33
COMMISSIONING
At the time of commissioning, please ensure a Commissioning Checklist is completed for the installation.
FILLING THE UNIT WITH WATER
• BEFORE FILLING CHECK AND TIGHTEN ALL MECHANICAL JOINTS AND CONNECTIONS IN CASE THESE HAVE
LOOSENED DURING TRANSIT.
• Check expansion vessel pre-charge pressure. The vessel is supplied precharged to 3.5 bar to match the control pressure
of the pressure reducing valve. The precharge pressure is checked using a car tyre gauge by unscrewing the plastic
cap opposite the water connection.
• Check all connections for tightness including the immersion heater(s). An immersion heater key spanner is supplied for
this purpose.
• Ensure the drain cock is CLOSED.
• Open a hot tap furthest from the cylinder.
• Open the cylinder isolating valve to ll the unit. When water ows from the tap, allow to run for a few minutes to thoroughly
ush through any residue, dirt or swarf, then close the tap.
• Open successive hot taps to purge the system of air.
SYSTEM CHECKS
• Check all water connections for leaks and rectify as necessary.
• Turn off water supply to the cylinder.
• Remove the pressure reducing valve head work to access the strainer mesh, clean and re-t.
• Manually open, for a few seconds, each relief valve in turn, checking that water is discharged and runs freely through
the tundish and out at the discharge point.
• Ensure that the valve(s) reseat satisfactorily.
DOMESTIC HOT WATER (DHW) CIRCULATION
Ensure the DHW circulation pump is set to speed setting II to ensure optimum DHW heating performance. Failure to
do so can result in excessive use of the back-up immersion heater or lower storage temperatures than required.
PRIMARY CIRCUIT
Fill the primary circuit following the Air Source Heat Pump commissioning instructions. Vent any trapped air. Check the primary
system for leaks and rectify as necessary. Flush the primary system in accordance with the instructions on Page 22 and add
a suitable inhibitor and anti-freeze solution when re-lling.
Switch on the electrical supply to the Air Source Heat Pump and immersion heater. Programme the Air Source Heat Pump
controller as detailed in the tting and user instructions supplied with the controller. Set the controller for hot water operation
only. After a short delay the primary pump on the return to the Heat Pump and the DHW pump should run and the Heat Pump
operate. The temperature of the primary ow to the cylinder should increase, if it does not, check for a wiring or piping error.
Allow the unit to heat up.
Select the heating only function on the controller. Both primary pumps should run and the Heat Pump operates. The primary
ow to the cylinder primary pipework manifold and the radiator circuit should become hot, if it does not check for a wiring or
piping error.
The minimum hot water setting is 40 °C. The maximum hot water setting is 60 °C. In hard water areas a maximum of 60 oC
is recommended.
When the heating and hot water temperatures are reached, the pumps should stop running and the Heat Pump stop operating.
Check that no water is discharged from either the expansion valve or temperature and pressure relief valve during the
heating cycle. If the user temperatures or “On” and “Off” times have been adjusted for commissioning purposes, the controller
should be reset to the desired settings. The operation of the controller should be demonstrated to the user and the controller
installation and user instructions left with them for future reference.
AUTOMATIC SYSTEM BY-PASS
An automatic differential bypass valve should be installed between the primary ow and the primary return to the main space
heating zone from the Low Loss Header such that a minimum ow rate can be maintained through the Heat Pump in the
event of the heating circuit being satised. See instructions supplied with the valve for setting details for the valve.