depending on the model. For ecoGEO B1, B2, C1 and C2 models, the production of DHW is done by deviating the hot water from the condenser into the coil of the DHW tank via a 3-way valve. EcoGEO B3 and C3 models are equipped with CHW patented technology (Closed Hot Water production system). This new technology consists of incorporating an additional heat exchanger (desuperheater) intended for DHW production only. This heat exchanger is placed in series with the main condenser and feeds hot water into the coil of the DHW tank through a closed circuit. Also, given the fact that cycle reversal is done after the desuperheater, it allows simultaneous DHW and heating/active cooling production. Therefore, the CHW system can produce DHW up to 45ºC and also heat it up slowly when the machine is working to produce heating, cooling or servicing the pool up to 70ºC.
Page 11
If the electric support is enabled, the electric resistance works only at the end to heat the DHW up to the antilegionela setpoint. Therefore the electric resistance is used as little as possible.
LEGIONELLA PROTECTION MODE The heat pump is equipped with a electric resistance installed in the DHW tank, intended for preventing
potential legionellosis outbreaks only. Once per week, the heat pump increases the storage tank temperature up to the setpoint temperature, and the electric heater is subsequently activated in order to increase the DHW temperature up to 65 ºC, i.e., a temperature at which the bacteria cannot survive more than 20 minutes. It is recommended to carry out the heating during the night, when no DHW is being consumed.
POOL MODE The pool mode allows activating an external 3-way valve for deviating the hot water supply from the heat pump into a heat exchanger through which heat is transferred to the water in the swimming-pool.
FAULT MODE In the event of heat pump failure, that impedes start the compressor, the electric heater can be activated
for daily DHW production, ensuring DHW production for the user in case of heat pump failure.
3.3. DIMENSIONS AND CONNECTIONS
The general dimensions of the range of ecoGEO B heat pumps are specified in Figure 3.2.
4567
9
8
10
600
700
1082
3
2
1
Page 12
No
Description
No
Description
1
Heat pump module
6
Brine outlet (G1’’ F)
2
Top cover
7
Brine inlet (G1’’ F)
3
Front panel
8
DHW tank outlet (G3/4’’ F)
4
Heating-cooling outlet (G1’’ F)
9
DHW tank inlet (G3/4’’ F)
5
Heating-cooling inlet (G1’’ F)
10
Power supply input
Figure 3.2. Dimensions and connections of ecogGEO B heat pumps.
The general dimensions of the range of ecoGEO C heat pumps are specified in Figure 3.2.
4567
9
8
10
600
700
1800
3
1
2
Page 13
Descripción
Descripción
1
Tank module
6
Brine outlet (G1’’ F)
2
Heat pump module
7
Brine inlet (G1’’ F)
3
Front panel
8
DHW outlet (G1’’ F)
4
Heating-cooling outlet (G1’’ F)
9
Mains water inlet (G1’’ F)
5
Heating-cooling inlet (G1’’ F)
10
Power supply input
Figura 3.3. Dimensions and connections of ecogGEO C heat pumps.
3.4. MAIN COMPONENTS
The main components and their position for the different models of ecoGEO B heat pump range are outlined below.
The Figure 3.4 shows the location of the main components of ecoGEO B1 heat pumps.
No
Description
No
Description
1
Electrical panel
14
Brine safety valve (3 bar)
2
Condenser
15
Heating safety valve (3 bar)
3
Evaporator
16
Brine circuit drain valve
4
Inverter compressor
17
Heating circuit drain valve
5
Combi filter dryer
18
Compressor suction temperature probe
6
Electronic expansion valve
19
Brine outlet temperature probe
7
High-pressure switch
20
Brine inlet temperature probe
8
Low-pressure switch
21
Heating outlet temperature probe
9
Brine circulation pump
22
Heating inlet temperature probe
10
Heating circulation pump
23
Discharge pressure transducer
11
Heating/DHW 3-way valve
24
Suction pressure transducer
12
Brine expansion vessel (5 litters)
25
Brine pressure transducer
13
Heating expansion vessel (12 litters)
26
Heating pressure transducer
Figure 3.4. Component location in ecoGEO B1 models.
Page 14
The Figure 3.5 shows the location of the main components of ecoGEO B2 heat pumps.
No
Description
No
Description
1
Electrical panel
15
Heating-cooling expansion vessel (12 litters)
2
Condenser
16
Heating-cooling safety valve (3 bar)
3
Evaporator
17
Brine circuit drain valve
4
Free cooling heat exchanger
18
Heating-cooling circuit drain valve
5
Inverter compressor
19
Compressor suction temperature probe
6
Combi filter dryer
20
Brine outlet temperature probe
7
Electronic expansion valve
21
Brine inlet temperature probe
8
High-pressure switch
22
Heating-cooling outlet temperature probe
9
Low-pressure switch
23
Heating-cooling inlet temperature probe
10
Brine circulation pump
24
Discharge pressure transducer
11
Heating-cooling circulation pump
25
Suction pressure transducer
12
Heating/DHW 3-way valve
26
Brine pressure transducer
13
Free cooling 3-way valve (brine side)
27
Heating-cooling pressure transducer
14
Free cooling 3-way valve (cooling side)
Figure 3.5. Component location in ecoGEO B2 models.
.
Page 15
The Figure 3.6 shows the location of the main components of ecoGEO B3 heat pumps.
No
Description
No
Description
1
Electrical panel
16
Heating-cooling circulation pump
2
Condenser/evap (normal/reverse cycle)
17
Heating-cooling expansion vessel (12 litters)
3
Evaporator/cond (normal/reverse cycle)
18
Heating-cooling safety valve (3 bar)
4
DHW desuperheater
19
DHW circuit drain valve
5
Inverter compressor
20
Brine circuit drain valve
6
Combi filter dryer
21
Heating-cooling circuit drain valve
7
Electronic expansion valve
22
Compressor suction temperature probe
8
4-way cycle reversing valve
23
Brine outlet temperature probe
9
Check valves for reverse cycling (x4)
24
Brine inlet temperature probe
10
DHW desuperheater check valve
25
Heating-cooling outlet temperature probe
11
Solenoid valve for DHW system activation (x2)
26
Heating-cooling temperature probe
12
High-pressure switch
27
Discharge pressure transducer
13
Low-pressure switch
28
Suction pressure transducer
14
DHW circuit circulation pump
29
Brine pressure transducer
15
Brine circulation pump
20
Heating-cooling pressure transducer
Figure 3.6. Component location in ecoGEO B3 models.
Page 16
The Figure 3.7 shows the location of the main components of ecoGEO C1 heat pumps.
1
3
22
2
4
5
6
7
9
8
24
30
29
10 11
14
12
16
15
27
21
25
13
31
32
28
20
19
17
23
18
26
Descripción
Descripción
1
DHW tank (170 litters)
17
Check valve DHW circuit
2
Electrical panel
18
Air vent DHW circuit
3
Condenser
19
DHW tank drain valve
4
Evaporator
20
Brine circuit drain valve
5
Inverter compressor
21
Heating circuit drain valve
6
Combi filter dryer
22
Anti-legionella resistance
7
Electronic expansion valve
23
DHW tank temperature probe
8
High-pressure switch
24
Compressor suction temperature probe
9
Low-pressure switch
25
Brine outlet temperature probe
10
Brine circulation pump
26
Brine inlet temperature probe
11
Heating circulation pump
27
Heating outlet temperature probe
12
Heating/DHW 3-way valve
28
Heating inlet temperature probe
13
Brine expansion vessel (5 litters)
29
Discharge pressure transducer
14
Heating expansion vessel (12 litters)
30
Suction pressure transducer
15
Brine safety valve (3 bar)
31
Brine pressure transducer
16
Heating safety valve (3 bar)
32
Heating pressure transducer
Figure 3.7. Component location in ecoGEO C1 models.
Page 17
The Figure 3.8 shows the location of the main components of ecoGEO C2 heat pumps.
1
3
25
2
4
6
7
8
10
9
27
33
32
11 12
17
16
13
19
34
30
24
28
29
18
35
31
23
22
20
26
5
15
14
21
Descripción
Descripción
1
DHW tank (170 litters)
19
Heating safety valve (3 bar)
2
Electrical panel
20
Check valve DHW circuit
3
Condenser
21
Air vent DHW circuit
4
Evaporator
22
DHW tank drain valve
5
Free cooling heat exchanger
23
Brine circuit drain valve
6
Inverter compressor
24
Heating circuit drain valve
7
Combi filter dryer
25
Anti-legionella resistance
8
Electronic expansion valve
26
DHW tank temperature probe
9
High-pressure switch
27
Compressor suction temperature probe
10
Low-pressure switch
28
Brine outlet temperature probe
11
Brine circulation pump
29
Brine inlet temperature probe
12
Heating-cooling circulation pump
30
Heating outlet temperature probe
13
Heating/DHW 3-way valve
31
Heating inlet temperature probe
14
Free cooling 3-way valve (brine side)
32
Discharge pressure transducer
15
Free cooling 3-way valve (cooling side)
33
Suction pressure transducer
16
Brine expansion vessel (5 litters)
34
Brine pressure transducer
17
Heating expansion vessel (12 litters)
35
Heating pressure transducer
18
Brine safety valve (3 bar)
Figure 3.8. Component location in ecoGEO C2 models.
Page 18
The Figure 3.9 shows the location of the main components of ecoGEO C3 heat pumps.
Descripción
Descripción
1
DHW tank (170 litters)
20
Brine safety valve (3 bar)
2
Electrical panel
21
Heating safety valve (3 bar)
3
Condenser/evap (normal/reverse cycle)
22
Check valve DHW circuit
4
Evaporator/cond (normal/reverse cycle)
23
Air vent DHW circuit
5
DHW desuperheater
24
DHW tank drain valve
6
Inverter compressor
25
DHW circuit drain valve
7
Combi filter dryer
26
Brine circuit drain valve
8
Electronic expansion valve
27
Heating circuit drain valve
9
4-way cycle reversing valve
28
Anti-legionella resistance
10
Check valves for reverse cycling (x4)
29
DHW tank temperature probe
11
DHW desuperheater check valve
30
Compressor suction temperature probe
12
Solenoid valve for DHW system activation (x2)
31
Brine outlet temperature probe
13
High-pressure switch
32
Brine inlet temperature probe
14
Low-pressure switch
33
Heating outlet temperature probe
15
DHW circuit circulation pump
34
Heating inlet temperature probe
16
Brine circulation pump
35
Discharge pressure transducer
17
Heating-cooling circulation pump
36
Suction pressure transducer
18
Brine expansion vessel (5 litters)
37
Brine pressure transducer
19
Heating expansion vessel (12 litters)
38
Heating pressure transducer
Figure 3.9. Component location in ecoGEO C3 models.
1
3
28
2
4
6
7
8
14
13
30
36
35
16 17
19
18
21
37
33
27
31
20
38
34
26
25
22
29
15
24
11
5
9
10
12
23
32
Page 19
3.5. REMOVING THE COVERS
For the heat pump installation, start-up and maintenance, it is necessary to access several areas inside the heat pump. This may require removing one or several covers from the equipment housing (see section 3.4).
REMOVING THE COVERS ECOGEO B MODELS
The top cover allows access to the electrical panel:
1. Pull the top cover upwards and place it where it cannot be damaged.
2. Remove the screws of the electrical panel cover.
3. Remove the electrical panel cover and place it where it cannot be damaged.
1
2
X8
Figure 3.10. Dismounting the top cover and the electrical panel cover.
The front cover allows access to the components of the heat pump module:
1. Remove the top cover as described above.
2. Remove the screws located on the bottom side of the cover.
3. Pull the cover upwards for disengaging the top side of the cover from the equipment housing.
4. Remove the cover by pulling frontwards and place it where it cannot be damaged.
NOTE
When removing the upper front cover, detach cautiously the cable between the micro-controller and
the front panel without damaging it.
Page 20
Figure 3.11. Dismounting the front cover.
The side covers allow access to the hydraulic part:
1. Remove the top and front covers as described above.
2. Remove the screws located on the front side of the cover that you want to dismount.
3. Pull the cover outwards for disengaging it from the equipment housing.
4. Remove the cover by pulling frontwards and place it where it cannot be damaged.
Figure 3.12. Dismounting the side covers.
1
2
1
Page 21
The heat pump rear cover can also be dismounted when necessary:
1. Remove the screws of the cover that you want to dismount.
2. Remove the cover and place it where it cannot be damaged.
Figure 3.13. Dismounting the rear cover.
X6
Page 22
REMOVING THE COVERS ECOGEO C MODELS
The top cover allows access to the electrical panel:
1. Remove the screws located on the top side of the cover.
2. Pull the cover upwards for disengaging the bottom side of the cover from the equipment housing.
3. Remove the cover by pulling frontwards and place it where it cannot be damaged.
1
2
Figure 3.14. Dismounting the top front cover.
Page 23
The bottom front cover allows access to the components of the heat pump module:
1. Remove the top cover as described above.
2. Remove the screws located on the bottom side of the cover.
3. Pull the cover upwards for disengaging the top side of the cover from the equipment housing.
4. Remove the cover by pulling frontwards and place it where it cannot be damaged.
Figure 3.15. Dismounting the bottom front cover.
1
2
Page 24
The side covers allow access to the hydraulic part:
1. Remove the top and front covers as described above.
2. Remove the screws located on the front side of the cover that you want to dismount.
3. Pull the cover outwards for disengaging it from the equipment housing.
4. Remove the cover by pulling frontwards and place it where it cannot be damaged.
Figure 3.16. Dismounting the side covers.
Page 25
The heat pump rear and top cover can also be dismounted when necessary:
1. Remove the screws of the cover that you want to dismount.
2. Remove the cover and place it where it cannot be damaged.
X4
X8
X6
Figure 3.17. Dismounting the rear and top cover.
Page 26
4. USER MANUAL
4.1. FRONT PANEL OVERVIEW
The heat pump front panel is equipped with a 6-key display as shown in Figure 4.1.
2
2
3
6
4
5
1
No
Description
No
Description
1
Screen
4
Alarms Menu access key [Alarm]
2
Scroll keys [↑]/[↓]
5
User Menu access key [Prg]
3
Select and enter key [←]
6
Back key [Esc]
Figure 4.1. Front panel.
The general functioning and operation of each key is outlined below.
SCROLL KEYS [↑]/[↓] On screens containing menu lists, it is possible to move the cursor inside the list. Once inside the menu
it is also possible to move to the previous or following screen. In screens containing configurable parameters, it enables to increase or decrease the parameter value selected with the cursor.
SELECT AND ENTER KEY [←] On screens containing menu lists, it is possible to access the selected menu with the cursor. On screens
containing configurable parameters, it allows moving the cursor to the next configurable parameter on the screen. The modified parameter is saved when moving the cursor to the next configurable parameter on the screen. Finally, it provides quick access to menu 1.8 INFORMATION from the home screen (see Table 4.2).
