ECB E10.14000.45 L-EUF, E10.12000.37 L-EUF Operating Manual

Page 1
Operation Manual
for the authorized specialist
Dual-fuel Burner E 10... L-EUF
06/2006 102.885.8162
Page 2
2
Inhalt
Overview Important Information Warranty Product Description .......................................... 3
Technische Daten ................................................................................................. 4
Dimensioned Drawings ......................................................................................... 5
Start-up Mode Oil Operating Mode General Safety Functions .............................. 6
Fuel-air Compound Control ................................................................................... 7
Hydraulic diagram L-E... / GL-E... Burner E 10 ..................................................... 8
Hydraulic Valves and Instruments Group .............................................................. 9
Start-up Burner Head Settings .......................................................................................... 10
Installation Mounting to Boiler Electrical Connection Presetting ........................................... 11
Boiler Lining ........................................................................................................ 12
Burner GL/L-EUF ................................................................................................ 12
Oil Connection Oil Pressure Control (Feed) ........................................................ 13
Nozzle rod linkage 32 - EH ................................................................................. 14
Start-up Return Nozzle Rod RDG 1250 ............................................................................ 17
Nozzle selection „Sonic“ ...................................................................................... 18
Checking Procedure ............................................................................................ 19
Adjusting Instructions Air Flow Rate Adjusting Procedure ..................................................................... 20
Elektronic Burner Control with Electronic Compound Controller ......................... 21
Flame Detecting System Type FLW 05 .............................................................. 22
Servomotor Type SAD 15.0 ................................................................................ 23
Electrical Actuator STM 40 .................................................................................. 24
Starting the BCS, Etamatic, VMS/FMS Electronic Compound Controller ........... 25
Adjusting Instructions Oil Pressure Switch Air Pressure Switch ........................................................... 26
Overview Flame monitor ..................................................................................................... 27
Flame monitor ..................................................................................................... 28
Fan Impeller ........................................................................................................ 32
Service Instructions Maintenance Burner ............................................................................................ 33
Exhaust Gas Test ................................................................................................ 35
Trouble Shooting Instructions ............................................................................. 36
Operating Trouble ............................................................................................... 38
System Diagram .................................................................................................. 39
Product description Brenner E10.12000/14000 L-EUF ....................................................................... 40
Overview
Page 3
3
Overview
Important Information Warranty Product Description
Important information
The burners of type E 10... L-EUF have been designed for the combustion of heavy fuel oil. The burners should be installed and taken into operation care
­fully by qualified personnel. The work should be done in accordance with the applicable regulations and guidelines. Only a duly authorized specialist should be entrusted with the installation of the gas system. Any repair work on monitors, limiters and automatic furnace controllers and on the other safety facilities are allowed to be done on the single items only by the manufacturers themselves or spe
-
cialists authorized by them. Original parts should only be exchan­ged by a duly qualified specialist.
Standards and regulations
The following standards should be observed in the interest of a safe, easy­on-the-environment and energy-saving operation of the burner:
EN267/ DIN4787
Oil Atomizing Bur­ners
VDE 0116 Electrical Equipment
of Furnaces
According to DIN 4755 the user must be instructed in the operation of the fur
-
nace system.
For the installation of an oil furnace sys­tem, care should be taken to observe DIN 4755, TRbF (Technical Regulation on Combustible Liquids) and the local furnace construction regulations appli
-
cable in the country.
Place of installation
The burner must not be operated in rooms containing corrosive vapours (e.g. spray, perchloroethylene, hydro
­carbon tetrachloride, solvent, etc.) and tending to heavy dust formation and only up to 60% relativ air humidity.
Adequate ventilation must be provided at the place of installation of the furnace system to ensure a reliable supply with combustion air.
Maintenance
The furnace system should be serviced at least once a year by an authorized specialist. It is recommended to con
­clude a maintenance agreement to this effect.
Warranty
Manufacturer will not accept any war­ranty if the operating instructions have not been duly observed in the start-up and maintenance of the burner and damages have been caused by impro
­per installation, incorrect adjustment, unauthorized interference or operating errors.
Product description
The burners of type E10...L-EUF have been designed as oil-burner for the combustion of heavy fuel oil according to DIN 51603-1. They are fitted with a free-flame burner head as a system to ensure low-NOx combustion.
The burners are equipped with combu­stion air fan and air pressure switch with test key, air box with actuator for the air dampers, oil pressure-atomizer with high-pressure oil pump, nozzle rod, return nozzle, and oil hydraulic system (with pressure switches, valves and control shaft), pressure hoses, electrical ignition system for the oil operating mode.
The burners are designed for operation with electronic compound control.
Page 4
4
Technische Daten
Gas-Gebläsebrenner E 10.12000/14000 G-EU2
LowNox mit Delta Brennkopf
Technical Data
Gas/light oil Forced Draught Burner
E10.12000/14000 L-EUF
Stand: 20.10.2005
Market Launch E10.14000 L-EUF Available not yet defined
Burner weight Approx . 650 kg plus 100 kg for transport rack CE-Conformity No CE-Confirmity, Equipment for heat generator, Single audit necessary (see
manufacturer declaration), Homologation according European directives planned for 2006
Acoustic Emission - Sound Pressure < 97 dBA (average value on enveloping surface at 1 m distance) Max. temperature of operating material max. 60°C (including impact from heat radiation)
Flame length max. at 3% O
2
5,9 m 6,4 m
Flame Diameter (depends on NOx requirements)
1,3 - 1,6 m 1,4 - 1,75 m
Protection Class IP40, IP54 as option NOx-Emissionen Emission Class 3 according EN267
Oil operation: 120-200 mg/kW h (0% O2 acc. EN267) Detailed values on request
Oil connection High pressure pump 30 bar mounted on burner
approx. 2700 l/h; 4,0 kW approx. 4000 l/h; 5,5 kW
Fan motor 400/690 V, 50/60 Hz, 2950/3550 U/min, IP55
37 kW 45 kW
Operation Type Continuously modulating Electronic Air-Fuel-Compound-Control Automatic Firing Device
Etamatik OEM or BCS 300 on burner Alternative electronic burner controls in separate cabinet
Fuels Fuel Oil EL Max. control ratio (FQ=frequency converter for motor)
1:3,5 bei Fuel oil EL 1:3,5 for Fuel oil EL
Deviating values on request
Low NOx with Free-Flame Combustion Technology Electronic Fuel-Air-Control
E10.12000.37 L-EUF E10.14000.45 L-EUF
Combustion Power Output Fuel Oil EL: 1500 - 12.000 kW Fuel Oil EL: 1750 - 14.000 kW
Boiler Furnace Pressure According line of operation field and 10 mbars less.
Deviating values on request.
Operation Fields E10 L-EUF according EN 267
0
5
10
15
20
25
30
35
40
0123456789101112131415
Combustion Power Output [MW]
Boiler Furnace Pressure [mbar]
E10.14000.45 L-EUF E10.14000.45 L-EUF with FQ E10.12000.37 L-EUF
Page 5
5
Overview
Dimensioned Drawings EK 10... L-EUF
EK 10...L-EUF
The cover of motor is removable in case of ope­ning boiler door for revi­sion
Drilling Template
Motor with disassembled protection grid
The air intake box can be rotated in steps of 22,5 °C, the swivelling function, however, is then not functional.
Note: In pecial cases, the air intake box can be mounted in a way that the opening shows to another direction. The dimen­sioned drawing will the differ slightly.
Page 6
6
Operation
Start-up Mode Oil Operating Mode General Safety Functions
Start-up mode
As soon as the furnace system is requi­red to supply heat the burner control cir­cuit will close and the program be started. After the program has run down the burner will start.
The air damper is closed when the
burner is out of operation.
