Eclipse Combustion 6500 User Manual

Page 1
Instruction Manual
No. 826, 05/03
Bi-Flame
Dual Burner Monitoring System
Model 6500
Version 1.8
Page 2
COPYRIGHT
Copyright 2003 by Eclipse Combustion. All rights reserved worldwide. This publication is protected by federal regulation and shall not be copied, distributed, transmitted, transcribed or translated into any human or computer language, in any form or by any means, to any third parties, without the express written consent of Eclipse Combustion.
DISCLAIMER NOTICE
LIABILITY AND
WARRANTY
In accordance with the manufacturer’s policy of continual product improvement, the product presented in this brochure is subject to change without notice or obligation.
The material in this manual is believed adequate for the intended use of the product. If the product is used for purposes other than those specified herein, confirmation of validity and suitability must be obtained. Eclipse Combustion warrants that the product itself does not infringe upon any United States patents. No further warranty is expressed or implied.
We have made every effort to make this manual as accurate and complete as possible. Should you find errors or omissions, please bring them to our attention so that we may correct them. In this way we hope to improve our product documentation for the benefit of our customers. Please send your corrections and comments to our Marketing Communications Manager.
It must be understood that Eclipse Combustion’s liability for its products, whether due to breach of warranty, negligence, strict liability, or otherwise, is limited to the furnishing of burner monitoring system replacement parts and Eclipse Combustion will not be liable for any other injury, loss, damage or expenses, whether direct or consequential, including but not limited to loss of use, income of, or damage to material arising in connection with the sale, installation, use of, inability to use or the repair or replacement of Eclipse Combustion’s products.
Eclipse Combustion, for a period of one year fr om shipment, warrants each Bi-Flame burner monitoring system to the original purchaser to be free from defects in material and workmanship under normal use as defined hereafter. Any operation expressly prohibited in this Guide, any adjustment or assembly procedures not recommended or authorized in these instructions, shall void the warranty.
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 3
About this manual
AUDIENCE
IMPORTANT NOTICES
DOCUMENT
CONVENTIONS
This manual has been written for the people who select and install the product and the technicians who work on it. They are expected to have previous experience with this kind of equipment.
• Read this manual carefully. Make sure that you understand the structure and contents of this manual.
• Obey all the safety instructions.
• Do not deviate from any instructions or application limits in this manual without written consent from Eclipse Combustion.
• If you do not understand any part of the information in this manual, do not continue. Contact your Eclipse sales office or Eclipse Combustion.
There are several special symbols in this document. You must know their meaning and importance.
The explanation of these symbols follows. Please read it thoroughly.
Danger: Indicates hazards or unsafe practices which WILL result in severe personal injury or even death. Only qualified and well trained personnel are allowed to carry out these instructions or procedures. Act with great care and follow the instructions.
Warning: Indicates hazards or unsafe practices which could result in severe personal injur y or damage. Act with great care and follow the instructions.
Caution: Indicates hazards or unsafe practices which could result in damage to the machine or minor personal injury. Act carefully.
Note: Indicates an important part of the text. Read the text thoroughly.
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 4
Table of Contents
2
3
1
About this manual....................................................................
Table of contents.......................................................................
Introduction...................................................................................
Product Description..........................................................................
Specifications ..............................................................................
Introduction...........................................................................................
Specifications .........................................................................................
Dimensions ............................................................................................
Modules Description ..............................................................
Introduction...........................................................................................
Module Description and Identification ...........................................
Relay Module.........................................................................................
Logic Module.........................................................................................
Power Module.......................................................................................
Sensor Module......................................................................................
Remote Display ....................................................................................
3
4
7 7
8 8 8 9
10 10 10 10 10 10 11 11
4
DIP Switch Selection .............................................................
Introduction...........................................................................................
DIP Switch Location............................................................................
DIP Switch Access................................................................................
S2 DIP Switch Settings........................................................................
S4 DIP Switch Settings........................................................................
S6 DIP Switch Settings........................................................................
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
12 12 12 12 13 13 13
Page 5
5
6
Function Summary..................................................................
Introduction...........................................................................................
Standard Features.................................................................................
Combustion Air Flow Check Terminal............................................
Main Fuel Valve Proof-of-Closure Terminal....................................
Low Fire Start T erminal ......................................................................
High Fire/High Fire Purge Check Terminal.....................................
Recycle Mode........................................................................................
Pilot Test Mode .....................................................................................
Interrupted or Intermittent Pilot.....................................................
Spark, Pilot Flame & Main Flame Separation .................................
Auxiliary Inputs.....................................................................................
History Log............................................................................................
Modulation Contacts...........................................................................
Valve Leak Sensing Device .................................................................
Remote Display Unit...........................................................................
RS232/RS485 Communication Interfaces ......................................
Logic Module Status Lights & Push-buttons ..................................
Limits.......................................................................................................
Air ............................................................................................................
Purge .......................................................................................................
Burner On..............................................................................................
Fault .........................................................................................................
Alarm.......................................................................................................
Low Fire..................................................................................................
High Fire.................................................................................................
Scan..........................................................................................................
Enter........................................................................................................
Reset........................................................................................................
System Faults.........................................................................................
System Lockout Conditions ..............................................................
14 14 14 14 14 14 14 15 15 15 15 16 16 17 18 19 19 19 19 20 20 20 20 20 20 20 20 20 20 21 21
System Installation..................................................................
Introduction...........................................................................................
Interlocks and Limit Switch Input ....................................................
Combustion Air Switch Input............................................................
Ignition Wiring.......................................................................................
Communication Wiring ......................................................................
Power Supply.........................................................................................
Low Fire Input.......................................................................................
Main Valv e Proof-of-Closure..............................................................
High Fire Input ......................................................................................
Auxiliary Inputs.....................................................................................
Remote Reset .......................................................................................
Remote Display ....................................................................................
Terminal Strips Identification & Location (Figure 6.1) ................
Wiring Diagram & Connections–Main Chassis (Figure 6.2) ........
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
22 22 22 22 23 23 23 23 23 23 23 23 24 25 26
Page 6
7
Sensor Installation ...................................................................
Introduction...........................................................................................
Sensor Wiring........................................................................................
Flame Rods ............................................................................................
Scanners..................................................................................................
Scanner Sighting Considerations......................................................
27 27 27 28 28 29
8
9
10
Test Procedures ...............................................................................
Introduction...........................................................................................
Flame Signal Strength ..........................................................................
Minimum Pilot Test...............................................................................
Pilot Flame Failure Test .......................................................................
Main Flame Failure Test.......................................................................
Spark Sighting Test................................................................................
Limits & Interlock Tests ......................................................................
Maintenance & Troubleshooting ..............................................
Introduction...........................................................................................
Maintenance...........................................................................................
Monthly Checklist ................................................................................
Yearly Checklist ....................................................................................
Troubleshooting....................................................................................
Remote Display Messages...........................................................
Introduction...........................................................................................
Bi-Flame Operating Sequence (Table 10.1) ...................................
Remote Display Diagnostic Messages (Table 10.2)......................
30 30 30 30 31 31 31 31
32 32 32 32 33 34
35 35 36 40
Appendix .............................................................................................
Conversion Factors .............................................................................
Illustrated Parts List.............................................................................
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
43 43 44
Page 7
Introduction
1
PRODUCT DESCRIPTION
The Eclipse Combustion Bi-Flame Burner Monitoring System controls the start-up sequence and monitors the flame of two individual gas, oil, or combination gas/oil burners connected to a common valve train. Its dynamic on-board testing checks for faulty relays, proof of valve closure, high and low fire switch interlocks, and shorted air switch.
The microcomputer based system features a plug-in modular design so any of the circuit board modules attached to the motherboard can be replaced when power is removed. Its DIP switches allow sequence and timing functions, as well as system configuration. It is also capable of modulation (high and low fire purging) and monitoring up to four auxiliary inputs, history logging, and interfacing to valve leakage detection devices. It is UL recognized, FM approved and CSA certified.
