Eccotemp Systems LLC EAQ10024 Owner Manual

Page 1
Page 2
English
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
WARNING: If the information in these
instructions is not followed exactly, a re or
• Do not store or use gasoline or other
ammable vapors and liquids in the vicinity of this or any other appliances.
• WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliances.
- Do not touch any electrical switch; do
not use any phone in your building.
- Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier,
call the re department.
• Installation and service must be performed by a qualied installer, service agency or
the gas supplier.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
2
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Page 3
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
PLEASE VERIFY THIS WATER HEATER IS RIGHT FOR YOU.
Congratulations on your purchase of the i12 Gas Tankless Water Heater.
THINGS YOU SHOULD KNOW ABOUT THIS WATER HEATER
English
INCOMING WATER
TEMPERATURE
ZONE 1
ZONE 2
ZONE 3
ALASKA
MODEL
RECOMMENDED USES HOUSEHOLD SIZE
Cabins, Apartments, Townhomes and Tiny Homes
Zones 2 and 3
(See map below)
37 - 47º F
52 - 62º F
67 - 77º F
showering and another washing
1-2 APPLICATIONS
Example: One person
dishes at the same time
OR+ +
showering and another washing
clothes at the same time
HAWAII
FLOW
U/M
80 75 70 65 60 55 50 45 40 35 30
TEMPERATURE RISE (IN DEGREES
Example: One person
TEMPERATURE CONTROLS
AUTOMATIC TEMPERATURE CONTROLS
The temperature is set from the front control panel and automatically adjusts at your sink or shower.
(See page 30 for more info)
STANDARD
APPLICATION FLOWS
1.0-2.0 GPM 1.5-2.0 GPM
4.0 – 5.0 GPM
)
1.0 – 1.5 GPM
FVI12 gpm 0.9 1.3 1.8 2.2 2.7 3.1 3.6 4.0 4.4 4.9 5.3
i12 gpm 0.7 1.0 1.4 1.7 2.1 2.4 2.8 3.1 3.4 3.8 4.1
20H gpm 1.1 1.7 2.3 2.8 3.4 4.0 4.5 5.1 5.7 6.2 6.8
20HI gpm 1.1 1.7 2.3 2.8 3.4 4.0 4.5 5.1 5.7 6.2 6.8
45H gpm 1.3 1.9 2.6 3.2 3.9 4.5 5.2 5.8 6.4 7.1 7.7
45HI gpm 1.3 1.9 2.6 3.2 3.9 4.5 5.2 5.8 6.4 7.1 7.7
EL22 gpm 1.3 1.9 2.6 3.2 3.9 4.5 5.2 5.8 6.4 7.1 7.7
EL22i gpm 1.3 1.9 2.6 3.2 3.9 4.5 5.2 5.8 6.4 7.1 7.7
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury, or death.
Installation and service must be performed by a qualied installer, or service technician.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
3
Page 4
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Use & Care Manual
English
With Installation Instructions for the Installer
APPLICATION
Residential
INSTALLATION
Indoor
BTU’S
74,500
Tankless Water Heater
WARNING: This water heater may not be suitable
for use in manufactured (mobile) homes! Please check
local code restrictions pertaining to permanent/xed
installations in manufactured homes in your area.
The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations for the proper installation and adjustment of the water heater; and two,
to the owner-operator, to explain the features, operation, safety
precautions, maintenance and troubleshooting of the water heater. This manual also includes a parts list.
It is imperative that all persons who are expected to install,
operate or adjust this water heater read the instructions carefully so they may understand how to perform these operations. If you don’t understand these instructions or any terms within it, seek professional advice.
FLOW RATE
4.0 GPM
Any questions regarding the operation, maintenance, service or warranty of this water heater should be directed to the seller from whom it was purchased. If additional information is required, refer to the section on If You Need Service.
Do not destroy this manual. Please read carefully and keep in a safe place for future reference.
Recognize this symbol as an indication of Important Safety Information!
California Proposition 65 Warning: This product contains chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
WARNING: If the information in these instructions is not followed exactly, a re or explosion may result causing property damage, personal injury or death.
FOR YOUR SAFETY!
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury, or death. Installation and service
must be performed by a qualied installer, service
agency or the gas supplier.
DO NOT store or use gasoline or other ammable
vapors or liquids or other combustible materials in the vicinity of this or any other appliance. To
do so may result in an explosion or re.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
WHAT TO DO IF YOU SMELL GAS
• DO NOT try to light any appliances.
• DO NOT touch any electrical switch;
do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the re department.
• DO NOT return to your home until authorized
by the gas supplier or re department.
4
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
Page 5
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Safety Information
Safety Precautions .................. 3-9
i12 Installation Instructions
Location ................................... 11-12
Typical Installation ............. 13-14
Water Connections ............. 15-16
Gas Supply ...................................... 16
Relief Valve ....................................17
Leak Testing ................................... 17
High Altitude ................................17
Venting .....................................18-23
Electrical Connection ................ 23
Pipe Insulation ............................ 24
Mounting ...................................... 25
Installation Checklist ................. 26
Operating Instructions
Start Instructions ................ 27-28
Water Temperature ................... 39
Maintenance
Housekeeping ............................ 30
Cleaning the Filter ..................... 31
Extended Shut-Down ...............31
Draining ................................. 31-32
Customer Service
Parts List.........................................33
Troubleshooting Tips
Before You Call ............................34
Error Code Guide .......................35
FOR YOUR RECORDS Write the model and serial numbers here:
#_______________________________
#_______________________________
You can nd them on a label on the water heater
and/or packaging.
Staple sales slip or canceled check here.
Proof of the original purchase date is needed to obtain service under the warranty.
READ THIS MANUAL
Inside you will nd many helpful hints on how to
use and maintain your water heater properly. A little preventive care on your part can save you time and money over the life of your water heater.
You’ll nd many answers to common problems in
the Troubleshooting Guide. If you review the chart
of Troubleshooting Tips rst, you may not need to
call for service.
READ THE SAFETY INFORMATION
Your safety and the safety of others are very important. There are many important safety messages in this manual and on your water
heater. Always read and obey all safety messages. This is the safety alert symbol. Recognize this symbol as an indication of Important Safety Information! This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER”, “WARNING”, “CAUTION” or “NOTICE”.
English
These words mean:
DANGER - An imminently hazardous situation that will result in death or serious injury.
WARNING - A potentially hazardous situation that could result in death or serious injury and/or damage to property.
CAUTION - A potentially hazardous situation that may result in minor or moderate injury.
NOTICE: Attention is called to observe a specied procedure or maintain a specic condition.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
5
Page 6
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
SAFETY PRECAUTIONS
English
Safety
READ ALL INSTRUCTIONS BEFORE USING
Be sure to read and understand the entire Use and Care Manual before attempting to install or operate this water heater. It may save you time and money. Pay particular attention to the Safety Instructions. Failure to follow these warnings could result in serious bodily injury or death. Should you have problems understanding the instructions in this manual, or have any questions, STOP, and
get help from a qualied service technician, or the local gas utility.
DANGER!
INSTALL AND PROPERLY VENT THE WATER HEATER
Failure to properly install the water heater indoors as outlined in the Installation Instructions in this manual can result in unsafe operation of the water heater. To
avoid the risk of re, explosion, or asphyxiation from carbon monoxide, never
operate this water heater unless it is installed properly and has an adequate
air supply for proper operation. Be sure to inspect the ue terminal for proper
installation at initial start-up; and at least annually thereafter. Refer to the Care
and Cleaning section of this manual for more information regarding ue terminal
inspection.
WARNING!
Gasoline, as well as other ammable materials and liquids (adhesives, solvents, paint thinners etc.), and the vapors they produce are extremely dangerous. DO NOT handle, use or store gasoline or other ammable or combustible materials
anywhere near or in the vicinity of a water heater or any other appliance. Be sure to read and follow the labels on the water heater, as well as the warnings printed in this manual. Failure to do so can result in property damage, bodily injury or death.
Vapors from ammable liquids will explode and catch re causing death or severe burns.
Do not use or store ammable products
such as gasoline, solvents or adhesives In the same room or area near the water heater.
Keep ammable products :
1. Far away from heater
2. In approved containers
3. Tightly closed
4. Out of children ‘s reach
Installation:
Do not Install water heater where ammable products will be stored or used unless the main burner ame Is at least 18” above the oor. This will reduce, but not eliminate, the risk of vapors being ignited by the main burner ame.
Read and follow water heater warnings and Instructions. If owners manual is missing, contact the retailer or manufacturer.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
6
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Water heater has a main burner ame. The main burner ame
1. Can come on at any time and
2. Will ignite ammable vapors.
Vapors:
1. Cannot be seen
2. Are heavier than air
3. Go a long way on the oor
4. Can be carried from other rooms to
the main burner ame by air currents.