The automatic furnace controller con­trols and monitors the starting function. The electric actuator opens the closed air damper to its full-load position so that the burner will sweep the furnace compartment and exhaust ports at the required air flow rates. Shortly after the pre-ventilation process has been star
­ted the lack-of-air cut-out must change over to operating position within a cer­tain time, i.e. the minimum air pressure setting must be reached and maintained until the burner is turned off. At the end of the specified pre-ventilation time the air damper will be moved into its partial­load position. This operation will be fol
­lowed by the pre-ignition procedure and the oil feed start.
The solenoid valves will open and thus allow the pressurized oil to flow to the nozzle and to the return line. The oil will be atomized, mixed with the combustion air and ignited. A safety period is provided to allow the flame to develop a proper and steady pattern. On the termination of the safety period, a flame signal must have been received by the automatic furnace con
­troller via the flame monitor and remain on until the regular shut-off. The start­up program of the burner has now been completed.
Oil operating mode
After flame formation, the burner will shortly remain in the separately set igni­tion load, and is then run to minimum output. Then the oil feed will start for load regulation. The load regulator will now control the burner automatically between its partial-load and full-load stages.
Depending on the heat rate required the servomotor will via the controller be given an "open" or "close" signal and thus increase or decrease the oil and air flow rates.
This compound control concept will vary the position of the oil control valve and air damper and thus adjust the oil flow rate in relation to the air flow rate. The stepless control will allow the bur­ner to be operated at any desired stage between its partial-load and full-load positions. The air damper will be closed when the burner is out of operation and will thus prevent cold air flowing through the burner chamber, heat exchanger and chimney. The interior cooling los
-
ses will be greatly minimized.
General safety functions
In case a flame does not develop when starting the burner (fuel release) the bur­ner will shut off at the end of the safety period (shut-off on trouble). A shut-off on trouble will also occur in the case of flame failure during operation, air flow failure during the pre-ventilation phase and pres­sure failure during the whole period of bur­ner operation. Any failure of the flame signal at the end of the safety period and a flame signal during the pre-ventilation phase (external light control) will result in a shut-off on trouble with the automatic furnace controller being lokked. Die Stö­rung wird am Display der elektronischen Regelung und/oder wenn vorhanden einer Störmeldelampe angezeigt.The
trouble is indicated by the trouble signal lamp lighting up. The automatic furnace controller can be unlocked immediately after a shut-off on trouble by pressing the unlocking key. The program unit will return to its starting position and proceed with the restart of the burner. A voltage failure will result in a regular shut-off of the burner. Upon voltage reco­very there may be an automatic restart unless another interlock is provided, e.g. by the safety system. In any case of trouble the fuel oil supply will be shut off right away. The program unit will stop at the same time causing also the trouble location indicator to stop. The symbols will indicate the kind of trouble.
When using the burner control system type BCS all operational and fault messa­ges may be indicated in plain text on an optionally available operating and display module.
When using the Etamatik/VMS/FMS system, the display is located directly on the control system, which is incorporated in the boiler switch cabinet. In the Etama­tik OEM, the control system is located in the electric module of the burner, and the customer interface is also located on this module or incorporated in the boiler switch cabinet. In the Etamatik OEM, a pro­gramming unit could be installed as an alternative to the customer interface.
sregulierung
ile
EIN
AUS
s
tellung
Leistungsregulierung
EIN
Gasventile Zündung
Startlast Teillast
Freigabe
AUS
Betriebsstellung
Vollast
Zündung/Ventile Pumpe
Teillast
EIN
Freigabe
Leistungsregulierung
Betriebsstellung
Vollast
AUS
Oil control steepless Gas control steepless
ON OFF
ON OFF
Full load
Operating position
Load regulator
Release
Start load Partial load
Ignition / gas valves
Full load
Operating position
Load regulator
Release
Partial load
Ignition/valves Pump
Page 7
7
Operation
Fuel-air Compound Control
Fuel-air compound control
This compound pneumatic control system with precision-adjustment capa­bility has been designed to allow the fuel and air flow rates to be steadily varied in sliding mode for an adjustment of the fuel-air ratio over the whole con
­trol range. In the stepless control mode the load will be controlled at any point within the control range depending on the heat demand.
Electronic compound control:
The air box includes an actuator for operating the air damper. The oil control valve incorporates an actuator for adju
­sting the return oil flow rate and thus the output of the burner. The actuators for the air and fuel flow control will be operated depending on output by the electronic compound con
­trol which will move them into the pro­grammed positions.
4
Luft
M
M
Öl Öl
RL
VL
1a
1b
M
3
2
Oil feed
Oil return
Air
Electronic compound control
1a Oil control valve with actuator 1b Air dampers with actuators 2Burner 3Boiler 4 Combustion air fan
Page 8
8
Hydraulic diagramm
120 Air damper 143 pressure gauge option 175 Filter 176 Pump 178 Feed solenoid valve 180 Nozzle rod 181 Return solenoid valve 184 Output control valve 187a Pressure regulating valve
(integrated in pump) 311 Return oil pressure switch 312 Feed oil pressure switch 349 Actuator
In case of TRD 604/72 hr control items (pos. 311, 312) need to be tested according to „special construc­tion design“ or must be installed twice.
312
RL
181
175
187 a
VL
176
311
178
178
M M
120
184
349
349
180
181
PI
143
PI
143
Hydraulic diagram -DIN / EN
RL
175
187 a
VL
176
311
312
178
178
181
180
181
M
184
120
M
349349
PI
143
PI
143
Hydraulic diagram -TRD 604/72 h
Page 9
9
Operation
Hydraulic Valves and Instruments Group
The hydraulic valves and instruments group is an integrated concept that combines several functions of the hydraulic systems of burners. Its modu
­lar construction makes it possible to meet a wide range of requirements and conditions of installation. Depending on the level of equipment of the hydraulic system, oil pressure swit­ches and pressure gauges (3) may be installed in the supply and return pipes of the basic module (1). The solenoid valve in the supply pipe is of servo-assi
­sted type while the return valve is directly controlled. The solenoids of the two valves are electrically connected in series which will prevent one of the val
­ves being opened alone if any of the solenoids is defective. For the replace­ment of the solenoid valves during maintenance work it should be ensured that the right valve type is installed in the correct direction of mounting. For mounting the solenoid valve in the sup
­ply pipe (type 321F2523) it must be ensured that the direction of flow shown be a stamped arrow on the valve flange is the same as the direction of flow of the oil (from the pump to the nozzle
rod). The solenoid valve in the return pipe (type 121 F2523) is marked with a stamped arrow opposite to the direction of the oil flow from the nozzle rod back to the pump.The volume flow control valve installed in the return pipe con
­sists of a bush pressed into the hydrau­lic valves and instruments group and locked against torsion and a control shaft. As the control shaft is turned, the contoured configuration of the bush and shaft will change the open cross section for the oil flowing back and thus vary the oil return flow rate. Control shafts with different control contour parameters are available for adjustment to various oil nozzle sizes. This concept ensures that an excellent control characteristic and a wide control range can be covered for a great variety of applications. The control contour parameter is affixed to the con
­trol shaft by means of an electric mar­ker. The current position of the control shaft is indicated by the position dis­play. From the "min." mark (low load of burner) the control shaft will turn clock­wise to the "max." mark (full load of bur­ner). If the control shaft has been removed during maintenance work care should be taken when reinstalling it to ensure the right mounting position of the control contour by observing the centre punch mark on the shaft end face. In the low load position (min.) the centre punch mark will in any case point up (12 o'clock position - see figure). If the hydraulic valves and instruments group is used in conjunction with nozzle rods not approved as safety shut-off valve according to EN 264, an exten
-
sion module (2) is available which
incorporates an additional solenoid valve each in the supply and return pipes. The extension module is atta
­ched directly to the basic module. The modules are sealed against each other by O-rings. Metal hoses are used for connection between the hydraulic valves and instruments group and the nozzle rod. The hose lines must be protected against exterior mechanical damage. The hoses must be positioned and mounted in accordance with the appli
­cable technical standards. For the installation care must be taken not to introduce torsional or buckling stresses neither by the mounting procedure nor by movements at a later stage. Speci
­fied bending radii of the hoses must not be changed.
