Ecoflam BLU BROCHURE

Page 1
GAS RANGE
BLU
www.ecoam-burners.com
Page 2
CUSTOMIZED BURNERS SOLUTIONS FOR ANY TYPE OF APPLICATION
OUR EXPERIENCE
Thanks to almost 50 years of experience in the design and production of burners, Ecoam offers a full range of blown air pressure jet burners covering an extremely wide range of power, from small products for residential heating appli­cations to high power burners dedicated to the industrial segment. Ecoam burners are renowned worldwide for providing high efciency and reliable operation with signicant ener­gy savings and feature extreme ease of installation, main­tenance and exible boiler-burner matching.
OUR MISSION
Following a philosophy of continuous improving, the R&D Laboratory is constantly working to produce better results, such as the reduced NOx level emissions. The development of new advanced combustion tech­nologies allows to propose solutions in respect of the most stringent environmental regulations and to create the perfect condition to face the new upcoming market requests, such as Ultra Low NOx performance and ErP­ready products.
OUR PRODUCT RANGE
The exibility of Ecoam solutions allows the manufacturing of highly customized products covering a range from 17 kW to 34 MW:
MAX GAS
17 - 700 kW
2
BLU
245 - 17000 kW
MAX
Light oil range
18 - 546 kW
MAIOR
Light oil range
300 - 17000 kW
MAXFLAM/OILFLAM
Heavy oil range 68 - 17000 kW
Page 3
OUR INTERNATIONAL APPROACH
Our products are designed, developed and manufactu­red in Italy, combining quality, reliability and high perfor­mance. All these features are necessary for the end-user satisfaction, which is the rst target for Ecoam. Reaching this outcome throughout its extensive worldwide network of distributors and customers has always been a challen­ging task for Ecoam, which was achieved only by deve­loping a close and personalized relationship with each customer, always taking into account the needs and the distinctive characteristics of each individual market.
OUR PROFESSIONAL TEAM
Ability to design state-of-the-art burners, manage demands of products for specic applications, ability to solve pro­blems in real time are just some of the characteristics of our technicians and engineers. But not only: Ecoam has a worldwide network of service technicians able to support the installation, the commissio­ning and the periodic maintenance activities of the burner.
MULTICALOR
Dual fuel (gas/light oil)
190 - 17000 kW
MULTIFLAM
Dual fuel (gas/heavy oil)
414 - 17000 kW
TS RANGE
All fuels
230 - 34000 kW
SPECIAL
VERSIONS
3
Page 4
Fuel Range
GAS BLU
RANGE OVERVIEW
Low NOx Classe 3 (NOx ≤ 80 mg/kWh)
BLU 700.1 LN
BLU 1000.1 LN
BLU 1200.1 LN
BLU 1500.1 LN
Low NOx Classe 2 (NOx ≤ 120 mg/kWh)
BLU 1000.1
BLU 1200.1
BLU 1700.1
BLU 2000.1
BLU 3000.1
BLU 4000.1
BLU 5000.1
BLU 6000.1
BLU 7000.1
BLU 8000.1
BLU 10000.1
BLU 12000.1
BLU 15000.1
BLU 17000.1
270 ... 700 kW
280 ... 875 kW
290 ... 1100 kW
300 ... 1550 kW
245 ... 970 kW
260 ... 1200 kW
342 ... 1770 kW
414 ... 2150 kW
630 ... 3000 kW
875 ... 3900 kW
1200 ... 5000 kW
1500 ... 5800 kW
1500 ... 7500 kW
2000 ... 8500 kW
2500 ... 10500 kW
2700 ... 13000 kW
3690 ... 15000 kW
4000 ... 17000 kW
Low NOx
Class 3
0
0
400
4000
800
8000
1200
12000
16000
1600
2000 kW
20000 kW
MAIN FEATURES
• Modulating version with PID controller with
digital set point display and real time value