Figure 1.1
Bi-Flame Burner Monitoring System
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 8
Specifications
2
INTRODUCTION
Specifications
Parameter Description Supply •120 VAC (+10%, -15%), 50/60 Hz standard. Internal power consumption: 24VA Temperature Ranges Unit Model Nos. Temperature Range Bi-Flame 6500 -40˚ to +60˚C (-40˚ to +140˚F) 90˚ U.V. Scanner 5600-90A -20˚ to +60˚C (0˚ to 140˚F) U.V. Scanner 5600-91 -40˚ to +125˚C (-40˚ to +257˚F) NEMA4 UV Scanner 5600-91N4 -20˚ to +125˚C (0˚ to 257˚F) Self-Check U.V. 5602-91 -40˚ to +60˚C (-40˚ to +140˚F) Remote Display 6000D to 50˚C (32˚ to 122˚F) Flame Failure Response • 3 seconds ±0.5 seconds. TFI/Pilot Interrupt • 5, 10 or 15 seconds selectable. Purge Time • Modulating: selectable from 0-225 seconds in 15 second increments,
or 0-15 minutes in 1 minute increments
• Process: selectable from 0-15 minutes in 1 minute increments, or 0-60 minutes in 4 minute increments.
This section gives a detailed overview of Bi-Flame specifications and dimensions.
Contact Ratings @ 120 VAC Function Affected Terminals Inductive Load Resistive Load (maximum total connected Output Relay J2-4 through J2-8 1/3 HP 10 amps load not to exceed 15 amps) Output Relay J2-3 1/2 HP 15 amps Modulation J3-1 through J3-4 1/3 HP 10 amps Approvals • UL Recognized; File MP1537 (category MCCZ2)
• FM Approved; J.I. 2Y3A5.AF (class 7610)
• CSA Certified; File 007989-0-000 (class 2632-01, 2642-01) Shipping Weight • 2.7 kilograms (6 lbs.)
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 9
DIMENSIONS
Main Chassis
Mounting Holes (4)
5 mm
(3/16") Dia.
183 mm
(7-3/16")
140 mm
(5-1/2")
237 mm
(9-5/16")
Remote Display
102 mm
(4") Square
229 mm
(9")
270 mm
(10-5/8")
(Shown with remote keypad and reset)
54 mm
(2-1/8")
Mounting Bracket & Screw (2)
Mounting
Bracket Slot (4)
21 mm
(13/16")
15-pin
Port
Terminal
89 mm
(3-1/2") Square
Contrast
Adjustment
Slot
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 10
Modules Descr iption
3
INTRODUCTION
MODULE DESCRIPTION
AND
IDENTIFICATION
Relay Module Location
In this section, you will find descriptions of the various modules which comprise the Bi-Flame dual burner flame monitoring system, whether standard or optional items.
Relay Module
The relay module contains the output relays which provide power for operating the ignition coil, pilot valve, main valve, combustion fan and alarm. This module is mounted in the first position on the left of the motherboard closest to the output terminals.
Logic Module
The logic module houses the microcomputer which provides all the sequential logic and safety start-up and shutdown circuitry. On the front of this module is the reset, scan and enter push-buttons, and status lights. This module is mounted in the second position from the left of the motherboard next to the relay module.
Power Module
10
The power module supplies the power required for the electronic circuitry. It is mounted in the motherboard to the right of the logic module. The green LED on the front indicates that power is on to the Bi-Flame.
Logic Module Location
Power Module Location
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 11
Sensor Module Location
Sensor Module
The sensor module is the flame sensing module of the Bi-Flame. It is mounted in the furthest right position of the mother board.
On the front of the sensor module are two “Flame On” LED’s, which illuminate when a flame is detected at the corresponding burner. Directly below the “Flame ON” LED are “Flame Fail” LED’s, which energize to show the first burner to lose its signal.
The sensor module incorporates test point connection jacks in the front of the unit. Using these, the flame signal strength of each burner can be measured using a 0-15 VDC, one meg ohm/v olt meter as explained and shown in “Flame Signal Strength” on page 30.
Remote Display
The remote display provides alphanumeric messages which indicate burner status as well as annunciate lockout condition in the Bi-Flame system. It also provides remote reset, a keypad and history logging capability.
A cable connects the remote display to the motherboard; this cable is available in six and 10 feet lengths.
Remote Display
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
11
Page 12
DIP Switch Selection
INTRODUCTION This section details the location, selection and description of the
Bi-Flame DIP switches, which allow for sequence and timing func­tions as well as system configuration.
Caution: To avoid electric shock, shut off the power supply when installing any control device. Flame monitoring systems must be installed by a qualified, licensed technician.
4
DIP SWITCH LOCA TION
DIP SWITCH ACCESS
All of the DIP switches are located in the logic module, which is mounted in the second position from the left of the motherboard next to the relay module (see page 10 for logic module location).
To gain access to the DIP switches, remove the circuit board cover. To do this, remove the four screws which hold the cover to the motherboard. Remove the cover by lifting up and off of the cir­cuit boards. The logic module is the second board from the left. Gently pull the logic module with a rocking motion to disengage the terminal pins at the module base. The photo below sh ows the DIP switch locations.
ON/OFF
S6
S4
12
S2
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 13
DIP SWITCH SETTINGS
S2 DIP Switches
ON/OFF
8
50/60Hz
7
6
5
S6
S4
S2
8 7 6
S2
5 4
S2 Modulation Purge Time, S4 - 8 = ON
8 7 6
S2
5 4
S2 Process Purge Time, S4 - 8 = OFF
Number
4 3 2 1
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1
of
PAF
MOD/PROC
TFI
LEAK 110/40
— — —
BLOWER
P U R G E
PILOT IMIT/IRPT
RECYCLE
DIP Switch Functions
ON
OFF
X4
120 sec.
Time
60 sec.
Not
30 sec.
Added
15 sec.
ON
OFF
X4
8 min.
Time
4 min.
Not
2 min.
Added
1 min.
X4
120/8
60/4 30/2 15/1
TFI
The S2 DIP switches permit programming of timing and sequence functions of the Bi-Flame.
Note: The S2 DIP switch settings at left are for illustrative purposes only; the actual settings of any of these switches will be
determined by your system conditions. SW1: Recycling mode selection (On=Recycling; Off=Non-recycling) SW2: Pilot selection (On=Intermittent, where pilot remains on during
burner cycle; Off =Interrupted, where pilot valve closes after main burner is established).
SW3: T rial-for -ignition (TFI) range selection; used with SW7 of the S4 DIP switch. See the table at left for proper selection.
SW4 through 8: Purge time selection; switch in off position selects indicated purge time. Selected purge times are additive. See illustration at left for exact times.
S4 DIP Switches
SW1: Fan operation on flame failure (on = fan turns off; off = fan stays on).
SW5: Leak test time (on=110 seconds; off=40 seconds). SW7: T rial-for -ignition (TFI) range selection; used with SW3 of the S2
DIP switches. See the table at left for proper selection. SW8: Purge mode; (on = modulation, off = process).
S6 DIP Switches
The S6 DIP switches are factory set for two burners. DO NOT CHANGE. Any other setting will result in an “UNMATCH#” fault condition.
SW6: Off, Not used. SW7: Off, Not used. SW8: Frequency Selection; (On = 50Hz, Off = 60 Hz)
THEN
SW3 of S2
If the
TFI
needed is:
5 seconds 10 seconds 15 seconds
DIP switch
must be
turned:
Off Off On
Trial-for-Ignition (TFI) Settings
AND
SW7 of S4
DIP Switch
must be
turned:
Off On
Off or On
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
13
Page 14
Function Summar y
5
INTRODUCTION This section describes the function features of the Bi-Flame that can
be found on the various terminal strips and the modules of the Bi­Flame.