Basic module
Extension module
Control shaft installation
Complete hydraulic valves and Instruments group
3
1
2
Page 10
10
E 10.1200 L-EUF
Start-up
Burner Head Settings E 10... L-EUF
Page 11
11
Installation Mounting to Boiler
Electrical Connection Presetting
Adjustment electrical ignition oil firing operation
Burner plate with gasket strip
Check before burner installation
Check the mixing unit for correct set­ting; see dimensioned drawing.
Burner head settings
The settings mentioned are factory set­tings. They are understood to be recommen­ded values and may be readjusted according to burner system conditions, exhaust gas analysis and combustion characteristics.
- Set the ignition electrodes according
to the sketch.
- Check the burner pipe mounting
according to Section “Boiler lining for burners” and the boiler manufacturer’s specifications.
Electric connection:
The electric connection including all installation materials as well as joints and earth terminals must be made in accordance with the applicable regulati
­ons. For the electrical installation of the burner reference should be made to the circuit diagram of the furnace system. The electric connection of the burner and gas valves and instruments is allo
­wed to be entrusted to authorized spe­cialists only.
Burner installation
For mounting the burner to the boiler make sure the connection plate is pre
­pared in accordance with the dimensi­ons given in the technical datasheets.
• Install the stud bolts in the connection
plate.
• Put the insulating base and burner in
place and fasten with bolts.
Arrangement of sealing tape on the boiler
- Evenly stick on self-adhesive tape
according to Figure.
- Adapt the flat gasket by cutting to the
boreholes in the area of the four. vertically arranged boiler fastening holes.
- In case of butt joints make sure the
bordering is fitting closely
NOTE: For the installation of the con­necting cables care must be taken to provide cable loops of sufficient length so that the boiler door and burner can be swung out as required. After the completion of the electric con­nection work make a check of the wiring of the burner electric system. This inclu­des a check for the direction of rotation of the burner motor (fan).
Boiler inspection glass cooling
For cooling and cleaning the boiler inspection glass, a cooling line (e.g. a hose) may be installed from the burner to the inspection glass. A connection piece is provided on the burner for this purpose.
Page 12
12
Installation
Boiler Lining Burner GL/L-EUF
Boiler lining
The burner lining must be installed at right angles to the burner tube.
Possible trimming work (bevelling, roun­ding) as is required for reversing boi­lers, for example, should done at a diameter not below 70 % of the combu­stion chamber diameter.
The space between the flame pipe of the burner and the boiler lining should be lined with heat resistant material, such as Cerafelt.
This space is not allowed to be lined with brickwork.
DF= Combustion chamber diameter
Burnertyp Dimension A Dimension T1 φ D φ D1
Standard 100 verl. 200 verl.
E 10 620 720 820 200 - 250 497 525
Page 13
13
Installation
Oil Connection Oil Pressure Control (Feed)
Oil connection
Hoses are used for connection to the oil lines and stop valves. The hoses must be installed according to the applicable standards (relieved of tensile load, free of distortion) to avoid kinking and exclude the danger of breakage. Take care when mounting the oil lines to bring their ends as close to the burners as possible and to arrange them in a way that the boiler door and the burner can be swung out without any obstruc
-
tion. Refer to the technical documentation for the line dimensions for the feed and return lines from the stop valves to the tank.
Oil filter
A filter must be installed upstream of the pump to protect the oil pressure pump and the hydraulic system.
Installation options
• Two-line installation (separate feed and return lines without delivery pump)
• Ring line system (with delivery pump and gas-air sepa­rator)
Oil hose aplication area
Burner type DN length
[mm]
double sided
connection
bending radius
min. R [mm]
E 10 25 1500 R 1" 250
Instrument mounting
Prior to adjusting the burner make sure to mount the test pressure gauges for measuring the feed pressure (Item 2) and return pressure (Item 1).
A vacuum gauge and pressure gauge are mounted to the oil pump for measu
-
ring the oil pressure.
NOTE: After the burner has been taken into operation the gauges must be removed again and the connections sealed with suitable means. If the gau
­ges are mounted to remain on the bur­ner they should be fitted with stop valves.
Oil pressure control (feed)
The feed pressure is controlled by means of the pressure regulator instal­led in the pump and should be set at approx. 25 to 30 bar depending on bur
­ner output and nozzle make. The pres­sure regulator is operated by turning its screw. Make sure to fill the pump with oil prior to taking into operation.
Pump bleeding
Open the feed and return stop valves and ensure the ring line (if any) is in operation. Reduce the oil pressure at the pressure regulating valve. Turn on the pump by pressing the contactor. Check the pump for proper direction of rotation. Check for proper oil delivery and absence of leaks in the hydraulic oil system. For bleeding the pump open the pressure gauge connection, for example. When taking the burner into operation proceed by gradually increa
­sing the pressure to operating level (25­30 bar).
Checking the pressure (oil suction pressure)
The maximum permissible vacuum is
0.2 bar. At higher vacuum levels the fuel oil will tend to gas evolution which may lead to operating trouble. In the ring line mode of operation the pump oil pres
-
sure is not allowed to exceed 5 bar.
1
2
Page 14
14
General
The burner feed pipe 32-EH is particu­larly suited for mounting to oil burners and is designed for the operation of return plate nozzles with needle shut­off. The powerful spring of the driving piston moves the shut-off needle into closing position, thus always ensuring a safe shut-off.
The driving piston is operated with oil tapped from the supplied pipe, and its opening function is controlled by the solenoid valve of the hydraulic block. The piston has a fixed travel.
The final position of the driving piston can be checked hydraulically and incor
­porated into the control system of the burner.
During the pre-ventilation of the burner, the shut-off needle keeps the bore in the nozzle plate closed and the oil circu
­lates in the feed pipe. When using heavy fuel oil, the complete hydraulic system is heated in the pre-scavenging stage. When the solenoid is turned on, or after a longer downtime, an imme
­diate atomizing and a perfect ignition are ensured.
The burner feed pipe is suitable for sup­ply pressures from 20 to 40bar and oil temperatures up to 140°C. The ambient temperature in the vicinity of the coil should not exceed a temperature of 60°C.
SW 41
SW 41
SW 41
swirl chamber plate
e
adapter
mounting
rod
Needle open Neddle closed
Nozzle plate
swivel nut
needle guidance
shut off needle
Nozzle rod linkage 32 - EH
Mounting the nozzle plates
The nozzle plate and the swirl chamber plate should be installed according to the attached sketch. The sealing surfaces on the adapter, on both sides of the swirl chamber plate and on the nozzle plate must not be damaged because this would endanger the proper sealing. When sealing these surfaces, never use material from other manufacturers.
Remove the swivel nut from the feed pipe, check that the needle guidance in the swirl chamber plate is sliding pro­perly over the needle head and place the plates into the nut evenly in proper position and proper sequence.
Now the nut together with the plates is carefully placed over the needle and tightened by hand as firm as possible. The cap nut is firmly tightened with a spanner. Spanner surfaces are provi­ded on the adapter to counter with the feed pipe when screwing down or off the cap nut. These surfaces are desi­gned for this purpose only!