• Version with fully electronic Burner
Management System available for all models
• Adjustable combustion head for easy
regulation and matching with different
• Congurated and special versions on
request according to feasibility
combustion chambers
• High turndown ratio up to 1:8
BLU 700.1 PABBLU 500.1 PAB BLU 2000.1 PAB
4
Page 5
CONFIGURATIONS
BLU range is available in the following operation modes:
BLU ... PAB
BLU ... PR
BLU ... PRE
Two stages Two stages Low NOx Class 3
Two stage progressive/modulating mechanical Two stage progressive/modulating mechanical Low NOx Class 3
Two stage progressive/modulating electronic Two stage progressive/modulating electronic Low NOx Class 3
Other available congurations:
• LPG versions up to BLU 6000.1
• Continuous ventilation versions
• Swirl system for ame geometry customization
• OEM and other special versions on request according to feasibility
FUEL
• Natural gas (G20, G25 according to EN676)
• LPG
EMISSIONS CONFORM TO
Class NOx mg/kWh
1 170
2 120 3 80
All models are in compliance with EN 676 European Standard
BLU 700.1 ... 2000.1 BLU 700.1 LN ... 1500.1 LN
BLU 1000.1 ... 17000.1 BLU 700.1 LN ... 1500.1 LN
BLU 1000.1 ... 17000.1 BLU 700.1 LN ... 1500.1 LN
All products are in accordance with the following directives:
• 2006/42/EC Machinery Directive
• 2014/30/UE EMC Directive
• 2014/35/UE Low Voltage Directive
• 2009/142/CEE Gas Appliances Directive
BLU 6000.1 PR
BLU 17000.1 PR
5
Page 6
Range Models
1
0
2 3
I
O
N
D / D1E
B C
A
H1
G
F
O
1
0
2 3
I
O
D / D1E
B C
A
G
F
O
BLU 700.1 LN - 1000.1 LN - 1200.1 LN - 1500.1 LN
• Fuels: natural gas, LPG
• Operation: two stages, two stage progressive or modulating with the installation of a power regulator and
dedicated probes
• Emission class: Low NOx class 3 (≤80 mg/kWh) according to EN676
WORKING DIAGRAM
mbar 10
8
6
4
2
Backpressure in the combustion chamber
0
0
BLU 700.1 LN
200 400 600 800 1000 1200 1400 1600 kW
BLU
1000.1 LN
Burner output
BLU 1200.1 LN
BLU 1500.1 LN
Low NOx
Class 3
Test conditions conforming to EN676
Temperature:
20°C
Pressure: 1013,5 mbar
Altitude: 0 m a.s.l.
TECHNICAL DATA
Burner output (kW) Power supply Motor (kW) NOx class Operation
BLU 700.1 LN 270 - 700 3/230-400/50Hz 1,1 Class 3 PAB, PR, PRE
BLU 1000.1 LN 280 - 875 3/230-400/50Hz 1,1 Class 3 PAB, PR, PRE
BLU 1200.1 LN 290 - 1100 3/230-400/50Hz 2,2 Class 3 PAB, PR, PRE
BLU 1500.1 LN 300 - 1550 3/230-400/50Hz 3 Class 3 PAB, PR, PRE
OVERALL DIMENSIONS
D / D1E
A
B C
O
I
F
L
G
H1
N
M
A B C D D1 E F G H1* I L M N O
Head lenght: D short / D1 long
*: with silencer (optional)
BLU 700.1 LN 650 330 320 175 395 555 170 390 600 190 190 M10 140 165
BLU 1000.1 LN 650 330 320 175 395 555 190 390 600 190 190 M10 140 165
BLU 1200.1 LN 670 350 320 310 460 555 200 390 600 190 190 M10 140 165
BLU 1500.1 LN 71 2 364 348 340 540 730 215 420 680 240 240 M14 138 187
6
Dimensions in mm
Page 7
Range Models
1
0
2
3
I
O
D / D1E
B C
A
G
F
O
BLU 1000.1 - 1200.1
• Fuels: natural gas, LPG
• Operation: two stages, two stage progressive or modulating with the installation of a power regulator and dedicated probes
• Emission class: Low NOx class 2 (≤120 mg/kWh) according to EN676
WORKING DIAGRAM
mbar 10
8
6
4
2
Backpressure in the combustion chamber
BLU 1000.1
BLU 1200.1
Test conditions conforming to EN676
Temperature:
20°C
Pressure: 1013,5 mbar
Altitude: 0 m a.s.l.