Combustion Air Flo w Check Terminal
The Bi-Flame checks that the combustion air flow switch is open be­fore start-up, closed during operation and open again at burner shut­down, thus preventing operation with an air switch that is defective, maladjusted or jumpered.
Main Fuel Valve Proof-of-Closur e T erminal
The Bi-Flame checks that the main fuel valve is closed before start­up and after burner shutdown. This ar rangement requir es a closed position switch on the main fuel valve.
Low Fire Start Terminal
The system checks for the low fire start position prior to light-off. If voltage is not present on this terminal within 15 minutes, the Bi-Flame goes to lockout and alarm.
High Fire Purge Check Terminal
The system checks that the air modulation motor reached the high fire position during high fire purge. The modulation motor or air valve must be fitted with a high fire position switch, which is then connected to the high fire check terminal. An air flow or pressure switch that is set to prove sufficient purge air may be used instead of the high fire position switch. If v oltage is not pr esent on this termi­nal within 15 minutes, the Bi-Flame goes to lockout and alarm.
14
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 15
Recycle Mode
When selected, the Bi-Flame will restart the sequence after flame or air failure. The recycle mode allows the system to re-initiate the start-up sequence automatically, once the main burners have been operating for at least 20 seconds. If the pilot flame fails to light dur­ing recycling, the system will lock out and annunciate a pilot flame fail. If the recycle is successful and the main burners are operational for at least 20 seconds, the system is ready for another recycle. At no time will the system recycle in the event of pilot flame fail.
Pilot T est Mode
This mode is entered by pressing the “Reset” and the “Enter” but­tons simultaneously then releasing the “Reset” button but holding the “Enter” button for another 10 seconds. The limits light will flash off and on, indicating that the system is in the test mode.
In the pilot test mode, the Bi-Flame operates normally with the excep­tion that the main valves are not energized, preventing the main burn­ers from igniting.
To exit the pilot test mode, simply press the “Reset” button and the Bi-Flame will exit the pilot test mode and restart the sequence. En­tering the pilot test mode erases the history log.
Interrupted or Intermittent Pilot
Pilot mode is selected using the DIP switch (see “S2 DIP Switch Settings” on page 13). An interrupted pilot shuts off after the main flame is established. An intermittent pilot continues during the en­tire main flame firing cycle.
Spark, Pilot Flame and Main Flame Separation
During the trial for ignition period (TFI), the pilot and ignition out­puts remain energized. At the end of the TFI, the pilot output re­mains on and the ignition output is de-energized. After a five sec­ond delay to prove the pilot flame, the main output is energized.
Note: Both pilots must light within the specified TFI or a pilot flame failure will occur. If one burner experiences either a pilot or main flame failure, then both burners will shut down. The failed burner will be indicated by the red “Flame Fail” light.
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
15
Page 16
Auxiliary Inputs
This feature provides four auxiliary inputs which are monitored by the Bi-Flame as alarm interlocks. This means that when the input voltage is interrupted, the system locks out and will annunciate on the optional remote display unit.
A voltage of 120 VAC must be present at the input for the Bi-Flame system to operate. If an auxiliary input loses its voltage for more than one second while the interlocks and limits input is powered, a lockout condition will occur. If the Bi-Flame is equipped with a re­mote display unit, the following message will occur:
Aux. Input #1 Aux. Input #2 Aux. Input #3 Aux. Input #4
AUX.LIM. #1 FAIL AUX.LIM. #2 FAIL AUX.LIM. #3 FAIL AUX.LIM. #4 FAIL
LKOUT HHHH:MM:SS LKOUT HHHH:MM:SS LKOUT HHHH:MM:SS LKOUT HHHH:MM:SS
Note: Unused auxiliary inputs should be connected to 120 VAC.
History Log
The history log is only accessible through the remote display unit with remote reset, and when the Bi-Flame is in a “LOCKOUT” or “LIMITS OPEN” condition. The history log records the total num­ber of operating cycles, total recycles, cause of last recycle and t h e last lockout messages up to a maximum of 10.
With a remote display available and the Bi-Flame in one of the two conditions described above, the history log can be accessed as fol­lows:
1) P ress and hold the ENTER key on the remote display unit until the following message appears:
TOTAL OPERATING CYCLES = XXXXXX (where X is a
digit between 1 and 9). The record number will display as long as the ENTER key is
pressed. The scan button on the logic board also scrolls the his­tory log.
2) If there has been a recycle, release and press the ENTER key to see: RECYCLES TOTAL = XXXXXX then release and press the ENTER key to see:
LAST RECYCLE BY AIR=XXXXXX or LAST RECYCLE BY FLAME=XXXXXX
3) Release and press the ENTER key a second time. The record number of the lockout message will be displayed:
RECORD #X (where X is the number of the most recent lockout)
(continued on next page)
16
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 17
History Log (continued)
4) Release the ENTER key and the most recent lockout message will display for seven seconds.
5) If you wish to see the next lockout message, press and release the ENTER key before the seven second time duration ends of the most recent lockout message display. This will prompt the next lockout message. If desired, continue this procedure until the maximum of ten lockout messages has been displayed (re­member that the highest record number is the most recent lockout message).
6) Continued pressing and releasing of the ENTER k ey in less than seven seconds keeps the history log active and repeats the lock­out message list; waiting longer than seven seconds deactivates the history log mode and the next display is the last sequence message before the history log was activated. For example, if the message “LIMITS OPEN” was displayed when the history log was activated, then that message will appear again after seven seconds.
7) If you wish to erase all of the lockout messages from the his­tory log, press the RESET and ENTER keys simultaneously while the history log is active. Release the RESET key, but hold the ENTER key for another five seconds. Wait five seconds and press and release the RESET key.
Modulation Contacts
The modulation feature incorporates “drive high”, “drive low”, and “automatic” contacts into the purge sequence. This feature allows the Bi-Flame to sequence internal dry contacts which can be used by the customer requiring a high fire purge of the combustion chamber before ignition.
The high fire purge time is selectable by means of S2 DIP switches on the logic board (see “S2 DIP Switch Settings” on page 13)
With this option, the modulation terminals on J3 terminal strip will sequence as follows:
Sequence Step Internal Contact Connections High Fire Purge Terminal 1 (COMMON) to Terminal 3 (HI FIRE) Low Fire Start Terminal 1 (COMMON) to Terminal 4 (LOW FIRE) Automatic Terminal 1 (COMMON) to Terminal 2 (AUTO) Post Purge Terminal 1 (COMMON) to Terminal 4 (LOW FIRE) Power Off Terminal 1 (COMMON) to Terminal 2 (AUTO) Power On/Limits Off Terminal 1 (COMMON) to Terminal 4 (LOW FIRE) Alarm Terminal 1 (COMMON) to Terminal 4 (LOW FIRE)
The Automatic step occurs 20 seconds after the main output has energized (see Table 10.1 beginning on page 36) and allows the burner firing rate to be controlled by an automatic temperature controller.
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
17
Page 18
Valve Leak Sensing Device (VLSD) Interface
The Bi-Flame Valve Leak Sensing Device (VLSD or VDK) interface
provides a 120 VAC output which triggers the start of the test pe-
riod. An input is also provided which receives a 120 VAC signal
from the VLSD. If the signal is received within the selected test pe-
riod (40 or 110 seconds, see page 13), then the test has been suc-
cessfully completed. This option includes the required sequential
software to initiate the valve leak test on start-up and shutdown of
the burners.
When the limits close to the Bi-Flame, the 120 VAC output to the
VLSD is activated. If an optional remote display is connected, the fol-
lowing message will appear:
VALVE LEAKAGE UNDER TEST XX (where X is the remaining seconds of the
test).
If the VLSD does not activate the VLSD 120 VAC input within the
test period, an alarm lockout will occur, and the following message
will appear on the optional remote display:
VALVE LEAK FAIL LKOUT HHHH:MM:SS
If a valve leak occurs, the fan output on the Bi-Flame will be acti-
vated to purge the combustion chamber of gases.
Note: If the VLSD input is not used, then it should be connected to 120 VA C.