Page 7
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
SAFETY PRECAUTIONS
IMPORTANT SAFETY INFORMATION READ ALL INSTRUCTIONS BEFORE USING
DANGER!
WATER TEMPERATURE SETTING
Safety and energy conservation are factors to be considered when selecting the water temperature setting. Water temperatures above 125°F can cause severe burns or death from scalding. The thermostat is adjusted to its lowest temperature position when shipped from the factory. Be sure to read and follow the warnings outlined on the label pictured below.
Time/Temperature Relationship in Scalds
Water Temperature
120°F
125°F
130°F
135°F
140°F
145°F
150°F
155°F
Table courtesy of Shriners Burn Institute
The chart shown above may be used as a guide in determining the proper water temperature for your
home.
Time To Produce a Serious Burn
More than 5 minutes
1 1/2to 2 minutes
About 30 seconds
About 10 seconds
Less than 5 seconds
Less than 3 seconds
About 1 1/2 seconds
About 1 second
English
Safety
Water temperature over 125°F can cause severe burns instantly or death from scalds. Children, disabled and elderly are at highest risk of being scalded. See instruction manual before setting temperature at water heater. Feel water before bathing or showering. Temperature limiting valves are available, see manual.
Turn Water Heater
On/O
Increase
Temperature
Enable
Child-Lock
Decrease
Temperature
DANGER: Households with small children, disabled,
or elderly persons may require a 120°F. or lower temperature setting to prevent contact with”HOT” water.
Maximum water temperature occurs while burner is on. To nd water temperature being delivered, turn on a hot
water faucet and place a thermometer in the water stream and read the thermometer.
The temperature of the water at the outlet of the water heater can be regulated by setting the temperature on the control panel. The control panel was set at 110°F before it was shipped from the factory.
The illustration to the bottom left illustrates the control panel and how to adjust the water temperature.
NOTICE: When this water heater is supplying general purpose hot water requirements for use by individuals, a
thermostatically controlled mixing valve for reducing point
of use water temperature is recommended to reduce the risk of scald injury. Contact a licensed plumber or the local plumbing authority for further information.
NOTICE: The factory setting allows operating temperatures between 80°F and 140°F.
NOTICE: This is an automatic temperature controlled tankless water heater. This means that the temperature must be set from the front LED control panel. You
can restrict the ow of the incoming water using the built in ow restrictor in order to achieve a desired set temperature. This tankless water heater is ow activated and will adjust gas ames to heat water as necessary.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
7
Page 8
English
Safety
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
SAFETY PRECAUTIONS
DANGER!
NATURAL GAS AND LIQUEFIED PETROLEUM MODELS
Both LP and natural gas have an odorant added to aid in detecting a gas leak. Some people may not physically be able to smell or recognize this odorant. If you are unsure or unfamiliar with the smell of LP or natural gas, ask the gas supplier.
Other conditions, such as “odorant fade”, which causes the odorant to diminish in intensity, can also hide or camouage a gas leak. Always check with commercial
leak detector or soapy water.
Gas detectors are recommended in LP and natural gas applications and their installation should be in accordance with the detector manufacturer’s recommendations and/or local laws, rules, regulations or customs.
Water heaters utilizing LP gas are dierent from natural gas models. A natural gas water heater will not function safely on LP gas and vice versa.
No attempt should ever be made to convert the water heater from natural gas
to LP gas. To avoid possible equipment damage, personal injury or re, do not
connect the water heater to a fuel type not in accordance with the unit data plate; propane for propane units and natural gas for natural gas units. These
units are not certied for any other fuel type.
LP water heaters should not be installed· below grade (for example, in a basement) if such installation is prohibited by federal, state and/or local laws, rules, regulations or customs.
Propane or LP gas must be used with great caution. It is heavier than air and
will collect rst in lower areas making it hard to detect at nose level.
Before attempting to operate the water heater, make sure to look and smell
for gas leaks. Use a soapy solution to check all gas ttings and connections.
Bubbling at a connection indicates a leak that must be corrected. When
smelling to detect a gas leak, be sure to sni near the oor also.
It is recommended that more than one method, such as soapy solution, gas detectors, etc., be used to detect leaks in gas applications.
Notice: If a gas leak is present or suspected:
DO NOT attempt to nd the cause yourself.
DO NOT try to light any appliances.
DO NOT touch any electrical switch.
DO NOT use any phone in your building.
Leave the house immediately and make sure your family and pets leave
also. Leave the doors open for ventilation and contact the gas supplier, a qualied service agency or the re department.
Stay away from the house (or building) until the service call has been made, the leak is corrected and a qualied agency has determined the area to be safe.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
8
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Page 9
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
SAFETY PRECAUTIONS
IMPORTANT SAFETY INFORMATION READ ALL INSTRUCTIONS BEFORE USING
WARNING!
For your safety, the information in this manual must be followed to
minimize the risk of re or explosion, electric shock, or to prevent property
damage, personal injury, or loss of life.
FOR INSTALLATIONS IN THE STATE OF CALIFORNIA
California Law requires that residential water heaters must be braced, anchored or strapped to resist falling or horizontal displacement due to earthquake motions. For residential water heaters up to 52 gallon capacity, a brochure with generic
earthquake bracing instructions can be obtained from: Oce of the State Architect,
400 P Street, Sacramento, CA 95814 or you may call 916-445-8100 or ask a water heater dealer.
However, applicable local codes shall govern installation. For residential water heaters of a capacity greater than 52 gallons or tankless style, consult the local building jurisdiction code for acceptable bracing procedures.
English
Safety
SAFETY PRECAUTIONS
Have the installer show you the location of the gas shut-o valve and how to shut it o if necessary. Turn o the manual shut-o valve if the water heater has been subjected to overheating, re, ood, physical damage or if the gas supply fails to shut o.
Read this manual entirely before installing or operating the water heater.
Use this water heater only for its intended purpose as described in this Use and Care Manual.
Be sure your water heater is properly installed in accordance with local codes and the provided installation instructions.
Unless recommended by an Eccotemp technician, all part replacements and
servicing should be referred to a qualied technician.
SAVE THESE INSTRUCTIONS
READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY .
This water heater must be installed in accordance with these instructions, local codes, utility company requirements, and/or in the absence of local codes, use the latest edition of the American National Standard/ National Fuel Gas Code. A copy can be purchased from either the American Gas Association, 400 North Capitol Street Northwest, Washington, DC 20001 as ANSI standard Z223.1 or National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269 as NFPA 54. In Canada, the latest edition of the CSA B149.1 Natural Gas and Propane Installation, and the Canadian Electrical Code, CSA C22.1Part1, in the absence of local codes.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
9
Page 10
English
Installation
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Installing the i12 water heater
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
10
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Page 11
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Location
Installation distances may vary by local code. It is the installer’s responsibility to verify installation requirements.
Make sure before installation that the gas type you will use is the same type on the data plate.
The water heater unit should be installed by professionals. Improper installation may cause failure or dangerous conditions such as gas leaking or explosion.
Failure to have the water heater installed by a professional will void your warranty.
The water heater cannot be installed in an un-vented bathroom, bedroom, basement, living room,
closet, outdoors, laundry room, stairway or an exit area. If installed in an exit area, it must be at
least 16.5 ft. or more away from the exit.
Vent pipe should extend from the wall at least 2”. The terminal must be at least 1.64 ft. away from obstruction and must be well vented.
Vent pipe should slope 3° downward to avoid condensing water and protect from rain entering.
Vent pipe should avoid direct, strong wind because the downdraft will cause malfunction.
The water heater should be installed far from any blockage, and with plenty of enough space for installation and maintenance. Adequate clearances for servicing must be provided.
English
Installation
The water heater should not be installed in the same room with a gas stove.
When determining the oor clearance, a clearance of 6 inches must be maintained between the
vent pipe and combustible material. A side wall clearance of 10 inches and a top clearance of 16 inches must be maintained.
The vent pipe can be up to 32 ft. in length with one elbow.
The vent pipe should be installed with a ame-retardant wall thimble. Owner must refer to vent
manufacturer’s instructions and specications. Z-Flex information can be found at www.novaex. com, please refer to page 18 for additional links. Installation guidelines for venting provided by NovaFlex, who is solely responsible for venting installation accuracy.
The power socket connecting the water heater should be grounded properly with a GFCI circuit protector.
The water heater should not be located in an area where leakage of the heat exchanger or
connections will result in damage to the area adjacent to it or to lower oors of the structure. When such areas cannot be avoided it is recommended that a suitable catch pan, adequately drained, must be installed under the water heater. The pan must not restrict combustion airow.
This unit MUST NOT be installed in a laundry room or in the same room as the washer/dryer. Installation of the unit in a laundry room or in the vicinity of a washer/dryer will void the warranty.