USER MENU ACCESS KEY [PRG] It provides quick access to menu 1. USER from anywhere within the application (see Table 4.2).
PRESSING [PRG]+[ESC] KEYS SIMULTANEOUSLY Pressing [Prg]+[Esc] keys simultaneously allows the quick access to menu 2. INSTALLER (see Table
4.3).
Page 27
ACCESS BUTTON TO THE ALARMS MENU [ALARM] It allows the quick access to the menu 1.9 ALARMS from any location within the program (see Table
4.2).
BACK BUTTON [ESC] It allows going to the previous menu from any part of the program.
4.2. PROGRAMS
ECOFOREST ecoGEO heat pumps have three main operating programs, which are described below.
WINTER PROGRAM The heat pump only allows activation of the operating modes HEATING, DHW, LEGIONELLA PROTECTION, POOL and FAULT. FREE COOLING and ACTIVE COOLING operating modes are not permitted.
SUMMER PROGRAM The heat pump only allows activation of the operating modes FREE COOLING, ACTIVE COOLING, DHW, LEGIONELLA PROTECTION, POOL and FAULT. HEATING operating mode is not permitted.
AUTO PROGRAM The heat pump automatically selects one of the WINTER / SUMMER operation programs based on several environmental parameters. In the example in Figure 4.2 if the outside temperature rises above 26 ° C over a period of 5 hours an automatic program to SUMMER WINTER program occurs. If the outside temperature drops below 12 ° C over a period of 5 hours an automatic program to WINTER SUMMER program occurs.
Figure 4.2. Example of AUTO program configuration.
MIX PROGRAM The MIX program does not work with SUMMER/WINTER program. It is designed to produce heating or
cooling, always prioritising the DHW. To produce heating the machine needs relay signals (thermostat signals) at points DI1 and / or DI4 to. To produce cooling the heat pump needs relay signals at points DI3 and / or points DI5.
Note that, to work with the mixed program, the th-tune terminals cannot be used implementing the “buffer tank” scheme. Also you should pay attention to the “heating stop temperature” in for heating and cooling in user menu (see section 4.5 points 1.3, 1.6 and 1.7).
To set the MIX program it is necessary to follow the steps in AUTO program and to set a summer temperature higher than the winter one. The machine will be in MIX program when the outdoor
Page 28
temperature is between the winter and the summer temperature. In addition you must put the time change to 0h.
4.3. OPERATION SHEMES
The ecoGEO heat pump can be connected to the heating-cooling system using three different schemes. The functionality and the menus available from the heat pump control program depend greatly on the type of connection plan used. The main features of each scheme are detailed below. Pump control
1 ZONE SCHEME Installations with the heat pump directly connected to the heating-cooling system supplying one
temperature level (hereinafter referred to as "1 Zone").
2 ZONE SCHEME Installations with the heat pump directly connected to the heating-cooling system supplying two different temperature levels controlled by the heat pump (hereinafter referred to as "2 Zone"). The heat pump supplies directly at the highest outlet temperature (Zone 1). The lowest outlet temperature (Zone 2) is reached by an external shunt group with a modulating mixing valve.
BUFFER TANK SCHEME Installations with the heat pump connected to a intermediate buffer tank between the heat pump and the
heating-cooling system.
4.4. HOME SCREEN
The front panel turns on when the external breaker of the heat pump is activated. While the application is loading, a display with the ECOFOREST logotype opens. After a few seconds, the home screen comes up showing different icons informing about the condition of the pump (operation program, operation mode, date and time, and status). Figure 4.3 shows the home screen and Table 4.1 contains the meanings for the icons that can appear on it.
Page 29
No
Description
No
Description
1
Heat pump status
6
Compressor status
2
Current date
7
Brine and heating pumps status
3
Current time
8
Compressor status
4
Mode
9
Temperature and energy information
5
Operating program
10
Cooling and heating shunts activation
Figure 4.3. Home screen.
Icon
Meaning
Heat pump ON
Heat pump OFF
Off by CONTROL PANEL
Off by ALARM
LOCKED by alarm
Off by SCHEDULE
Off by REMOTE
NIGHT schedule activated
WINTER program activated
SUMMER program activated
Automatic program selection enabled
Mix program activated
Heating SOURCE
HEATING mode activated
Heating BUFFER tank mode activated
COOLING mode activated
Cooling BUFFER tank mode activated
DHW mode activated
POOL mode activated
LEGIONELLA PROTECTION mode activated
FAULT mode activated
FLOOR DRYING mode activated
Brine pump running
Compressor running
Heating pump running
Compressor starting
Compressor stopped
Heating shunt 1 activated
Heating shunt 2 activated
Cooling shunt 1 activated
Cooling shunt 2 activated
Compressor on waiting time
Reversing the cycle
Electric heater activated
Table 4.1. Meanings for home screen icons.
The application is structured into two main menus with different access levels:
Page 30
MENU 1. USER This menu is accessed from anywhere inside the program by pressing [Prg]. It can be accessed by the
end user of the heat pump and allows turning on/off the equipment, selecting the operation program and setting several comfort parameters (see section 4.5).
MENU 2. INSTALLER This menu is accessed from anywhere within the program by pressing [Prg]+[Esc] simultaneously and
subsequently introducing the PW1 installer’s password. It allows configuring the necessary parameters for setting the type of installation in which the pump is going to function, to adjust different operating parameter of the heat pump and to perform several start-up and maintenance tasks (see section 4.6).
4.5. USER MENU
1. USER menu
Level 1 submenu
Level 1 submenu
Level 1 submenu
1.1. On/Off
1.1.1. On/Off ecoGEO
1.1.2. AUTO program
1.2. Schedule
1.2.1. Date/Time
1.2.2. Daily saving time
1.2.3. Schedule
1.2.3.1. Nigth-time
1.2.3.2. Schedule HP ON/OFF
1.2.3.3. DHW schedule
1.2.3.4. Heating schedule
1.2.3.5. Cooling schedule
1.2.3.6. Pool schedule
1.3 Heating
1.3.1 Heating
1.3.2 Heating curve
1.4. DHW/Legionela
1.4.1. DHW
1.4.2. Legionella
1.5. Pool
1.5.1. Pool
1.6. Free cooling
1.7. Active cooling
1.8. Información
1.8.1. Brine/Heating
1.8.2. DHW
1.8.3. Heating/Cooling
1.8.4. Heating buffer tank
1.8.5. Cooling buffer tank
1.8.6. th-Tune
1.8.7. Compressor
1.8.8. Expansion valve
1.8.9. Energy meters
1.8.10. Month energy meters
1.8.11. Year energy meters
1.8.12. Version
1.9. Alarmas
1.9.1. Alarmas
1.9.2. Reset alarmas
1.9.3. Alarm log
Table 4.2. USER menu structure.
Page 31
The following describes the features included in each menu.
MENU 1.1. ON/OFF
MENU 1.1.1. ON/OFF ECOGEO 1
It allows switching the heat pump status between ON / OFF. The selected status can be modified by schedule, alarm or digital inputs.
It allows selecting the operation program between AUTO / WINTER / SUMMER.
MENU 1.1.2. AUTO PROGRAM
It allows changing the parameters for the AUTO program.
MENU 1.2. SCHEDULE
MENU 1.2.1. DATE/TIME
It allows adjusting the date and the time in the control programme of the pump.
MENU 1.2.2. DAILY SAVING TIME
It allows enabling/disabling the automatic time change between seasons. It allows adjusting the time zone to be applied and the dates/times at which time change will occur
The schedules configured on the heat pump are only for the heat pump. there is no relation between these schedules and the th-tune schedules.
MENU 1.2.3 SCHEDULE
The schedules configured on the heat pump are only for the heat pump. there is no relation between these schedules and the th-tune schedules.
MENU 1.2.3.1. NIGHT-TIME
It allows ENABLE / DISABLE and set a time frame for the maximum speed of the compressor to reduce noise emissions. Note that reducing the speed of the compressor reduces also the power of the heat pump. (see points 12.6 and 12.7).
MENU 1.2.3.2. SCHEDULE HP ON/OFF
It allows two possible configurations:
Status ON: The machine is turned on during the period or periods that have been
established and the rest time is off.
State OFF: The machine is turned off during the period or periods that have been set
and it is always turned on in any other period.
MENU 1.2.3.3 DHW SCHEDULE
It allows ENABLE / DISABLE the schedules of DHW mode. It also allows defining slots where ENABLE / DISABLE DHW for each day of the week and set mark the setpoint temperature accumulation for each time slot. Additionally, it is possible to copy the schedule established on a day on to another day. To do this so, set the day you want to copy in "Copy to” and choose "YES". Once the message "SUCCESSFUL COPY" appears, the new day is ready.
Page 32
MENU 1.2.3.4. HEATING SCHEDULE
It allows ENABLE / DISABLE the schedule of heating mode. It also allows defining slots where ENABLE / DISABLE heat production for each day of the week. If you have installed the “buffer tank” configuration you can choose the set temperature in the buffer tank.
Additionally it is possible to copy the schedule established on a day to another day. To do this,
set the day you want to copy in "Copy to” and choose "YES". Once the message
"SUCCESSFUL COPY" appears, the new day is ready.
MENU 1.2.3.5. COOLING SCHEDULE
It allows ENABLE / DISABLE the schedule of cooling mode. It also allows defining slots where
ENABLE / DISABLE cool production for each day of the week. If you have installed the “buffer
tank” configuration you can choose the set temperature in the buffer tank.
Additionally it is possible to copy the schedule established on a day to another day. To do this,
set the day you want to copy in "Copy to” and choose "YES". Once the message
"SUCCESSFUL COPY" appears, the new day is ready.
MENU 1.2.3.6. POOL SCHEDULE
It allows ENABLE / DISABLE the schedule of pool mode. It also allows defining slots where ENABLE / DISABLE pool production for each day of the week.
Additionally it is possible to copy the schedule established on a day to another day. To do this, set the day you want to copy in "Copy to” and choose "YES". Once the message "SUCCESSFUL COPY" appears, the new day is ready.
MENU 1.3. HEATING In this menu you can ENABLE / DISABLE the heating mode. It should also adjust the maximum outside temperature value above which disables.
In 1 ZONE and 2 ZONES schemes the flow setpoint temperatures for each zone are shown. This value is configured in the installer menu, see section 2.2.3.1, with temperature curve or fixed setpoint. If the user wishes to increase or decrease these temperatures should go to the next page "1.3.2 Heating Curve" and fill or empty the bars of the zone concerned. Each section that moves are added or subtracted 2 °C. Initially the bar is at the midpoint can fill two sections (totaling 4 °C) or empty it completely (minus 4ºC).
In the scheme BUFFER TANK setpoint temperature and offset for the tank temperature is displayed. This value is configured in the installer menu, see section 2.2.3.1. If a fixed setpoint was chosen this value is editable in the user menu. If a temperature curve was chosen can be changed using bars as explained in the previous paragraph.
MENU 1.4. DHW/LEGIONELLA
MENU 1.4.1. DHW
It grants to adjust the DHW temperature set point, as well as the offset (temperature difference) below the temperature set point from which the production of DHW is enabled.
If the electrical resistance disables support the "Setpoint - Offset" value must not exceed 45. The difference will be automatically modified to enforce this rule. This is due to the fact that the compressor struggles to start with tank temperatures above 45 ° C.
Page 33
If you have enabled the electrical support the "Setpoint - Offset" value can be higher than 45 ° C but the compressor only start when the tank temperature is below 45C so much of the DHW produced will be resistance.
Furthermore only for B3 and C3 models must be configured CHW value. The high temperature of the compressor discharge can heat the water up to maximum 70ºC. You can configure up to 70 but only produce DHW at this temperature when the machine is working to produce another demand, is heating, cooling or swimming pool.
MENU 1.4.2. LEGIONELLA PROTECTION
It allows to ENABLE/DISABLE the LEGIONELLA PROTECTION mode. It is also possible to set the day of the week and the time at which the LEGIONELLA PROTECTION mode is to start.
MENU 1.5. POOL
MENU 1.5.1. POOL
It permits to ENABLE/DISABLE the POOL mode. It also allows you to set the minutes per hour of winter program. This parameter sets the minutes per hour that the machine works with pool only under the case there is demand for heating and pool at the same time.
In summer mode the cooling has preference over the pool. If we want to establish some kind of preference for the pool we can only limit the operation of the cooling in the cooling schedule as explained in section 1.2.3.4.
MENU 1.6. FREE COOLING This menu is only available in ecoGEO B2 models. It allows ENABLING/DISABLING the FREE COOLING mode. It should also adjust the minimum outside temperature value below which disables.
It also allows setting the free cooling temperature. Keep in mind that if you install terminals th-tune and configure a different system than fan coil, humidity control can take a different setpoint value to avoid condensation.
MENU 1.7. ACTIVE COOLING This menu is only available in models ecoGEO B3 and C3. In it you can ENABLE / DISABLE active cooling completely. It should also adjust the minimum outside temperature value below which disables.
In 1 ZONE and 2 ZONAES schemes the flow setpoint temperature for each zone are shown. Is possible to configure this value in the installer menu, see section 2.2.3.1, using curve or fix temperature setpoint. You can only change these values if the setpoint chosen in the installer menu is fixed.
In the scheme BUFFER TANK the setpoint temperature and the offset are shown. Is possbile to configure this value in the installer menu, see section 2.2.3.1, using curved or fix temperature setpoint. You can only change these values if the setpoint chosen in the installer menu is fixed.
Keep in mind that if you install terminals th-tune and configure a different system than fan coil, humidity control can take a different setpoint value to avoid condensation.
MENU 1.8. INFORMATION It shows all the information related to the operation of the heat pump and the condition of the installation.
This menu can be quickly accessed by pressing key [←] from the home screen.
Page 34
MENU 1.8.1. BRINE / HEATING
It shows the flow and return temperatures of brine and heating/cooling circuits and the temperature difference. It also shows pressure of both circuits and the % of the circulation pumps.
MENU 1.8.2. DHW
It shows the DHW set point temperature and the current temperature of the DHW tank.
MENU 1.8.3. HEATING / COOLING (ONLY FOR 1 ZONE AND 2 ZONES CONFIGURATION)
This screen is only available with 1 zone and 2 zones configuration. It shows the current setpoint temperature in each zone, the actual flow temperature and the percentage of bypass (0-10V signal) of the mixing valve for zone 2.
It also shows the current outdoor temperature.
MENU 1.8.4. HEATING BUFFER TANK (ONLY FOR BUFFER TANK CONFIGURATION)
This screen is only available with buffer tank configuration. It shows the current and the actual setponit temperature for heating. It also shows the current outdoor temperature.