0
0
200 400 600 800 1000 1200 1400 kW
Burner output
TECHNICAL DATA
Burner output (kW) Power supply Motor (kW) NOx class Operation
BLU 1000.1 245 - 970 3/230-400/50Hz 1,1 Class 2 PAB, PR, PRE
BLU 1200.1 260 - 1200 3/230-400/50Hz 2,2 Class 2 PAB, PR, PRE
OVERALL DIMENSIONS
H1
D / D1E
B C
I
A
F
O
G
N
0
I
1
2
O
3
L
M
Head lenght: D short / D1 long
Dimensions in mm
*: with silencer (optional)
A B C D D1 E F G H1* I L M N O
BLU 1000.1 PAB 608 328 280 174 394 543 190 401 601 185/200 185/200 M10 138 168
BLU 1200.1 PAB 608 328 280 309 459 543 200 401 601 185/200 185/200 M10 138 168
BLU 1000.1 PR 657 328 329 174 394 543 190 401 601 185/200 185/200 M10 138 420
BLU 1200.1 PR 657 328 329 309 459 543 200 401 601 185/200 185/200 M10 138 420
BLU 1000.1 PRE 702 422 280 174 394 651 190 401 601 185/200 185/200 M10 138 168
BLU 1200.1 PRE 702 422 280 309 459 651 200 401 601 185/200 185/200 M10 138 168
7
Page 8
Range Models
1
0
2 3
I
O
D / D1E
B C
A
G
F
O
BLU 1700.1 - 2000.1
• Fuels: natural gas, LPG
• Operation: two stages, two stage progressive or modulating with the installation of a power regulator and dedicated probes
• Emission class: Low NOx class 2 (≤120 mg/kWh) according to EN676
WORKING DIAGRAM
mbar 12
10
BLU 2000.1BLU 1700.1
8
6
4
2
Backpressure in the combustion chamber
Test conditions conforming to EN676
Temperature:
20°C
Pressure: 1013,5 mbar
Altitude: 0 m a.s.l.
0
0
400 800 1200 1600 2000 2400 kW
Burner output
TECHNICAL DATA
Burner output (kW) Power supply Motor (kW) NOx class Operation
BLU 1700.1 342 - 1770 3/230-400/50Hz 3 Class 2 PAB, PR, PRE
BLU 2000.1 414 - 2150 3/400/50Hz 4 Class 2 PAB, PR, PRE
OVERALL DIMENSIONS
D / D1E
F
O
N
G
H1
A
B C
0
I
1 2
O
3
I
L
M
Head lenght: D short / D1 long
*: with silencer (optional)
A B C D D1 E F G H1* I L M N O
BLU 1700.1 710 385 325 340 540 660 250 398 681 240 240 M14 125 250
BLU 2000.1 730 405 325 345 545 660 270 398 681 240 240 M14 125 250
8
Dimensions in mm
Page 9
Range Models
1
0
2 3
I
O
D / D1E
B C
A
G
F
O
BLU 3000.1 - 4000.1 - 5000.1 - 6000.1
• Fuels: natural gas, LPG
• Operation: two stage progressive or modulating with the installation of a power regulator and dedicated probes
• Emission class: Low NOx class 2 (≤120 mg/kWh) according to EN676
WORKING DIAGRAM
mbar 25
20
15
BLU 5000.1
BLU 4000.1
BLU 6000.1
Test conditions conforming to EN676
Temperature:
20°C
Pressure: 1013,5 mbar
Altitude: 0 m a.s.l.
10
BLU 3000.1
5
Backpressure in the combustion chamber
0
0
1000 2000 3000 4000 5000 6000 kW
Burner output
TECHNICAL DATA
Burner output (kW) Power supply Motor (kW) NOx class Operation
BLU 3000.1 630 - 3000 3/400/50Hz 5,5 Class 2 PR, PRE
BLU 4000.1 875 - 3900 3/400/50Hz 7,5 Class 2 PR, PRE
BLU 5000.1 1200 - 5000 3/400/50Hz 11 Class 2 PR, PRE
BLU 6000.1 1500 - 6000 3/400/50Hz 15 Class 2 PR, PRE
OVERALL DIMENSIONS
D / D1E
F
O
A
B C
0
I
1
2
O
3
I
L
N
G
H1
M
Head lenght: D short / D1 long
*: with silencer (optional)
A B C D D1 E F G H1* I L M N O
BLU 3000.1 941 448 493 330 530 780 290 471 746 315 315 M16 195 250
BLU 4000.1 941 448 493 365 565 780 320 471 746 315 315 M16 195 250
BLU 5000.1 1019 495 524 375 575 970 320 570 965 330 330 M16 195 250
BLU 6000.1 1069 545 524 375 575 970 360 57 0 965 330 330 M16 195 250
Dimensions in mm
9
Page 10
Range Models
1
0
2 3
I
O
D / D1E
B C
A
G
F
O
BLU 7000.1 - 8000.1 - 10000.1 - 12000.1
• Fuels: natural gas, LPG
• Operation: two stage progressive or modulating with the installation of a power regulator and dedicated probes
• Emission class: Low NOx class 2 (≤120 mg/kWh) according to EN676
WORKING DIAGRAM
mbar 40
32
24
BLU 7000.1
16
8
Backpressure in the combustion chamber
BLU 8000.1
BLU 10000.1 BLU 12000.1
Test conditions conforming to EN676
Temperature:
20°C
Pressure: 1013,5 mbar
Altitude: 0 m a.s.l.