The water heater should be installed as close as practical to the vent termination to minimize vent length and the number of elbows required for venting.
A gas red water heater, or any other appliance should not be installed in a space where liquids which give o ammable vapors are to be used or stored. Such liquids include gasoline, LP gas (butane or propane), paint or adhesives and their thinners, solvents or removers.
The water heater should be installed far from heat sources, ammable and dangerous materials. Because of natural air movement in a room or other enclosed space, ammable vapors can be carried some distance from where their liquids are being used or stored. The open ame of the water heater’s main burner can ignite these vapors causing an explosion or re which may result in severe burns, death or property damage.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
11
Page 12
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Location
English
Installation
CONTINUED...
Raising the water heater will reduce, BUT NOT eliminate the possibility of lighting the vapor of any ammable liquids which may be improperly stored or accidentally spilled.
If the water heater is installed in a garage, it should be installed so that the direct ignition system and main burner are no less than 18 inches above the garage oor.
Hot and cold-water lines should be insulated to conserve water and energy.
The water heater must be located so it is not subject to physical damage, for example, by moving vehicles, area ooding, etc.
The water heater should be installed with the proper venting materials and termination
suitable for Category III venting. Failure to install and properly vent the water heater to the
outdoors as outlines in the Venting Section of this manual can result in unsafe operation.
Owner must refer to vent manufacturer’s instructions and specications. Z-Flex information can be found at www.novaex.com, please refer to page 18 for additional links.
For other than a direct vent appliance, the appliance must be located as close as practicable to a chimney or gas vent.
DO NOT install water heater where subject to vibrations, or on the road use.
DO NOT install the water heater in Recreational Vehicles, Mobile Homes, Boats and other Watercraft.
DO NOT install the water heater near vents for heating or cooling. A minimum of 4 feet should be maintained.
If the clearances stated on the Instruction/Warning Label, located on the front panel of the
heater dier, install the water heater according to the clearances stated on the label.
WARNING: Combustible construction refers to adjacent walls and ceilings and should not be confused with combustible or ammable products and materials. Combustible and/ or ammable products and materials should never be stored in the vicinity of this or any
gas appliance.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
12
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Page 13
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Typical Installation
Proper operation of the water heater requires air for combustion and ventilation. Provisions for combustion and ventilation air must comply with referenced codes and standards.
Combustion and Ventilation Air
A conned space is one having a volume of less than 50 cubic feet per
1,000 BTUH of the aggregate input of all appliances within that space.
The air must be supplied through two permanent openings of equal area.
One is to be located within 12” above the oor and the other is to be located within 12” below the ceiling.
The minimum net free area of each opening must not be less than one square inch per 1,000 BTUH of the total input rating of all the appliances in the enclosure (but not less than 100 square inches), if each opening
communicates with other unconned areas inside the building.
Buildings of unusually tight construction shall have the combustion and ventilation air supplied from outdoors, or a freely ventilated attic or crawl space. If air is supplied from outdoors, directly or through vertical ducts,
there must be two openings located as specied above and each must
have a minimum net free area of not less than one square inch per 4,000 BTUH of the total input rating of all the appliances in the enclosure.
If horizontal ducts are used to communicate with the outdoors, each opening must have a minimum net free area of not less than one square inch per 2,000 BTUH of the total input rating of all the appliances in the
enclosure. If ducts are used, the minimum dimensions of rectangular air ducts shall not be less than 4”.
NOTICE: If the water heater is installed in an unconned space within a building of conventional frame, masonry or metal construction, inltration air is normally adequate for proper combustion and ventilation air must be made.
English
Installation
NOTICE: If the duct openings which supply combustion and ventilation air are to be covered with a protective screen or grill, the net free area (openings in the material) of the covering material must be used in determining the size of openings. Protective screening for the openings MUST NOT be smaller than ¼” to prevent clogging by lint or other debris.
Corrosive Atmospheres
The air in beauty shops, dry cleaning establishments, photo processing labs, and storage areas for liquid and powdered bleaches or swimming pool chemicals often contain such halogenated hydrocarbons.
An air supply containing halogenated hydrocarbons may be safe to breathe, but when it passes through
a gas ame corrosive elements are released that will
shorten the life of any gas burning appliance.
Propellants from common spray cans or gas leaks from A/ C and refrigeration equipment are highly
corrosive after passing through a ame.
The water heater warranty is voided when failure of the heater is due to operation in a corrosive atmosphere.
NOTICE: The water heater should not be installed near any air supply containing halogenated hydrocarbons.
Inspect Shipment
Not Included
Inspect the water heater for possible damage. Check the markings on the rating plate of the water heater to be certain the type of gas supplied corresponds to the water heater requirements. Verify all included parts are present (see below).
These items are not included but are recommended and available for purchase
at www.eccotemp.com
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
13
Page 14
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Typical Installation
English
Installation
Cold Water
NOTICE: The National Fuel Gas Code (NFGC) mandates a manual gas shut- o valve: See (NFGC) for complete instructions. Local codes or plumbing authority requirements may vary from the instructions or diagrams provided and take precedent over these instructions.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
14
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Page 15
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Water Connections
Plumbing should be carried out by a qualied plumber in accordance with local codes. Use approved plumbing
materials and tools only.
Install a Check Valve between the water heater and the water shuto valve (See illustration below).
To conserve energy and to prevent freezing, insulate both cold and hot water supply lines. DO NOT cover the drain valves.
Flow Restrictor
Water Inlet
Filter
Check Valve
Nipple
CAUTION: This water heater must only be used with the following water supply system conditions:
• With clean, potable water free of corrosive chemicals, sand, dirt, or other contaminates.
• With inlet water temperatures above 32°F, but not to exceed 120°F.
• Free of lime and scale deposits.
DO NOT reverse the hot and cold water connections. The water heater will not operate.
To ensure proper operation of the water heater, the following water pressure guidelines should be followed:
Operation of the i12 gas tankless water heater requires a minimum water ow rate of 0.6 GPM to activate and
0.8 GPM to maintain activation.
Additional water pressure is required for long pipe runs and outlet tting(s) water pressure drops.
To maintain proper performance, ensure sucient water supply pressure. The Required Water Flow Rate = Min. Operating Water Pressure (0.8 GPM) + Pipe Pressure Loss + Faucet and Shower Pressure Loss + Safety Margin (more than 5 psi).
To supply hot water to upper oors, additional water pressure (0.44 psi/ft) must be ensured. The measurement should be calculated by the distance between the water inlet of the water heater (ground level) to the hot
water faucet (upper oor level).
Well water systems should be set at a range of 50-60 psi.
When the water is supplied from a water supply tank, the height of the tank and the diameter of the pipes and their relation to water pressure, should be taken into consideration. Gravity water pressure is not recommended.
Install a shuto valve near the inlet of the water heater for service and draining purposes. Before connecting the water supply pipe to the water heater, open the
shut-o valve ·and clean out sand, debris, air, caulking material, etc. inside the pipe. Connect to the water inlet, then check water pressure. Close the shuto valve and clean the water lter.
Be sure to put the ow restrictor lever in an upright position like the diagram to the left. You’ll adjust this as needed seasonally to achieve desired temperatures.
If a water heater is installed in a closed water supply system, such as one having a backow preventer in the cold-water supply line, means shall be provided to control thermal expansion. Contact the water supplier or local plumbing
inspector on how to control this situation.
English
Installation
IMPORTANT: Do not apply heat to the HOT or COLD water connections. Any heat applied to the water
supply ttings will permanently damage the internal components of the water heater.
NOTICE: If the water pressure resistance of a shower head is too high, the burner in the water heater will fail to ignite. Keep the shower head clean from debris that could cause additional pressure drop.
Notice: If using mixing valves on the outlet, choose one which prevents cold water pressure from overcoming hot
water line pressure.
DO NOT use pipes with smaller diameters than the water supply connection of the water heater.
Be sure to connect the water inlet and the hot water outlet as shown on the water heater. If reversed, the water heater will not function.
Installation of unions or exible copper connections are recommended on the HOT and COLD water lines, so that
the water heater may disconnect easily for servicing if necessary.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
15
Page 16
English
Installation
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Water Connections
In regards to the HOT WATER OUTLET:
• Connections between the water heater and point(s) of use should be as short and direct as possible.
• DO NOT use lead or non-approved plastic pipe.
• To conserve energy and minimize heat loss, insulation of hot water piping is recommended.
NOTICE: The pressure rate of hot water may vary when more than two faucets (appliances, xtures, etc.) are being used simultaneously.
NOTICE: The pipes MUST be completely drainable. If the hot water
faucets are located at a point higher than the water heater, place a drain
valve at the lowest point (see diagram to the left).