MENU 1.8.5. COOLING BUFFER TANK (ONLY FOR BUFFER TANK AND ECOGEO B3 AND C3)
This screen is only available with buffer tank configuration and with ecoGEO B3 and C3 heat pumps. It shows the current and the actual setponit temperature for cooling. It also shows the current outdoor temperature.
MENU 1.8.6. TH-TUNE (ONLY FOR TH-TUNE THERMOSTATS CONFIGURATED)
It shows the actual and the setpoint temperature of each terminal Th-Tune and also the relative humidity.
MENU 1.8.7. COMPRESSOR
It shows the current pressure and temperature of the suction (low) and the discharge (high) of the compressor. It also shows on the right of all the condensation temperature corresponding to the hight pressure. This temperature corresponds to the temperature that the refrigerant fluid changes the phase at high pressure. At the bottom It shows the current compressor speed, total working hours and the inverter temperature.
MENU 1.8.8. EXPANSION VALVE
It shows the current pressure and temperature in the evaporator outlet, it’s the same value of the compressor suction (low) of the last screen. It also shows the evaporation temperature corresponding to the low pressure. This temperature corresponds to the temperature that the refrigerant fluid changes the phase at low pressure.
On the bottom left shows the superheating SH. It is the difference between the two temperatures shown on this screen. The SH is used for the controller to chose the % status of the expansion valve.On the bottom right is shown the % status of the expansion valve.
MENU 1.8.9. ENERGY METERS
It shows the current power in heating and cooling mode and the current electric power. It also shows the performance values for heating COP and for cooling EER.
Page 35
MENU 1.8.10. MONTH ENERGY METERES
It shows the energy values explained on the previous screen accumulated during a month.
MENU 1.8.11. YEAR ENERGY METERES
It shows the energy values explained on the previous screen accumulated during a year.
MENU 1.8.12. VERSION
It shows information on the application version, the BIOS and the expansion valve drivers installed in the heat pump.
MENU 1.9. ALARMS This menu can be quickly accessed by pressing key [Alarm] from the home screen.
MENU 1.9.1. ALARMS
It shows the alarms that are currently activated. All the alarms included in this menu do not enable to start the compressor. If the cause of the alarm is solved, it will automatically disappear from the menu and the compressor can be restarted. There are some alarms that, if repeating five subsequent times, will trigger the locked alarm preventing the heat pump from starting until the active permanent alarm is manually removed.
MENU 1.9.2. RESET ALARMS
It allows removing manually the permanent alarms caused by five consecutive alarms due to the same cause.
MENU 1.9.3. ALARM LOG
Provides access to the record of all alarms that occurred during the period of operation of the heat pump, indicating the date and time they were activated.
This alarm log can be deleted from menu 2. INSTALLER.
4.6. INSTALLER MENU
Table 4.3 shows the submenu structure for menu 2. INSTALLER.
2. INSTALLER menu
Level 1 submenu
Level 1 submenu
Level 1 submenu
2.1. Language
2.2. Configuration
2.2.1. Heat pump model
2.2.2 Source
2.2.3. Services
2.2.3.1. Heating/cooling
2.2.3.2. DHW
2.2.3.3. Pool
2.2.3.4. Special programs
2.2.4 Remote control
2.2.4.1. HP remote control
2.2.4.2. DHW switch
2.2.4.3. Program switch
2.2.4.4. BMS configuration
2.2.5. Protections
2.2.5.1. Compressor capacity
2.2.5.2. Brine alarm
Page 36
2.2.5.3. Pressure Brine/Heat
2.2.5.4. Cooling outlet temp
2.2.5.5. Pump protections
2.2.5.6. Trial period
2.2.6. Probe conf.
2.2.6.1. Brine outlet temp.
2.2.6.2. Brine inlet temp.
2.2.6.3. Heating outlet temp.
2.2.6.4. Heating inlet temp.
2.2.6.5. Brine pressure
2.2.6.6. Heating pressure
2.2.6.7. Suction temp
2.2.6.8. Suction pressure
2.2.6.9. Discharge pressure
2.2.6.10. DHW temp
2.2.6.11. Temp Outlet Z2
2.2.6.12. Outside temperature
2.3. Manual test
2.3.1. Brine pump
2.3.2. Heating pump
2.3.3. Inverter contactor
2.3.4. Electric heater cont.
2.3.5. Shunt group Z2
2.3.6. Alarm system
2.3.7. DHW valve
2.3.8. Free cooling valve
2.3.9. DHW pump
2.3.10. Reversing valve
2.3.11. Pool
2.3.12. Zone 1 valve
2.4. Alarm log
2.5. Default values
2.4. Change password
Table 4.3. INSTALLER menu structure.
The functions included in each menu are as follows:
MENU 2.1. LANGUAGE This allows selecting the language of the application of the heat pump.
MENU 2.2. CONFIGURATION
MENU 2.2.1. HEAT PUMP MODEL
This allows selecting the model of the heat pump in the range ecoGEO range.
MENU 2.2.2. EXTERNAL ACTIVATION
This allows activating/deactivating the remote turning on/off of the heat pump through a voltage-free signal connected to a digital input DI2 (see section 7).
Page 37
MENU 2.2.3. SERVICES
MENU 2.2.3.1. HEATING / COOLING
It allows select the parameters of heating and cooling:
INSTALLATION SCHEME. Select the system diagram that the heat pump between 1
ZONE / 2 ZONES / BUFFER TANK.
HEATING/COOLING EMISSION SYSTEM: Select the emission system for each zone
between UNDERFLOOR HEATING / LOW TEMPERATURE RADIATORS / FAN COIL.
THERMOSTATS ZONE 1 and 2: Select the control terminal of each area between TH-
TUNE and thermostats or both. Also you should select the bus adress of each th-Tune. It is recommended to use the address 1 for the th-Tune of zone 1 and adress 2 for the th-Tune of zone 2. The operating logic in the case of the two activated terminal is explained in detail in section 8.3.
HEATING AND COOLING CURVES. It allows set the flow setpoint temperature of each
zone for heating and cooling. This can be fix or with a curve according to the outside temperature.
INSULATION. Set the level of insulation of the building to chose the type of heating
curve temperature.
MENU 2.2.3.2. DHW
This allows activating/deactivating the DHW mode.
MENU 2.2.3.3. POOL
It allows ENABLE / DISABLE the POOL mode and also de flow temperature setpoint for POOL mode. It also possible to choose the logic of activation between normally open and normally closed NO/NC.
MENU 2.2.3.4. SPECIAL PROGRAMS
This menu is available only with the scheme DRYING FLOOR. It allows adjusting the maximum outlet temperature, the maximum time of operation and the waiting time of the drying floor mode.
MENU 2.2.4 REMOTE CONTROL
MENU 2.2.4.1. HP REMOTE CONTROL
It allows ENABLE / DISABLE and choose the logic NO / NC (NO = Normally Open NC = Normally Closed) to control the ON/OFF of the whole heat pump. It must be connected to digital input DI2.
MENU 2.2.4.2. DHW SWITCH
It allows ENABLE / DISABLE and choose the logic NO / NC (NO = Normally Open NC = Normally Closed) to control the ON/OFF of the DHW. It must be connected to the digital input DI7.
MENU 2.2.4.3. PROGRAM SWITCH
It allows ENABLE / DISABLE the remote control for the current winter or summer program. It must be connected to the digital input DI8. The logic is:
Page 38
Relay OPEN: summer program. Relay CLOSED: Winter program.
MENU 2.2.4.4. BMS CONFIGURATION
This allows setting the communication data parameters of the port of the micro-controller where the indoor th-Tune terminal is connected (BMS port). To use the th-Tune terminals, it is necessary to use the default configuration, which is shown in Figure 4.4.
Figure 4.4. Default configuration of the BMS port for the correct operation of the th-Tune indoor
terminals.
MENU 2.2.5. PROTECTIONS
MENU 2.2.5.1. POWER LIMITATION
This allows adjusting the maximum thermal power given by the heat pump, which is established by limiting the maximum rotation speed of the compressor.
In section 12.6 there are illustrations with the relations of the thermal power provided by the different heat pump models as a function of the rotation speed of the compressor for the different operation conditions. Furthermore, in section 12.7, there are illustrations with the relations of the electrical consumption of the different heat pump models as a function of the rotation speed of the compressor for the different operation conditions.
MENU 2.2.5.2. BRINE ALARM
It allows adjusting the value under which the alarm is activated due to low temperature in the brine system.
MENU 2.2.5.3. PRESSURE BRINE/HEATING
This allows adjusting the values under which the alarm are activated due to low pressure in the brine and heating-cooling circuits.
MENU 2.2.5.4. COOLING OUTLET TEMPERATURE
This menu is available only in the models ecoGEO B3. This allows adjusting the value under which the alarm is activated due to low outlet temperature in ACTIVE COOLING mode.
MENU 2.2.5.5. PUMP PROTECTIONS
This allows seting the maximum and minimum speed of the circulation pumps (brine pump and heating/cooling pump).
Page 39
MENU 2.2.5.6. TRIAL PERIOD
This allows activating/deactivating a trial period in which the heat pump is blocked. It also allows adjusting the trial period time. Once the heat pump is blocked, it is possible to unblock by deactivating the trial period.
MENU 2.2.6. PROBE CONFIGURATION
MENU 2.2.6.1. BRINE OUTLET TEMPERATURE
It shows the type of temperature probe installed in the brine circuit outlet and its current reading. It also allows entering a correction for the sensor reading.
MENU 2.2.6.2. BRINE INLET TEMPERATURE
It shows the type of temperature sensor installed in the brine circuit inlet and its current reading. It also allows entering a correction for the sensor reading.
MENU 2.2.6.3. HEATING OUTLET TEMPERATURE
It shows the type of temperature sensor installed in the heating-cooling circuit outlet and its current reading. It also allows entering a correction for the sensor reading.
MENU 2.2.6.4. HEATING INLET TEMPERATURE
It shows the type of temperature sensor installed in the heating-cooling inlet circuit and its current reading. It also allows entering a correction for the sensor reading.
MENU 2.2.6.5. BRINE PRESSURE
It shows the type of pressure sensor installed in the brine circuit and its current reading. It also allows entering a correction for the sensor reading.
MENU 2.2.6.6. HEATING PRESSURE
It shows the type of pressure sensor installed in the heating-cooling circuit and its current reading. It also allows entering a correction for the sensor reading.
MENU 2.2.6.7. SUCTION TEMPERATURE
It shows the type of temperature sensor installed in the compressor suction (refrigerant circuit) and its current reading. It also allows entering a correction for the sensor reading.
MENU 2.2.6.8. SUCTION PRESSURE
It shows the type of pressure sensor installed in the compressor suction (refrigerant circuit) and its current reading. It also allows entering a correction for the sensor reading.
MENU 2.2.6.9. DISCHARGE PRESSURE
It shows the type of pressure sensor installed in the compressor discharge (refrigerant circuit) and its current reading. It also allows entering a correction for the sensor reading.
MENU 2.2.6.10. DHW TEMPERATURE
It shows the type of pressure sensor installed in the DHW tank and its current reading. It also allows entering a correction for the sensor reading.
Page 40
MENU 2.2.6.11. BUFFER TANK / OUTLET TEMPERATURE Z2
In 2 ZONES scheme show the type of temperature sensor installed in the outlet temperature for Zone 2 of the heating-cooling circuit and its current reading. In scheme BUFFER TANK shows the type of temperature sensor installed in the buffer tank and its current reading. It also allows entering a correction for the sensor reading.
MENU 2.2.6.12. OUTSIDE TEMPERATURE
It shows the type of outside temperature sensor and its current reading. It also allows entering a correction for the sensor reading.
MENU 2.3. MANUAL TEST
MENU 2.3.1. BRINE PUMP
This allows activating/deactivating manually the brine pump and adjusting its percentage of rotation speed.
MENU 2.3.2. HEATING PUMP
This allows activating/deactivating manually the heating-cooling pump and adjusting the percentage of rotation speed.
MENU 2.3.3. INVERTER CONTACTOR
This allows activating/deactivating manually the contactor to activate the inverter. The activation of the inverter doesn’t imply the compressor start, it only allows verifying that the inverter is properly energized.
MENU 2.3.4. ELECTRIC HEATER CONTACTOR
This allows activating/deactivating manually the legionella protection electric heater. The electric heater is deactivated automatically when exiting the menu 2.4.7. MANUAL TEST.
MENU 2.3.5. DHW VALVE
This menu is available only in the models ecoGEO B1 and ecoGEO B2. This allows activating/deactivating manually the 3-way valve for DHW production. The value ON positions the valve in DHW mode and the value OFF positions the valve in HEATING mode.
MENU 2.3.6 DHW PUMP
This menu is available only in the model ecoGEO B3. This allows activating/deactivating manually the circulation pump and the solenoid valves of the DHW production system (CHW system).
MENU 2.3.7. FREE COOLING VALVE
This menu is available only in the model ecoGEO B2. This allows activating/deactivating manually the free cooling 3-way valves. The value ON positions the valves in FREE COOLING mode and the value OFF positions the valve in HEATING/DHW mode.
MENU 2.3.8. POOL
This allows activating/deactivating manually the 3-way derivation valve to the pool heat exchanger. The position of the valve for the values ON/OFF depends on its hydraulic installation.
Page 41
MENU 2.3.9. REVERSING VALVE
This menu is available only in the model ecoGEO B3. This allows activating/deactivating manually the 4-way cycle reversing valve. The value ON positions the valve in HEATING mode (direct cycle) and the value OFF positions the valve in ACTIVE COOLING mode (reverse cycle).
MENU 2.3.10. ZONE 1 VALVE
This allows activating/deactivating manually the 2-way valve for Zone 1. The value ON energize the valve and the value OFF de-energized it.
MENU 2.3.11. SHUNT GROUP Z2
This allows activating/deactivating manually the power supply of the external shunt group and adjusting the percentage of bypass of the 3-way modulating valve.
MENU 2.3.12. ALARM SYSTEM
This allows activating/deactivating manually the alarm signal of the heat pump (digital signal).
MENU 2.4. ALARM LOG This allows deleting the alarms log record of the heat pump.
MENU 2.5. DEFAULT VALUES
MENU 2.5.1. INICIALIZATION It allows deleting the adjustments made in Menu 1. USER and 2. INSTALLER and recovering the default configuration.
MENU 2.5.2. RESET ENERGY METERS It allows resetting the energy meters.
MENU 2.6. CHANGE PASSWORD
This allows changing the access password (PW1) to the menu 2. INSTALLER.
5. TRANSPORT AND LOCATION
Follow these steps in the indicated order to disassemble the heat pump and place it in its final place of installation.
