PHASE
SEQUENCE INDICATOR
INSTRUCTION MANUAL
99 Wa
Phone 781-665-1400 Toll Free 1-800-517-8431
TestEquipmentDepot.com
shington Street Melrose, MA 02176

R
RED
LEAD
S T
YELLOW
or WHITE
LEAD
BLUE
or BLACK
LEAD
P1 P2 P3
1
PUSH ON
CHECK
R
E
C
R
O
C
T
22
CAT. 600V
PHASE ROTATION
INDICATOR
(1) Pushbutton Switch
(2) Phase Rotation Indication Window
(3) Open Phase Check Lamps
(4) Rotating Disc
3
2
4

1. INTRODUCTION
NOTE
This meter has been designed and tested according to
IEC Publication 348, Safety Requirements for
Electronic Measuring Apparatus, IEC 1010 (EN 61010)
and other safety standards. Follow all warnings to
ensure safe operation.
WARNING
READ "SAFETY NOTES" (NEXT PAGE)
BEFORE USING THE METER.
2
-1-

2. SAFETY NOTES
l Read the following safety information carefully before
attempting to operate or service the meter.
l Use the meter only as specified in this manual
otherwise the protection provided by the meter may be
impaired.
l Rated environmental conditions
(1) Indoor use.
(2) Installation Category .
(3) Pollution Degree 2.
(4) Altitude up to 2000 Meter.
(5) Relative Humidity 80% Max.
(6) Ambient Temperature 0~40°C.
l Observe the International Electrical Symbols Iisted
below.
Meter is protected throughout by double
insulation or reinforced insulation.
Warning ! Risk of electric shock.
Caution ! Refer to this manual before using
the meter.
Alternating current.
~
-2-

3. FEATURES
l TWO FUNCTIONS IN ONE UNIT
It is designed to check phase sequence. Lamps
provided on the unit will tell you whether phase is open
or which phase is open at a glance.
l LARGE SIZE ALLIGATOR CLIPS
Can easily hold terminals of switch boards.
l HIGHLY RELIABLE
Can check a wide range of 3-phase power source from
90V to 600V.
Sealed against dust, the unit ensures highly dependable
and trouble-free performance.
l FUNCTIONAL DESIGN
Small, lightweight and portable. Designed for maximum
ease of operation.
l SAFETY DESIGN
No exposed metal parts. Safety features are
incorporated thrughout, including the pushbutton switch
designed to minimize damage due to negligence.
-3-

4. MEASURING METHODS
(1)Connect color coded alligator clips to the terminals of a
3-phase power source where a rotating electrical
machine, such as a motor will be connected.
Connecting order may be optional.
(2)Press the pushbutton switch located on top of the unit.
Keep this button pressed during phase sequence or
open phase check. When the pushbutton switch is
released, it immediately goes off.
(3)Make sure that all of the three lamps for open phase
check are on. If so, there is no open phase. When any
of the three lamps is not on, there is open phase.
Open phase check
lamp "R" is not on
Open phase on terminal where
RED alligator clip is connected
Open phase check
lamp "S" is not on
Open phase check
lamp "T" is not on
Open phase on terminal where
YELLOW alligator clip is connected
Open phase on terminal where
BLUE alligator clip is connected
¶ When the open phase check lamps are not on, the
rotating disc does not turn.
(4)Check the rotating direction of the inside disc through
the phase sequence indication window.
l When the rotating disc turns counter-clockwise,
alternate the connection of the two of the three alligator
clips, then the rotating disc will turn clockwise.
l When the rotating disc turns clockwise, phase
sequence is R, S and T in order of the power source
terminals where the RED, YELLOW and BLUE alligator
clips are connected.
-4-

5. SPECIFICATIONS
l Voltage 90V~600V AC.
l Frequency Response 50/60Hz.
l Safety Standard
BS EN 61010-1 IEC 1010-1 CAT 600V.
l Storage Temperature & Humidity
-20°C ~ +60°C at 90% max.
relative humidity.
l Operating Temperature & Humidity
-10°C ~ +40°C at 80% max.
relative humidity.
l Dimensions
134(L) x 85(W) x 45(D)mm.
l Weight Approx. 540g.
l Cord 1.1m each of Red(R), Yellow(S) and Blue(T) cord.
l Accessories
Instruction Manual, carrying Case.
¶Remark
In case continuous use is necessary, it is recommended
that making measurements does not operate
continuously over 10 minutes, or keep a interval of ten
-minute off operation at least.
2
2
-5-

6. MAINTENANCE
l Cleaning and Storage
(1) To avoid electrical shock or damage to the meter, do
not get water inside the case.
(2) Periodically wipe the case with a damp cloth and
detergent do not use abrasives or solvents.
2