Gas Supply
WARNING: Do not attempt to convert this water heater for use with a dierent type of gas other than the type shown on the rating plate. Such conversion could result in hazardous operating conditions. Please have a professional connect the gas pipe.
The Manual Gas Appliance Shuto Valve must be installed at the gas connection of the water heater at the time of installation (see diagram to the left).
The branch gas supply line to the water heater should be clean black steel pipe or other approved gas piping material.
A ground joint union or ANSI design certied semi-rigid or exible gas appliance connector should be installed in the gas line close to the water heater.
The National Fuel Gas Code (NFGC) mandates a manual gas shut-o valve: See (NFGC) for complete instructions.
A sediment trap should be installed at the bottom of the gas line.
The inlet gas pressure to the water heater must not exceed 10.5“ w.c.
for natural or 14” w.c. for LP gas. For purposes of input adjustment,
the minimum inlet gas pressure (with main burner on) is shown on the water heater rating plate. If high or low gas pressures are present, contact your gas supplier for correction
The water heater and its indivdual shuto valve must be disconnected from the gas supply piping system during any pressure testing of that
system at test pressures in excess of ½ psi (3.5 kPa).
The water heater must be isolated from the gas supply piping system
by closing its individual manual shuto valve during any pressure
testing of the gas supply piping system at test pressures equal to or
less than ½ psi (3.5 kPa).
DO NOT use excessive force (over 31.5 ft lbs.) in tightening the pipe, particularly if pipe compound is used, as
the unit may be damaged.
Compound used on the threaded joints of the gas piping must be of the type resistant to the action of LP gas. Use compound sparingly and use on male threads only.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
16
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Page 17
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Relief Valve
A new pressure relief valve, complying with the Standard for relief Valves and Automatic Gas Shut-O Devices for Hot Water Supply Systems, ANSI Z21.22, must be installed at the hot water outlet connection of the water heater at the time of installation. Local codes shall govern the installation of relief valves. Pressure relief valves are not included with your water heater but are available for purchase at www.eccotemp.com
For safe operation of the water heater, be sure that:
The pressure rating of the relief valve must not exceed 150 psi, the maximum working pressure of the water heater as marked on the rating plate.
The BTUH rating of the relief valve must equal or exceed the BTUH input of the water heater as marked on its rating plate.
No valve of any type should be installed between the relief valve and the water heater.
Discharge from the relief valve should be piped to a suitable drain to eliminate potential water damage. Piping used should be of a type approved for the distribution of hot water.
Hot and cold water lines should be insulated up to the water heater.
The discharge line must be NO SMALLER than the outlet of the valve and must pitch downward to allow complete drainage (by gravity) of the relief valve and discharge line.
The end of the discharge line should not be threaded or concealed and should be protected from freezing. No valve of any type, restriction or reducer coupling should be installed in discharge line.
NOTICE: The diagram below illustrates a pressure only relief valve. If local codes require a combination temperature and pressure relief valve be installed, an extension piece may be needed.
NOTICE: Local codes govern the installation of relief valves. If local codes require that a temperature and pressure relief valve should be installed the manufacturer recommends a type 40XL Watts T&P relief valve or an equivalent model be used.
English
Installation
NOTICE: Manual operation of relief valves should be performed
at least once a year. Turn o the electrical power and gas shuto
valve. Lift and release lever on the relief valve and check the manual operation of the relief valve. You should take precaution to avoid contact with the hot water coming out of the relief valve and to prevent water damage.
NOTICE: If the relief valve on the system discharges periodically,
this may be due to thermal expansion in a closed water supply
system. Contact the water supplier or local plumbing inspector on how to correct this situation. Do not plug the relief valve.
Leak Testing
WARNING:
Never use an open ame to test for gas
leaks, as property damage, personal injury, or death could result.
Pressure Testing the Gas Supply System
WARNING: Install a gas pressure regulator, in the gas supply line, which does not exceed the maximum supply pressure. DO NOT use an industrial type gas regulator.
The water heater must be isolated from the gas piping system by closing the manual gas shut-o valve during
any pressure testing of the gas supply piping at pressures equal to or less than 1/2 psi (14’w.c.) .
The water heater and its gas connections must be leak tested at normal operating pressures before it is placed in operation.
• Turn on the gas shut-o valve(s) to the water heater.
• Use a commercial leak detector or soapy water solution to test for
leaks at all connections and ttings. Bubbles indicate a gas leak that
must be corrected. All connections should also be leak tested after the water heater is placed in operation.
High Altitude
The Eccotemp i12 Gas Tankless Water Heater has been tested for use at elevations up to 2000 feet. Installation
and use of the Eccotemp i12 above 2000 feet may eect overall product eciency and performance. Installation
and use of the Eccotemp i12 above 5000 feet is not recommended.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
17
Page 18
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Venting
English
Installation
DANGER: Failure
to install the vent
adapter and properly
vent the water heater
to the outdoors as outlined in the Venting section of this manual will result in unsafe operation of the water heater causing death, serious injury, explosion, or
re. To avoid the risk of re, explosion,or
asphyxiation from
carbon monoxide,
NEVER operate the water heater unless it
is properly vented and has adequate
air supply for proper operation as outlined in the Venting section of this manual.
WARNING: Use
UL approved Category III Stainless Steel vent
material only. No
other vent material
is permitted. Owner
must refer to vent manufacturer’s
instructions and
specications. Z-Flex
information can
be found at www. novaex.com, see
page 18 for additional links.
The installation of venting must comply with national codes, local codes, and the vent manufacturer’s instructions. Owner must refer to vent manufacturer’s instructions and
specications. Z-Flex information can be found at www.novaex.com,
please refer to page 18 for additional links.
The water heater must be vented to the outdoors as described in these instructions. DO NOT connect this
water heater to an existing Vent or
Chimney: it must be vented separately from all other appliances.
All vent components (adapters, pipe, elbows, terminals, etc.) should be UL
1738 Certied Stainless Steel Venting
Material (e.g. AL29-4C).
The specied vent termination must
be used. The termination must be used. The termination should be a 90° elbow type with screen. (Refer to page 18).
Use a vent pipe with an antidisconnection structure. The use of a High Temperature Silicone (500° F) may be required to seal vent connections. To prevent
accidental gas exhaust leakage, apply a ¼” wide bead approximately ¼” from the end and another bead
against the joint side of the stop bead.
Follow vent manufacturer’s installation instructions. The unit can be vented either horizontally or vertically.
Vent pipe runs must be adequately supported along both horizontal and vertical runs.
The maximum recommended
unsupported span should be no more
than ve (5) feet. Support isolation
hanging bands should be used. DO NOT use wire. (See diagram below).
2 Degree Downward Slope.
WARNING: Refer to pages 16-17 for clearances to
combustible material.
If the vent piping passes through a closed space, wrap the vent pipe with inammable insulation material that is at least 3/4” thick. DO NOT let the insulation material make contact with ammable materials. A minimum clearance of 6” between the vent pipe and ceiling should be maintained. Follow local codes.
For maintenance and inspection purposes, the following holes are required to be made:
• Two (2) inspection openings that allow access to venting. One ( 1) of these openings should be close to where the vent pipe enters the ceiling. The other opening should be near the vent termination.
• A ventilation hole with a 16 sq. in. opening should be made at least every 10 feet.
NOTICE : Vent pipes must be completely insulated with
inammable material when installed in alcoves, closets, and garages and must not touch any ammable
material.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
18
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
Page 19
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Venting
Maximum Vent Length
Owner must refer to vent manufacturer’s instructions and specications. Z-Flex information can be found at www.novaex.com, please refer to page 18 for additional links.
The system will not operate if there is excessive restriction (pressure
Number of
90° elbows
(bends)
1
2
3
One (1) 90° Elbow is
Equivalent to 5 Feet of
Straight Pipe
Maximum
Length of
Straight Pipe
32’
27’
22’
drop) in the venting system. A maximum of 32 feet of vent pipe
may be used provided there is only one 90° elbow in the system. If additional elbows are required: two elbows can be used with 27 feet, and three elbows can be used with 22 feet of vent pipe.
A 90° elbow is equivalent to 5 feet of straight pipe. A 45° elbow is equivalent to 2 feet 6 inches of straight pipe.
The termination elbow does not count as an elbow when determining total vent lengths.
The vent must be installed with a slight downward slope of ¼” per
foot of horizontal run toward the vent terminal (see diagram below). This ensures that any condensate formed during operation of the unit evacuated from the water heater.
A ¼” per foot upward slope is acceptable when it is not possible to
vent with a downward slope, however, a UL approved Category III Stainless Steel condensate trap MUST be installed at the beginning of the horizontal run (See page 20 “Typical Horizontal Termination
w ¼” per foot UPWARD Slope” or page 14, “Standard Vertical Vent Termination” for examples).