1. Carefully take the heat pump out of the package (wooden box, plastic, etc.).
2. Carefully take the moorings that fix the heat pump.
3. Check that the heat pump has not been damaged during transportation and that all its components are included.
4. Place the heat pump in its place of installation.
Take into account the recommendations about its transport and location of sections 5.1 to 5.3.
Page 42
5.1. TRANSPORT AND HANDLING
EcoGEO heat pumps must be transported in vertical position in such a way that they are not exposed to inclement weather.
When moving the heat pump to its place of installation, it must be carefully handled. If strictly necessary, the heat pump can be disassembled in two modules for easy transportation and handling.
5.2. RECOMMENDATIONS FOR LOCATION
The heat pump must be installed on a stable base, preferably concrete, which is capable of supporting the total weight indicated in the technical specifications (see section 12.1) as well as the volume of water contained in the DHW tank (170 kg approx.). If the heat pump is installed on an unstable base (for example, wood), this must be reinforced so that it supports the total weight of the equipment.
Before selecting the place of installation of the heat pump, consider the following recommendations.
Choose a dry place where there is no risk of frost. If possible, install the heat pump with the back side towards an exterior wall and in a place where the
noise emissions do not cause a problem. Whenever possible avoid installation against bedrooms or other places where noise emissions may be annoying. Avoid installing the heat pump near a corner, as this may amplify the level of the equipment noise emission.
Check that the heating-cooling, brine, mains water and DHW piping can be installed properly. To
avoid condensation in the piping of the brine circuit, try to minimize as much as possible these sections inside the building and insulate them properly.
Check that there is enough space to carry out the installation and maintenance work of the heat
pump comfortably (see section 5.3).
Once the heat pump is positioned in its final location, it is necessary to level it so that it remains in horizontal position. For this reason, it is fitted with adjustable feet of up 25 mm in height to compensate for possible irregularities of the base surface. Is the irregularities of the base cannot be compensated with the height­adjustable feet; the base must be sufficiently leveled before installing the heat pump.
NOTE
Do not install the heat pump near machines which issue electromagnetic activity, as they may
interfere with the electronic components and make the equipment stop working properly.
NOTE
The heat pump should never be bent more than 45º vertically as this may provoke the malfunctioning
of the equipment.
DANGER!
The heat pump can weigh up to 240 kg net. The device must be handled by, at least, two operators
using a hand truck to avoid personal injuries.
Page 43
5.3. SERVICE AREAS
It is recommended to leave enough space around the heat pump in order to make installation and maintenance work easier. The recommended minimum distances regarding walls and other elements are the following.
300 mm from the sides. 600 mm from the front. 10 mm from the back
600 mm
300 mm300 mm
10 mm
Figure 5.1. Recommended minimum service areas regarding the heat pump.
600 mm
300 mm300 mm
10 mm
Page 44
6. HYDRAULIC INSTALLATION
6.1. HEATING/COOLING CIRCUIT CONECTION
Inside the heat pump there are included the following components required for the heating-cooling system (see section 3.4).
Variable speed and high efficiency circulation pump (energy class A). Expansion vessel (12 litres). Safety valve (6 bar gauge). Drain valve.
To connect the heating-cooling circuit, consider the information indicated in Figure 6.1 and the following recommendations.
Use the flexible hoses that are included with the heat pump in order to avoid excessive stress in the
inlet and outlet pipes.
Install shut-off valves in the outlet and inlet pipes of the heating-cooling circuits, as close to the heat
pump as possible to facilitate future maintenance work of the heat pump.
Install a strainer in the heating-cooling circuit inlet. Install air vents in all places of the installation where air bubbles may form.
NOTE
EcoGEO B heat pumps must not be used in heating systems with high temperature radiators or in
other appliances which require outlet temperatures of above 55 ºC, which would make the equipment
malfunction. Make sure the pipe connections are not subject to stress as this may cause leaks. The inlet and outlet pipes of the heating/cooling circuit must be insulated thermally to prevent
unnecessary heat losses and avoid risks of freezing the fluid.
DANGER!
Do not install components that may clog the inlet or outlet ports of the safety valve of the
heating/cooling system; there may be risk of breaking some of its components and cause injury
and/or damage to property. When installing the heating/cooling circuit, special care must be taken to avoid getting water on the
electrical panel and this could produce personal injury from electrical shock and/or make the
equipment malfunction.
Page 45
Insulate thermally all the inlet and outlet pipes in order to prevent unnecessary heat losses and
condensation problems.
No
Description
No
Description
1
Heat pump
4
Shut-off valve
2
Heating-cooling outlet, (G1’’ F)
5
Strainer
3
Heating-cooling inlet, (G1’’ F)
Figure 6.1. General scheme of heating-cooling circuit connections.
352
4 4
1
ecoGEO B1
ecoGEO B2
ecoGEO B3
T
2
5
3
4 4
1
ecoGEO C1
ecoGEO C2
ecoGEO C3
Page 46
6.2. DHW TANK CONNECTION
To connect the DHW circuit, take into account the information of Figure 6.2 for ecoGEO B1, B2 and B3 and the Figure 6.3 for ecoGEO C1, C2 and C3.
To facilitate future maintenance work of the heat pump, install shut-off valves in the mains water inlet
and in the DHW outlet.
Install a check valve in the mains water inlet in order to avoid possible hot water returning from the
tank to the main network.
Install a check valve in the DHW coil circuit in order to avoid possible inverse circulation of the water. Install air vents where necessary in the DHW coil circuit in order to avoid possible air bubble
formation.
If necessary, install a security group (expansion vessel + safety valve) in the mains water inlet to
avoid possible overpressures in the DHW tank.
Due to LEGIONELLA PROTECTION mode (see section 3.2) the temperature of water in the DHW
tank may reach 70 ºC. If the installation of the DHW in the place lacks thermostatic taps, it is recommended to install a thermostatic mixing valve in the DHW outlet to avoid risk of scalding.
If the maximum system pressure can exceed 5 bars, it is recommended to install a pressure
reducing valve in the mains water inlet in order to avoid overpressure in the DHW tank.
For a correct operation of the installation, a mains water pressure of at least 2 bars must be
guaranteed in order to obtain a DHW flow rate of at least 20-25 l/min. Remember that the water pressure is reduced during periods of high water consumption. Check that the minimum operating pressure of the installation is ensured under these conditions.
Insulate thermally the DHW outlet pipe in order to prevent unnecessary heat losses.
NOTE
For proper operation of ecoGEO B heat pumps during DHW preparation the coil of the DHW tank
should has a minimum heat transfer area of 2.5 m2. Make sure the pipe connections are not subject to stress as leaks may occur.
DANGER!
Do not install components that may clog the inlet or outlet ports of the safety valve of the DHW tank;
there may be risk of breaking the tank and causing injury and/or damage to property. When installing the DHW circuit, special care must be taken to avoid getting water on the electrical
panel. This could produce personal injury from electrical shock and/or make the equipment
malfunction.
Page 47
No
Description
No
Description
1
Heat pump
7
Shut-off valve
2
DHW tank
8
Check valve
3
DHW coil circuit outlet (G3/4” F)
9
Strainer
4
DHW coil circuit inlet (G3/4” F)
10
Thermostatic mixing valve
5
Mains water inlet, (G1’’ F)
11
Safety valve (8 bar)
6
DHW outlet, (G1’’ F)
12
Expansion vessel
Figure 6.2. General scheme of DHW circuit connection for ecoGEO B1, B2 and B3.
10
5
6
11
77
77
2
34
1
ecoGEO B1
ecoGEO B2
ecoGEO B3
8
12
9
Page 48
Descripción
Descripción
1
Heat pump
5
Thermostatic mixing valve
2
Mains water inlet, (G1’’ F)
6
Safety valve (8 bar)
3
DHW Outlet, (G1’’ F)
7
Expansion vessel
4
Shut-off valve
Figure 6.3. General scheme of DHW circuit connection for ecoGEO C1, C2 and C3.
2
3
6
44
1
ecoGEO C1
ecoGEO C2
ecoGEO C3
5
7
Page 49
6.3. BRINE CIRCUIT CONNECTION
When brine systems are used with more than one circuit, these must be connected in parallel so that the flow rate circulation through each is similar. The maximum length of all the brine system pipes should not exceed 400 m.
Figure 6.4. Types of brine systems.
In vertical probe systems, it is recommended to use circuits between 80 and 150 m long, with a minimum separation between circuits of 8 meters.
In horizontal collector systems, it is recommended to bury the coil between 1.2 and 2 meters deep and with a separation between tubes of at least 0.8 meters.
The refrigerant evaporation temperature can fall below 0 ºC. For this reason, in brine systems with groundwater, it is recommended to use an intermediate intercooler to prevent freezing problems and fouling in the evaporator of the heat pump.
Horizontal collector
Groundwater system
Vertical probe
NOTE
Insulate thermally the brine circuit pipes in order to prevent condensation and/or frost formation as
the brine circuit pipes may reach temperatures below 0 ºC. Make sure there pipe connections are not subject to stress as this may cause leaks. In brine systems with groundwater, it is recommended to use an intermediate exchanger to avoid
freezing problems and evaporator fouling.
DANGER!
Do not install components that may clog the inlet or outlet ports of the safety valve of the brine
system. There may be risk of breaking some of its components and causing injury and/or damage to
property. When installing the brine circuit, special care must be taken to avoid getting antifreeze mixture on the
electrical panel as this could produce personal injury from electrical shock and/or make the
equipment malfunction.
Page 50
Inside the heat pump there are included the following components required for the brine system.
Variable speed and high efficiency circulation pump (energy class A). Expansion vessel (5 liters). Only in ecoGEO B1, C1, C2 y C3 models. Safety valve (3 bars gauge). Only in ecoGEO B1, C1, C2 y C3 models. Drain valve
To connect the brine circuit, take into account the information in Figure 6.5, Figure 6.6 and Figure 6.7 and the following recommendations.
Use the flexible hoses that are included with the heat pump in order to avoid excessive stress in the
inlet and outlet pipes.
Install shut-off valves in the outlet and inlet heating-cooling circuits, as close to the heat pump as
possible to facilitate future maintenance work.
Install the necessary components to carry out the filling/emptying of the working fluid in the return
pipe.
Install a expansión vessel and a safety valve with ecoGEO B2 and B3. The ecoGEO B1, C1, C2 and
C3 have an expansión vessel (5 litters) and a safety valve (3 bar) integrated in the heat pump.
Install a strainer in the inlet circuit. It is recommended to install shut-off valves just before and after
the strainer in order to avoid antifreeze mixture losses during cleaning or filter replacement.
Install air vents at all points of the installation where air bubbles may form. Insulate thermally the brine circuit pipe in order to prevent unnecessary heat losses and avoid
condensation problems.
2 3
5
44
6
1
ecoGEO B1
Page 51
No
Description
No
Description
1
Heat pump
4
Shut-off valve
2
Brine outlet, (G1’’ F)
5
Strainer
3
Brine inlet, (G1’’ F)
6
Brine filling fitting
Figure 6.5. General scheme of brine circuit connection for ecoGEO B1 models.
No
Description
No
Description
1
Heat pump
5
Strainer
2
Brine outlet, (G1’’ F)
6
Brine filling fitting
3
Brine inlet, (G1’’ F)
7
Expansion vessel
4
Shut-off valve
8
Safety valve
Figure 6.6. General scheme of brine circuit connection for ecoGEO B2 and B3 models.
2 3
5
8
7
44
6
1
ecoGEO B2
ecoGEO B3
Page 52
Description
Description
1
Heat pump
4
Shut-off valve
2
Brine outlet, (1’’ F)
5
Strainer
3
Brine inlet, (1’’ F)
6
Brine filling fitting
Figure 6.7. General scheme of brine circuit connection for ecoGEO C models.
3
5
44
2
6
1
ecoGEO C1
ecoGEO C2
ecoGEO C3
Page 53
7. ELECTRICAL INSTALLATION
The electrical installation of the heat pump must be carried out by a qualified installer in accordance with the applicable local regulations and these instructions. Figure 7.1 and Figure 7.2 show the location of the main components of the electrical panel of heat pumps with single-phase and three-phase power supply, respectively.
No
Description
No
Description
1
Electric connections
7
Upper terminal block
2
Power breaker
8
Lower terminal block
3
Control breaker
9
Micro-controller
4
Ground terminal
10
EMI filter
5
Inverter / compressor contactor
11
Inverter
6
Legionella protection contactor
12
Housing
Figure 7.1. Location of components of the electrical panel of heat pumps with single-phase power supply
(230 V / 50 Hz, 1/N/PE~).
NOTE
The power cord should be connected only to the terminals indicated. Otherwise, the equipment may
malfunction.
DANGER!
To carry out the installation and maintenance work on the heat pump, it is necessary to install an
external breaker that shuts off all circuits, as personal injury due to electrical shock could occur.
Page 54
No
Description
Nor
Description
1
Electric connections
7
Upper terminal block
2
Power breaker
8
Lower terminal block
3
Control breaker
9
Micro-controller
4
Ground terminal
10
Choke Filters
5
Inverter / compressor contactor
11
Inverter
6
Legionella protection contactor
12
Housing
Figure 7.2. Location of components of the electrical panel for heat pumps with three-phase power supply
(400 V / 50 Hz, 3/N/PE~).
The internal components of the heat pump are connected to the electrical panel with terminal blocks for quick standing connections. For more detailed information about the electrical panel connections, see sections
12.3 to 12.5. The electrical installation necessary to use the heat pump is only the power cord connection, control signals,
external temperature probes and external control valves.
7.1. POWER SUPPLY
Depending on the model, the heat pump may require single-phase 230 V / 50 Hz, 1/N/PE ~ or , three-phase 400 V / 50 Hz, 3/N/PE ~ power supply. To carry out the electrical installation, follow the following steps.
1. Insert the power cord through the cable grommet located at the bottom of the rear cover of the heat pump. In order to do this, it is necessary to remove the front and side covers (see section 3.5).
2. Lead the cable through the cable grommet located at the left top of the electrical panel, fixing the cable properly to the structure.
3. Connect the power supply cord following Figure 7.3 in single-phase models and following Figure 7.4 in three phase models (see also sections 12.3 to 12.5).
5
10
11
6
9
3
811 12
12 7
2
10
1
410
Page 55
4. It is recommended to install an external breaker that shuts off all circuits (1 phase + neutral in single­phase models and 3 phase + neutral in three phase models).
Figure 7.3. Connection diagram of the power supply in single-phase models.
Figure 7.4. Connection diagram of the power supply in three-phase models.
Table 7.1 shows the sections necessary for the power cord and the minimum current for which the external switch must be selected.
Model
Power
supply
Cable
section
External
breaker
ecoGEO B 3-12 kW
Single-phase
6 mm2
32 A
ecoGEO B 5-22 kW
Single-phase
10 mm2
40 A
ecoGEO B T 5-22 kW
Three-phase
4 mm2
16 A
Table 7.1. Cable and external breaker sizing.
