serviceable parts inside. Do not attempt to open any
part of
Power Distribution Unit (
PDU
)
. Doing so may expose you to
possible shock hazard and
voids
the
product
warranty.
SSSSPDU
PDU----116M
116M
PDUPDU
116M116M
Important Safety Instruction
• The PDU does not provide short-circuit protection. Therefore, Echola Systems does
not recommend plugging the unit directly into any unprotected power source, such
as a wall outlet. Always connect to an appropriately rated branch circuit’s outlet
which provides short-circuit protection using standard Circuit Breakers or Fuses.
• Always maintain reliable earthing of the PDU. Do not connect the PDU to an
ungrounded outlet or adapters or extension cords that doesn’t have ground
connection.
• The power requirement of each equipment connected to the PDU’s outlet should not
exceed individual outlet’s rated maximum capacity (refer to specification of
appropriate model for ratings).
• The aggregate power requirements of equipments connected to all outlets at any
time should not exceed the maximum input capacity of PDU (refer to specification of
appropriate model for ratings).
• Install the PDU where it may be easily disconnected for service.
•
The PDU is designed for indoor use only. Avoid exposing to extreme ambient
temperatures.
Echola Systems L.L.C
1161 Ringwood Ct, Ste 100
San Jose, CA-95131
Phone: 408 321 9663
http://www.echola.com/power
Page 2
Rack Horizontal Installation
Vertical Installation at the back of the Rack
Installing in a Rack
The PDU can be installed in a standard 19” rack or
enclosure. It can be mounted horizontally at front of
the rack or vertically at the back as shown below.
Outlet-1 Outlet-8
Echola Systems L.L.C
1161 Ringwood Ct, Ste 100
San Jose, CA-95131
Phone: 408 321 9663
http://www.echola.com/power
Page 3
SPDU-108M Specification
Input
16A (Aggregate current of all outlets can't exceed Max.
Interfaces
Physical
Acceptable Input voltage range 100-120V AC
NEMA L5-20P
or
Input plug type
NEMA 5-20P
Maximum Input Current 20A (16A Derated)
Input Current Monitoring Accuracy ±5%
Input Frequency 50/60 Hz
Cord Length 8/10 feet
Output
Output voltage Same as Input
Output receptacle type NEMA 5-20R
Maximum Output current/outlet
Number of Outlets 8
Outlet Current Monitoring Accuracy ±10%
Network Interface RJ45, 10Base-T Ethernet
Front Panel display 2x16 Color character LCD with LED backlight
Input current)
Environmental
Operating Environment 32-113° F
Operating Relative Humidity 0-95%
Operating Elevation 0-10000 feet
Net weight ~10 lbs
Maximum height 1.75 inches (1U)
Maximum width 17.5 inches
Maximum depth 8 inches
Color Olive Green front panel, Grey chassis
Echola Systems L.L.C
1161 Ringwood Ct, Ste 100
San Jose, CA-95131
Phone: 408 321 9663
http://www.echola.com/power
Page 4
SPDU-116M Specification
Input
of all outlets can't exceed Max.
Interfaces
Physical
Acceptable Input voltage range 100-120V AC
Input plug type NEMA L5-30P
Maximum Input Current 30A (24A Derated)
Input Current Monitoring Accuracy ±5%
Input Frequency 50/60 Hz
Cord Length 8 feet
Output
Output voltage Same as Input
Output receptacle type NEMA 5-20R
Maximum Output current/outlet
Number of Outlets 16
Outlet Current Monitoring Accuracy ±10%
Network Interface RJ45, 10Base-T Ethernet
Front Panel display 2x16 Color character LCD with LED backlight
16A (Aggregate current
Input current)
Environmental
Operating Environment 32-113° F
Operating Relative Humidity 0-95%
Operating Elevation 0-10000 feet
Net weight ~15 lbs
Maximum height 3.5 inches (2U)
Maximum width 17.5 inches
Maximum depth 8 inches
Color Olive Green front panel, Grey chassis
Echola Systems L.L.C
1161 Ringwood Ct, Ste 100
San Jose, CA-95131
Phone: 408 321 9663
http://www.echola.com/power
Page 5
SPDU-208M Specification
Input
16A (Aggregate current of all outlets can't exceed Max.