English
Installation
Minimum Vent Length
The venting may be as short as 12”,
provided one vent termination is installed to the outdoors through a sidewall, one 90° elbow is included in the installation, and the wall thimble is installed.
NOTICE: Make sure that the seam of the vent pipe in horizontal runs is toward the top of the installation (see illustration to the left)
Draining the Condensate
In certain conditions, installations in unconditioned space or having long horizontal or vertical runs may accumulate condensate.
Condensate is known to be acidic; refer to local, state (provincial) or federal codes for proper handling methods.
In order to prevent condensate from draining back into the water heater, we recommend a condensate trap and drain to be installed in a horizontal vent section as close as practical to the water heater vent connection.
Not following proper condensate procedures will void warranty.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
19
Page 20
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Venting
English
Installation
Termination Clearances
Clearance Requirements from Vent Terminations to Building Openings
*All clearance requirements are in accordance with ANSI Z21.10.3a-2017 and the National Fuel Gas Code, ANSI Z223.1
Maintain the following clearances to any
opening in any building:
• 4’ below, 4’ horizontally from, or 1’ above any door, operable window, or gravity air inlet into any building.
• 3’ above any forced air inlet within 10’.
Vent Clearances When
Heater is Installed Indoors
A) A minimum clearance value determined by testing in accordance with Clause 5.20, or;
B) A reference to the following footnote:
“Clearance in accordance with local installation codes and the requirements of the gas supplier.”
• A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
• Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
Illustration
Notes:
1) In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code
2) In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Cod
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
20
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Page 21
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Venting
Ventilation Parts
Owner must refer to vent manufacturer’s instructions and specications by visiting www.novaex. com. Installation guidelines for venting is provided by NovaFlex, who is solely responsible for venting
installation accuracy.
Z-Flex parts are available for purchase by visiting www.eccotemp.com.
Z-Flex Installation Instructions: www.novaex.com/information_centre/zex/032-Vent%20Residential/Z-Vent%20Installation%2Guide%
20CURRENT.pdf
Z-Flex Ventilation Parts:
https://www.eccotemp.com/installation
Part Name Description SKU# Description
i12 90 Degree Elbow Stainless Steel 90° Elbow 1200031 90 Degree Elbow
Eccotemp 2.5" to 3" Vent Adapter
Eccotemp 3" Horizontal Vent Kit
Eccotemp 3" Vertical Vent Kit
i12 Termination Pipe Stainless Steel Termination Pipe 1001029 i12 Termination Pipe
i12 Wall Thimble
Replacement
i12 18" Vent Extension Stainless Steel Vent Extension: 18" 12000300 i12 18" Vent Extension
Stainless Steel Adapter 2SVPA03 2.5" to 3" Adapter Paloma
Stainless Steel Horizontal Vent Kit 2ZVEWD03 3" Vent Kit Horizontal
Stainless Steel Vertical Vent Kit 2SVSRPKE03 3" Vent Kit Vertical
Stainless Steel Wall Thimble 1200034 i12 Wall Thimble
English
Installation
Part# 2SVSTB03
Outside wall
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
21
Page 22
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Venting
English
Installation
Installation
Only the 2.5” vent kit provided with the i12 or approved Z-Flex Stainless Steel venting should be used for installation.
The wall thimble requires mechanical support from the wall suf­fucuent to support any incidental loads on the system. If the wall is not sucient enough to support the wall thimble, then appropri­ate additional framing and/or blocking is required.
Installation Procedure:
Prepare an opening for the wall thimble in the wall. The opening
must be 6-1/2 inches in diameter for a 3” vent system. The opening
should be round.
The opening must be able to accommodate the 2” vent system and
wall thimble provided. Consult manual or building codes for distance
from amable materials.
The wall thimble is designed to adapt to any wall thickness from
3-1/2” to 6” thick. If the wall is thicker than 6” the wall thimble may be extended using a piece of 6” diameter snaplock or welded seam galvanized pipe up to 6” long.
Select the larger diameter half of the wall thimble for the outside of the wall.
Outside wall
Apply a continuous bead of high quality silicone or silicone/la-
tex caulk on the inside of the outer ange. This will be the only
weather seal to keep moisture outside the building. Ensure a
sucient seal is made.
Position this portion of the wall thimble into the prepared hole from the outside. Secure the assembly into the prepared open­ing using fasteners as indicated by sheathing or structural mem­bers, sealing the screw heads with more caulking.
Use 4 hollow wall anchors, at least 1/8” in diameter and of appropri­ate length for the thickness of the sheathing, if sheathing is particle
board or other composite material. Use 4 #10x1-1/4” wood screws
for plywood, solid wood sheathing or members. Use suitable mason­ry anchors when passing through solid masonry walls. Reinstall the decorative sheathing around the wall thimble. This assembly may be
painted to match the exterior decor.
Slide the interior portion of the thimble into the inside hole. Be
certain the interior and exterior thimble halves overlap at least 1”. If insucient overlap exists, extend the interior portion with
single wall galvanized pipe.
Secure the vent section that protrudes through the wall thimble to the 90 degree elvbow attached to the water heater.
The exhaust pipe should be sloped downward at an approximate 3 degree grade in order to avoid rain (or condensation entering
the heater) through the exhaust pipe.
WARNING: Use UL approved Category III vent material only. No other vent material is
permitted. Owner must refer to
vent manufacturer’s instructions and specications. Z-Flex information can be found at www.novaex.com, refer to page
18 for additional links.
CAUTION: Follow the vent
manufacturers installation
instructions as design might vary
om manufacturer to manufacturer.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
22
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Page 23
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Venting
Continued...
WARNING: Field wiring connections and electrical grounding must comply with local codes,
or in the absence of local codes, with the latest edition of the National Electrical Code,ANSI/
NFPA 70, or in Canada, Canadian Electrical Code, CSA C22.1Part1.
Electrical Connection
POWER CORD:
English
Installation
The electric power supply requirement for this water heater is 120 VAC/60HZ, 2 Amps.
The water heater comes with a three (3) pin power supply cord. Use only a power outlet with a ground terminal.
The installation of an electric leakage breaker is recommended. (GFCI)
Keep any excess of the power supply cord on the outside of the water heater.
WARNING: Shock hazard line voltage is present. Before servicing the water heater, turn o the electrical power to the water heater at the main disconnect or circuit breaker. Failure to do so could result in severe personal injury or death.
Electrical Wiring Diagram
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify correct operation after servicing.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
23
Page 24
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Pipe Insulation
English
Installation
Insulation blankets, available to the
general public, for external use on
gas water heaters are not necessary. The purpose of an
WARNING: If
local codes require
external application of
insulation blanket kits the manufacturer’s
instructions included
with the kit must be
carefully followed.
insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. This water heater does not store water making an insulation blanket unnecessary.
The manufacturer’s warranty does not cover any damage or defect caused by installation, attachment or use of any type of energy saving
Inlet Pipe and Outlet Pipe Installation
Use pressure resistant pipe to connect the inlet and outlet water pipes of the water heater and the local water pipe (Make sure to place the rubber ring).Before connecting the
inlet water pipe, ush the inside of the pipe.
or other unapproved devices (other than those authorized by the manufacturer) into, onto or in conjunction with the water heater.
The use of unauthorized energy saving devices may shorten the life of the water heater and may endanger life and property.
The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized devices.
Hot and Cold Pipe Insulation Installation
For increased energy eciency,
use pipe insulation. Please install the insulation, according to the instructions above, making sure to insulate all the way to the top. Do not cover any drain or pressure valve(s).
NOTICE: The hot and cold pipes
should be insulated as shown help to provide additional freeze protection
During Installation of this water heater
Do’s
DO check inlet gas pressure to ensure that it is within the range specied on the rating plate.
DO provide adequate air for combustion and ventilation as discussed in the Use & Care Manual and the
National Gas Code (CAN/CGA B 149 in Canada).
DO maintain proper clearances to combustibles as specied by applicable code.
DO ensure that the ue terminal location complies with the guidelines found in the Use & Care Manual and
National Fuel Gas Code (CAN/CGA B 149 in Canada).
Dont’s
DON’ T block or restrict the air intake opening located on the back side of the water heater.
DON’ T remove the front cover unless absolutely necessary. This should only be done after being examined by
a qualied service technician.
DON’ T install this product where standing water may occur.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
24
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Page 25
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Mounting
Make sure the location of the water heater allows for easy access and operation.
In case of dry wall or concrete wall use dry wall anchors or lag bolts.
The water heater requires 120VAC/ 60Hz. Have a receptacle with ground terminal near the water heater. The length of the power supply cord is 5 feet.
Drill the holes as per the sizes in the gure to the left, put 2 expansion screws into the top holes, and 2 rubber screws into the
bottom holes.
Hang up the water heater unit, tighten the expansion screws, and put
2 wood thread screws into the bottom holes.