7.2. ZONE 1 VALVE
The heat pump allows activating/deactivating an external On/Off zone valve with 230 Vac power supply to cut the flow through Zone 1 of the heating-cooling circuit when there is no demand in this zone. Make the hydraulic installation in such a way that the valve opens/closes when energized/de-energized. In order to make the electrical installation, follow Figure 7.5 (see also sections 12.3 to 12.5).
PE
L
N
PE
L
N
PE
L1
L2
PE
L1
L2
L3
N
L3
N
Page 56
Figure 7.5. Connection diagram of Zone 1 valve to the electrical panel.
7.3. EXTERNAL SHUNT GROUP FOR ZONE 2
The heat pump allows controlling an external shunt group to produce a second outlet temperature level through a modulating 3-way valve with 0-10 Vdc signal. Make the hydraulic installation in such a way that the 0 Vdc signal corresponds to 0% of recirculation (0% bypass) and 10 Vdc to 100% recirculation (100% bypass). In order to make the electrical installation, follow Figure 7.6 (see also sections 12.3 to 12.5).
Nor
Description
Nor
Description
1
Modulating 3-way valve
4
Analogue output 0-10 V
2
Circulation pump
5
Relay output (230 Vac)
3
Outlet temperature probe
6
Analogue NTC input
Figure 7.6. Connection diagram for the external shunt group of Zone 2 to the electrical panel.
76
77
78
PE
N
L
35
36
37
PE
N
L
19
20
33
34
0 Vdc
0 - 10 Vdc
1
2
3
4
5
6
35
36
37
PE
N
L
5
Page 57
7.4. OUTDOOR TEMPERATURE PROBE
The outdoor temperature probe is connected through a two-pole cable to the lower terminal block of the electrical panel, as shown in Figure 7.7 (see also sections 12.3 to 12.5). In order to install the temperature probe, follow these recommendations.
1. Install the outdoor temperature probe towards the north or northeast wall of the house.
2. Place the probe in a well-ventilated place sheltered from the wind and the rain.
3. Do not install the outdoor temperature probe within a distance less than 1 m from windows or doors in order to avoid the possible effect of warm air currents.
4. Use a cable of 50 m maximum length and a minimum section of 0.75 mm2 for connecting the probe. For longer lengths (up to 120 m) it is recommended to use 1.5 mm2 cable.
Figure 7.7. Connection diagram for the outdoor temperature probe to the electrical panel.
Icon
Description
Recommended location for installation
Not recommended location for installation
Figure 7.8. Recommended locations for installing the outdoor temperature probe (north facade).
21
22
Page 58
7.5. TEMPERATURE PROBE AND LEGIONELLA PROTECTION ELECTRIC HEATER OF THE EXTERNAL DHW TANK
The temperature probe of the DHW tank is connected through a two-pole cable to the lower terminal block at the electrical panel, while the legionella protection electric heater is connected to upper terminal block , as shown in Figure 2.1
Figure 7.9. DHW tank connection schema.
7.6. BUFFER TANK TEMPERATURE PROBE
The buffer tank temperature probe is used only in the scheme BUFFER TANK. It is connected through two­pole cable to the lower terminal block of the electrical panel, as shown in Figure 7.10 (see also sections 12.3 to 12.5).
Figure 7.10. Connection diagram of the buffer tank temperature probe.
7.7. EXTERNAL ACTIVATION OF THE HEAT PUMP
The heat pump can be activated/deactivated through a external voltage- free signal. This signal is connected directly to the micro-controller through connector J4, as shown in Figure 7.11 (see also sections 12.3 to
12.5).
19
20
Phase
Neutral
96
97
17
18
Page 59
No
Description
No
Description
1
Micro-controller connector J4
3
Pool activation
2
External activation signal of the heat pump
4
Common digital inputs
Figure 7.11. Connection diagram of the external activation signal of the heat pump and pool mode
activation.
7.8. POOL VALVE
The heat pump allows controlling the activation of an external pump, as well as a 3-way valve to deviate the heating flow to the pool heat exchanger. To that end, it is required a voltage-free signal that informs the heat pump whenever there is demand of heating the pool, generally from a cronothermostat. This signal is directly connected to the micro-controller through the J4 connector, as shown in Figure 7.11 (see also sections 12.3 to 12.5).
In order to make the power installation, follow Figure 7.12 (see also sections 12.3 to 12.5).
DI3
DI4
DI5
DI6
DI1
DI7
DIC114
2DI2
3
Page 60
No
Description
No
Description
1
3-way deviation valve to pool On/Off
3
Relay output (230 Vac)
2
Pool circulation pump
Figure 7.12. Connection diagram of the circulation pump and the pool valve to the electrical panel.
8. INDOOR CONTROL DEVICES
Geothermal pumps ecoGEO can be controlled, through th-Tune (with Modbus connection) or through conventional relay type thermostats. With both options, the heat pump allows controlling 1 or 2 different outlet temperatures (hereinafter Zone 1 and Zone 2), depending on the selected operating scheme and installation.
8.1. TH-TUNE INDOOR TERMINALS
ecoGEO geothermal pumps are programmed to be used with Carel th-Tune indoor terminals. These terminals send information about the indoor temperature and humidity of the room. These should be located in the most representative part of each zone, generally in the larger one, for example, in the living room. The heat pump takes de temperatures registered by the th-Tune terminals as reference in order to make a precise control of the indoor temperature.
To install the th-Tune terminal, it is necessary to connect the power supply and the RS485 serial cable. Before installing, take into account the following recommendations.
54
55
56
PE
N
L2
54
55
56
PE
N
1
2 3
3
53
L1
L
NOTE
In order to get the best indoor comfort services and optimize the energy efficiency of the heat pump,
it is recommended to make an indoor control through indoor th-Tune terminals.
The activation signals of the heat pump, control with thermostats and the pool control (DI1 to DI6
inputs) must be voltage-free contacts.
Page 61
1. Before connecting the power supply terminal, carefully read the instructions included in the Th-Tune manual. Check that the supply voltage is correct. There are models with 24 Vac/Vdc and 230 Vac.
2. To connect the RS485 serial port use AWG type 20-22 two-pole shielded cable. For cable lengths exceeding 500 m, it is necessary to install a 120 Ohm resistance between Rx+/Tx+ and Rx-/Tx- in the first terminal and in the last one in order to prevent possible communication problems. For more information, see the Th-Tune manual.
The RS485 serial cable connection is made directly to the card installed in the micro-controller BMS connector, as shown in Figure 8.1 (see also sections 12.3 to 12.5). 1 or 2 terminals can be connected depending on the fact of how many different outlet temperatures are controlled (1 or 2).
BMS Port
GND
Rx+/Tx+
Rx-/Tx-
Zone 1
Terminal
Zone 2
Terminal
Figure 8.1. Connection diagram of the RS485 serial cable to the electrical panel.
8.2. CONVENTIONAL RELAY THERMOSTATS
ECOFOREST geothermal pumps can be controlled through one or various conventional relay thermostats, allowing the switching on/off of the heat pump according to heating demand of the house. For this reason, it has 4 digital independent inputs, 2 dedicated to the heating demand of each of the zones with different outlet temperature, and 2 dedicated to the cooling demand in each of the zones with different outlet temperature (only in models ecoGEO B2 and B3). Each of these control signals derives from one or various thermostats. If more than one thermostat is used per signal, these must be connected in parallel in such a way that if only one of them is active, this can be detected by the heat pump. The input signals are connected directly to the micro-controller through the J4 connector, as per 8.2 (see also sections 12.3 to 12.5).
Page 62
No
Description
No
Description
1
Micro-controller J4 connector
4
Heating activation Zone 2
2
Heating activation Zone 1
5
Free/Active cooling activation Zone 2
3
Free/Active cooling activation Zone 1
6
Common digital inputs
Figure 8.2. Connection diagram of thermostat signals to the micro-controller.
8.3. COMBINATION OF TH-TUNE INDOOR TERMINALS WITH CONVENTIONAL RELAY THERMOSTATS
It is posible to combine the th-Tune terminals (explained in section 8.1) and relay thermostats (explained in section 8.2) in the same zone. The Table 8.1 explains the logic when you combine Th-tune and relay thermostat.
THERMOSTAT
demand
No demand
TH
TUNE
demand
working
working
No demand
working
stop
OFF
stop
stop
Table 8.1. Logic of demands with Th-tune + thermostat configuration
In short, all combinations of th-Tune and thermostats are possible.
T1T2Tn
DI3
T1T2Tn
T1T2Tn
DI4
T1T2Tn
DI5
DI6
2
3
4
5
DI1
DI7
DIC1 6
DI2
1
Page 63
9. FILLING THE CIRCUITS
Before configuring and starting up the equipment, it is necessary to fill, purge and pressurize properly all the circuits of the heat pump. In order to do that, follow the steps of the following sections.
9.1. FILLING THE HEATING/COOLING CIRCUIT
To fill the heating-cooling circuit, use water only. Before starting the heat pump, make sure the air contained in the heating-cooling circuit has been completely purged, its pressure is suitable and there are no leaks in the circuit.
In order to facilitate the filling of the heating-cooling circuit, it may be convenient to activate the heating pump. In order to do so, access INSTALLER MENU -> CONFIGURATION -> ACT. MANUAL COMPO. -> HEATING/COOLING PUMP -> State, switch value to ON.
To drain the heating-cooling circuit completely, the heat pump has a drain valve at the lowest part of the circuit, just under the heating-cooling circulation pump (see section 3.4).
9.2. FILLING THE DHW COIL CIRCUIT
The circuit of the DHW external buffer coil is connected to the climate control circuit. For this reason, the filling of this circuit must be simultaneously accomplished with the filling of the climate control circuit. To do it,
NOTE
Do not add anti-corrosion or anti-freezing additives to water in the DHW buffer coil circuit. Joints or
other components may be damaged a leak provoked.
DANGER!
During the process of filling the DHW circuit, be very careful that water does not drop on the electrical
board. It may cause personal injury due to electrocution and/or provoke the equipment malfunction.
NOTE
Do not add antifreeze or anti-corrosion additives to the heating/cooling system fluid as this may
damage the seals and other components and cause leaking.
Before filling the heating/cooling circuit, it is convenient to carry out the electrical installation so that
the heating/cooling circuit pump can be used.
DANGER!
During the filling of the heating/cooling circuits, special care must be taken to avoid getting water on
the electrical panel as this could produce personal injury from electrical shock and/or make the equipment malfunction.
Page 64
open the manual or automatic deaerators which are installed in the circuit that connects the heat pump to the DHW buffer coil until be sure that the circuit is completely empty of air.
9.1).
1
3
6
4 5
2
7
Descripción
Descripción
1
DHW tank
5
DHW outlet
2
DHW coil circuit outlet
6
Check valve
3
DHW coil circuit inlet
7
Air vent DHW circuit
4
Mains water inlet
Figure 9.1. Filling the DHW coil circuit for ecoGEO C1, C2 and C3 models.
If the above mentioned process does not guarantee that the circuit is completely empty of air, you may need to activate manually the circulator pump of the coil circuit. In ecoGEO B1 and B2 models, activate manually on several occasions the 2 way climate control/DHW valve (INSTALLER MENU-> CONFIGURATION -> MANUAL TEST -> DHW VALVE -> State, change value to ON) while the heating-cooling circulator pump is activated until being sure of a proper deaeration of the coil. In ecoGEO B3 models activate manually the DHW circulator pump (INSTALLER MENU-> CONFIGURATION -> MANUAL TEST-> DHW PUMP -> State, change value to ON).
In ecoGEO B1 and B2 models, the circuit emptying of the buffer coil is accomplished together with the heating-cooling circuit through the emptying valve placed below the heating-cooling pump (see section 3.4).
To empty the circuit of the buffer coil in ecoGEO B3 models, use the valve placed just below the DHW circulator pump (see section 3.4).
Page 65
9.3. FILLING THE BRINE CIRCUIT
The brine system temperature may drop below 0 ºC, so a mixture of water antifreeze with a freezing point around -17 ± 2 ºC should be used. It is recommended to use a propylene glycol antifreeze (max. 33% by volume) or ethylene glycol (max. 30% by volume) with corrosion inhibitor.
The estimated volume of the antifreeze mixture required to fill the brine circuit must be calculated taking into account the following.
Heat pumps (exchangers + pipes + expansion vessel, 5 litres). Brine pipe per lineal meter. It is not recommended to use pipes with diameters lower than those
shown in Table 9.1 as the high speeds of circulation of liquid may cause noise and corrosion problems.
Type of piping
Inner diameter (mm)
Volume (l/m)
PEM DN 40
36
1
PEM DN 32
28
0.6
Cooper 28
25.6
0.5
Table 9.1. Volume calculation per lineal meter of pipe.
Filling the brine circuit must be done through an external filling pump, as indicated in Figure 9.2, following these steps.
1. Prepare the antifreeze mixture in properly concentration in the external tank (11).
2. Connect the outlet port of the filling pump (10) to the filling valve C (9).
3. Connect a transparent hose from the filling valve B (8) to the external antifreeze tank so that its end is immersed.
4. Close the filling valve A (7).
5. Open the filling valves B and C.
6. Activate the external filling pump to fill the circuit.
7. Activate in manual mode the brine circuit pump (INSTALLER MENU -> CONFIGURATION -> MANUAL TEST -> BRINE PUMP -> State, switch the value to ON) in order to facilitate the circulation of the antifreeze mixture through the circuit.
8. Keep the external filling pump and the brine pump running until no air bubbles are seen in the fluid that goes through the transparent hose to the antifreeze mixture tank.
NOTE
Before filling the brine circuit, it is necessary to complete the electrical installation so that the brine
pump can be activated.
Check the local regulations before using any kind of antifreeze mixture.
DANGER!
During the filling of the brine circuit, special care must be taken to avoid getting antifreeze mixture on
the electrical panel as it may cause personal injury from electric shock and/or cause equipment malfunction.
Page 66
9. Deactivate in manual mode the brine circuit pump (INSTALLER MENU -> CONFIGURATION -> MANUAL TEST -> BRINE PUMP -> State, switch the value to OFF).
10. Open the filling valve A, maintaining the external filling pump connected in order to eliminate the air contained between filling valves B and C.
11. Close the filling valve B and pressurize the brine circuit up to the service pressure through the filling pump.
12. Close the filling valve C.
13. Disconnect the external filling pump and the rest of the filling components.
Description
Description
1
Heat pump
8
Brine filling fitting
2
Brine outlet
9
Filling valve A
3
Brine inlet
10
Filling valve B
4
Shut-off valve
11
Filling valve C
5
Strainer
12
External filling pump
6
Expansion vessel
13
External antifreeze mixture tank
7
Safety valve
Figure 9.2. Brine circuit filling.