Page 15
15
Nozzle rod linkage 32 - EH
Connections
The connections on the block of the feed pipe are identified as follows:
S Oil supply to the nozzle and to the
hydraulic system of the needle actuation. A filter with a mesh size smaller than 50 µm should be pre­connected. The pressure should be kept above 20bar.
MS Here, the supply pressure of the
nozzle is available. A pressure gauge or a pressure sensor can be connected to evaluate this pressure.
R Oil return from the nozzle. A pres-
sure or a quantity governor can be connected for fuel oil flow control.
MR Here the return pressure of the
nozzle is available. A pressure gauge or a pressure sensor can be connected to evaluate this pressure.
L Oil return from the hydraulic
system of the needle actuation. In principle, this oil should be allo­wed to flow off without back pres­sure. If this pipe is connected to a ring main having a low overpres
­sure, it is essential to observe that the pressure at connection „S“ must in any case be at least 20 bar higher than that pressure which is applied at connection “L”. Only then, the proper needle function is ensured.
C Here, the switching pressure of
the needle piston is available. A pressure gauge or a pressure sensor can be connected to eva
­luate this pressure. The pressure is lower than the pressure at con­nection “S” when the needle is closed and during the switching procedure of the needle piston. Only during the time while the needle is fully open, there will be a pressure that is as high as the pressure at connection “S”. These properties allow the final position of the needle to be checked hydraulically.
When selecting the screwed connec­tions, make sure that the ducts in the connecting block of the feed pipe can not be covered, not even in part. Even a partial covering of these ducts will result in a malfunction of the feed pipe.
Page 16
16
Nozzle rod linkage 32 - EH
Function
During the pre-scavenging stage, both the external solenoid in the supply line and the external quantity or pressure governor in the return line are open. The attached solenoid is de-energized and the valve used for needle actuation is closed, the spring-loaded rod thus keeps the needle in the bore of the nozzle plate at the front of the feed pipe closed so that the oil cannot reach the furnace chamber too early. The pres
­sure at connection “C” is 0 bar or equal to the ring main pressure if the connec­tion “L” has been connected to a ring main. The oil circulates from connection “S” via the swirl chamber plate in the nozzle through the feed pipe to the con
­nection “R”, thus warming it up to opera­ting temperature. (For heavy oil only)
Operating voltage and type of current are indicated on the attached coil. The moment the attached solenoid is turned on, the oil is released for needle actua
­tion; the rod is withdrawn, and the nozzle needle is opened. During the short time where the piston moves from closed to open needle position, the pressure at connection “C” is always at least 2bar lower than the pressure at connection “S”. From the moment on where the piston reaches its final posi
­tion and the needle is opened fully, a pressure is applied at connection “C” which is as high as the pressure at con
-
nection “S”.
The interruption of the power supply to the attached solenoid causes the needle to be closed by means of the spring. The oil outflow on the nozzle will stop immediately.
The pressure at connection “C” will go down to 0 bar or reaches again the same level as in the ring main if connec
­tion “L” is connected with the ring main. The circulation from connection “S” via the swirl chamber plate to connection “R” will still take place. The temperature of the feed pipe is thus maintained.
Service
Normally, the burner feed pipe is maintenance-free.
The only moving part in the feed pipe is the rod linkage used for actuating the needle with the piston. After a longer period, the O-rings could be worn out. For replacement, complete O-ring sets are available.
Page 17
17
Start-up
Return Nozzle Rod RDG 1250
Function description
The return nozzle rod RDG 1250 is for return nozzle without integrated needle valve and comes with M14 screw con
­nection (for example Sonic DZ 1000, CBM M14).The locking mechanism consisted of a slider with seal ring (Pos. 2 and 6) in the forward flow section and a needle valve (Pos. 5) in the return flow section, using the sliding rod con
­trol by a hydraulic control-piston system located at the back of the nozzle rod. The opening pressure of RDG 1250 is about 3 bar in forward flow section or 13 to 20 bar in return flow section. When the solenoid valves are open, the pres
­sure from the oil would retract the con­trol-piston via the pressure channel (Pos. 7) and then push open the slider .
Both the control-piston and sliding rod with needle valve would remain open as long as there is an existing oil pressure. The same oil pressure would keep the slider open. Under normal circum
­stances, both locking mechanisms would open at the same time. The oil in the forward flow section would exit through the nozzle head to be mixed with the air for combustion. The remai
­ning oil would be redirected through the return holes of the nozzle back into the return flow section of the nozzle rod assembly. When it is not in operation, the swirl plate in the nozzle head blocks the return flow.The return oil flow rate can be adjusted accordingly using a pressure control valve If the pump pres
­sure is too low (<20 bar), thereby pre­venting the control needle from opening all the way, variations in throughput are to be expected as the needle position will affect the return oil flow.
Control-piston opening distance H is set in the factory at 9mm. Any adjustment at installation site is not necessary.
1
5
3
6
4
7
2
H
The Control piston opens at ca. 13 bar; Fully open at 20 bar. Close at 10 bar.
1 Return Nozzle 2 Slider 3 Spring (Forward) 4 Sliding rod 5 Needle valve 6 Seal ring (Forward) 7 Pressure channel Distance H = 9 mm
Forward
Valve
Page 18
18
Start up
Nozzle selection „Sonic“
160 kg/h
240 kg/h
300 kg/h
350 kg/h
400 kg/h
450 kg/h
500 kg/h
550 kg/h
650 kg/h
700 kg/h
750 kg/h
800 kg/h
850 kg/h
900 kg/h
950 kg/h
1000 kg/h
Diagram - of Sonic-Spray return nozzle DZ 1000-60° with controlled return Light fuel Oil Feed pressure 28bar
Return nozzles of the type Sonic­Spray are available in different ratings with an angle of spray of 45°, 60° or 80°.
The 45° nozzles are preferably used for reversed-flow furnaces while the 60° and 80° nozzles are operated in three-pass boilers and swirl-type mixing installations, respectively.
Quantity Oil Nozzle [kg/h]
Return Pressure at the Hydraulicblock [bar]
Page 19
19
Start-up
Checking Procedure
Check the following prior to the initial operation of the boiler system:
• Take care to observe the operating instructions supplied by the boiler manufacturer. The boiler must be mounted ready for operation.
• Ensure that the heating system is filled with water to capacity.
• Check the complete system for correct electrical wiring.
• Check the burner motor for correct direction of rotation.
• Check for the proper setting of the temperature and pressure controllers, limiters, safety switches and electrical limit switches.
• Bleed the fuel-carrying lines (make sure they are free of air).
• Check tank, lines and oil pump are fil­led with oil and correct oil nozzle is fit­ted.
• Check the oil hydraulic system is free of leaks.
• Check the exhaust gas ports are ope­ned and adequate fresh air intake is ensured.
• With burner in starting position check that air damper is in „CLOSED“ posi
-
tion.
• Check that automatic furnace control­ler is unlocked and in its original posi­tion.
Oil start-up
Open all shut-off valves of oil supply system.
• Set fuel selector switch to its „Oil“ posi­tion.
• Fill pump with oil.
• Mount pressure gauge in the feed line and return line.
• Mount the pressure gauge for checking the pump suction pressure.
Bleeding
Shortly start the burner and check for proper direction of rotation. Bleed the oil line and oil pump.
CAUTION: The hydraulic system has been filled with test oil by the manufac
­turer. This may cause ignition trouble when initially operating the system. To protect the pump, the oil pressure con
­troller is factory-set at zero pressure. When starting the burner take care to increase the oil pressure slowly to the operating level.
Prior to the initial fuel feed start make a functional test of the burner program flow:
Oil system:
• Open all shut-off valves of the oil sup­ply system.
• The oil solenoid valve in the feed line disconnect on the terminal strip (see Circuit Diagram).