0
0
2000 80004000 10000 120006000 14000 kW
Burner output
TECHNICAL DATA
Burner output (kW) Power supply Motor (kW) NOx class Operation
BLU 7000.1 1500 - 7500 3/400/50Hz 15 Class 2 PR, PRE
BLU 8000.1 2000 - 8500 3/400/50Hz 18,5 Class 2 PR, PRE
BLU 10000.1 2500 - 10500 3/400/50Hz 22 Class 2 PR, PRE
BLU 12000.1 2700 - 13000 3/400/50Hz 37 Class 2 PR, PRE
OVERALL DIMENSIONS
D / D1E
F
O
N
G
H1
A
B C
0
I
1 2
O
3
I
L
M
Head lenght: D short / D1 long
A B C D D1 E F G H1* I L M N O
BLU 7000.1 1210 585 625 47 0 - 1212 420 775 1270 460 460 M20 195 232
BLU 8000.1 1280 655 625 47 0 - 1212 420 775 1270 460 460 M20 195 232
BLU 10000.1 1310 685 625 470 - 1212 420 775 1270 460 460 M20 195 232
BLU 12000.1 1420 795 625 47 0 - 1212 450 775 1270 460 460 M20 195 232
10
Dimensions in mm
*: with silencer (optional)
Page 11
Range Models
1
0
2 3
I
O
M
L
I
G
D / D1E
B C
A
H1
N
O
N
D / D1E
B C
A
H1
H1
G
F
F
O
1
0
2 3
I
O
D / D1E
B C
A
G
F
O
BLU 15000.1 - 18000.1
• Fuels: natural gas, LPG
• Operation: two stage progressive or modulating with the installation of a power regulator and dedicated probes
• Emission class: Low NOx class 2 (≤120 mg/kWh) according to EN676
WORKING DIAGRAM
mbar 40
32
BLU 15000.1 BLU 18000.1
24
16
8
Backpressure in the combustion chamber
Test conditions conforming to EN676
Temperature:
20°C
Pressure: 1013,5 mbar
Altitude: 0 m a.s.l.
0
0
2000 80004000 10000 12000 14000 160006000 18000 20000 kW
Burner output
TECHNICAL DATA
Burner output (kW) Power supply Motor (kW) NOx class Operation
BLU 15000.1 3690 - 15000 3/400/50Hz 45 Class 2 PR, PRE
BLU 18000.1 4000 - 17000 3/400/50Hz 55 Class 2 PR, PRE
OVERALL DIMENSIONS
D / D1E
F
O
B C
A
I
N
G
L
M
1150
A B C D D1 E F G H1* I L M N O
Head lenght: D short / D1 long
*: with silencer (optional)
BLU 15000.1 1530 810 720 590 - 1860 550 1320 1670 619 619 M20 210 320
BLU 18000.1 1580 860 720 590 - 1860 550 1320 1670 619 619 M20 210 320
Dimensions in mm
11
Page 12
HEAD OFFICE: Via Roma, 64 31023 Resana (TV)
Company subject to the direction and coordination of Ariston Group, Via A. Merloni, 45 - 60044 Fabriano (AN) - Italy
REGISTERED OFFICE: Viale A. Merloni, 45 60044 Fabriano (AN)
Tel.: +39 0423 719500 Fax: +39 0423 719580 Email: export@ecoam-burners.com
Version 1.2 - 01/02/2022
ECOFLAM Bruciatori S.p.A. reserve the right to make any adjustments, without prior notice, which is considered necessary or useful to its products, without affecting their main features.
www.ecoam-burners.com
Loading...