Interfaces
Physical
Acceptable Input voltage range 200-240V AC
Input plug type NEMA L6-20P
Maximum Input Current 20A (16A Derated)
Input Current Monitoring Accuracy ±5%
Input Frequency 50/60 Hz
Cord Length 8/10 feet
Output
Output voltage Same as Input
Output receptacle type
Maximum Output current/outlet
Number of Outlets 8
Outlet Current Monitoring Accuracy ±10%
Network Interface RJ45, 10Base-T Ethernet
Front Panel display 2x16 Color character LCD with LED backlight
IEC 320 C13 (7) IEC 320 C19 (1)
Input current)
Environmental
Operating Environment 32-113° F
Operating Relative Humidity 0-95%
Operating Elevation 0-10000 feet
Net weight ~10 lbs
Maximum height 1.75 inches (1U)
Maximum width 17.5 inches
Maximum depth 8 inches
Color Olive Green front panel, Grey chassis
Echola Systems L.L.C
1161 Ringwood Ct, Ste 100
San Jose, CA-95131
Phone: 408 321 9663
http://www.echola.com/power
Page 6
SPDU-216M Specification
Input
16A (Aggregate current of all outlets can't exceed Max.
Interfaces
Physical
Acceptable Input voltage range 200-240V AC
Input plug type NEMA L6-30P
Maximum Input Current 30A (24A Derated)
Input Current Monitoring Accuracy ±5%
Input Frequency 50/60 Hz
Cord Length 8/10 feet
Output
Output voltage Same as Input
Output receptacle type
Maximum Output current/outlet
Number of Outlets 16
Outlet Current Monitoring Accuracy ±10%
Network Interface RJ45, 10Base-T Ethernet
Front Panel display 2x16 Color character LCD with LED backlight
IEC 320 C13 (14) IEC 320 C19 (2)
Input current)
Environmental
Operating Environment 32-113° F
Operating Relative Humidity 0-95%
Operating Elevation 0-10000 feet
Net weight ~15 lbs
Maximum height 3.5 inches (2U)
Maximum width 17.5 inches
Maximum depth 8 inches
Color Olive Green front panel, Grey chassis
Echola Systems L.L.C
1161 Ringwood Ct, Ste 100
San Jose, CA-95131
Phone: 408 321 9663
http://www.echola.com/power
Page 7
Initial Software Configuration
You may need to change network settings of Echola PDU device before connecting it to
your network's switch/router. If your network has a DHCP server then you may want to
skip this section and connect PDU Ethernet port to their network's switch/router and the
IP address will be assigned automatically by your DHCP server. The assigned IP address
will be shown on the LCD panel. Use that IP to login into PDU and manage it.
If you don't have a DHCP server running on your network then you may want to configure
Static IP; there are three ways you could do this:
1. Using NBNS (NetBIOS Name Service) of PDU
2. Using built-in DHCP server of PDU
3. Using Static IP configuration of your PC/Laptop
Using NBNS (NetBIOS Name Service)
Using NBNS (NetBIOS Name Service)
Using NBNS (NetBIOS Name Service)Using NBNS (NetBIOS Name Service)
You would need a Windows based Laptop or a PC to configure PDU using this method for
the first time. You may also need a ethernet crossover cable to connect PDU to a PC or a
Laptop but most of the modern PC/Laptops would work with either type of cable (straight
or crossover). Make sure the PC/Laptop IP option "Obtain IP address automatically" is
checked in the Internet Protcol Properties of the ethernet interface. Now launch the
internet browser and type http://echolasys in the address bar and press Enter key. Now
you will be prompted with a PDU's login dialog; If this is first time then use default
username and password. After login, you will see the main menu page of the PDU. Now
click on the Setup tab of the menu to bring the Network Config menu. From here you can
assign static IP, subnet mask and gateway and save your configuration. Thats it, now you
are set to connect PDU to your network/switch/router and access it from remote.
•
Default Username
Default Username: admin
Default UsernameDefault Username
•
Default Password
Default Password: admin
Default PasswordDefault Password
Using built
Using built----in DHCP server
Using builtUsing built
in DHCP server
in DHCP serverin DHCP server
The procedure is same as above NBNS except that instead of using hostname 'echolasys' in
your browser you will have to use the IP address (like http://192.168.2.222) displayed on
the LCD panel. This method works for non-windows PC/Laptop as well.
Using Static IP configuration
Using Static IP configuration
Using Static IP configurationUsing Static IP configuration
Configure your PC/Laptop ethernet port's IP address to match the network portion of
default IP adress of PDU.