• Start burner and check program flow for correct start-up sequence.
1. Fan starts.
2. Pre-ventilating damper.
3. Air pressure check.
4. Partial-load air damper.
5. Ignition.
6. Valves open (disconnected valve
remains closed).
7. Shut-off upon trouble after expiry
of safety period (see automatic furnace controller).
• Reconnect the valve.
• Unlock the automatic furnace control­ler.
Page 20
20
Adjusting Instructions
Air Flow Rate Adjusting Procedure
Adjusting procedure
• Set the selector switch to its "Manual" or "Hand" position.
Air flow rate adjustment
The air control curve of the compound controller is factory-set so that the air damper is closed in minimum position and open in maximum position. The combustion air flow rate required for proper fuel combustion is controlled by an electronic fuel-air compound con
­trol system over the full load range. A check is made by analyzing the exhaust gases.
For the gradual adjustment of the load points (fuel flow rate, air flow rate), a procedure should be used as described in the operating instruc
­tions for the electronic compound control system.
A fuel test should be made at each point if possible.
Page 21
21
Adjusting Instructions
Elektronic Burner Control with Electronic Compound Controller
BCS
Etamatic OEM
Refer to the documentation supplied with the electronic compound control system for the pre-operational work on the burner, the checking requirements (e.g. actuators, limit switches, potentio­meters etc.) and the instructions for the initial operation of the electronic com­pound control system.
Etamatic
Page 22
22
Adjusting Instructions
Start-up of Burner Control System Type BCS 300 Flame Detecting System Type FLW 05
Description
The electronic burner control system type BCS 300 is a programmable auto­matic firing controller of modular con­struction with integrated electronic compound controller. It is designed for the control and automatic control of oil, gas and dual-fuel burners of medium to larger outputs. The automatic firing controller may be used for intermittent or continuous mode of operation and for furnace systems built according to TRD. The controller consists of the following units that communicate via a safety-ori­ented bus system:
- burner controller module type BCS 300 (attached to burner)
- flame detector module type BCS­FLW 05 (attached to burner)
- fuel and air servomotors
- operating and display unit type BAM (not required for operation of furnace system)
The system also incorporates a PID firing rate controller with standard or servo-control parameterization capabi
-
lity and a valve leak tester.
Technical data:
Operating voltage: 230 V a.c. Frequency: 50-60 Hz Power input:
BCS incl. BAM:<15 VA
FLW 05: <1.5 VA Back-up fuse: max. 10 AF Equipment fuse: 6.3 A slow-blow
0.1 A slow-blow
Permissible ambient temperature:
in operation: 0 - 60 °C
during storage: -20 - 70 °C
Starting the burner control system
NOTE: The burner control system is
allowed to be started by duly qualified specialists only. The personnel opera
­ting the system should strictly observe the applicable instructions for start-up.
Before proceeding with the pro­gramming of the system make a check of its wiring (especially for compliance with the relevant DIN-VDE standards and the regulations of the local power supply company).
The parameterization of the automatic firing controller programs, the valve leak test and the firing rate adjustment will be handled from the operating and dis
-
play module.
NOTE: For selecting the automatic con­troller programs and adjusting the pre­ventilation times care should be taken to observe the applicable standards. The fixed safety time settings are not allowed to be extended by external swit­ching operations.
The fuel-air compound curves may be programmed by means of the operating and control module or a laptop compu
­ter. If the compound controller is adjusted by means of the operating and display module it will only be possible to correct the curve point settings. A completely new curve and the defini­tion of new curve points can be achie­ved with the aid of a laptop computer only.
After the automatic controller programs have been set it will be possible to check the inputs and outputs of the bur
­ner control system for proper functioning via the operating and dis­play module.
NOTE: For the tests, all manual fuel shut-off valves must be kept in closed position in any case.
The compound modules are provided with a basic curve when delivered ex works. This may be changed by means of the operating and control module to adjust it to the local conditions. For this purpose, it is possible to correct the damper positions for the 10 index points in the range from 10, 20, 30, etc. to 100.
Flame detecting system
The flame detector module type FLW 05 is used in conjunction with the burner control system. The following flame sensors may be connected to the flame detector module:
-QRA 2
- QRA 53/55
-RAR 7/8
- ionization electrode
- any flame detector with contact output
The sensor to be used will be selected by appropriate programming in the bur­ner control system. The type of sensor used will depend on the burner opera­ting mode (continuous or intermittent). The flame boosters integrated in the flame detector will be checked for pro­per operation at an interval of 90 seconds in continuous mode. Flame detectors with contact output must if run in continuous mode be intrin­sically safe because only the parts of the BCS flame detector are checked for safe operation.
The intensity of the flame signals (UV sensor, light sensor, ionization elec­trode) is evaluated in the burner control system and indicated on the operating and display module. This allows an exact orientation of the flame sensors. It is not possible to measure the flame intensity by means of instruments.
The flame sensors must be checked for accumulation of dirt at regular intervals. Take care that the sensor window is kept free of dust all the time. The flame intensity display may be used as an indicator for the dirt accumulation load. If the situation cannot be remedied by cleaning it will be necessary to replace the flame sensor.
Page 23
23
Adjusting Instructions Start-up of Burner Control System Type
BCS 300 Servomotor Type SAD 15.0
The electronic compound control system type BCS makes use of digitally activated servomotors type SAD 15.0. These consist of a stepping motor with electronic trigger and power pack. A driver with digital feedback via enco­der disk is provided for monitoring the function and direction of rotation. Take care to observe the instruction for operation for the burner control system type BCS 300.
Dimensions:
Connection:
P1 : N, L, PE
P2, P3 : 1 - EA SA
2 - EB SB 3 - OK WD 4 - GND 5 - AA MA 6 - AB MB
NOTE: Check the zero position of the servomotors prior to start-up.
Technical documentation:
BCS 300, Dungs
Technical data:
Maximum torque 15 Nm Gear reduction 745:1 Positioning times (at 200 Hz) 22.3s/90° Positioning accuracy <±0.3° Direction of rotation from zero mark to 90°counterclockwise (looking on drive
shaft)
Angular resolution stepping motor 0.02°
rotation monitoring 1°
Unidirectional positioning by external load
initial stress at 0.6 Nm
Supply voltage 230 V a.c. +10/-15%, 50 Hz Current decrease 20 ms ±30% (after last step) Protection classification IP 54 Shaft, flanged with cylindrical pin 12 dia.
h8
Ambient temperature in operation -20 to +60 °C
Cable gland with PG 11 conduit thread
and earthing
Through hole for M6 thread
P1
N L PE
P3 P2 zu
Page 24
24
Adjusting Instructions
Technical data:
Voltage: 230V AC Frequency: 50 Hz Angle of rotation: 90° Running time: 40 sec. for 90° Torque: 15 Nm Static holding moment:
8 Nm
Dimensiones (B x H x T):
(93 mm x 144 mm x 149 mm)
Potentiometer (integrated):
5 kΩ
Electrical Actuator STM 40
The actuator STM 40 is used in connec­tion with the electronic burner control systems (Etamatic (S), Etamatic OEM (S), VMS, FMS) of the firm „Lamtec“ .
5 k
Ω
Page 25
25
Start-up
Starting the BCS, Etamatic, VMS/FMS Electronic Compound Controller
Starting the electronic compound controller
For starting the electronic ratio control­ler make sure to proceed as described in the operating instructions.
NOTE:
Only duly qualified personnel must be employed for starting the controller. For the initial operation make a check that the controller settings are in line with the furnace system requirements. The configuration of the compound con
­troller is shown on the sticker attached to the housing side wall.