18
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 19
Remote Display Unit
The remote display with keypad allows remote reset and activation of the history log option. It is panel mountable and features a back­lit liquid crystal display in a 1/4 DIN housing. It connects to the Bi­Flame by a six or ten foot cable. The display incorporates the fol­lowing features:
1) P rovides status messages for the Bi-Flame sequence. (See Sec­tion 10)
2) Indicates lockout conditions when they occur, as well as the amount of time into the sequence when the lockout occurred and the amount of time elapsed from lockout.
3) P rovides continuous monitoring of each burner’s flame signal strength during main burner operation. (Pressing ENTER once will lock on a particular burner’s status; pressing ENTER a sec­ond time will resume scrolling).
4) Incorporates a remote reset key.
5) P rovides the interface required for the History Log.
6) Incorporates keys for pilot test mode.
L
OGIC MODULE ST A TUS
L
IGHTS
& P
USH-BUTT ONS
RS232 Communication Interfaces (RS485 optional)
Terminals 1, 5, and 6 on Bi-Flame terminal strip J7 provide a serial ASCII output communication interface for remotely monitoring the system sequence and status using a terminal or a modem; refer to Section 10 for the types of messages sent by the Bi-Flame.
The communications protocol is 8 bit, no parity , 1 stop bit and1200 baud. This feature is pr o vided standar d as a RS232 interface.The RS485 interface is optional.
Sending a carriage return (<CR> = ASCII Hex 0D) from the terminal causes the Bi-Flame to retransmit the last message. Sending a CTRL­E (<ENQ> = ASCII Hex 05) accesses the optional history log.
The logic module provides all the sequential logic, and safety start­up and shutdown circuitry. On the front of the module is the reset, scan and enter push-buttons, and status lights. This section de­scribes the their respective functions.
Limits
This LED illuminates when the operation limits are made. These limits are wired in series to terminal J1-1. This input becomes energized to begin the burner sequence. When in the test mode, this LED flashes (see “Pilot Test Mode” on page 15).
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
19
Page 20
Air
This LED illuminates when the air switch is closed and power is thereby applied to the air switch input. The Bi-Flame also checks this input for an air switch short (see “Combustion Air Flow Check Ter­minal” on page 14).
Purge
This LED illuminates whenever the combustion blower is energized, including the purge period and the main burner period of the se­quence. It blinks on and off while the purge is in process and remains constant when the purge process is complete.
Burner On
This LED illuminates when the main gas valve is energized, permitting gas flow to all the burners.
Fault
This LED illuminates when a system fault is detected (see “System Faults” on page 21).
Alarm
This LED illuminates when an alarm condition causes a system lock­out (see “System Lockout Conditions” on page 21).
Low Fire
This LED illuminates during the low fire period of the purge cycle.
High Fire
This LED illuminates during the high fire period of the purge cycle.
Scan
This push-button can be used to scroll the history log.
Enter
This push-button is used with the RESET button to enable the pilot test mode.
Reset
This push-button resets the control. It is also used with the ENTER button to enable the pilot test mode.
20
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 21
System Faults
A system fault (illuminated by the fault LED on the logic cards) pre­vents gas ignition but does not lock out the system. System fault con­ditions are as follows:
1) If a flame is detected out of sequence, which may be caused by: a) a faulty scanner b) electrical interference on the sensor leads c) a flame exists in the burner due to a gas leak or other condition.
2) Air flow switch closed before start-up.
System Lockout Conditions
A system lockout will occur (illuminated by the alarm LED on the logic card) for any of the following conditions:
1) Air failure–loss of combustion anytime during the operational
cycle.
2) Pilot flame fail–loss of flame during the trial for pilot ignition
period.
3) Main flame fail–loss of flame during the main burner trial for ig-
nition.
4) Main fuel valve–open after cycle shutdown or before start-up
with interlocks closed.
5) Unmatched burners–the S6 DIP switch is not set correctly (see
“S6 DIP Switch Settings” on page 13).
6) Relay fail–failure of Bi-Flame internal relays.
7) Low fire fail–low fire switch open for more than 15 minutes
prior to trial for ignition.
8) High fire fail–high fire switch has not closed within 15 minutes
of high fire purge.
9) Flame fail–loss of flame after main flame has been established.
10) Auxiliary input fail–loss of input voltage to any of the four “Aux” terminals after the limit input is made.
11) Valve leak fail–valve leak sensing device has detected a leak.
12) Wiring error which puts external voltage on any of the output terminals.
13) W elded internal contacts or other malfunctions in the Bi-Flame.
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
21
Page 22
System Installation
6
INTRODUCTION
INTERLOCKS AND
LIMIT
SWITCH INPUT
In this section, the necessary procedures are detailed to integrate a Bi-Flame into a burner system; Figure 6.1 (page 25) illustrates the various terminal strips mentioned.
Note: Shut off the power supply before any module is removed or replaced from the unit, including the remote display.
Caution: Installation and maintenance must conform with the National Electrical Code and all other national and local codes and authori­ties having jurisdiction.
Interlocks are generally pressure or temperature switches which, when activated, start the burner. Limit switches are generally pressure, temperature and other switches which, when activated, stop the burner. The interlocks and limit switches are wired in series. A break in this circuit will shut the burner down, but will not produce an alarm. This input is considered the normal operation control input to the Bi-Flame system.
22
COMBUSTION AIR
SWITCH
INPUT
This input is for monitoring the combustion air switch separately from other interlocks and limits. When wired to this input, the air switch will be proven open before start-up and after shutdown. It will also be proven closed 10 seconds after the combustion air blower is energized.
If the air switch opens during the main firing cycle, the system will either lockout or recycle, depending on the DIP switch selection.
If this terminal is not used, place a jumper between the combustion blower output (terminal 3 on terminal strip J2) and the air switch input (terminal 2 on terminal strip J1). This jumper must not be used in place of a required air flow switch interlock.
If the combustion air blower is controlled outside of the Bi-Flame system, then the air switch must be wired between the combustion blower output and the air switch input. Connecting the air switch in this manner will prevent the open contact (air short) check on the switch.
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 23
IGNITION WIRING
Route ignition wiring a sufficient distance from all sensors and other low voltage wiring to avoid electrical interference, which may cause erratic operation of the Bi-Flame system.
Caution: Do not connect multiple ignition coils in excess of output relay contact rating
COMMUNICATION
WIRING
POWER SUPPLY
LOW FIRE POSITION
INPUT
MAIN VALVE
PROOF
-OF-CLOSURE
Route communication wiring, using shielded cable, a sufficient distance from ignition and other high voltage wiring to avoid electrical interference.
All input power must be single phase 120 VAC, 60/50 Hz selectable, see page 13. All circuits must have a common 15 amp fuse and disconnect. The neutral must be grounded. Do not use solid-state triac output devices in any of the input circuits. 120 VAC wiring must be at least 90°C 16 AWG minimum and satisfy all applicable codes.
It is possible to wire the system for checking low fire start position prior to pilot ignition. To use this feature, the low fire start switch must be connected to the low fire start input (terminal 4 on terminal strip J1). If this feature is not used, a jumper must be placed between terminals 1 and 4 on terminal strip J1.
The system can be wired to check for the proof of valve closure (POVC) switch on the main gas valve prior to start-up and after the end of the burner cycle.
To use this feature the POVC switch must be connected to the POVC switch input (terminal 3 on terminal strip J1). If this feature is not used, a jumper must be placed between terminals 2 on terminal strip J2 and 3 on terminal strip J1.
HIGH FIRE POSITION
INPUT
AUXILIARY INPUTS
The system can be wired to check for high fire position during the high fire purge portion of the sequence. To use this feature, the high fire position switch must be connected to the high fire input (terminal 5 on terminal strip J1). If this feature is not used, a jumper must be placed between terminals 1 and 5 on terminal strip J1.