To drain the brine circuit, the heat pump has a drain valve in the lower point of the outlet pipe (see section
3.4).
3
5
44
2
8
1
ecoGEO B1 ecoGEO B2 ecoGEO B3
ecoGEO C1 ecoGEO C2 ecoGEO C3
10 11
9
13
13
7
6
Page 67
10. SETTINGS AND START UP
Before starting up the heat pump, it will be necessary to set it in order to work with the heating-cooling system used and to define the main working parameters.
To set up the equipment, power the heat pump by the external switch. Don’t forget to turn on the heat pump and the front panel. It will be necessary to drive the internal power switches (upper terminal block) and control (lower terminal block). Once powered the heat pump, wait until the initial screen appears on front panel and follow the next steps.
10.1. SELECTING THE FRONT PANEL LANGUAGE
Access INSTALLER MENU (press [Prg]+[Esc] and enter the installer password PW1) -> LANGUAGE and select the front panel language.
10.2. SELECTING THE HEAT PUMP MODEL
Access INSTALLER MENU (press [Prg]+[Esc] and enter the installer password PW1) -> CONFIGURATION ­> HEAT PUMP MODEL and select the model ecoGEO used from the available options.
10.3. SOURCE SYSTEM SELECTION
-> SOURCE . To connect a geothermal source select ground source. If you have a hybrid source or an air source, use the manual of ECOFOREST ecoAIR..
10.4. SELECTING THE WORKING SCHEME
Access INSTALLER MENU (press [Prg]+[Esc] and enter the installer password PW1) -> CONFIGURATION ­> SERVICES -> HEATING COOLING.
1. On OPERATION SCHEME screen select the type of installation that is connected to the heat pump among the options 1 ZONE / 2 ZONE / BUFFER TANK.
1 ZONE for installations with the heat pump directly connected to the heating-cooling system
supplying one temperature level (1 Zone).
2 ZONES for installations with the heat pump directly connected to the heating-cooling system
supplying two different temperature levels controlled by the heat pump (2 Zones).
BUFFER TANK for installations with heat pump connected to an intermediate buffer tank
between the heat pump and the heating-cooling system.
10.5. SELECTING THE INDOOR CONTROL DEVICES
It is possible to control the heat pump by th-Tune inside ambient terminals or by voltage-free contact signals from one or more relay outputs thermostats. It is also possible use th-Tune terminals and relay thermostats for the same zone. Access INSTALLER MENU (press [Prg]+[Esc] and enter the installer password PW1) -> CONFIGURATION -> SERVICES -> HEATING/COOLING.
CONTROL BY TH-TUNE TERMINALS
1. On the screen TH-TUNE select ON/OFF the control by Th-tune terminals.
Page 68
If you selected the 1 ZONE scheme, adjust the address of the Th-Tune terminal main zone (1 by
default).
If you selected the 2 ZONE scheme, in addition to the above, adjust the address of the Th-Tune
terminal from Zone 2 (2 by default).
2. Adjust in the Th-Tune terminals the same values selected before for each one of the zones. The Th­Tune terminals are set up by default with a address value of 1, thus, if you use the values by default is only necessary modify the address of the Th-Tune terminal from Zone 2.
CONTROL BY RELAY THERMOSTAT SIGNALS
1. On the screen RELAY THERMOSTATS Z1 select ON/OFF the control by thermostats in the Zone 1. Select as well the control logic of the digital inputs aimed at heating (DI1) and cooling (DI3) among the options NO / NC (normally open/normally closed).
2. On the screen RELAY THERMOSTATS Z2 select ON/OFF the control by thermostats in the Zone 2. Select as well the control logic of the digital inputs aimed at heating (DI1) and cooling (DI3) among the options NO / NC (normally open/normally closed). The screen aimed to the Zone 2 is only available in the 2 ZONE scheme.
10.6. SETTING THE HEATING CURVE
It is possible to configure a fix value of flow setpoint for heating and for cooling. It is also possible configure a curve to change the flow set point temperature depending the outside temperature. The Figure 10.1 shows a diagram with the parameters used to adjust the heating curve.
17
19
21
23
25
15
20
25
30
35
40
45
50
55
-20 -15 -10 -5 0 5 10 15 20 25
Heating outlet temperature [ºC]
Outside temperature [ºC]
B
B1
C2
A2
C
A
A1
D
Page 69
Description
Description
A
Inside design point (DPI)
B2
Outlet temperature for the DPE.
A1
Inside design temperature
C
Heating stop point (PCC)
A2
Outlet temperature for the DPI.
C1
Heating stop temperature.
B
Outside design point (DPE)
C2
Outlet temperature for the PCC.
B1
Outside design temperature
D
Heating curve
Figure 10.1. Adjusting the parameters to define the heating curve.
Table 10.1 shows the recommended values for each emitting system.
Parameter
Emission system
Recommended value
Remarks
Inside design temperature
-
21 – 23ºC
Regulations on Building
Heating Installations
Outside design temperature
-
-
UNE 100001:2001
Outlet temperature for the outside design point
Under-floor
30 – 35ºC
Technical Committee
CEN/TC 228
Fancoils/convectors
40 – 45ºC
Low temperature
radiators
45 – 50 ºC
Slope heating curve
-
1,00
-
1
Minimum ambient temperature for working installation. Depending on the locality in which the installation is located.
Table 10.1. Recommended values for the adjustment parameters of the heating curve.
It is possible to configure the flow temperature in ACTIVE COOLING mode similarly than the heating mode. If the heat pump is controlled through a th-Tune and the emission system is “heating floor”, the humidity controller will limit the setpoint temperature to the dew point.
1. On the screen HEATING or COOLING of the user menu, adjust the maximum/minimum outside temperatures to disable the heating/cooling production.
In ecoGEO B1 models, adjust the maximum outside temperature value above which the
heating production is disabled. (20 ºC by default).
In ecoGEO B2/B3 models, in addition to the above, adjust the minimum outside temperature
value below which the active cooling/free cooling production is disabled (20 ºC by default).
2. On the screen HEATING ZONE or BUFFER TANK ((Access installer menu (press [Prg] + [Esc] and enter the password PW1 installer) -> CONFIGURATION -> SERVICES -> HEATING/COOLING) you can find a curve like the Figure 10.1 to configure the inside design point and the outside design point.
3. On the screen HEAT. EMISSION SYSTEM select the type of emission system of the heating system between HEATING FLOOR/FANCOILS/LOW TEMP RADIATORS.
4. On the screen COOL. EMISSION SYSTEM select the type of emission system of the COOLING system between HEATING FLOOR/FANCOILS/LOW TEMP RADIATORS.
5. On the screen INSULATION select the grade of building insulation among the options GOOD / MODERATE / BAD. If you selected the BUFFER TANK scheme, you don’t need to set up the parameters shown on this screen.
Figure 10.2, Figure 10.3 and Figure 10.4 show the heating curves depending on the inside and outside design points for heating systems equipped with under-floor, fancoils and low temperature radiators, respectively.
Page 70
Figure 10.2. Heating curves for heating systems equipped with under-floor and for inside design
temperatures at a) 18º C, b) 21º C and c) 24 ºC.
17
19
21
23
25
15
20
25
30
35
40
45
50
55
-20 -15 -10 -5 0 5 10 15 20 25
Heating outlet temperature [ºC]
Outside temperature [ºC]
a)
17
19
21
23
25
15
20
25
30
35
40
45
50
55
-20 -15 -10 -5 0 5 10 15 20 25
Heating outlet temperature [ºC]
Outside temperature [ºC]
b)
17
19
21
23
25
15
20
25
30
35
40
45
50
55
-20 -15 -10 -5 0 5 10 15 20 25
Heating outlet temperature [ºC]
Outside temperature [ºC]
c)
Page 71
Figure 10.3. Heating curves for heating systems equipped with fancoils and for inside design temperatures
at a) 18º C, b) 21º C and c) 24 ºC.
17
19
21
23
25
15
20
25
30
35
40
45
50
55
-20 -15 -10 -5 0 5 10 15 20 25
Heating outlet temperature [ºC]
Outside temperature[ºC]
a)
17
19
21
23
25
15
20
25
30
35
40
45
50
55
-20 -15 -10 -5 0 5 10 15 20 25
Heating outlet temperature [ºC]
Outside temperature[ºC]
b)
17
19
21
23
25
15
20
25
30
35
40
45
50
55
-20 -15 -10 -5 0 5 10 15 20 25
Heating outlet temperature [ºC]
Outside temperature[ºC]
c)
Page 72
Figure 10.4. Heating curves for heating systems equipped with low temperature radiators and for inside
design temperatures at a) 18º C, b) 21º C and c) 24 ºC.
17
19
21
23
25
15
20
25
30
35
40
45
50
55
-20 -15 -10 -5 0 5 10 15 20 25
Heating outlet temperature [ºC]
Outside temperature [ºC]
a)
17
19
21
23
25
15
20
25
30
35
40
45
50
55
-20 -15 -10 -5 0 5 10 15 20 25
Heating outlet temperature [ºC]
Outside temperature [ºC]
b)
17
19
21
23
25
15
20
25
30
35
40
45
50
55
-20 -15 -10 -5 0 5 10 15 20 25
Heating outlet temperature [ºC]
Outside temperature [ºC]
c)
Page 73
10.7. EXPAMPLES OF HEATING CURVE
In the following lines, you have some examples of setting the heating curve depending on the kind of emitting system used and on the design conditions considered for its sizing.
EXAMPLE 1
If you want to adjust the heating curve for a house with a heating emitting system by under-floor for the following design conditions:
The inside room temperature of the house used for system design is about 21 ºC. The minimum outside ambient temperature considered in the design is about -6 ºC. The outlet temperature leading to the heating system used for under-floor sizing for outside ambient
conditions given in the previous section is 35 ºC.
The maximum ambient temperature above which you want the heat pump does not attend to the
heating demand is 16 ºC.
To set the heating curve, adjust the values of the parameters shown in Table 10.2. Figure 10.5 shows the heating curve obtained with such setting up.
Parameter
Values Example 1
Heating stop temperature.
16 ºC
Inside design temperature
21 ºC
Outside design temperature
-6 ºC
Outlet temperature for outside design point
35 ºC
Heat emission system
Under-floor
Table 10.2. Heating curve adjustment for the Example 1.
Figure 10.5. Heating curves obtained for parameters in Example 1.
17
19
21
23
25
15
20
25
30
35
40
45
50
55
-20 -15 -10 -5 0 5 10 15 20 25
Heating outlet temperature [ºC]
Outside temperature [ºC]
B
A
C
B2
C2 A2
A1C1B1
Page 74
EXAMPLE 2
If you want to adjust the heating curve for a house with a heating emitting system by fancoils for the following design conditions:
The inside room temperature of the house used for system design is about 24 ºC. The minimum outside ambient temperature considered in the design is about -14 ºC. The outlet temperature leading to the heating system used for fancoils sizing for outside ambient
conditions given in the previous section is 45 ºC.
The maximum ambient temperature above which you want the heat pump does not attend to the
heating demand is 14 ºC.
To set the heating curve, adjust the values of the parameters shown in Table 10.3. Figure 10.6 shows the heating curve obtained with such setting up.
Parameter
Values Example 2
Heating stop temperature.
14 ºC
Inside design temperature
24 ºC
Outside design temperature
-14 ºC
Outlet temperature for outside design point
45 ºC
Heat emission system
Fancoils
Table 10.3. Heating curve adjustment for the Example 2.
Figure 10.6. Heating curves obtained for parameters in Example 2.
17
19
21
23
25
15
20
25
30
35
40
45
50
55
-20 -15 -10 -5 0 5 10 15 20 25
Heating outlet temperature [ºC]
Outside temperature [ºC]
B
A
C
B2
C2
B1 C1 A1
A2
Page 75
EXAMPLE 3
If you want to adjust the heating curve for a house with a heating emitting system by low temperature radiators for the following design conditions:
The inside room temperature of the house used for system design is about 18 ºC. The minimum outside ambient temperature considered in the design is about -2 ºC. The outlet temperature leading to the heating system used for low temperature radiators sizing for
outside ambient conditions given in the previous section is 50 ºC.
The maximum ambient temperature above which you want the heat pump does not attend to the
heating demand is 12 ºC.
To set the heating curve, adjust the values of the parameters shown in Table 10.4. Figure 10.7 shows the heating curve obtained with such setting up.
Parameter
Values EXAMPLE 3
Heating stop temperature
12 ºC
Inside design temperature
18 ºC
Outside design temperature
-2 ºC
Outlet temperature for outside design point
50 ºC
Heat emission system
Low temperature radiators
Table 10.4. Heating curve adjustment for the Example 3.
Figure 10.7. Heating curves obtained for parameters in Example 3.
17
19
21
23
25
15
20
25
30
35
40
45
50
55
-20 -15 -10 -5 0 5 10 15 20 25
Heating outlet temperature [ºC]
Outside temperature [ºC]
A
B
C
B1
B2
A1
C2
C1
A2
Page 76
10.8. DOMESTIC HOT WATER ON/OFF
Access the INSTALLER MENU (press [Prg] + [Esc] and enter the PW1 installer password) -> CONFIGURATION -> SERVICES. On the DHW screen, select YES / NO to the DHW mode and YES / NO support with the resistance. Also select the temperature for legionella protection applicable treatment.
Access to the USER MENU (Press [Prg]). In the screen DHW select the setpoint and offset. If the resistance support was not configurated, the setpoint value – offset should not exceed 45ºC.
For ecoGEO B3 and C3 models should be configured CHW temperature system with a maximum of 70ºC. The DHW can reach this temperature when the heat pump works for another demand like heating, cooling or swimming pool.
If you want to do legionella treatment , this must also be setted in the user menu.
10.9. SWIMMING POOL ON/OFF
Access installer menu (press [Prg] + [Esc] and enter the password PW1 installer) -> CONFIGURATION -> SERVICES. At the pool screen, select YES / NO to the POOL mode. If you activate the pool also adjust the setpoint flow temperature of the heat pump.
10.10. DIGITAL INPUT SIGNAL
Access the INSTALLER MENU (press [Prg] + [Esc] and enter the password PW1 installer) -> CONFIGURATION -> REMOTE CONTROL. Sellect ON / OFF on input DI2 to choose the working mode of the heat pump. Sellect ON / OFF on input DI7 to choose working with the DHW. Is also needed to choose the logic NO/NC (Normally Open / Normally Closed).
Select also PROGRAM switch if you need to control the winter/summer mode on the DI8 point:
Relay open: summer program.
Relay closed: winter program
10.11. POWER LIMITATION AND SETTING PROTECTIONS
Access INSTALLER MENU (press [Prg]+[Esc] and enter the installer password PW1) -> CONFIGURATION ­> PROTECTIONS.