CAUTION: Reinforcement of the wall is required in case the wall is
not strong enough to hold the water heater.
Indoor units must be installed with CAT III
Sealant
3.9”
vent pipe in acc ordance with vent
supplier/ Manufacturer in accordance with
local code. Owner must refer to vent
4.8”
manufacturer’s instructions and specications. Z-Flex information can be found at www.novaex.com, please refer
to page 18 for additional links.
English
Installation
3.9”
2.9”
Back Installation
Side Installation
5.5”
5.5”
A. BACK INSTALLATION
1. Insert the vent pipe through the installation holes in the wall with the terminal sticking out.
2. Connect the elbow to the vent pipe and water heater, moving straight backwards
until the expansion screws go into the holes
of the water heater. Screw the nuts tight (pay attention to the direction of the elbow).
B. SIDE INSTALLATION:
1. Aim the holes in the water heater onto
3.9”
the expansion screws, hang it up and screw
the nuts tightly.
4.8”
2. Put the vent pipe through the holes in the wall, and connect the elbow with the water heater and vent pipe.
C. VERTICAL INSTALLATION
Please refer to local installation professional or venting manufacturer:
The installation hole in the wall needs to
be sealed by re-retardant material or wall
thimble, making sure the water heater is tight
and will not come o.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
25
Page 26
English
Installation
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Installation Checklist
A. Water Heater Location
Installed indoors. Close to area of mostly used outlet. Protected from freezing temperatures. Proper clearance from combustible surfaces observed.
Sucient fresh air supply for proper operation of water heater. Air supply free of corrosive elements and ammable vapors.
Provisions made to protect area from water damage.
Sucient room to service heater.
Combustible materials, such as clothing, cleaning materials, rags, etc. clear of the heater and vent piping. Water heater is properly attached to the wall.
B. Water Supply
Water supply has sucient pressure.
Air purged from water heater and piping. Water connections tight and free of leaks
Water lter is clean and in place.
Materials used are as instructed in this manual. Water pipes are insulated.
C. Gas Supply
Gas type matches rating plate.
Gas supply pressure is sucient for the water heater. Gas line equipped with shut-o valve, union and sediment trap.
Approved pipe joint compound used. Commercial leak detector or soap and water solution used to check all
connections and ttings for possible gas leak.
Gas Company inspected installation (if required).
D. Relief Valve
Pressure Relief Valve properly installed and discharge line run to open drain Discharge line protected from freezing.
E . Electrical Wiring
Voltage matches rating plate. Water heater is properly grounded . Wiring meets all local codes. GFCI Protection where required.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
26
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Page 27
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Start Instructions
Before operating this water heater, be sure to read and follow the instructions on the label pictured below and all other labels on the water heater, as well as the warnings printed in this manual. Failure to do so can result in unsafe operation of the water heater resulting in property damage, personal injury, or death. Should you have any problems reading or following the instructions in this manual. STOP, and get help from
a qualied person.
FOR YOUR SAFETY BEFORE USING THE WATER HEATER
WARNING: If you do not follow these instructions exactly, a re or
explosion may result causing property damage, personal injury or loss of life.
A. This water heater does not have a pilot. It is equipped with an ignition device which automatically
lights the burner. Do not try to light the burner by hand.
B. BEFORE OPERATING smell all around the water heater area for gas. Be sure to smell next to the
oor because some gas is heavier than air and will settle on the oor. Test all connections with
a commercial leak detector or soapy water.
WHAT TO DO IF YOU SMELL GAS
DO NOT try to light any appliance • DO NOT touch any electric switch; DO NOT use any
phone in your building. • Immediately call your gas supplier from a neighbor’s phone. Follow
the gas supplier’s instructions. • If you cannot reach your gas supplier or re department. • DO
NOT return to your home until authorized by the gas supplier or re department.
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not
push in or turn by hand, don’t try to repair it, call a qualied service technician. Force or
attempted repair may result in a re or explosion.
D. DO NOT use this water heater if any part has been under water. Immediately call a qualied
service technician to inspect the water heater and to replace any part of the control system and any
gas control which has been under water.
OPERATING INSTRUCTIONS
English
Operating
1. STOP! Read the safety information above on this label.
2. Turn o all electric power to the water heater.
3. Set the thermostat to lowest setting.
4. DO NOT attempt to light the burner by hand.
5. Turn the Gas Shut-o Valve located on the outside of the
unit clockwise to the “OFF” position.
6. Wait ve (5) minutes to clear out any gas. If you smell gas, STOP! Follow “B” in the safety
information above on this label. If you don’t smell gas, go to the next step.
7. Turn the Gas Shuto Valve located on outside of the unit counterclockwise to the “ON” position.
8. Turn on all electric power to the water heater.
9. Set thermostat to desired setting.
10. If the water heater will not operate, follow the instructions “To Turn O Gas To water
heater” and call your service technician or gas supplier.
TO TURN OFF GAS TO WATER HEATER
1. Turn o all electric power to the water heater if service is to be performed.
2. Turn the Gas Shut-o Valve located on the outside of the unit clockwise to the “OFF” position.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
27
Page 28
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Start Instructions
English
Operating
Continued...
Turning on the Water Heater
1. Make sure the gas type you will use is same as the type on the data plate.
2. Turn on the main gas valve, plug in the power cord (be sure the socket is well grounded), and
press the “ON/OFF”button on the control panel. Set temperature to 120° F.
3. Turn on the faucet, and the fan will begin working. You will hear the ignition sound after a few seconds. The burner will ignite, and hot water will come out. If the burner is not ignited successfully, the ignition sound will last a few seconds. If the burner still fails to ignite, turn
o the faucet and wait for 10-20 seconds, and repeat the above procedures.
For rst use and/or if the water heater has not been used for a considerable period of time, the
repeat of the above procedures may be required, due to accumulated air inside the gas pipe.
Safety Precautions
If there is any diculty in understanding or following the Operating Instructions or the Care and Cleaning section, it is recommended that a qualied person or serviceman perform the work.
DO turn o manual gas shut-o valve if water heater has been subjected to over
heating, re, ood, physical damage or if the gas supply fails to shut o.
DO NOT turn on water heater unless water and gas supplies are fully opened.
DO NOT turn on water heater if cold water
supply shut-o valve is closed.
DO NOT install in a laundry room.
DO NOT allow combustible materials such as newspaper, rags or mops to accumulate near water heater.
DO NOT store or use gasoline or other
ammable vapors and liquids, such as
adhesives or paint thinner, in vicinity of this or any other appliance. If such
ammables must be used, open doors
and windows for ventilation, and all gas burning appliances in the vicinity should
be shut o including their pilot lights, to
avoid vapors lighting.
NOTICE: Flammable vapors can be drawn by air currents from surrounding areas to
the water heater
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
28
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Page 29
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Water Temperature
DANGER: There is a hot water scald potential if the temperature is set too high. Households with
small children, disabled, or elderly persons may require a 120°F or
lower temperature setting to
prevent contact with HOT water.
Water Temperature
120°F
125°F
130°F
135°F
140°F
145°F
150°F
155°F
Table courtesy of Shriners Burn Institute
Time To Produce a Serious Burn
More than 5 minutes
1 1/2to 2 minutes
About 30 seconds
About 10 seconds
Less than 5 seconds
Less than 3 seconds
About 1 1/2 seconds
About 1 second
Output temperature of water is regulated by setting the temperature on the front of the unit. Safety factors should be considered when selecting the water temperature.
Water temperature above 120°F can cause severe burns or death from scalding. The thermostat is adjusted to its lowest temperature position when shipped from the factory.
Be sure to read and follow the warnings outlined in this manual and on the label located on the water heater.
Mixing valves are available for reducing point of use water temperature by mixing hot and cold water in
branch water lines.
Procedures for adjusting the thermostat for energy
ecient operation at the minimum water temperature
setting consistent with the consumer’s needs.
Contact a licensed plumber or the local plumbing authority for further information.
English
Operating
Setting the Temperature:
The Eccotemp i12-LP/NG models are AUTOMATIC TEMPERATURE CONTROLLED tankless water
heaters. You will need to set your maximum
temperature on the i12 Gas Tankless Water Heater and then adjust your sink or shower water temperature at the source.
The i12 is a ow activated unit and should maintain
at least 0.6 GPM to activate and 0.6 GPM to maintain ativation.
Turn Water Heater
On/O
Enable
Child-Lock
Increase
Temperature
Decrease
Temperature
Automatic vs. Manual Temperature Control
The i12 is an automatic temperature controlled tankless water heater. Below explains the dierences between an automatic
and manual temperature controlled tankless water heater. For additional questions please visit support.eccotemp.com.
Automatic Temperature Control: The unit will self-adjust temperature according to what is being requested of at the output water source (sink or shower). It also will regulate the temperature automatically according to how many applications are being used at the same time.