The system can be wired to check auxiliary status conditions with the four auxiliary inputs. To use this feature, the auxiliary input switches must be wired to the auxiliary inputs (terminals 7,8,9 and 10 on terminal strip J1). If this feature is not used, these inputs must be connected to 120 VAC.
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
23
Page 24
REMOTE RESET
This feature permits remote mounting of a switch to reset the Bi­Flame. To use this feature, a normally closed remote reset switch must be wired between terminals 1 and 4 on terminal strip J7. When it is depressed or actuated, the connection between the terminals is momentarily interrupted and resets the Bi-Flame. This is a low voltage signal circuit that must be routed separately from other control voltage wiring. Use two-conductor shielded cable with the shield connected on one end only to terminal 1 of J7.
Note: If reset is required from both the dispaly and the J7 terminals, use a normally open switch.
REMOTE DISPLAY
When installed, the remote display must be grounded. Panel mounting is through a 1/4 DIN cutout (see page 9). Use either the six or ten foot cable to connect it to the motherboard.
Warning: Power must be off when inserting or removing the cable.
24
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 25
Figure 6.1
Terminal Strips Identification & Location
Main Chassis
J1
J2
J3
J4
J7
J6
Remote
Display
Connection
J5
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
25
Page 26
Figure 6.2
Wiring Diagram & Connection s–Main Chassis
VDK/VLSD
J4
Terminals
Flame Rod
1 2 3 4
On/Off
Interlocks & Limits
Leak Detect Aux. Input #1 Aux. Input #2 Aux. Input #3 Aux. Input #4
2
Yellow
Blue
Shield
Air Flow
POVC Low Fire High Fire
5600-90A
or 5600-91
U.V. Scanner
15 A. Fuse
Terminals
1
1
1
1
J1
1 2 3 4 5 6 7 8 9
10
Burner #1
J3
Terminals
1 2 3 4
GND (Return)
120 VAC
Common
Auto High Fire Low Fire
Terminals
120 VAC
Neutral
Signal (UV)
Neutral
Customer Supplied (if used)
ACT004
P1-1
P1-2
P1-4
Temperature
Controller
4 to 20 mA
J7
Rx
6 5
RS 232
Tx
4 3 2 1
Remote
Reset
Pushbutton
(if required)
B
A
C
D
5602-91
U.V.
Self-Check
Scanner
­+
Terminals
Terminals
J5
1 2
Flame Rod
3 4
J2
1 2 3 4 5 6 7 8
2
Blue
Yellow
Shield
Neutral
Fan Motor
Main Pilot
Ignition
Leak Detect
Alarm
MS
Pilot Gas Valve
VDK/VLSD
5600-90A
or 5600-91
U.V. Scanner
Main Gas Valve
Block Valve
Ignition Coil
Ignition Coil
Burner #2
J1 (Input) Terminals
1 – Limits Input 2 – Air Switch Input 3 – POVC Switch Input 4 – Low Fire Switch Input 5 – High Fire Switch Input 6 – VDK/VLDS Input 7 – Aux. #1 8 – Aux. #2 9 – Aux. #3 10 – Aux. #4
1 1 1 1
J2 (Output) Terminals
1 – Neutral 2 – 120 VAC 3 – Fan 4 – Main Gas Valve 5 – Pilot Gas Valve 6 – Ignition Transformer 7 – VDK/VLSD 8 – Alarm
1
When not used, must be tied into 120 VAC.
2
Using both sensors isn’t mandatory; you may use a flame rod, or a UV scanner, or both.
Auxiliary Inputs
J3 (Modulation) Terminals
1 – Common 2 – Auto 3 – Hi Fire 4 – Low Fire
Modulation Motor Connections for High Fire & Low Fire Start
J4 (Sensors/Burners 1 & 3) Terminals
1 – Flame Rod 2 – Ground (Yellow) 3 – U.V. (Blue)
Burner #1
J5 (Sensors/Burners 2 & 4) Terminals
1 – U.V. (Blue) 2 – Ground (Yellow) 3 – Flame Rod 4 – Shield Connection
2
4 – Shield Connection
J7 (Interface) Terminals
Bi-Flame Power Inputs
Outputs
6 – RS 232/RS 485 Interface 5 – RS 232/RS 485 Interface 4 – Reset 3 – Scan 2 – Enter 1 – Ground
2
Burner #2
26
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 27
Sensor Installation
7
INTRODUCTION
SENSOR WIRING
This section describes the proper wiring, installation and sighting con­siderations for all sensors that can be used with a Bi-Flame.
Warning Incorrect sensor installation may cause the sensor to generate a false flame signal, causing unburned fuel to collect in the combustion chamber. The re­sult can be explosions, injuries and property dam­age. Be cer tain that the flame sensor detects only pilot and main flames, not glowing refractory, burner or ignition parts.
Route sensor wiring a sufficient distance from ignition and other high voltage or high current wiring to avoid electrical interference. Interference from ground currents, nearby conductors, radio-fre­quency emitters (wireless divices), and inv erter drives can induce false flame signals. Shielded cables can help reduce interference with the shield connected to ground at the control end only. The wire type and its capacitance (picofarads or microfarads) to ground may cause low signal problems, so a gr ounded shield may decr ease the signal due to the cable’s internal capacitance. Multiple U.V. tube-type sensor leads run together without shielding may interfere or “cross talk”, so the shield or flexible armor must be grounded to prevent this situa­tion. For flame rod sensor runs approximately 100 feet (30 meters) or greater, use Eclipse part number 21741 coax cable. To achieve the maximum wiring distance, the shield should not be grounded (keep in mind that an ungrounded shield provides less protection against electrical interference).
Do not ground the shield to terminal GND.
Note: Unshielded sensor wiring must not be run in common with other wires; it must be run in separate conduit. Multiple unshielded flame sensor wiring must not be run together in a common conduit or wireway. Use #14 to #18 AWG wire suitable for 90°C (194°F) and 600 volt insulation, or better grade if required by the application. Multiple shielded cables can be run in a common conduit.
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
27
Page 28
FLAME RODS
Flame Rod
WRONG
Rod Detects
Weak Pilot
PILOT
Flame Rod Position
CORRECT
Rod Detects
Only Strong
Pilot Flame
Flame rods should be used only on gas burners. They accumulate soot on oil burners, causing nuisance shutdowns and unsafe operat­ing conditions.
See the burner manufacturer’s literature for flame rod mounting location. When installing flame rods, please consider the following:
1) Keep the flame rod as short as possible and at least 13 mm (1/2") away from any refractory .
2) Position the rod into the side of both the pilot and main flames, preferably at a descending angle to minimize drooping of the flame rod against burner parts. Flame rod position must ad­equately detect the pilot flame at all burner draft conditions. Ex­tend the rod 13 mm (1/2") into nonluminous flames, such as blue flames from burning an air/gas mixture. For partially luminous flames, such as atmospheric air/gas mixtures, place the rod at the edge of the flame.
3) Provide a burner/flame grounding area that is at least four times greater than the flame rod area contacting the flame. The flame rod/burner ground ratio and position of the rod in the flame may need adjustment to yield maximum flame signal strength.
4) Ignition interference from the spark plug may increase or decrease the flame signal strength. Reversing the ignition transformer pri­mary leads may reverse this effect. Reducing the spark gap or add­ing grounding area between the flame rod and spark plug may eliminate the interference.
SCANNERS
U.V . Scanner
(Model 5600-91)
90° U.V .
Scanner
(Model 5600-90A)
Self-Check
U.V . Scanner
(Model 5602-91)
Use only Eclipse model 5600-90A, 5600-91, 5602-91or 5600-91N4 scanners. Consult the burner manufacturer’s instructions for mounting location. When installing scanners, please consider the following:
1) Position the scanner within 457 mm (18") of the flame.
2) Bushing threads are 1/2 inch F.N.P.T. for scanner models 5600-90A, 5600-91 and 5600-91N4; model 5602-91 has 1 inch F.N.P.T. bushing threads.