Functional test without burner start
After the electronic compound controller has been connected electrically pro­ceed with adjusting the potentiometers of the actuators. Start the fan for checking the feedback of the fan speed (press the fan contactor). As soon as the potentiometer feedback data have been properly set proceed with programming the compound con­troller. An exact description of the pro­gramming procedure can be found in the operation manual supplied with the compound controller.
NOTE:
The start-up manual of the compound controller contains information on trouble signals, detailed instructions for start-up and for programming the con
-
troller.
Page 26
26
Adjusting Instructions
Oil Pressure Switch Air Pressure Switch
Oil pressure switch
Oil pressure switches are provided to burners for monitoring the oil pressure. Depending on the burner design, the oil pressure switches can be installed eit­her in the return line only or in both the return line and feed line. The cut-out pressure will be selected depending on the burner system data (ring line pres­sure, oil nozzle, etc.).
Oil pressure damper
An oil pressure damper or a capillary pipe may be installed in the connection fitting (2) to make up for oil pressure variations.
Operating pressure adjustment
For adjusting the operating pressure, remove the setting know (1) by pulling it upward and reinstall it again the other way round. After the adjustment has been completed make sure to install the setting know in its original position again.
Switching difference
The switching difference may be selec­ted on the pressure switches within the limits shown in the table. For the adjust­ment, turn the threaded pin in the set screw (3) for the switching point. One turn will change the switching difference by approx. 20 % of the total range of the switching difference. The oil pressure switch has a facility for attaching a seal.
1
2
3
Typ e
Setting
range
Switching difference
Location
DSB 143 F... 0 - 6 bar 0,3 - 1,6 bar Return line acc. to DIN / EN
DSB(F) 170 F... 15 - 40 bar 1,2 - 4,5 bar Feed line acc. to DIN/EN in pumps
without quick-action stop valve
DSF 146 F... 0 - 10 bar 0,5 - 2,5 bar Return line acc. to TRD 604/ 72h
DSB 158 F... 3 - 25 bar 1,0 - 4,3 bar Feed line acc. to TRD 604/ 72h
Air pressure switch
The air pressure switch is provided for monitoring the pressure of the combu­stion air fan. The pressure switch DL 50A has been designed for switching on, off or over an electric circuit in the case of changes of the actual pressure levels from the set­point setting. The pressure switch DL 50A can be used as overpressure, vacuum or differential pressure monitor for air and non-aggressive gases but not for gases according to DVGW Worksheet G 260/l.
Determining the differential pre­flushing pressure and adjusting the differential pressure switch
• Burner in the pre-aeration phase.
• Measure pressure on test
connection (2).
• Measure vacuum on test
connection (3).
• Add the measured pressures.
• Set the scale to 90% of the calculated value.
Certification
The pressure switch has been tested in accordance with DIN 3398 Part 2 and is registered by CE/DIN-DVGW. It has been registered in other important gas consumption countries.
Switch function test
Test buttons are provided to check the switch functions for proper operation (with safety cut-out and interlock). The burner is normally run in partial-load condition when testing the safety functions. On pressing button (4) the vacuum will be removed which causes the differential pressure to drop below the required level. If it is necessary to test the pressure switch functions under full-load conditions this may be done by pressing button (1).
Page 27
27
Overview
Flame monitor
IR Flame Detector FFS 06
For IR flame detectors and UV flame detectors, the minimum response thres
­holds are 15 mV AC and 25 mV AC, respectively. Refer to the technical documentations of the flame monitors for further commissioning instructions.
Note: The UV flame detectors are not provided with this sensitivity adjust­ment. They are optimized by aligning to the flame to be monitored in the best possible way using the measurable signal voltage on the measuring line.
Criteria for flame detectors
Detector type spectral radiation range application - fuel
FFS 06 UV-1 260-400nm oil, gas
FFS 06 UV-2 210-380nm oil, gas (special gases such as
refinery and high furnace gases)
FFS 06 (IR) 1200-2800nm oil, gas, furnaces with heavy flue
gas recirculation, waste gases with yellowish colouring without UV radiation
Sensitivity
Adjustment to be made on switches S1 and S2 which are accessible after opening the detector housing.
factory configur­ation
Figure 2
Assembling and commissioning of flame detectors
The flame detector should be installed in the provided mounting at an inspec­tion opening of the burner in a way that the burner flame to be monitored is clearly visible in the overall operational range of the furnace. The sensitivity of the IR flame detector FFS 06 to the bur­ner flame can be adapted via the thres­hold switch in the flame detector. In doing so, the sensor housing should be unscrewed and the setting on the thres­hold switches made according to the Figure (2).
Page 28
28
Overview
Flame monitor
Pin configuration
Connection of the flame detectors is according to colour code in compliance with the pin configuration on the flame monitor to be used or the Etamatic / BCS. The detector cable has a measu
­ring cable (pink) where the signal voltage can be measured with a com­mercially available potential-free measuring instrument (measuring resi
-
stance >5MΩ, e.g. a hand-held multi­meter in compliance with EN 61010). The measurement used to ideally align the flame detector FFS 06 to the flame is relative to frame (blue) of the detector line.
DURAG Compact Flame Monitor D-LX 100
Function
After turning on, the compact flame monitor will first undergo a self test and then repeat the same during operation at regular intervals. The radiation of the flame is converted into an electric flame signal using a highly sensitive photocell. It is only the flaring portion of the flame signal which is processed by the two microprocessors of the compact flame monitor D-LX 100. Thus, the monitoring is independent of outside light, insofar it is constant light. Depending on the set operating point, the flame signal causes the flame contact to switch. This opera
­ting point can be adjusted on the unit in 10 steps. The safety time can be fac
­tory-set to the values of 1, 3 or 5 sec. In addition, the flame intensity determined is made available on the measuring out
-
put as analogous value.
Application
The DURAG compact flame monitor D­LX 100 is the first flame monitor of its kind. Its radiation detectors cover the spectral range from 190 to 520nm. All blue burning flames, such as gas or oil flames, can be monitored with these flame monitors. In particular, flames the UV radiation of which are absorbed by dust, water vapour or other substances, and can therefore not be monitored with conventional UV cells, are safely detec
­ted by means of the new highly sensi­tive UV semiconductors. This flame monitors provided with the highly sensi­tive UV semiconductors have also pro­ven themselves in NOx-reducing combustion techniques, such as the waste gas recirculation.
Ultraviolet flame monitor D-LX 100 UL / UA / UAF
The radiation detectors used in these flame monitors cover a spectral range from 190 to 520nm. All blue burning fla
­mes, such as gas or oil flames, can be monitored with these flame monitors. In particular, flames the UV radiation of which are absorbed by dust, water vapour or other substances and can, therefore, not be monitored with con
­ventional UV cells, are safely detected by means of the new highly sensitive UV semiconductors.
This flame monitors provided with the highly sensitive UV semiconductors have also proven themselves in NOx­reducing combustion techniques, such as the waste gas recirculation.
Infrared flame monitor D-LX 100 IG / IS
Depending on type, the radiation detec­tors used for the IR flame monitors have a spectral sensitivity between 300 and 1100nm or 780 and 1800nm. These flame monitors are particularly suited for the monitoring of yellow burning coal or wood dust flames which contain no or only very small UV radiation portions. IR flame monitors are also well suited for the monitoring of oil flames even if addi
-
tional substances are burned.
Figure 3
Page 29
29
Overview
Flame monitor
Selenium Photocell Detector RAR …
Application
RAR… is used for the monitoring of yel­low burning oil flames.
WARNINGS: When observing the following
warnings, unsafe conditions hazardous to life, property and environment can be avoided!
It is not permitted to open the unit or to make changes or modifications!
- Never do any work in the power sup­ply area without first disconnecting all external power supplies.
- Provide for appropriate protection against direct contact on the power supplies.