Manual Temperature Control: You must adjust the temperature manually each time you use the unit. The temperature must be adjusted according to the amount of applications being used at the same time due to the
uctuation of pressure.
NOTICE: If inlet water temperature is high, and set
temperature is low, the actual temperature might be higher than the set temperature, and viceversa..
WARNING: Should overheating occur or the gas supply fail to shut o, turn o the manual
gas control valve to the water heater.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
29
Page 30
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Housekeeping
English
Maintenance
DANGER: Before
manually operating
the relief valve, make
certain no one will
be exposed to the
danger of the hot
water released by the valve. The water may be hot enough to
create a scald hazard.
The water should be
released into a
suitable drain to prevent injury or
property damage.
DANGER: Hotter water increases the potential for Hot Water Scalds.
DANGER: Failure to perform the recommended
Routine Preventative
Maintenance can harm the proper operation of this water heater, which
can cause carbon
monoxide dangers,
excessive hot water
temperatures and other potentially hazardous conditions.
Properly maintained, your water heater will provide years of dependable trouble-free service. It is recommended that a periodic inspection of the burner,
relief valve, water lter and venting
system should be made by service
personnel qualied in gas appliance
repair.
It is suggested that a routine preventive maintenance program be established and followed by the user.
At least once a year, lift and release the lever handle on the pressure relief valve, located in the hot outlet piping of the water heater, to make certain the valve operates freely. Allow several gallons to
ush through the discharge line to an
open drain.
Rapid closing of faucets or solenoid valves in automatic water using appliances can cause a banging noise heard in a water pipe. Strategically located risers in the water pipe system or water hammer arresting devices can be used to minimize the problem.
Inspect the area around the water heater to ensure a safe operating environment. Keep water heater area clear and free from combustible materials, gasoline, and other
ammable vapors and liquids. Ensure
the unit has not been damaged. If damage or denting is present, contact a service personnel to verify proper operation.
Check for any abnormal sounds during normal operation of the water heater.
All piping should be checked for gas and/or water leaks. Refer to page 14 of this manual for instructions on leak testing.
The air intake and cold water supply
lters should be cleaned monthly. Refer to the “Housekeeping” section for
further information.
DO NOT operate the water heater if you feel something is wrong with the unit.
DO NOT allow children to operate or otherwise handle the unit.
NOTICE: If the pressure relief valve on the hot water heater discharges periodically, this may be due to a problem in the water system. Contact the water supplier or your plumbing contractor on how to correct this. DO NOT plug the relief valve outlet.
NOTICE: After inspection, maintenance, and/ or cleaning, ensure proper operation by turning on
a hot water faucet.
Before performing any Housekeeping tasks to this water heater, be sure to turn the unit o and disconnect
the power supply.
Vacuum around the water heater for dust, dirt and lint on a regular basis. Clean the water heater and remote control by using a damp soft cloth with a few drops of mild detergent and gently wiping the surfaces of the unit. Wipe any remaining moisture with a dry soft cloth.
To ensure sucient ventilation and combustion air supply, proper clearances must be maintained. The water lters should be cleaned on a monthly basis. Combustion system is fan-assisted
CLEANING THE WATER HEATER:
• Make sure the unit is OFF and the electrical power supply has been disconnected.
DO NOT scrub the appliance with a brush.
• Use only mild soapy water, other cleaners may damage the surface of the water heater.
DO NOT remove any label including the rating plate while cleaning or servicing.
DANGER: Shock Hazard. Make sure the electrical power to the water heater is o to avoid potential
serious injury or damage to components.
DANGER: Combustible materials, such as clothing, cleaning materials, or ammable liquids, etc., must not be placed against or next to the water heater.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
30
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
Page 31
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Cleaning the Water Filter
HOW TO CLEAN THE WATER FILTER:
1. Make sure the unit is OFF and the electrical power supply
2. has been disconnected.
3. Turn the water supply OFF to the heater.
4. Disconnect the water source from the water inlet.
5. Use a screw driver and gently remove the lter from inside the water inlet.
6. To remove severe dust, use a soft brush and wash with running water.
7. Return the lter to the water heater inlet pipe and reconnect your water supply.
8. Turn the electrical power supply and cold water supply ON to the water heater.
Extended Shut-Down
If the water heater is to remain idle for an extended period of time, the power and water to the appliance should be turned o.
The water heater and piping should be drained if they might be subjected to freezing temperatures.
After a long shut-down period, the water heater’s operation and controls should be checked by qualied
service personnel.
English
Maintenance
Draining your Water Heater
When the temperature falls below 32°F, water in your plumbing system or water heater can turn to ice and
then expand causing damage to the water heater. This damage is not covered under your manufacturer’s
warranty. If these conditions are anticipated, please drain the water heater as follows to help but not guarantee from freezing. Below are instructions for draining water out of the water heater.
1. Close the gas shut-o valve(s).
2. Close the water shut-o valve.
3. Turn the on/o switch to the OFF position and disconnect breaker at least 10 seconds after step #1.
4. Open drain valve.
5. Open all hot water faucets. Before proceeding to the next step, make sure that COLD water is coming out of
all hot water faucets.
6. To put the water heater back into operation after draining, follow the steps below.
7. Reinstall the water lter. Close the hot water outlet drain valve.
8. Open the water shut-o valve and close again after making sure that water comes out from hot water faucets.
(This step is to remove air from the water lines).
9. Reconnect the breaker and turn the on/o switch to the ON position, fully open the gas shut-o valve and the
water shut-o valve.
NOTICE: The water heater may not operate unless the above procedure is followed correctly.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
31
Page 32
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Draining your Water Heater
English
Maintenance
CONTINUED...
WARNING: Failure to follow these instructions while draining the water heater can cause serious damage to the water heater as well as personal injury including scalding.
6 Month Cleaning Routine
To prevent water scale, lime or rust deposit buildup and ensure your Eccotemp tankless
water heater is running as eciently as possible it is highly recommended that you
clean your Eccotemp tankless water heater every 6 months. To do this we recommend
that you use our Eccotemp EZ-Flush System Descaler Kit. For more information and to
purchase please visit us at www.eccotemp.com or call 1-866-356-1992.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
32
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Page 33
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Parts List
To purchase replacement parts for your i12 Gas Tankless Water Heater please contact Technical Support support@eccotemp.com or 1-866-356-1992.
Contact Eccotemp to place orders for any parts.
All parts orders should include:
The model and serial number of the water heater from the
WARNING: For your safety,
DO NOT attempt to disassemble
this unit for any reason
rating plate.
Specify type of gas (natural or LP) as marked on the rating plate.
Part description (as noted below) and number of parts desired.
English
Maintenance
CAUTION: For your safety, DO NOT attempt repair of electrical wiring, gas piping, burners, or other safety devices. Refer repairs to qualied service personnel.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
33
Page 34
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Before you call
English
Troubleshooting
Problem
Not enough or
no hot water
Save time and money! Review the charts on the following pages rst and you may not
need to call for service. This water heater incorporates a variety of shut o devices that
prevents the operation of the water heater down if undesirable combustion conditions
occur. Such as the presence of a blockage of the combustion air vent insucient gas
or pressure which can impact the safe operation of the water heater. Please contact a
Qualied Service Technician if this occurs.
Possible Cause
Water shuto valve is not fully opened.
The ow restrictor may be open too much.
Hot water faucet is not fully opened
Water piping is frozen Allow piping to thaw.
No electricity or water supply is cut o.
Unit is not “ON”.
Check shuto valve and open fully.
Adjust the ow restrictor in the (-) direction to reduce the amount of water ow.
Open hot water faucet completely. (The main burner goes o when incoming water volume is inadequate.
Check that proper power is being supplied and/or water supply is adequate.
Turn the unit “ON” by the button on the remote control.
What To Do
Water not
hot enough.
Water too hot
The temperature may be set too low
Mixing Valve malfunction (if applicable).
Error code displayed on remote control panel
The temperature may be set too low.
The ow restrictor may be open too much.
The gas valve is not fully opened.
The temperature is set too high
The ow restrictor may be closed too much.
Water shuto valve is not fully opened.
Small amount of water has been heated.
Increase the temperature setting.
Check and replace if necessary.
See instructions for Error Code and if required, contact a dealer for service.
Increase the temperature setting.
Adjust the ow restrictor in the (-) direction to reduce the amount of water ow.
Check and open the gas valve fully.
Decrease the temperature setting.
Adjust the ow restrictor in the (+) direction to increase the amount of water ow.
Check shuto valve and open fully.
Allow more water to ow by adjusting the ow restrictor in the (+) direction.
Water lter is clogged Clean the lter with a tooth brush.
Fan continues
to rotate after
hot water faucet
This function is to purge unburned gas 10-15 seconds.