3) The ambient temperature limits of each scanner varies, (see speci­fications). For higher temperatures, use Eclipse heat insulator 49099 or the Heat Block Seal, Model 23HBS, that has a purge fit­ting.
4) An optional magnifying lens (Eclipse #49600-98) may also be used to increase the flame signal strength in difficult sighting situations.
28
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 29
SCANNER SIGHTING
CONDITIONS
MAIN
BURNER
Scanner
Sight
Line
SCANNER
U.V. Scanner Sighting
1/3 of
Flame Length
Aim scanners at the third of the flame closest to the burner nozzle, as shown at left. This is especially true for oil flames which typically have less UV radiation in the outer flame. The scanner should view the in­tersection of the pilot and main flames. When sighting scanners, please consider the following:
1) Sight the scanner away from the ignition spark. Sighting the spark or its reflections from burner internals can be misinterpreted as a flame signal.
2) Do not allow the scanner to detect a pilot flame that is too small to ignite the main burner.
3) Perform a minimum pilot test when installing or adjusting any pilot or main burner system; see “Minim um Pilot Test” on page 30.
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
29
Page 30
Test Procedures
8
INTRODUCTION
FLAME SIGNAL
STRENGTH
MINIMUM PILOT TEST
This section describes the test procedures that must be performed after installation to insure that the Bi-Flame is operating properly; these procedures are mandatory.
Insert the positive probe of a 0-15 VDC, one megohm/volt meter into the test point on the front cover, as sho wn in the photo at left. Con­nect the negative probe to ground. A good flame signal strength will read between 6 and 11 VDC; anything below 4 VDC is inadequate.
Run the following test procedures to ensure that the sensor will not detect a pilot flame too small to reliably light the main flame:
1) Manually shut off the fuel supply to the burner, but not to the pi­lot.
2) Start the system normally.
3) To enter the pilot test mode, press the RESET and ENTER but­tons simultaneously. Then release the RESET button but keep the ENTER button depressed for another 10 seconds. The Limits LED will blink, signalling that the system is in the pilot test mode.
4) The control will hold the operating sequence at the pilot flame step. Measure signal strength as described above.
30
Voltmeter hook-up to the Bi-Flame
5) Reduce pilot fuel until the flame relay drops out. Increase pilot fuel until the flame signal is greater than 4 VDC, and flame relay just manages to pull in. This is the minimum pilot. If you don’t think this flame will be able to safely light the main burner, re­align the sensor so that it requires a larger pilot flame and re­peat steps 2 through 5.
6) Push the RESET button to exit the test mode and begin the normal start-up sequence again.
7) When the sequence reaches the main flame trial for ignition, smoothly restore the fuel supply to the burner. If the main burner does not light within five seconds, immediately shut off the burner supply to shut down the system. Realign the sensor so that it requires a larger pilot flame. Repeat steps 1 through 6 until the main burner lights off smoothly and reliably.
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 31
PILOT FLAME FAILURE
TEST
1) Manually shut off the fuel supply to one individual pilot and main burner, or all burners if the system has a single fuel supply.
2) Place system in pilot test mode (please refer to page 15).
3) Start the system normally. The controller should lock out*; if it doesn’t, then the controller is detecting a false flame signal (see Section 7). Find the problem and correct it before resuming normal operation.
4) Repeat steps 1 through 4 until all burners have been tested.
MAIN FLAME FAIULRE
TEST
(For Interrupted Pilot Systems)
SPARK SIGHTING TEST
1) Manually shut off the fuel supply to the main burner, or all burn­ers if the system has a single fuel supply, but not to the pilot.
2) Start the system normally. This should ignite the pilot and lock out* after pilot interruption. If the system does not lock out, the controller is detecting a false flame signal (see Section 7). Find the problem and correct it before resuming normal operation.
3) Repeat steps 1 through 3 until all burners have been tested.
1) Ma nually shut off the fuel supply to the pilot and main burner.
2) Start the system normally.
3) Measure the flame signal as described in “Flame Signal Strength” in this section.
4) If a flame signal greater than 4 VDC is measured for more than three seconds during the trial for ignition, the sensor is picking up a signal from the spark plug or the ignition current is inter­fering with the sensor wiring. If this is an abnormal condition, correct before resuming normal operation.
LIMITS AND INTERLOCK
TESTS
Periodically check all interlock and limit switches by manually trip­ping them during burner operation to make sure they cause the system to shut down.
Warning Never operate a system that is improperly adjusted or has faulty interlocks or limit switches. Always replace faulty equipment with new equipment before resum­ing operation. Operating a system with defective safety equipment can cause explosions, injuries, and property damage .
* The burner at which a flame fails will be identified by the red “Flame Fail-
ure” LED on the cover.
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
31
Page 32
Maintenance and Troubleshooting
INTRODUCTION This section is divided into two parts:
• The first par t describes the maintenance procedures.
• The second part helps you to identify problems that may occur, and gives advice on how to solve these problems.
9
MAINTENANCE
Preventative maintenance is the key to a reliable, safe and efficient system. The core of any preventive maintenance program is a list of periodic tasks.
In the paragraphs that follow are suggestions for a monthly list and a yearly list.
Note: The monthly list and the yearly list are an average interval. If your environment is dirty, then the intervals may be shorter.
Caution: Turn off power before disconnecting or installing sensors, con­trols or modules.
Monthly Checklist
1. Inspect flame-sensing devices for good condition and cleanliness. Keep the glass lens of scanners clean with a soft, damp cloth, since small amounts of dust will measurably reduce the flame signal strength. Wash the flame rod electrode and insulator with soap and water, then rinse and dry thoroughly.
32
2. Test all the alarm systems for proper signals.
3. Check ignition spark electrodes and check proper gap.
4. Test interlock sequence of all safety equipment as described in
Test Procedures: man ually make each interlock fail, noting what related equipment closes or stops as specified by the manufac­turer.
Test flame safeguard by manually shutting off gas to the burner.
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 33
Yearly Checklist
1. Test (leak test) safety shut-off valves for tightness of closure.
2. Test pressure switch settings by checking switch movements against pressure
setting and comparing with actual impulse pressure.
3. Visually check ignition cable and connectors.
4. Make sure that the following components are not damaged or distorted:
• the burner nozzle
• the spark plugs
• the flame sensors
• the flame tube or combustion block of the burner
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
33
Page 34
TROUBLESHOOTING
PROBLEM POSSIBLE CAUSE SOLUTION
Cannot initiate start sequence
• Main valve is not closed.
• Air pressure switch has not made contact.
• High gas pressure switch has tripped.
• Low gas pressure switch has tripped.
• Malfunction of flame safeguard system such as a shorted-out flame sensor or electrical noise in the sensor line.
• Purge cycle not completed.
Check proof-of-valve-closur e switch. Check air pressure switch adjustment.
Check air filter . Check blower r otation. Check outlet pressure from blower.
Check incoming gas pressure; adjust gas pressure if necessary .
Check pressure switch setting and operation.
Check incoming gas pressure; adjust gas pressure if necessary .
Check pressure switch setting and operation.
Have qualified electrician in vestigate and rectify.
Check flame safeguard system, or purge timer .
Scrambled messages on remote display.
“UNSAFE AIR SHOR T” message appears on displa y.
Burner flame fails but no flame failure indication occurs.
• Main power is off.
• No power to control unit.
• Improper grounding in system.
• Improperly adjusted air switch.
• Air switch either shorted or wir ed wrong.
• A faulty scanner.
• Improperly connected sensor wires.
• Electrical interference from other current carrying wires.
Make sure pow er is on to contr ol system.
Call qualified electrician to investigate.
Check grounding in system.
Check air switch settings. Check wiring to air switch.
Check scanner as explained in checklists in “Maintenance” portion of this Section.
Check wiring diagram on page 26 as well as appropriate sensor information in Section 7.
Check Note information on page 27 regarding sensor wiring.
