Ecoflam MAX BROCHURE

Page 1
LIGHT OIL RANGE
MAX
www.ecoam-burners.com
Page 2
CUSTOMIZED BURNERS SOLUTIONS FOR ANY TYPE OF APPLICATION
OUR EXPERIENCE
Thanks to almost 50 years of experience in the design and production of burners, Ecoam offers a full range of blown air pressure jet burners covering an extremely wide range of power, from small products for residential heating appli­cations to high power burners dedicated to the industrial segment. Ecoam burners are renowned worldwide for providing high efciency and reliable operation with signicant ener­gy savings and feature extreme ease of installation, main­tenance and exible boiler-burner matching.
OUR MISSION
Following a philosophy of continuous improving, the R&D Laboratory is constantly working to produce better results, such as the reduced NOx level emissions. The development of new advanced combustion tech­nologies allows to propose solutions in respect of the most stringent environmental regulations and to create the perfect condition to face the new upcoming market requests, such as Ultra Low NOx performance and ErP­ready products.
OUR PRODUCT RANGE
The exibility of Ecoam solutions allows the manufacturing of highly customized products covering a range from 17 kW to 34 MW:
MAX GAS
17 - 700 kW
2
BLU
245 - 17000 kW
MAX
Light oil range
18 - 546 kW
MAIOR
Light oil range
300 - 17000 kW
MAXFLAM/OILFLAM
Heavy oil range 68 - 17000 kW
Page 3
OUR INTERNATIONAL APPROACH
Our products are designed, developed and manufactu­red in Italy, combining quality, reliability and high perfor­mance. All these features are necessary for the end-user satisfaction, which is the rst target for Ecoam. Reaching this outcome throughout its extensive worldwide network of distributors and customers has always been a challen­ging task for Ecoam, which was achieved only by deve­loping a close and personalized relationship with each customer, always taking into account the needs and the distinctive characteristics of each individual market.
OUR PROFESSIONAL TEAM
Ability to design state-of-the-art burners, manage demands of products for specic applications, ability to solve pro­blems in real time are just some of the characteristics of our technicians and engineers. But not only: Ecoam has a worldwide network of service technicians able to support the installation, the commissio­ning and the periodic maintenance activities of the burner.
MULTICALOR
Dual fuel (gas/light oil)
190 - 17000 kW
MULTIFLAM
Dual fuel (gas/heavy oil)
414 - 17000 kW
TS RANGE
All fuels
230 - 34000 kW
SPECIAL
VERSIONS
3
Page 4
Fuel Range
LIGHT OIL MAX
RANGE OVERVIEW
MAX 1
MAX 4
MAX 8
MAX 12
MAX 15
MAX 20
MAX 30
MAX P 12 AB
MAX P 15 AB
MAX P 25 AB
MAX P 35 AB
MAX P 45 AB
18 ... 41 kW
20 ... 59 kW
47 ... 105 kW
60 ... 130 kW
73 ... 190 kW
86 ... 237 kW
110 ... 319 kW
60 ... 130 kW
77 ... 190 kW
102 ... 300 kW
166 ... 427 kW
202 ... 546 kW
MAIN FEATURES
0 100 200 300 400 500 600 kW
• High efciency fan ventilation system
(HPV) allowing easy matching with boilers having high combustion chamber back pressure
• Electrical wiring simple to
disassemble for easy maintenance
MAX 1 MAX 4
• Combustion head easy to assemble
and adjust
• The hinge ange allows easy access
to burner head without losing burner settings (MAX 35 and MAX 45)
• Models from MAX 1 to MAX 12 work
with 50-60 Hz electrical frequency
MAX 12
4
Page 5
CONFIGURATIONS
MAX range is available in the following operation modes:
MAX One stage All models
MAX P ... AB Two stages MAX P 35 AB - P 45 AB
MAX P ... AB HS Two stages with hydraulic jack MAX P 12 AB HS ... P 45 AB HS
Other available congurations:
• Continuous ventilation versions
• High temperature versions
• Versions with specic pump for light oil with maximum viscosity 5°E at 20°C
• OEM and other special versions on request according to feasibility
FUEL
• Light oil (viscosity from 1,6 cSt to 6 cSt at 20°C)
MAX 30
EMISSIONS
Class NOx mg/kWh
1 250
2 185
3 120
All models are in compliance with EN 267 European Standard
MAX P35 AB HS
CONFORM TO
All products are in accordance with the following directives:
• 2006/42/EC Machinery Directive
• 2014/30/UE EMC Directive
• 2014/35/UE Low Voltage Directive
5
Page 6
Ø60
A
B C
D/D1
E
F
G
M
L
I
M
L
I
Max 8-12
Snorkel
Ø 80
Max 4
Snorkel
Ø 60
A
B C
Ø60
A
B C
A
B C
D/D1
E
F
G
F
G
D/D1
E
M
L
I
M
L
I
Max 8-12
Snorkel
Ø 80
Max 4 Snorkel
Ø 60
D/D1
E
G
M
L
I
Range Models
MAX 1 - 4 - 8 - 12
• Fuel: light oil (viscosity from 1,6 cSt to 6 cSt at 20°C)
• Operation: one stage
• Emission class: Low NOx class 2 (≤185 mg/kWh) according to EN267
WORKING DIAGRAM
mbar 4
MAX 4
3
2
1
Backpressure in the combustion chamber
MAX 1 MAX 12
MAX 8
Test conditions conforming to EN267
Temperature:
20°C
Pressure: 1013,5 mbar
Altitude: 0 m a.s.l.