- Before commissioning, check the wiring and all safety functions.
- After being subjected to any impact load, take these detectors out of ope
­ration as safety functions may be affected even if there is no external damage visible.
Assembling
- Observe the applicable local safety regulations.
- Mount the detector to the burner by means of snap-on fastening (can be locked into place in light metal flange attached to burner).
Installation
- Allow only qualified personnel to per­form the installation.
Electrical connection of detectors
Ensure a trouble-free and loss-free signal transmission if possible:
- Never run the detector cable together with other cables.
- Cable capacitance reduces the
size of the flame signal.
- Use a separate cable.
- Take care to observe the permissible length of detector cables, see “Type Overview”
- Always run the ignition cables with a large distance to the unit and to other cables if possible.
Commissioning
- Allow only qualified personnel to per­form commissioning and maintenance work.
- The intensity of the light radiation on the location of the detector is checked by measuring the detector current.
Circuit for detector current measure­ment
A Incidence of light M Micro-ammeter direct current,
internal resistance 5000 Ω
Refer to the data sheet of the respective automatic furnace controller for mini
-
mum required detector current values.
Disposal
The detector contains electrical and electronic components and must not be disposed of as household waste. It is essential to observe the local and appli
-
cable legal conditions and regulations.
Design
- Dust-proof TS plastics enclosure
- Photocell under protective glass
- Shipment optional with/without flange and shackle, see “Type Overview”
Type Overview Type Length of Detector Cable Flange and Shackle
RAR7 up to max. 20m without RAR7(1) up to max. 20m with RAR8 up to max. 100m without RAR8(1) up to max. 100m with
When ordering please state the type designation according to type overview.
Technical Data
Class I System of protection IP40 Any mounting position Weight approx. 85g
Environment Transpor t: IEC 721-3-2
Climatic conditions: class 2K2 Mechanical conditions: class 2M2 Temperature range: -20 to +60°C Humidity: <95% relative humidity
Operation: IEC 721-3-3 Climatic conditions: class 3K5 Mechanical conditions: class 3M2 Temperature range: -20 to +60°C Humidity: <95% relative humidity
Dewing, icing and ingress of water are not permitted! Function
In this monitoring mode, the radiation of oil flames in the visible range of the light spectrum is used for the formation of the flame signal. The light-sensitive ele
­ment is a selenium cell. When lit, it deli­vers a direct voltage and thus causes the current to flow to the input of the flame signal amplifier. The RAR… is thus an active detector. The cell is non­sensitive in the infrared area so that the slightly glowing firebricks of the furnace are not detected.
Dimensioned drawings
Dimensions in mm
Page 30
30
Overview
Flame monitor
Flame Detectors QRA… Flame detectors for Siemens auto­matic furnace controllers for the monitoring of gas and oil flames
Application
The flame monitors are used for monito­ring gas flames, yellow and blue burning oil flames as well as for ignition spark inspections.
QRA2 intermittent operation QRA53continuous operation
WARNINGS:
When observing the following warnings, unsafe conditions hazar
­dous to life, property and environ­ment can be avoided!
- Never do any work in the power sup-
ply area without first disconnecting all external power supplies.
- Provide for appropriate protection
against direct contact on the power supplies.
- Check the wiring and all safety
functions.
- Halogen lamps, welding apparatus,
special lamps as well as the ignition spark may have a sufficient high UV portion so that the cell will ignite. X-ray and gamma radiation may generate a wrong flame signal as well.
Mounting
- Observe the applicable local safety
regulations.
Installation
- Allow only qualified personnel to per-
form the installation.
- Take care to observe the permissible
length of the detector cable, see “Technical Data”.
- Always run the ignition cables separa-
tely keeping a large distance to the QRA… and to other cables if possible.
Electrical connection of detector
Ensure a trouble-free and loss-free signal transmission if possible:
- Never run the detector cable together
with other cables.
Cable capacitance reduces the
size of the flame signal.
Use a separate cable.
Commissioning
- Allow only qualified personnel to per­form commissioning and maintenance work.
- A trouble-free burner operation can be ensured only if the intensity of the UV radiation on the location of the detec
­tor is still so large that it is ignited safely during each half-wave.The intensity of the UV radiation on the location of the detector is checked by measuring the detector current.
Measuring circuit for QRA2 ..., QRA10... and QRA5 series D
Legend
Measuring circuit for QRA5 up to series C
1… Circuit of micro-ammeter between adapter QGQ1.../AGQ2...and flame detector A – Incidence of radiation M – Micro-ammeter direct current internal resistance 5000 Ω C – Electrolytic capacitor 100...470...µF,DC 10...25 V
Design
Flame detector QRA2…
Plastic-encapsulated design, metalli­zed to prevent a static charge in the air flow of the blower, directly mounted on burner. Shipment optional with/without flange and shackle, see “Type Over
-
view”.
Flame Detector QRA 5
The UV cell is located behind a swivel­mounted shutter on the front end of the detector pipe flanged onto the housing. A quartz window protects the cell and the shutter from contamination. The detector housing contains a step motor as shutter drive as well as the electronic components for the shutter control.
Connector AGM19
Connector AGM19 with cable for the electrical connection of the flame detec
-
tors QRA53… and QRA55…
Required minimum detector current values: See the respective data sheets of the automatic furnace controllers or the operator’s manual of the KF8832.
Disposal
The detector contains electrical and electronic components and must not be disposed of as household waste. It is essential to observe the local and appli
-
cable legal conditions and regulations.
Page 31
31
Type Overview Flame Monitor:
Typ sensitivity flange with shackle clamped cover spare UV cell QRA2 without QRA2(1 ) with QRA 2.9 without QRA 2.9(1) with QRA2M without QRA2M(1) with QRA10.C normal 4 502 1131 0 QRA10M.C hight 4 502 4065 7
Typ sensitivity clamped cover clamped cover spare UV cell QRA53.C27 AC 220…240 V QRA53.C17 AC 100…110 V QRA53.D27 AC 220…240 V QRA53.D17 AC 100…110 V QRA55.C27 AC 220…240 V QRA55.C17 AC 100…110 V QRA55.D27 AC 220…240 V QRA55.D17 AC 100…110 V
normal
125 mm
4 502 4065 7
hight
normal
77 mm
hight
normal 4 502 1131 0
hight
4 502 4065 7
black
green
Note
All QRA5… will be supplied with shackle. A connecting cable AGM19 is required for connection (see “Accesso
-
ries” for QRA5…).
Technical Data
General Data
Average lifetime of UV cell:
- approx. 10,000h at max. +50°C, hig­her ambient temperatures will signifi­cantly decrease the lifetime.
System of protection
- QRA2… IP40
- QRA53…, QRA55 IP 54
Dimensioned drawings
All dimensions in mm
Mounting position: any
Transport: IEC 721-3-2
Climatic conditions: class 2K2 Mechanical conditions: class 2M2 Temperature range: -20 to +60°C Humidity: <95% relativ
humanity
Operation: IEC 721-3-3 Climatic conditions: class 3K5 Mechanical conditions: class 3M2 Temperature range: -20 to +60°C Humidity: <95% relative humidity
Dewing, icing and ingress of water are not permitted!
Function
In this monitoring mode, the UV radia­tion of gas and oil flames is used for the formation of the flame signal. The radia­tion detector is a UV sensitive cell with two electrodes which is ignited by radia tion in the wave length range between 190 and 270nm, thus generating a cur
­rent in the flame detector circuit. The UV cell does not respond to the after-glowing firebricks of the furnace or the daylight.