34
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 35
Remote Displa y Messages
INTRODUCTION This section covers how the optional remote display is used with
the Bi-Flame. The remote display provides LCD messages which monitor the status of the Bi-Flame’s functions as well as any lock­out conditions. This section is divided into two parts or tables:
• The first table describes the start-up and shutdown monitoring se­quences of the Bi-Flame and how the progress (or halt) of the se­quence can be monitored by the messages on the remote display.
• The second table alphabetically lists and explains the diagnostic messages which can appear on the remote display.
Note: Some of the messages which may appear with some of the options are not shown; refer to Section 5, Function Summary, for details.
10
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
35
Page 36
VERSION VX.X
NORMAL MESSAGE
CHECKSUM = XXXX
ERROR MESSAGE #1
UNSAFE FLAME ON
Table 10.1
Bi-Flame Operating Sequence
PO WER ON
Was internal saf e start check successful?
YES NO
EXTERNAL INTERLOCK CHECKS
Is flame signal present?
YES NO
Various lockout messages
Is proof of closure cir cuit closed?
If signal is eliminated within 30 seconds, sequence continues. If not, then . . .
ERROR MESSAGE #2 – 30 SECONDS AFTER #1
UNSAFE FLAME ON LK OUT XXXX:XX:XX
Fan and Alarm energized.
NORMAL MESSAGE
VALVE LEAKAGE UNDER TEST XX
Countdown of XX based on DIP switch
Is voltage present at VDK input before time out?
ERROR MESSAGE #1
UNSAFE AIR SHOR T
If switch is not opened within 30 seconds and the limit input is
present....
ERROR MESSAGE #2 – 30 SECONDS AFTER #1
UNSAFE AIR SHOR T LK OUT XXXX:XX:XX
Fan and Alarm energized.
Is voltage present at AUX inputs ?
YES
AUX. LIM. # X F AIL LKOUT XXXX:XX:XX
#X is 1, 2, 3, or 4 to show absent input
Is voltage present at air flow switch?
YES NO
Is voltage present at interlock switch?
NO
LIMITS OPEN TIME = XXXX:XX:XX
ERROR MESSAGE
YES NO
ERROR MESSAGE
MAIN VALVE FAIL LK OUT XXXX:XX:XX
Fan and Alarm energized.
YES NO
ERROR MESSAGE
Holds until answer is yes.
36
YES
NORMAL MESSAGE
SAFE START OK VX.X CS=XXXX
NORMAL MESSAGE
FAN ENERGIZED
Fan output is energized; modu­lator is sent to low fire.
BURNER START-UP
(see next page)
NO
V ALVE LEAK FAIL
ERROR MESSAGE
LK OUT XXXX:XX:XX
Fan and alarm energized.
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 37
Table 10.1
Bi-Flame Operating Sequence (continued)
BURNER START-UP
Is voltage pr esent at air flow switch
within ten seconds?
AIR PROVEN
NORMAL MESSAGE
NORMAL MESSAGE
WAIT FOR HI. FIRE SWITCH XX:XX
Modulator sent to high fire.
NORMAL MESSAGE
PURGE A T HIGH FIRE XX
Countdown of “XX” seconds as set by DIP switch.
YES NO
AIR NOT PR OVEN
ERROR MESSAGE
LK OUT XXXX:XX:XX
Is voltage present
at high fire input?
YES NO
ERROR MESSAGE
HIGH FIRE FAIL LK OUT XXXX:XX:XX
WAIT FOR LO.FIRE
NORMAL MESSAGE
SWITCH XX:XX
Modulator sent to low fire.
NORMAL MESSAGE
PILOT TRIAL FOR IGNITION XX
Spark energized until pilot flame proven; pilot valve energized for countdown of “XX” seconds (“XX” equals selected trial for ignition).
NORMAL MESSAGE
PILOT ON XX
After “XX” equals zero (0)...
NORMAL MESSAGE
PILOT ON IGNITION OFF
Delay 5 seconds.
Is voltage present
at low fire input?
YES NO
ERROR MESSAGE
LOW FIRE FAIL LK OUT XXXX:XX:XX
Is pilot flame signal present?
YES NO
PILOT # (0X) FAILED
ERROR MESSAGE
LK OUT XXXX:XX:XX
X = burner number.
NORMAL MESSAGE
MAIN FLAME ON
Is flame signal present?
YES NO
Is flame signal present?
(see next page)
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
MAIN # (0X) FAILED
ERROR MESSAGE
LK OUT XXXX:XX:XX
X = burner number.
37
Page 38
Table 10.1
Bi-Flame Operating Sequence (continued)
BURNER START-UP (continued)
Is flame signal present ?
YES
MAIN FLAME ON
NORMAL MESSAGE
NO
ERROR MESSAGE
MAIN # (O X) FAILED
X = burner number.
MAIN FLAME ON
NORMAL MESSAGE
PILOT OFF
Pilot will shut off 10 seconds after main flame is energized.
IF Interrupted Pilot is selected
NORMAL MESSAGE
AUTOMATIC MODULATION
Modulator sent to automatic 20 seconds after main valve is energized.
NORMAL MESSAGE
FLAME #(OX) XX.XV TIME = XXXX:XX:XX
Flame signal = XX.X Volts DC; (X) = Number of burner being monitored; the Bi-Flame will scroll through each burner con­tinuously during the burner-on cycle.
38
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 39
Table 10.1
Bi-Flame Operating Sequence (continued)
Continued operation.
BURNER SHUTDOWN
Shutdown is started by opening
the operating interlock circuit.
Is voltage pr esent at interlocks?
YES NO
Is proof of closure cir cuit closed?
YES NO
NORMAL MESSAGE
VALVE LEAKAGE UNDER TEST XX
Countdown of XX based on DIP switch
POST PURGE
NORMAL MESSAGE
XX
Fuel valves de-energized; fan energized for 15 seconds.
ERROR MESSAGE
MAIN VALVE FAIL LK OUT XXXX:XX:XX
Fan and alarm energized.
ERROR MESSAGE #1
UNSAFE AIR SHOR T
If switch is opened within 30 seconds, sequence continues. If not, then . . .
ERROR MESSAGE #2 – 30 SECONDS AFTER #1
UNSAFE AIR SHOR T LK OUT XXXX:XX:XX
Alarm energized.
Is voltage present at VDK input before time out?
YES
NO
V ALVE LEAK FAIL LK OUT XXXX:XX:XX
Is voltage pr esent at air flow switch?
YES NO
UNSAFE FLAME ON
Fan is energized. If signal is elimi­nated within 30 seconds, se­quence continues. If not, then . .
UNSAFE FLAME ON LK OUT XXXX:XX:XX
ERROR MESSAGE #1
ERROR MESSAGE #2 – 30 SECONDS AFTER #1
Fan and Alarm energized.
ERROR MESSAGE
Fan and alarm energized.
Is flame signal present?
YES NO
NORMAL MESSAGE
LIMITS OPEN TIME = XXXX:XX:XX
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
39
Page 40
Table 10.2
MESSAGE TYPE EXPLANATION
Remote Display Diagnostic Messages (Listed Alphabetically)
AIR FAILURE LKOUT XXXX:XX:XX
AIR FAILURE RECYCLING
AIR NOT PROVEN LKOUT XXXX:XX:XX
AIR PROVEN
AUTOMATIC MODULATION
AUX.LIM.#1 FAIL LKOUT XXXX:XX:XX
AUX.LIM.#2 FAIL LKOUT XXXX:XX:XX
AUX.LIM.#3 FAIL LKOUT XXXX:XX:XX
AUX.LIM.# 4 FAIL LKOUT XXXX:XX:XX
FAN ENERGIZED
Lockout Combustion air flow limit switch (strip J1, terminal 2) opened for
more than two seconds once initially proven.
Status Combustion air flow limit switch (strip J1, terminal 2) opened;
control will recycle once if “recycle” DIP switch has been se­lected.
Lockout Combustion air flow limit switch (strip J1, terminal 2) did not
make within ten seconds of fan being energized.