1. On the screen POWER LIMITATION, adjust the compressor speed range between 25-100% for each mode, DHW, heating, cooling and swimming pool. The selected value can set the heat output range and power consumption of the heat pump (see paragraphs 12.6 and 12.7).
2. On the screen BRINE ALARM, adjust the minimum temperature of the brine circuit below which the heat pump is off (-7 ºC by default).
3. On the screen PRESSURE BRINE/HEATING adjust the minimum pressures in the brine and heating-cooling circuits below which the heat pump is off (1 bar gauge by default).
4. On the screen COOLING OUTLET TEMP, adjust the minimum outlet temperature in ACTIVE COOLING mode below which the heat pump is off (4 ºC by default). This screen is only available in ecoGEO B3 models.
Page 77
10.12. TEMPERATURE PROBE CALIBRATION
In the temperature probe where the extension cords are used (outdoor temperature probe, external DHW temperature probe, buffer tank temperature probe) the temperature measure can be affected, especially if you use long extension cords, and small sections. Please verify that values provided by the probes where extension cords are used, comparing with the value provided by a manual meter and, if necessary, adjust the required correction following the next steps.
Access INSTALLER MENU (press [Prg]+[Esc] and enter the installer password PW1) -> CONFIGURATION ­> PROBE CONF. On the screen for the probe you want to correct, adjust the required value of the correction.
In the PROBE CONF. menu, you can make corrections for all temperature and pressure sensors. It’s recommended only corrections for external temperature probes that have been used with extension cord.
10.13. FINAL INSPECTION AND START UP OF THE INSTALLATION
Before initial operation, check the following points in order to ensure that it have been completed successfully.
CHECKING THE HEATING-COOLING, BRINE AND DHW CIRCUITS
1. The heating-cooling installation was performed according to Figure 6.1, including all components.
2. The DHW installation was performed according to Figure 6.2, including all components.
3. The brine installation was performed according to Figure 6.5, including all components.
4. Flow and return pipes from different circuits have been isolated properly.
5. The heating-cooling and brine circuits have been filled, aerated and pressurized properly.
6. The installation has been checked in order to detect fluids leak.
CHECKING THE ELECTRIC INSTALLATION.
1. The heat pump’s power supply installation has been performed according to Figure 7.3 in single­phase models and Figure 7.4 in three-phase models.
2. The electric installation includes an external switch that cuts all circuits.
3. The inside ambient terminals have been correctly positioned and installed.
4. The outside temperature probe has been correctly positioned and installed.
5. The buffer tank temperature probe has been correctly installed (only in installations with intermediate buffer tank).
NOTE
The initial operation should only be done once after checking the heating-cooling, brine and DHW
circuits have been filled and aerated properly.
Note that if during the operation of the installation, any alarm is activated, may be due to a faulty
bleeding of the circuits.
EcoGEO heat pumps have a program to conduct the floor drying in under-floor installations (see
section 4.6).
Page 78
6. The external shunt group has been correctly installed (only in installations with external shunt group for the second outlet temperature controlled by the heat pump).
OPERATION AND INSPECTION OF ABNORMAL NOISES
1. Check the equipment for abnormal noises that indicate possible damages to some components during transport or installation. It is necessary to verify the heat pump in all operating modes (heating production, DHW and active cooling or free cooling where applicable) to ensure that there is no any abnormal noise.
2. Check as well any abnormal noises elsewhere in the installation.
Page 79
11. IDENTIFYING PROBLEMS AND TROUBLESHOOTING
11.1. ALARM LIST
There are a number of parameters that the heat pump monitors at all moments to verify proper operation of the equipment. If any of these parameters are not within the standard, an alarm is activated to inform the user that there is an abnormal operation of the heat pump. If any alarms are active, the button [Alarm] on the front panel lights up in red and, if you press this button, you can access to the alarm menu (see section 4.5, menu 1.9).
If the cause of the alarm is solved, this one disappears automatically. There are some alarms which if repeated five times consecutive; a permanent alarm is activated, so that the heat pump cannot start until the permanent alarm is erased manually.
Table 11.1 shows the possible alarms and corresponding messages displayed on the front panel.
Alarm Nº
MESSAGE
1
High discharge pressure
2
Low suction pressure
3
Low brine circuit pressure
4
Low heating-cooling circuit pressure
5
High discharge temperature
6
High inverter temperature
7
Low brine outlet temperature
8
Low brine inlet temperature
9
High heating outlet temperature
10
Failure of any temperature probe (indicated on screen the defective probe)
11
Failure of any pressure transducer (indicated on screen the defective transducer)
12
Failure of any inside ambient th-Tune terminal (indicated on screen the defective terminal)
13
Failure of reading temperature in any indoor th-Tune terminal (indicated on screen the defective terminal)
14
Failure of reading humidity in any indoor th-Tune terminal (indicated on screen the defective terminal)
15
Failure of internal clock in any indoor th-Tune terminal (indicated on screen the defective terminal)
16
Incorrect superheat degree
Table 11.1. Alarm list and messages visualized on the front panel.
.
Page 80
11.2. COMFORT PROBLEMS
Table 11.2 shows some of the common comfort problems with which you can find, as well their possible causes and remedies.
Symptoms
Possible cause
Remedy
Too low DHW temperature
High demand on punctual DHW
Wait some hours and then check if the DHW temperature has increased.
Too low DHW production set point temperature
Increase the DHW production set point temperature (see USER MENU -> DHW/LEGIONELLA PROTECTION -> DHW ­> Change set point value)
Damaged heat pump
Please contact technical support
Too high or too low indoor ambient temperature
Occasional high demand of heating-cooling
Wait some hours and check again the inside ambient temperature
Defective setup of the heating curve.
Set up correctly the heating curve (See USER MENU -> HEATING -> Decrease/Rise the heating curve)
The operating program (winter/summer) is incorrect
Select the correct operating program or select the AUTO mode (see USER MENU -> ON/OFF -> ON/OFF ECOGEO 1 -> Change program into AUTO)
Too high or too low indoor set point temperature
Set up correctly the inside ambient temperature in the th-Tune terminal or in the heat pump front panel
Damaged heat pump
Please contact technical support
Heat pump not running
The minimum time between starts of the heat pump has not been achieved (20 minutes)
Wait 20 minutes and check if the heat pump run again.
There are active alarms
Turn off the active alarms (see ALARM MENU
- > RESET ALARMS -> Change Reset Alarms to Yes)
There are active alarms that cannot be turned off
Please contact technical support
Power breaker is turned off from the electrical panel of the heat pumps.
Rearm the power breaker from the electrical panel of the heat pump.
Control breaker is turned off from the electrical panel of the heat pump.
Rearm control breaker from the electrical panel of the heat pump.
The external power supply breaker is turned off
Rearm the power supply breaker from the heat pump
Damaged heat pump
Please contact technical support
Table 11.2. Identification and comfort troubleshooting.
Page 81
12. TECHNICAL SPECIFICATIONS
12.1. TECNICAL DATA
In the Table 12.1 you can find the main technical specifications of the heat pumps ecoGEO.B1, B2 y B3.
Geothermal heat pump ecoGEO B
TECHNICAL DATA
Unit
ecoGEO B1
ecoGEO B2
ecoGEO B3
3-12
5-22
3-12
5-22
3-12
5-22
Application
Heating and DHW
- ● ● ● ● ● ●
Active cooling
- ● ●
Built-in free cooling
- ● ●
Single-phase
Power supply
230 V / 50 Hz, 1/N/PE~
- ● ● ● ● ● ●
Magnetothermal protection
A
32
40
32
40
32
40
Three-phase
power supply
400 V / 50 Hz, 3/N/PE~
- ● ● ●
Magnetothermal protection
A
--
16
--
16
--
16
Refrigerant
Type
-
R410A
R410A
R410A
R410A
R410A
R410A
Components
Compressor
-
Scroll with Copeland inverter
Expansion valve
-
Carel Electronics
Heat exchangers
-
Alfa Laval plates
Circulation pumps
-
Wilo High-efficiency variable speed (Class A)
Expansion vessels
-
Heating-cooling circuit and brine circuit
Eficiencia
Heating output1
kW
3-15
5-26
3-15
5-26
3-15
5-26
Heating output2
kW
3-14
5-23,5
3-14
5-23,5
3-14
5-23,5
Electric power consumption2
kW
0,7-3,7
1,4-5,5
0,7-3,2
1,4-5,5
0,7-3,2
1,4-5,5
COP2
-
4,6
4,9
4,6
4,9
4,6
4,9
EER3
-
--
--
--
--
6,1-6,9
6,1-6,9
Cooling capacity
3
kW
--
--
--
--
4-16,3
6,9-30
Free cooling capacity
kW
--
-- 6 6
--
--
Refrigerant
circuit
Refrigerant charge
kg
1,35
1,70
1,35
1,70
1,50
2,00
Masimum working pressure
bar
42
42
42
42
42
42
Compressor oil type
-
POE
POE
POE
POE
POE
POE
Compressor oil charge
kg
1,18
1,18
1,18
1,18
1,18
1,18
Heating-
cooling circuit
Maximum/minimun temperature
ºC
60/20
Maximum working pressuere
bar 3 Nominal flow rate
l/h
1200 - 4500
Brine circuit
Maximum/mínimum teperature
ºC
20/-10
Maximum working pressure
bar 3 Nominal flow rate
l/h
1200 - 4500
Recomended antifreeze5
-
Propylene glicol / freezing point of wáter at -17 ±2 ºC
DHW
Maximun DHW temperature
ºC
55
55
55
55
55
55
Maximum legionella temperature
ºC
70
70
70
70
70
70
Soundproofing
Noise emission level
4
dB
42
42
42
42
42
42
Dimensions
Height x width x depth
mm
1000 x 600 x 700
Weight
Unladen weight (without
packaging)
kg
170
175
170
175
175
180
1) Consultar siempre las regulaciones regionales antes de utilizar el medio anticongelante.
1) According to EN 14511, 5/2 – 30/35 ºC (including circulation pumps, inverter and with single-phase power supply).
2) According to EN 14511, 0/-3 – 30/35 ºC (including circulation pumps, inverter and with single-phase power supply).
3) According to EN 14511, 7/12 – 30/35 ºC (including circulation pumps, inverter and with single-phase power supply).
4) According to EN 14511. Values in parentheses include the compressor's acoustic isolation kit.
5) Please, always check the regional regulations before using the antifreeze.
Table 12.1. Tabla de características técnicas de las bombas de calor ecoGEO B1, B2 y B3.
Page 82
In the Table 12.2 you can find the main technical specifications of the heat pumps ecoGEO.C1, C2 y C3.
Geothermal heat pump ecoGEO C
TECHNICAL DATA
Unit
ecoGEO C1
ecoGEO C2
ecoGEO C3
3-12
5-22
3-12
5-22
3-12
5-22
Application
Heating and DHW
- ● ● ● ● ● ●
Built-in DHW tank, 170l
- ● ● ● ● ● ●
Active cooling
- ● ●
Built-in free cooling
- ● ●
Single-phase
Power supply
230 V / 50 Hz, 1/N/PE~
- ● ● ● ● ● ●
Magnetothermal protection
A
32
40
32
40
32
40
Three-phase
power supply
400 V / 50 Hz, 3/N/PE~
- ● ● ●
Magnetothermal protection
A
--
16
--
16
--
16
Refrigerant
Type
-
R410A
R410A
R410A
R410A
R410A
R410A
Components
Compressor
-
Scroll with Copeland inverter
Expansion valve
-
Carel Electronics
Heat exchangers
-
Alfa Laval plates
Circulation pumps
-
Wilo High-efficiency variable speed (Class A)
Expansion vessels
-
Heating-cooling circuit and brine circuit
Eficiencia
Heating output1
kW
3-15
5-26
3-15
5-26
3-15
5-26
Heating output2
kW
3-14
5-23,5
3-14
5-23,5
3-14
5-23,5
Electric power consumption2
kW
0,7-3,7
1,4-5,5
0,7-3,2
1,4-5,5
0,7-3,2
1,4-5,5
COP2
-
4,6
4,9
4,6
4,9
4,6
4,9
EER3
-
--
--
--
--
6,1-6,9
6,1-6,9
Cooling capacity
3
kW
--
--
--
--
4-16,3
6,9-30
Free cooling capacity
kW
--
-- 6 6
--
--
Refrigerant
circuit
Refrigerant charge
kg
1,35
1,70
1,35
1,70
1,50
2,00
Masimum working pressure
bar
42
42
42
42
42
42
Compressor oil type
-
POE
POE
POE
POE
POE
POE
Compressor oil charge
kg
1,18
1,18
1,18
1,18
1,18
1,18
Heating-
cooling circuit
Maximum/minimun temperature
ºC
60/20
Maximum working pressuere
bar 3 Nominal flow rate
l/h
1200 - 4500
Brine circuit
Maximum/mínimum teperature
ºC
20/-10
Maximum working pressure
bar 3 Nominal flow rate
l/h
1200 - 4500
Recomended antifreeze5
-
Propylene glicol / freezing point of wáter at -17 ±2 ºC
DHW
Maximun DHW temperature
ºC
55
55
55
55
55
55
Maximum legionella temperature
ºC
70
70
70
70
70
70
Soundproofing
Noise emission level
4
dB
42
42
42
42
42
42
Dimensions
Height x width x depth
mm
1800 x 600 x 700
Weight
Unladen weight (without
packaging)
kg
270
275
270
275
275
280
1) According to EN 14511, 5/2 – 30/35 ºC (including circulation pumps, inverter and with single-phase power supply).
2) According to EN 14511, 0/-3 – 30/35 ºC (including circulation pumps, inverter and with single-phase power supply).
3) According to EN 14511, 7/12 – 30/35 ºC (including circulation pumps, inverter and with single-phase power supply).
4) According to EN 14511. Values in parentheses include the compressor's acoustic isolation kit.
5) Please, always check the regional regulations before using the antifreeze.
Table 12.2. Technical specifications of the ecoGEO C1, C2 and C3 heat pumps .
Page 83
12.2. INTERNAL SCHEMATICS OF THE HEAT PUMPS
Figure 12.1 shows the internal schematic of ecoGEO B1 heat pumps and Table 12.3 shows their main components.