0
0
20 40 60 80 100 120 140 kW
Burner output
TECHNICAL DATA
Burner output (kW) Flow rate (kg/h) Power supply Motor (W) NOx class Operation
MAX 1 18 - 41 1,5 - 3,5 1/230V/50-60Hz 75 Class 2 1 stage
MAX 4 20 - 59 1,7 - 5 1/230V/50-60Hz 75 Class 2 1 stage
MAX 8 47 - 105 4 - 8,9 1/230V/50-60Hz 100 Class 2 1 stage
MAX 12 60 - 130 5,1 - 11 1/230V/50-60Hz 130 Class 2 1 stage
OVERALL DIMENSIONS
MAX 1 MAX 4 - 8 - 12
A
B C
F
D/D1
A
E
G
B C
D/D1
F
G
E
M
L
I
A B C D D1 E F G I L M
MAX 1 288 143 145 80 140 153 89 160 92/107 92/107 M8
MAX 4 297 149 148 90 145 204 89 160 90/107 90/107 M8
MAX 8 303 155 148 90 145 204 89 160 100/120 100/120 M8
MAX 12 317 169 148 100 155 204 98 160 100/120 100/120 M8
6
Head lenght: D short / D1 long
Dimensions in mm
Page 7
Max 8-12
Snorkel
Ø 80
Max 4
Snorkel
Ø 60
A
B C
A
B C
Ø60
A
B C
A
B C
D/D1
E
F
G
F
G
D/D1
E
M
L
I
M
L
I
L
I
M
Max 8-12
Snorkel
Ø 80
Max 4
Snorkel
Ø 60
M
L
I
M
L
I
Range Models
MAX 15 - 20 - 30
• Fuel: light oil (viscosity from 1,6 cSt to 6 cSt at 20°C)
• Operation: one stage
• Emission class: Low NOx class 2 (≤185 mg/kWh) according to EN267
WORKING DIAGRAM
mbar 5
4
3
MAX 20
2
1
Backpressure in the combustion chamber
MAX 15
MAX 30
Test conditions conforming to EN267
Temperature:
20°C
Pressure: 1013,5 mbar
Altitude: 0 m a.s.l.
0
0
50 100 150 200 250 300 350 kW
Burner output
TECHNICAL DATA
Burner output (kW) Flow rate (kg/h) Power supply Motor (W) NOx class Operation
MAX 15 73 - 190 6,2 - 16 1/230V/50Hz 130 Class 2 1 stage
MAX 20 86 - 237 7,3 - 20 1/230V/50Hz 200 Class 2 1 stage
MAX 30 110 - 319 9,3 - 27 1/230V/50Hz 200 Class 2 1 stage
OVERALL DIMENSIONS
A
B C
D/D1
E
F
G
M
I
L
Head lenght: D short / D1 long
Dimensions in mm
A B C D D1 E F G I L M
MAX 15 392 202 190 160 260 276 107 201 120/131 120/131 M8
MAX 20 392 202 190 160 260 276 125 201 120/131 120/131 M8
MAX 30 392 202 190 160 260 276 125 201 120/131 120/131 M8
7
Page 8
Max 8-12
Snorkel
Ø 80
Max 4
Snorkel
Ø 60
A
B C
A
B C
Ø60
A
B C
A
B C
D/D1
E
F
G
F
G
D/D1
E
M
L
I
M
L
I
Range Models
MAX P 12 HS - P 15 HS - P 25 HS
• Fuel: light oil (viscosity from 1,6 cSt to 6 cSt at 20°C)
• Operation: two stages with hydraulic jack
• Emission class: Low NOx class 2 (≤185 mg/kWh) according to EN267
WORKING DIAGRAM
mbar 6
5
4
MAX P12 AB HS
3
2
1
Backpressure in the combustion chamber
MAX P15 AB HS MAX P25 AB HS
Test conditions conforming to EN267
Temperature:
20°C
Pressure: 1013,5 mbar
Altitude: 0 m a.s.l.