•
Default IP Address of
Default IP Address of PDU
Default IP Address of Default IP Address of
•
Default Gateway of
Default Gateway of PDU
Default Gateway of Default Gateway of
PDU: 192.168.2.222
PDUPDU
PDU: 192.168.2.222
PDUPDU
Echola Systems L.L.C
1161 Ringwood Ct, Ste 100
San Jose, CA-95131
Phone: 408 321 9663
http://www.echola.com/power
Page 8
•
Default Subnet mask of
Default Subnet mask of PDU
Default Subnet mask of Default Subnet mask of
PDU: 255.255.255.0
PDUPDU
For example you can configure your PC/Laptops IP address as 192.168.2.222 and access
the main menu of PDU. After configuring the PC/Laptop ethernet address, just use any
internet browser to access PDU with new configure IP address. Now you will be prompted
with PDU's login dialog; If this is first time then use default username and password. Now
the default network settings of IP, subnet mask and gateway can be changed to match your
network setting through Setup tab.
•
Default Username
Default Username: admin
Default UsernameDefault Username
•
Default Password
Default Password: admin
Default PasswordDefault Password
User Authentication
User Authentication
User AuthenticationUser Authentication
Admin user is always the previlaged user who can access any web page. You can also create
a different user who can access to main Control/Monitor page but is not allowed to access
Setup page. This user is by default called "guest" but name can be changed using Setup-
>User tab and default password is "guest" as well.
If the authentication fails "Authentication Required" message will be displayed. The
authentication can optionally be disabled for Control/Monitor web page (the home page)
on the main menu by using Setup->User setting so that admin or guest user can access
main page without login but the Setup web page will still require login.
User Interfaces
User Interfaces
User InterfacesUser Interfaces
Front Panel LCD
Front Panel LCD
Front Panel LCDFront Panel LCD
LCD moving character display on the front panel displays following important information.
This is useful when you are near the device to setup or monitor.
1. Hostname
2. IP Address
3. Outlet Status
4. Total Current Consumption in Amps
The outlet status shows the status of all 8 outlets and it could be one of the following,
(1) o (Empty circle): means corresponding outlet is switched OFF
(2) ● (Filled circle): means corresponding outlet is switched ON
(3) x (Cross): means corresponding outlet has been shut off due to overload
(Individual port overload protection feature)
Echola Systems L.L.C
1161 Ringwood Ct, Ste 100
San Jose, CA-95131
Phone: 408 321 9663
http://www.echola.com/power
Page 9
Web Interface
Web Interface
Web InterfaceWeb Interface
User can configure, monitor and control the PDU through user friendly web interface. The
web interface uses AJAX for providing near real-time update on current consumption for
each outlets, total current, Temperature and outlet statuses.
To access GUI from any smart phone/mobile devices, just use letter ‘/m’ after the ipaddress
or the hostname, like http://192.168.2.21/m
For more details on web interface please refer to User’s Manual at
http://www.echola.com/support.
Echola Systems L.L.C
1161 Ringwood Ct, Ste 100
San Jose, CA-95131
Phone: 408 321 9663
http://www.echola.com/power
Page 10
Automation
Automation
AutomationAutomation
You can either use Tcl scripting language (refer to separate document for automation using
Tcl) or Perl for automation. Here is an example how to use Perl script which uses api.xml
file from the PDU to parse certain outputs. If you are on windows you can use strawberry
perl.
############################################################
# Command Syntax: perl xmlget.pl http://<ipaddress> #
############################################################
use LWP::UserAgent;
use XML::Simple;
$IPADDR = shift;
# create objects
$xml = new XML::Simple;
$ua = LWP::UserAgent->new;
Echola Systems L.L.C
1161 Ringwood Ct, Ste 100
San Jose, CA-95131
Phone: 408 321 9663
http://www.echola.com/power
Page 11
If you get
connection lost messages
connection lost messagesconnection lost messages
connection lost messages
when you are on any GUI page (telnet or snmp
might still work), you will have to make sure you are running latest version of
configurations. If you have such config
uration you may want to connect the PDU
to the primary router (router
that
acts as gateway or dhcp server).
Troubleshooting
•
JAVA on the PC where you run the browser to log into the smart PDU. The older
versions of java (ver <= 5 or early 6 versions) doesn't work well with the AJAX
calls that we use for real time updates. You can check whether you have latest java
by clicking on following link http://java.com/en/download/testjava.jsp and do an
update to avoid this intermittent problem.
• Also check for any malware/anti-virus/firewall software which might block the
http connection to PDU.
• We don’t support router-behind-router or router hacked to work in bridge-mode
For any technical questions, email to support@echola.com.
Echola Systems L.L.C
1161 Ringwood Ct, Ste 100
San Jose, CA-95131
Phone: 408 321 9663
http://www.echola.com/power
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.