Status Combustion air flow limit switch (strip J1, terminal 2) closed
within ten seconds of fan being energized.
Status Modulating motor is sent to automatic operation. Terminal 1 is
connected to terminal 2 on terminal strip J3.
Lockout Auxiliary input #1 has lost its voltage during system operation,
causing a lockout at the indicated time.
Lockout Auxiliary input #2 has lost its voltage during system operation,
causing a lockout at the indicated time.
Lockout Auxiliary input #3 has lost its voltage during system operation,
causing a lockout at the indicated time.
Lockout Auxiliary input #4 has lost its voltage during system operation,
causing a lockout at the indicated time.
Status Blower motor (strip J2, terminal 3) is energized at the start of pre-purge.
FLAME # ( ) FAIL RECYCLING
FLAME # (X) FAILED LKOUT XXXX:XX:XX
FLAME # (Y) XX.XV TIME=XXXX:XX:XX
HI FIRE FAIL
INTERNAL FAULT
LIMITS OPEN TIME=XXXX:XX:XX
LOW FIRE FAIL LKOUT XXXX:XX:XX
Status Main flame lost during automatic modulation; control will recycle
once if “recycle” has been selected.
Lockout Main flame lost during operation in the automatic modulation
mode. Burner number (X) given of failed unit.
Status Main flame of burner number (Y) is proven in the automatic modula-
tion mode; flame strength is XX.XV (volts DC). Elapsed time is shown in hours:minutes:seconds.
Lockout High damper or high purge rate switch did not make and hold for
high pre-purgee.
Lockout Internal control failure; replace controller.
Status The controller has completed its internal checks and is standing by
for the interlocks (strip J1, terminal 1) to close.
Lockout Low fire switch (strip J1, terminal 4) is open just prior to pilot trial
for ignition.
40
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 41
Table 10.2
MESSAGE TYPE EXPLANATION
Remote Display Diagnostic Messages (continued)
MAIN # ( ) FAILED
MAIN FLAME ON
MAIN FLAME ON PILOT OFF
MAIN VALVE FAIL LKOUT XXXX:XX:XX
PILOT FLAME FAIL LKOUT XXXX:XX:XX
PILOT ON
XX
PILOT TRIAL FOR IGNITION XX
PLT/MVL ENERGIZ. XX:XX:XX LOCKOUT
POST PURGE
XX
PROGM SWITCH ERR LKOUT XXXX:XX:XX
Lockout Main flame was not established during the main burner trial for ignition.
Lockout Main valve has been energized and main flame proven during trial
for ignition.
Status Pilot valve (strip J2, terminal 5) is de-energized and main flame is on.
Lockout Main valve proof-of-closure is open before startup or after burner
shutdown.
Lockout Pilot flame was not established during the pilot trial for ignition.
Status Pilot flame is proven; transformer is de-energized; remaining
countdown for pilot trial for ignition is “XX”.
Status Pilot valve and ignition transformer are energized; countdown for
pilot trial for ignition begins at “XX”.
Lockout An external source of voltage is present on the ignition, pilot or
main output terminals.
Status 15 second post purge is started on burner shutdown; “XX” shows
countdown.
Lockout DIP switch improperly set or changed during cycle.
PURGE AT HIGH FIRE XX
RECORD #X
RELAY FAIL LKOUT XXXX:XX:XX
SAFE START OK UNSAFE AIR SHORT
UNSAFE AIR SHORT LKOUT XXXX:XX:XX
Status Modulating motor is sent to high fire; “XX” shows purge countdown.
Status Part of the optional history log which records the total number of
operating cycles and the last lockout messages up to a maximum of 10.
Lockout Internal relay(s) fail initial check. Check ratings. If lockout still oc-
curs after overload is eliminated, replace control. Status Control has completed internal safe-start check. Status Combustion air switch is closed before start-up or after shut-
down; control holds start-up until switch re-opens; if interlocks
close before switch opens, alarm will energize in 30 seconds. Lockout Same conditions as above, except the interlocks closed for 30 sec-
onds before the switch re-opened, causing a lockout and the alarm.
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
41
Page 42
Table 10.2
Remote Display Diagnostic Messages (continued)
MESSAGE TYPE EXPLANATION
UNSAFE FLAME ON
UNSAFE FLAME ON LKOUT XXXX:XX:XX
UNSAFE–FLM–PURGE
UNSAFE–FLM–PURGE LKOUT XXXX:XX:XX
VALVE LEAKAGE UNDER TEST XX
VALVE LEAK FAIL LKOUT XXXX:XX:XX
WATCHDOG FAIL LKOUT XXXX:XX:XX
XXXXXXX XXXXXTESTXX
Hold Flame signal—actual, induced, or faulty scanner—is detected be-
fore start-up or after shutdown. The fan is energized. If the cause is corrected within 30 seconds, as in afterburn, the control will turn off the fan and continue the sequence.
Lockout Same conditions as above, except the cause has not been corrected
within 30 seconds, resulting in a lockout and alarm.
Hold Flame signal—actual, induced, or faulty scanner—is detected dur-
ing the selected purge time period. The fan is energized. If the cause is corrected within 30 seconds, as in afterburn, the control will turn off the fan and continue the sequence.
Lockout Same conditions as above, except the cause has not been corrected
within 30 seconds, resulting in a lockout and alarm.
Status Indicates that the optional valve leak sensing device has been acti-
vated and the test period “XX” has begun.
Lockout The test period for valve leak sensing has exceeded XX seconds
and failed; check the gas shut-off valves.
Lockout Internal control failure; replace controller.
Status In combination with other messages, shows the control is in the
minimum pilot test mode.
42
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 43
Appendix
CONVERSION
F ACTORS
Metric to English.
FROM TO MULTIPLY BY
cubic meter (m3) cubic foot (ft3) 35.31
cubic meter/hour (m
degrees Celsius (°C) degrees Fahrenheit (°F) (°C x 1.8) + 32
kilogram (kg) pound (lb) 2.205
kilowatt (kW) Btu/hr 3414
meter (m) foot (ft) 3.28 millibar (mbar) inches water column ("wc) 0.401 millibar (mbar) pounds/sq in (psi) 14.5 x 10
millimeter (mm) inch (in) 3.94 x 10
Metric to Metric.
3
/h) cubic foot/hour (cfh) 35.31
FROM TO MULTIPLY BY
kiloPascals (kPa) millibar (mbar) 10
meter (m) millimeter (mm) 1000
millibar (mbar) kiloPascals (kPa) 0.1
millimeter (mm) meter (m) 0.001
-3
-2
English to Metric.
FROM TO MULTIPLY BY
Btu/hr kilowatt (kW) 0.293 x 10
cubic foot (ft3) cubic meter (m3) 2.832 x 10
cubic foot/hour (cfh) cubic meter/hour (m3/h) 2.832 x 10
degrees Fahrenheit (°F) degrees Celsius (°C) (°F – 32) ÷ 1.8
foot (ft) meter (m) 0.3048
inches (in) millimeter (mm) 25.4
inches water column ("wc) millibar (mbar) 2.49
pound (lb) kilogram (kg) 0.454
pounds/sq in (psi) millibar (mbar) 68.95
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
-3
-2
-2
43
Page 44
ILLUSTRATED PARTS LIST
Pos.
No.
Downtimes due to a failure can be kept to a minimum by stocking recommended spares.
Qty. Description
1 2 3 4 5 6 6 7
1
Mother Board (6500M)
1
Relay module circuit board
1
Logic module circuit board
1
Power module circuit board
1
Sensor circuit board
1
183 cm (6ft) cable for remote display
1
305 cm (10ft) cable for remote display
1
Remote display with keypad
1
2 3 4
5
Eclipse
Part Number
20315 22494 22495 22496 20314 15426
15426-1
15422
View shown with cover removed.
6 7
44
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
Page 45
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
45
Page 46
826 Instruction Manual 05/03
Loading...