Normal operation. There is no need to call for service. Check for error code.
is closed.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
34
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Page 35
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Error Code Guide
When an error code is displayed:
• Close the hot water faucet.
• Wait for 5 minutes before turning the unit on again.
• Open the hot water faucet.
NOTICE: If an error code other than those listed
below is displayed, immediately turn o the hot
water faucet, take note of the error code, turn
o the switch on the remote control and call the customer assistance number.
Error
Code
E0
E1
Error Description Possible Cause What To Do
Hot water sensor failure
Ignition system failure
Junction port loose, Short circuit
The gas valve is not opened or fully opened, Water shut-o valve is not open, Junction port loose
If the error code remains shown:
Close the hot water faucet.
Take the proper action shown below and attempt operation of the water heater again.
If the error code is still shown:
Turn o the hot water faucet.
Take note of the error code displayed and call the customer service assistance number
in the “If You Need Service” section.
Call for Service
Check and open gas fully, Check and open water valve, Call for Service
English
Troubleshooting
There is ame when no
E2
water coming in
Over-heating
E3
protection
Cold water
E4
temperature sensor
Pressure Switch
E5
Over-heating
E6
solenoid valve
E7
vent pipe block vent pipe is blocked clean the pipe
E8
Electric circuit problem Call for Service
Dry Combustion, Problem of over heating controller
problem with sensor, problem with sensor’s plug or socket, none of the above
Motor problem, Voltage of power supply is too low
Gas pressure is too high, Water shuto valve is not fully opened, The temperature is set too low
open circuit of the valve, short circuit of the valve, none of the above
Call for Service
replace the sensor, x it, replace the computer board
Call for Service
Check shut-o valve and open fully, Increase temperature setting
connect the valve, replace the valve, replace the computer board
CAUTION: For your safety DO NOT attempt repair of gas piping, remote control,
burners, vent connectors or other safety devices. Refer repairs to qualied service
personnel.
CAUTION: Make certain power to water heater is “OFF” before removing protective cover FOR ANY REASON.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring
errors can cause improper and dangerous operation. VERIFY PROPER OPERATION AFTER SERVICING.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
35
Page 36
English
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Eccotemp Systems ,LLC Limited Warranty Information
Model(s) i12-LP and i12-NG
Eccotemp hereby warrants this product to be free of material defects in materials and workmanship when installed
and operated according to Eccotemp’s installation and operating instructions. This Limited Warranty extends to the
original purchaser and subsequent owners, but only while the product remains as the site of the original installation.
This Limited Warranty terminates if moved or reinstalled at a new location. There are no warranties, express or
implied made or given other than contained in this Limited Warranty. No agent, employee or representative of Eccotemp has any authority to bind Eccotemp to any representation or warranty concerning the Product not contained in this Limited Warranty. Eccotemp reserves the right and authority to change, modify or alter this warranty at any given time.
Except as expressly set forth herein, THERE ARE NO REPRESENTATIONS OR WARRANTIES, EXPRESS OR IMPLIED,
INCLUDING, WITHOUT LIMITATION, AS TO MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO ANY GOODS SOLD HEREUNDER. BUYER’S EXCLUSIVE REMEDY IS LIMITED TO REPAIR OR REPLACEMENT OF THE GOODS SOLD, AT ECCOTEMP’S DISCRETION. ECCOTEMP SHALL NOT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Limited Warranty Period
This Warranty is extended by Eccotemp Systems to the Owner. This warranty takes eect on the date of installation of the Product or 30 days after the date of purchase, whichever occurs rst, and is eective until the specied
anniversary of such date as follows:
1) Limited Two-Year replacement (years 1 through 2) of defective parts other than the heat exchanger- Labor not
included.
2) Limited additional Two-Year replacement (years 1 through 2) on the heat exchanger when the Product is used in a
single-family dwelling – Labor not included.
3) Limited additional Two-Year replacement (years 1 through 2) on the heat exchanger when the Product is used for
commercial capacity, if it is used in other than a single family dwelling, or if the Product is supplied with pre-heated or circulated water – labor not included.
Item Period of Coverage
Heat Exchanger 2 years
All other parts 2 years
Coverage’s are void if the unit is used in a hot water circulation loop, in series with a circulation system or where an on-demand recirculation system is not incorporated.
Owner is responsible for all other costs incidental to repair such as labor, shipping, delivery and permits. Proof of purchase required. Products repaired will be covered under this Limited Warranty for the remainder of term of the original purchase.
Shipping Related Costs:
Within the rst 30 days of purchase, Eccotemp will cover all ground shipping costs for warranty related issues, excluding AK, HI, Canada, and any location outside of the continental US. After the rst 30 days of purchase, Eccotemp will cover all ground non expedited shipping costs to the customer for warranty related issues, excluding AK, HI, Canada, and any location outside of the continental US. After the rst 30 days of purchase, the customer is
responsible for all shipping to Eccotemp, regardless of reason or circumstance. The method for warranty related shipping will be Ground equivalent with the provider of Eccotemp’s choosing.
AK, HI, Canada, and any location outside of the continental US, will be responsible for all shipping costs, regardless of reason or circumstance.
All shipments of any type of product coming to Eccotemp for any reason must have an RGA for any repairs to be made. Please contact Eccotemp to obtain an RGA number prior to shipping anything to Eccotemp. Failure to do so could result in loss of product. Eccotemp will not be responsible for replacement due to loss or damage if these steps are not properly followed.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
36
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Page 37
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Exclusions
Please refer to the Installation Manual and Use & Care Manual supplied with your new Eccotemp Systems product. This Limited Warranty becomes null and void if any of the following are determined to be a contributing factor by Eccotemp to the failure of the product:
1. Abuse, misuse, alteration, neglect or misapplication.
2. mproper, dangerous, destructive maintenance procedures or inadequate maintenance.
3. Damages caused by services performed by servicers other than Eccotemp Systems.
4. Installation in a corrosive or otherwise destructive environment.
5. Damage as a result of freezing within the unit or surrounding piping.
6. Scale buildup.
7. Incorrect gas or water pressure.
8. Acts of force Majeure.
9. Damage as a result of use with non-portable, untreated or poorly treated well water, or water with high PH
levels or hardness levels in excess of 12 grains per gallon (200mg/L).
10. Incorrect sizing for the application.
11. Products with original serial numbers that have been removed or altered and cannot be readily determined.
12. Acts of God including, but not limited to; re, ood, or nature disaster.
English
This Product is not to be used as a pool or spa heater.
In the event of an Eccotemp Systems recognized defect, malfunction, or failure to conform to this Warranty and based upon Eccotemp approval of warranty claim, Eccotemp Systems, at its sole and absolute discretion, will settle the warrant claim of such defect, malfunction, or failure to conform to this Warranty. In order to make a claim under this Warranty, The Owner must notify Eccotemp of the failure of the Product to conform to this Warranty.
Under this Warranty, Eccotemp Systems will only provide replacement parts as described in the “Limited Warranty
Period”. The Owner will be responsible for any cost incurred including labor costs for servicing the unit, shipping,
delivery, and handling of the replacement part, cost for permits or materials necessary for the repair, or incidental
costs resulting from damage external to the unit resulting from the failure.
NOTWITHSTANDING ANYTHING IN THIS WARRANTY TO THE CONTRARY, EXCEPT FOR ECCOTEMP SYSTEMS’ AFFIRMATIVE OBLIGATIONS EXPRESSLY SET FORTH IN THIS WARRANTY, ECCOTEMP SYSTEMS DISCLAIMS ANY AND ALL WARRANTIES, EITHER EXRESS OR IMPLIED, REGARDING THE PRODUCT AND ITS FUNCTIONALITY, PERFORMANCE, MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSE OR INTELLECTUAL PROPERTY RIGHTS. ECCOTEMP SYSTEMS DISCLAIMS ALL OTHER OBLIGATIONS OR LIABILITIES ON ITS PART AND NEITHER ASSUMES NOR AUTHORIZES ANY OTHER PERSON TO ASSUME FOR ECCOTEMP SYSTEMS AN OTHER LIABILITIES IN CONNECTION WITH THE PERFORMANCE OF THE PRODUCT. THIS WARRANTY ONLY COVERS REPLACEMENT PARTS AND DOES NOT COVER COST OF LABOR OR SERVICES UNDER ANY CIRCUMSTANCES.
This warranty only applies to the 50 states of the U.S.A and Territories of Canada. Eccotemp Systems shall not be liable for any claim or demand against Eccotemp Systems by any other part for damages of any kind, including, but not limited to incidental and consequential damages, arising out of the subject matter of this Agreement.
Some States do not allow exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specic legal rights. You may also have other rights that
vary from State to State.
PLEASE NOTE: i12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
37
Page 38
Loading...