Figure 12.1. Internal schematic of ecoGEO B1 heat pumps.
ecoGEO B1
T
T
T
T
T
7
2 1 5 634
8
910
12
13
15
17
18
P
21
22
23 24
25
28
29
19 20
11
P P
26 27P31
P
30
14
16
P
Page 84
No
Description
No
Description
1
Brine outlet (G1´´F)
17
Heating safety valve
2
Brine inlet (G1´´F)
18
Heating/DHW 3-way valve
3
Heating outlet (G1´´F)
19
Brine drain valve
4
Heating inlet (G1´´F)
20
Heating drain valve
5
DHW circuit outlet (G3/4´´F)
21
Compressor suction temperature probe
6
DHW circuir inlet (G3/4´´F)
22
Brine outlet temperature probe
7
Inverter compressor
23
Brine inlet temperature probe
8
Electronic expansion valve
24
Heating outlet temperature probe
9
Condenser
25
Heating inlet temperature probe
10
Evaporator
26
Compressor suction pressure transducer
11
Combi filter dryer
27
Compressor discharge pressure transducer
12
Brine circulation pump
28
Heating circuit pressure transducer
13
Heating circulation pump
29
Brine circuit pressure transducer
14
Brine expansion vessel
30
Low pressure switch
15
Heating expansion vessel
31
High pressure switch
16
Brine security valve
Table 12.3. Legend of components in the internal schematic of ecoGEO B1 heat pumps.
Page 85
Figure 12.2 shows the internal schematic of ecoGEO B2 heat pumps and Table 12.4 shows their main components.
Figure 12.2. Internal schematic of ecoGEO B2 heat pumps.
ecoGEO B2
T
T
T
T
T
7
2 1 5 63
910
12
13
14
15
16
18
19 17
P
P
22
23
24
25
26
29
30
20 21
8
11
P
27
P
28
4
P
32
P
31
Page 86
No
Description
No
Description
1
Brine outlet (G1´´F)
17
Heating/DHW 3-way valve
2
Brine inlet (G1´´F)
18
Free cooling 3-way valve (brine side)
3
Heating-cooling outlet (G1´´F)
19
Free cooling 3-way valve (cooling side)
4
Heating-cooling inlet (G1´´F)
20
Brine drain valve
5
DHW circuit outlet (G3/4´´F)
21
Heating-cooling drain valve
6
DHW circuit inlet (G3/4´´F)
22
Compressor suction temperature probe
7
Inverter compressor
23
Brine outlet temperature probe
8
Electronic expansion valve
24
Brine inlet temperature probe
9
Condenser
25
Heating-cooling temperature probe
10
Evaporator
26
Heating-cooling temperature probe
11
Combi filter dryer
27
Compressor suction pressure transducer
12
Free cooling heat exchanger
28
Compressor discharge pressure transducer
13
Brine circulation pump
29
Brine pressure transducer
14
Heating-cooling circulation pump
30
Heating-cooling pressure transducer
15
Heating-cooling expansion vessel
31
Low pressure switch
16
Heating-cooling security valve
32
High pressure switch
Table 12.4. Legend of components in the internal schematic of ecoGEO B2 heat pumps.
Page 87
Figure 12.3 shows the internal schematic of ecoGEO B3 heat pumps and Table 12.6 shows their main components.
Figure 12.3. Internal schematic of ecoGEO B3 heat pumps.
ecoGEO B3
T
T
T
T
7
2 1 5 63
9
1112
19
20
21
22
20
18
P
P
26
27
28
29
30
33
34
23 24
131414
8
14
14
T
10
25
4
P P
16
31 32
15
17
P
36
P
35
Page 88
No
Description
No
Description
1
Brine outlet (G1´´F)
19
Brine circulation pump
2
Brine inlet (G1´´F)
20
Heating-cooling circulation pump
3
Heating-cooling outlet (G1´´F)
21
Heating-cooling expansion vessel
4
Heating-cooling (G1´´F)
22
Heating-cooling security valve
5
DHW circuit outlet (G3/4´´F)
23
Brine drain valve
6
DHW circuit inlet (G3/4´´F)
24
Heating-cooling drain valve
7
Inverter compressor
25
DHW circuit's drain valve
8
4-way reversing valve
26
Compressor suction temperature probe
9
Electronic expansion valve
27
Brine outlet temperature probe
10
DHW desuperheater heat exchanger
28
Brine inlet temperature probe
11
Condenser / Evaporator
29
Heating-cooling outlet temperature probe
12
Evaporator / Condenser
30
Heating-cooling inlet temperature probe
13
Combi filter dryer
31
Compressor suction pressure transducer
14
Check valves for reverse cycling
32
Compressor discharge pressure transducer
15
DHW desuperheater check valve
33
Brine pressure transducer
16
Solenoid valve for only heating-cooling
34
Heating-cooling pressure transducer
17
Solenoid valve for DHW production
35
Low pressure switch
18
DHW circulation pump
36
High pressure switch
Table 12.5. Legend of components in the internal schematic of ecoGEO B3 heat pumps.
Page 89
Figure 12.4 shows the internal schematic of ecoGEO C1 heat pumps and Table 12.6 shows their main components.
Figure 12.4. Internal schematic of ecoGEO C1 heat pumps.
ecoGEO C1
T
T
T
T
T
10
7
8
2 1 3456
9
11
1213
15
16
18
17
2019
21
22
P
P
27
28
29 30
31
32
35
36
26
24 25
14
P P
33 34
23
T
P
38
P
37
Page 90
Descripción
Descripción
1
Brine outlet (G1´´F)
20
Heating safety valve
2
Brine inlet (G1´´F)
21
Heating/DHW 3-way valve
3
Heating outlet (G1´´F)
22
DHW circuit check valve
4
Heating inlet (G1´´F)
23
DHW circuit automatic air vent
5
DHW outlet (G1´´F)
24
Brine drain valve
6
Mains water inlet, (G1’’ F)
25
Heating drain valve
7
DHW tank
26
DHW tank drain valve
8
DHW coil
27
Compressor suction temperature probe
9
Legionella protection electric heater
28
Brine outlet temperature probe
10
Inverter compressor
29
Brine inlet temperature probe
11
Electronic expansion valve
30
Heating outlet temperature probe
12
Condenser
31
Heating inlet temperature probe
13
Evaporator
32
DHW tank temperature probe
14
Combi filter dryer
33
Compressor suction pressure transducer
15
Brine circulation pump
34
Compressor discharge pressure transducer
16
Heating circulation pump
35
Heating circuit pressure transducer
17
Brine expansion vessel
36
Brine circuit pressure transducer
18
Heating expansion vessel
37
Low pressure switch
19
Brine security valve
38
High pressure switch
Table 12.6. Legend of components in the internal schematic of ecoGEO C1 heat pumps.
Page 91
Figure 12.5 shows the internal schematic of ecoGEO C2 heat pumps and Table 12.7 shows their main components.
Figure 12.5. Internal schematic of ecoGEO C2 heat pumps.
ecoGEO C2
T
T
T
T
T
10
7
8
2 1 345
9
1213
15
16
17
19
18
2120
23
24 22
25
P
P
30
31
32 33
34
35
38
39
29
27 28
11
14
P
36
P
37
6
26
P
41
P
40
T
Page 92
Descripción
Descripción
1
Brine outlet (G1´´F)
22
Heating/DHW 3-way valve
2
Brine inlet (G1´´F)
23
Free cooling 3-way valve (brine side)
3
Heating-cooling outlet (G1´´F)
24
Free cooling 3-way valve (cooling side)
4
Heating-cooling inlet (G1´´F)
25
DHW circuit automatic air vent
5
DHW outlet (G1´´F)
26
DHW circuit check valve
6
Mains water inlet, (G1’’ F)
27
Brine drain valve
7
DHW tank
28
Heating-cooling drain valve
8
DHW coil
29
DHW tank drain valve
9
Legionella protection electric heater
30
Compressor suction temperature probe
10
Inverter compressor
31
Brine outlet temperature probe
11
Electronic expansion valve
32
Brine inlet temperature probe
12
Condenser
33
Heating-cooling temperature probe
13
Evaporator
34
Heating-cooling temperature probe
14
Combi filter dryer
35
DHW tank temperature probe
15
Free cooling heat exchanger
36
Compressor suction pressure transducer
16
Brine circulation pump
37
Compressor discharge pressure transducer
17
Heating-cooling circulation pump
38
Brine pressure transducer
18
Brine expansion vessel
39
Heating-cooling pressure transducer
19
Heating-cooling expansion vessel
40
Low pressure switch
20
Brine security valve
41
High pressure switch
21
Heating-cooling security valve
Table 12.7. Legend of components in the internal schematic of ecoGEO C2 heat pumps.
Page 93
Figure 12.6 shows the internal schematic of ecoGEO C2 heat pumps and Table 12.8 shows their main components.
Figure 12.6. Internal schematic of ecoGEO C3 heat pumps.
ecoGEO C3
T
T
T
T
10
7
8
2 1 345
9
12
1415
22
23
25
24
26
21
P
P
34
35
36
37
38
39
42
43
32
30 31
161717
11
17
17
T
13
28
33
6
P P
19
40 41
18
20
29
T
P
45
P
44
27
Page 94
Descripción
Descripción
1
Brine outlet (G1´´F)
24
Heating-cooling expansion vessel
2
Brine inlet (G1´´F)
25
Heating-cooling expansion vessel
3
Heating-cooling outlet (G1´´F)
26
Heating-cooling security valve
4
Heating-cooling (G1´´F)
27
Heating-cooling security valve
5
DHW outlet (G1´´F)
28
DHW circuit check valve
6
Mains water inlet, (G1’’ F)
29
DHW circuit automatic air vent
7
DHW tank
30
Brine drain valve
8
DHW coil
31
Heating-cooling drain valve
9
Legionella protection electric heater
32
DHW circuit's drain valve
10
Inverter compressor
33
DHW circuit's drain valve
11
4-way reversing valve
34
Compressor suction temperature probe
12
Electronic expansion valve
35
Brine outlet temperature probe
13
DHW desuperheater heat exchanger
36
Brine inlet temperature probe
14
Condenser / Evaporator
37
Heating-cooling outlet temperature probe
15
Evaporator / Condenser
38
Heating-cooling inlet temperature probe
16
Combi filter dryer
39
DHW tank temperature probe
17
Check valves for reverse cycling
40
Compressor suction pressure transducer
18
DHW desuperheater check valve
41
Compressor discharge pressure transducer
19
Solenoid valve for only heating-cooling
42
Brine pressure transducer
20
Solenoid valve for DHW production
43
Heating-cooling pressure transducer
21
DHW circulation pump
44
Low pressure switch
22
Brine circulation pump
45
High pressure switch
23
Heating-cooling circulation pump
Table 12.8 Legend of components in the internal schematic of ecoGEO C3 heat pumps.
Page 95
12.3. ELECTRICAL PANEL CONECTIONS
Figure 12.7. Upper terminal block of ecoGEO B1, B2, C1 and C2 heat pumps with single-phase electric
power supply (230 V / 50 Hz, 1/N/PE~).
41 42
43 44 45
46 47 48 49 50 51 52 54
55 56 68 69
70 71 72
73
74 75
53
95
85
96 97
86 87
92
82
93
83
94
84
90
80
91
81
L
N
PE
Page 96
Figure 12.8 shows the upper terminal block of the electrical panel of ecoGEO B3 and C3 heat pumps with single-phase electric power supply (230 V / 50 Hz, 1/N/PE~).
Figure 12.8. Upper terminal block of ecoGEO B3 and C3 heat pumps with single-phase electric power
supply (230 V / 50 Hz, 1/N/PE~).
41 42
43 44 57
58 59 60 61 62 63 64 54
55 56 68 69
70 71 72
73
74 75
53
95
85
96 97
86 87
92
82
93
83
94
84
90
80
91
81
L
N
PE
Page 97
Figure 12.9 shows the upper terminal block of the electrical panel of ecoGEO B1, B2, C1 and C2 heat pumps with three-phase electric power supply (400 V / 50 Hz, 3/N/PE~).
Figure 12.9. Upper terminal block of ecoGEO B1, B2, C1 and C2 heat pumps with three-phase electric
power supply (400 V / 50 Hz, 3/N/PE~).
41 42
43 44 45
46 47 48 49 50 51 52 54
55 56 68 69
70 71 72
73 74 75
53
95
85
96 97
86
87
115
106
114
107
L1 N
PE
105
113
112
104
110109 111108
102101 103100
L2 L3
Page 98
Figure 12.10 shows the upper terminal block of the electrical panel of ecoGEO B3 and C3 heat pumps with three-phase electric power supply (400 V / 50 Hz, 3/N/PE~).
Figure 12.10. Upper terminal block of ecoGEO B3 and C3 heat pumps with three-phase electric power
supply (400 V / 50 Hz, 3/N/PE~).
41 42
43 44 57
58 59 60 61 62 63 64 54
55 56 68 69
70 71 72
73 74 75
53
95
85
96 97
86
87
115
106
114
107
L1 N
PE
105
113
112
104
110109 111108
102101 103100
L2 L3
Page 99
Terminal No.
Component
T_1
Ground
Single-phase power supply (230 V / 50 Hz, 1/N/PE~)
90
Phase
91
Neutral
T_1
Ground
Three-phase power supply (400 V / 50 Hz, 3/N/PE~)
108
Phase L1
109
Phase L2
110
Phase L3
111
Neutral
93
Phase
Single-phase inverter/compressor
94
Neutral
113
Phase
Three-phase inverter/compressor
114
Phase
115
Phase
96
Phase
Legionella protection electric heater. Maximum consumption 16 A 230 Vac
97
Neutral
41
Phase
Low pressure switch
42
Neutral
43
Phase
High pressure switch
44
Neutral
45
Phase
3-way valve for heating/DHW mode (only ecoGEO B1 and B2)
46
Phase
47
Neutral
48
Ground
49
Phase
3-way valves for free cooling (only ecoGEO B2)
50
Phase
51
Neutral
52
Ground
53
Phase
3-way valve for pool Maximum consumption 1 A 230 Vac
54
Phase
55
Neutral
56
Ground
57
Phase
4-way reversing valve (only ecoGEO B3)
58
Neutral
59
Phase
Solenoid valve for heating-cooling (VS1) (only ecoGEO B3) Production of heating or cooling only
60
Neutral
61
Ground
62
Phase
DHW circulation pump (BACS) + DHW solenoid valve (VS2) (only ecoGEO B3) Production of DHW and heating or cooling simultaneously
63
Neutral
64
Ground
68
Phase
Brine circulation pump
69
Neutral
70
Ground
71
Phase
Heating-cooling circulation pump
72
Neutral
73
Ground
74
Phase
Alarm signal. Maximum consumption 1 A 230 Vac
75
Neutral
Table 12.9. Shows the legend with the upper terminal block connections of ecoGEO B1, B2, B3, C1, C2 and
C3 heat pumps' panel board.
Page 100
Figure 12.11 shows the panel board's terminal block at the bottom of ecoGEO B1, B2, B3, C1, C2 and C3 heat pumps.
Figure 12.11. Lower terminal block of ecoGEO B1, B2, B3, C1, C2 and C3 heat pumps.
89
88
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 76 77 78
Loading...