0
0
50 100 150 200 250 300 350 kW
Burner output
TECHNICAL DATA
Burner output (kW) Flow rate (kg/h) Power supply Motor (W) NOx class Operation
MAX P 12 AB HS 60 - 130 5,1 - 11 1/230V/50-60Hz 130 Class 2 P AB HS
MAX P 15 AB HS 77 - 190 6,5 - 16 1/230V/50Hz 130 Class 2 P AB HS
MAX P 25 AB HS 102 - 300 8,6 - 25,4 1/230V/50Hz 200 Class 2 P AB HS
OVERALL DIMENSIONS
B C
A
D/D1
E
F
G
M
I
Head lenght: D short / D1 long
A B C D D1 E F G I L M
MAX P 12 AB HS 308 169 139 100 155 204 98 160 100/120 100/120 M8
MAX P 15 AB HS 392 202 190 160 260 276 107 201 120/131 120/131 M8
MAX P 25 AB HS 392 202 190 160 260 276 125 201 120/131 120/131 M8
8
L
Dimensions in mm
Page 9
Max 8-12
Snorkel
Ø 80
Max 4
Snorkel
Ø 60
A
B C
A
B C
Ø60
A
B C
A
B C
A
B C
D/D1
E
F
G
F
G
D/D1
E
F
G
D/D1
E
M
L
I
M
L
I
L
I
M
Range Models
MAX P 35 - P 45
• Fuel: light oil (viscosity from 1,6 cSt to 6 cSt at 20°C)
• Operation: two stages and two stages with hydraulic jack
• Emission class: Low NOx class 2 (≤185 mg/kWh) according to EN267
WORKING DIAGRAM
8
6
4
2
Backpressure in the combustion chamber
MAX 35
MAX 45
Test conditions conforming to EN267
Temperature:
20°C
Pressure: 1013,5 mbar
Altitude: 0 m a.s.l.
0
0
TECHNICAL DATA
MAX P 35 AB 166 - 427 14 - 36 1/230V/50Hz 300 Class 2 AB
100 200 300 400 500 600 700 kW
Burner output (kW) Flow rate (kg/h) Power supply Motor (W) NOx class Operation
Burner output
MAX P 45 AB 202 - 546 17 - 46 3/230-400V/50Hz 550 Class 2 AB
MAX P 35 AB HS 166 - 427 14 - 36 1/230V/50Hz 300 Class 2 AB HS
MAX P 45 AB HS 202 - 546 17 - 46 3/230-400V/50Hz 550 Class 2 AB HS
OVERALL DIMENSIONS
E
D/D1
F
G
A
B C
L
M
I
Head lenght: D short / D1 long
Dimensions in mm
A B C D D1 E F G I L M
MAX P 35 501 294 207 175 365 466 160 280 185/200 185/200 M8
MAX P 45 501 294 207 175 365 466 160 280 185/200 185/200 M8
9
Page 10
HEAD OFFICE:
HEAD OFFICE: Via Roma, 64
Via Roma, 64 31023 Resana (TV)
31023 Resana (TV)
Company subject to the direction and coordination of Ariston Thermo SpA. Via A. Merloni, 45 - 60044 Fabriano (AN) - CF 01026940427
Company subject to the direction and coordination of Ariston Group, Via A. Merloni, 45 - 60044 Fabriano (AN) - Italy
Version 1.2 - 01/02/2022
Version 1.2 - 01/02/2022
ECOFLAM Bruciatori S.p.A. reserve the right to make any adjustments, without prior notice, which is considered necessary or
ECOFLAM Bruciatori S.p.A. reserve the right to make any adjustments, without prior notice, which is considered necessary or useful to its products, without affecting their main features.
useful to its products, without affecting their main features.
REGISTERED OFFICE:
REGISTERED OFFICE: Viale A. Merloni, 45
Viale A. Merloni, 45 60044 Fabriano (AN)
60044 Fabriano (AN)
Tel.: +39 0423 719500
Tel.: +39 0423 719500 Fax: +39 0423 719580
Fax: +39 0423 719580 Email: export@ecoam-burners.com
Email: export@ecoam-burners.com
www.ecoam-burners.com
www.ecoam-burners.com
Loading...