Eclipse Eclipse 8PK-ST1520 Manual

Page 1
8PK-ST1520
Digital Earth Resistance Tester
Users Manual
Tes
t Equipment Depot - 800.517.8431
99 Washington Street Melrose, MA 02176
TestEquipmentDepot.com
Page 2
1.INTRODUCTION ............................
2.SAFETY NOTES.............................
3.FATURES........................................
4.SPECIFICATIONS..............................
5.LAYOUT...........................................
6.MEASURING METHODS.................
7.MAINTENANCE................................
Page
1 2 3 4 5 6-7 8
1.INTRODUCTION
This meter has been designed and tested according to CE safety requirements for Electronic Measuring Apparatus, EN61010-1 and other safety standards. Follow all warnings to ensure safe operation.
Application:
Earth Resistance Tester is used to measure the ohms(Ω) of an earth grounding installation for buildings (residential, office, labs, hospitals), computer server rooms, military installations, cellular sites, radio and cable towers, etc. It is used to determine if the earth (or ground) is a good conductor of electricity.
1
Page 3
Purpose of Earth Groun
(1)Avoid human and animal electrical shock. (2)Avoid unnecessary property and equipment damage. (3)Prevent fire or explosion. (4)Integrate electrical signal to attain proper operation or measuring purpose. (5)Provide a means of dissipation for power surges cau and other types of electrical interference.
sed by lightning strikes, static charges,
ding:
2.SAFETY NOTES
Read the following safety information carefully before attempting to operate or service the meter.
Use the meter only as specified in this manual. otherwise, the protection provided by this meter may be impaired.
Rated environmental conditions: (1) Indoo (2) Installation Category III. (3) Pollution (4) Altitude up (5) Relative humidity 80% max. (6) Ambi
r U
se.
ee 2.
Degr
to 2000 mete
ent temperatu
r.
re 0~40°C.
Observe the International Electrical Symbols
listed Below:
2
Page 4
Meter is protected throughout by
e insulation or reinforced
doubl insulation Warning! Risk of electric shock.
Caution! Refer to this manual before using the Meter.
3.FEATURES
Capable of measuring earth voltage.
2mA measuring current permits earth resistance
tests without tripping earth leakage current breakers in the circuit under test.
Battery operated.
Auto power off function. The timer operates auto-
matically about 3~6 minutes when the "PUSH BUTTON SWITCH" and "TIMER ON BUTTON" are pressed at the same time to keep the tester power on.
Data hold function.
Small and light weight.
Designed to meet EN61010-1 CAT III 200V.
t Equipment Depot - 800.517.8431
Tes
99 Washington Street Melrose, MA 02176
TestEquipmentDepot.com
3
Page 5
4. SPECIFICATIONS
Measurement Ranges Earth Resistance
0-20Ω/0-200Ω/0-2000Ω
Earth Voltage
0-200V AC (40-500Hz)
Accuracy Earth Resistance
± ( 2% rdg+2dgt ) or ± 0.1Ω. which is greater. Earth Voltage ± ( 1% rdg+2dgt )
Earth Resistance Resolution
Measurement System Earth resistance by constant
Low Battery Indication "B" symbol appears on the display Data Hold Indication "DH" symbol appears on the
Over Range Indication Open Circuit Indication Display LCD 3½ digit (2000 counts)
Power Source 1.5V(AA)×6. Dimensions 163(L)×100(W)×50(D)mm Weight 480g approx. (battery included) Accessories Test leads (AL-36:red-15m yellow-
0-20(0.01) 0-200(0.1) 0-2000(1)
current inverter 820Hz approx. 2mA.
display "1"(SMD)
LED will be unlit
10m green-5m) Auxiliary earth bars. Heavy-duty case Instruction manual Batteries
4
Page 6
5.LAYOUT
(1) "E", "P", "C" Terminal (2) O
peration Indicator (3) Data Hold Switch (4) Time (5) LC
r Off Button
D Displ
ay
(6) Function Switch (7) Ohm R (8) Push Ope (9)Timer On Button
5
ange Switc
button
ration
h
Page 7
6.MEASURING METHODS
BEFORE PROCEEDING MEASUREMENT, READ SAFETY NOTES ON PAGE 2.
In proceeding with measurement, if "B" symbol appears on the display, replace with new batteries.
Earth Voltage Measurement: (1) Connection with test leads:
Connect green, yellow test leads to instrument terminals E, P with auxiliary earth bars P1, driven into earth " IN A STRAIGHT LINE".(Fig.1)
(2) Set the function
press the"PUSH-ON" button and "TIME ON" button at the same time make certain that the voltage reading is LESS THAN 10V AC, otherwise accurate earth resistance measurement may not be made.
switch
to ACV position and
6
Page 8
Earth Resistance Meas
urement:
(1) Connection with test leads:
Connect green, yellow and red test leads to instrument terminals E, P and C with auxiliary earth bars P1, C1 driven into earth "IN A STRAIGHT LINE".(Fig.2)
(2) Set the Range Switch to suitable range and set the function switch to position then press the PUSH-ON BUTTON and TIME ON BUTTON at the same time and take the reading on the display.
WARNING
When none of E, P and C terminals connected with test leads, the display shows "1" at function.
Follow the proper connection such as Fig.2, the LED(red) indicator wi correct current circulation
ll lit. This proves a
is under its operation.
7
Page 9
7.MAINTENANCE
Battery Replacement:
When the symbol "B" appears on the display, replace the batteries as follows :
(1) Disconnect the test leads from the instrument
and turn off the power.
(2) Use a screwdriver to unscrew the screw on
back cover then slide the cover, take out the batterie SUM-3.
(3) Place back cover and secure by a screw.
Cleaning and storage: (1)
Periodicall and detergent ; do not use abrasives or solvents.
(2) If the meter is not to be used for periods of
longer than 60 days, remo store them separately.
WARNING To avoid electrical shock or damage to the meter, do not get water inside the case.
s and replace with new batteries Type
y wipe the case with a d
amp cloth
ve the batteries and
Test Equipment Depot - 800.517.8431
99 Washington Street Melrose, MA 02176
TestEquipmentDepot.com
8