Overview
Flame monitor
incidence of radiation
shackle for direct mounting
Page 32
32
Adjustment
Fan Impeller
Note:
Prior to removing the fan impeller, the shaft or the fan impeller must be mar­ked on the edge of the suction funnel so that the fan impeller is in the same posi­tion when reassembling, or the same overlapping of the suction funnel (dimension in Fig.) can be readjusted as initially. An axial displacement of the impeller on the shaft may result in a lower efficiency, thus having a reduced air flow.
Prior to removing the bush from the disk, the position of the bush in the disk must be marked so that a rotating against one another can be prevented. Rotating the bush deteriorates the balance of the fan impeller.
To demount the impeller, remove the screws (1) and (2), screw in one of them as separating screw into the hole (3) having half a thread in the bush and tighten it. This causes the bush to loosen. Open the bush by means of a wedge if requi­red. Remove the loose impeller ran wit­hout striking a blow and without damage by hand.
- Clean and degrease all bright-finished
surfaces. A requirement for achieving a high slipping moment is always a clean and fat free surface of all parts to be fitted into one another.
- For reassembly: Place the disk and
the bush into their initial position (wit
­hout rotating) into one another, make sure that the holes are congruent.
- Screw the bush into or out from the disk until about 2..3 mm of the bush are protruding.
- For new installation: Mark the dimen­sion x on the inside of the fan impeller.
- Mount the fan impeller onto the shaft. For this, open the bush by means of a wedge if required. Adjust the position to maintain the dimension x using the marking(s).
- Align the two opposing screws (1) and (2) and tighten them evenly step by step. In doing so, start with the first step of the torque (max. 10 Nm) by tightening one screw, then rotate the fan impeller by half a rotation and tigh
­ten the other screw with the same tor­que, afterwards rotate the fan impeller to the initial position. Increase the tor
­que by one step and proceed until the specified torque is reached as descri­bed above. The torque steps should not be larger than 10 Nm.
- check the dimension X.
The following torques must be follo­wed:
SM 25, Bushes No. 2517 – centre bore 42 and 48 mm:
Torque: 50 Nm. WM30 Bushes No.3030 – centre bore 48 mm:
Torque: 90 Nm.
Overlapping of suction funnel above fan impeller:
Burner X [mm]
E10 6
Page 33
33
Service Instructions
Maintenance Burner
Furnaces should be inspected once a year. An extract from DIN 4755, 4756 reads as follows:
„To ensure a high operational readi­ness, functionality, safety and eco­nomic efficiency, the user should have the boiler system inspected by an authorized person of the manu­facturer or other specialist once a year. The whole system must be checked for proper operation and faults detected should be rectified without delay. It is advisable howe
­ver to make another inspection of the system in addition to the one speci
­fied herein.“ The inspection should comprise the following work:
1. Inspect the boiler internals and
insulating packages and replace by new ones if required. Check boiler for possible accumulation of dirt.
2. Remove the nozzle, check it and
replace it by new one if required.
3. Clean the ignition electrodes.
4. Check the ignition electrode and
spark functions and readjust if required.
5. Clean the burner interior and exte-
rior.
6. Clean the fan impeller.
7. Check the fan impeller for possi-
ble deformation and cracks.
8. Clean the UV flame sensor.
9. Clean the filters and screens.
10. Check the electrical connections.
11. Check the burner head setting.
12. Check the control equipment for
proper operation, setting and safety period.
13. Check the pressure switch for pro-
per setting and operation.
14. Check the oil pump by measuring
its pressure and vacuum levels.
15. Check the hydraulic oil system for
absence of leaks.
16. Check the oil hoses for possible damage and twisting.
17. Clean the air damper and check for smooth operation.
18. Check the combustion process and make exhaust gas tests:
• Fuel throughput rate adjustment
• Heating chamber temperature
(intake temperature)
• Exhaust gas temperature
• Pressure in combustion
chamber and exhaust gas pipe
•CO2 and O2 contents of exhaust
gases
• CO test, soot test
• UV sensor current measurement
19. Enter measured data in test record.
Note: Before doing maintenance and adjusting work:
- Disconnect the external power sup-
ply. Turn the main switch to the OFF position.
- Close all shut-off valves upstream the
burner.
Swivelling out and closing the air intake box
The air intake box is swivelled out as follows:
- Loosen the plug connectors of the
power supply and the return line (1) on the servomotor of the air damper.
- Pull off the hose of the air pressure
detector (3) from the nipple on the air intake box (5).
- Screw out the screws (6) to (9).
- Swivel out the air intake box.
1
3
5
7
8
9
6
Page 34
34
Service Instructions
Maintenance Burner
Should there be not enough space, such as in double furnace tube boilers, the air intake box can also be easily taken off its hinges after screwing out the fastening screws and a slight swivelling.
The air intake box is closed in reversed order of the steps described above.
Note: When mounted the hinge is no fastening point. It is merely used to accommodate the air intake box in open state and as an aid upon screwing on. The actual fastening is by the four screws.
Removing and closing the casing cover
Before removing the casing cover do the following steps:
- Swivel out or disassemble the air intake box.
The casing cover is removed as follows:
- Screw out the screws (1) to (6).
- Remove the casing cover.
When closing the casing cover do the following steps:
- Screw in the screws (1) to (6) by doing only a few turns.
- Tighten the screws beginning with the screws (1) and (2), followed by the screws (3) and (4) and finally by the screws (5) and (6).
Assembling and disassembling the flame monitor
Before disassembling the flame moni­tor, do the following steps:
- Swivel out the air intake box.
- Remove the casing cover.
Assembling and disassembling the nozzle rod linkage
Before disassembling the nozzle rod lin­kage, do the following steps:
Swivel out the air intake box. Remove the casing cover.
The nozzle rod linkage is disassembled as follows:
- Open all quick-release couplings of the oil pipes (10).
- Loosen the fastening screw (11) of the nozzle rod linkage.
- Pull off the nozzle rod linkage togehter with swirler (12) and centering device (13).
The nozzle rod linkage is reassembled in reversed order.
11
10
12
13
2
3
6
5
1
4
4
3
2
1
Page 35
35
Exhaust Gas Test
Exhaust gas test
To ensure an economically efficient and trouble-free operation of the system it will be necessary to adjust the burner specifically in accordance with the furnace system. This is achieved by means of a fuel-combustion air compound control unit which adjusts the burner to ensure a proper combustion. Exhaust gas tests are required for this purpose. The percentage CO
2
and O2 and the exhaust gas
temperature will have to be measured to determine the efficiency and combustion quality. Prior to any measurement make sure to check the boiler and exhaust gas system for absence of leaks.
Secondary air will falsify the measured results
Check that the exhaust gases have a residual oxy­gen (O2) content as low as possible and a carbon
dioxide (CO
2
) content as high as possible.
The carbon monoxide content of the exhaust gases must be below the currently applicable specificati
­ons in all load stages. In the fuel oil combustion mode the permissible soot number in the exhaust gas is not allowed to be exceeded.
Ratio between O2- and CO2- for light oil EL (CO
2
max =15,40%)
% O
2
% CO2 % O2 % CO2
0,00 15,40 3,00 13,19 0,10 15,33 3,10 13,12 0,20 15,25 3,20 13,04 0,30 15,18 3,30 12,97 0,40 15,11 3,40 12,89 0,50 15,03 3,50 12,82 0,60 14,96 3,60 12,75 0,70 14,88 3,70 12,67 0,80 14,81 3,80 12,60 0,90 14,74 3,90 12,53 1,00 14,66 4,00 12,45 1,10 14,59 4,10 12,38 1,20 14,52 4,20 12,31 1,30 14,44 4,30 12,23 1,40 14,37 4,40 12,16 1,50 14,29 4,50 12,08 1,60 14,22 4,60 12,01 1,70 14,15 4,70 11,94 1,80 14,07 4,80 11,86 1,90 14,00 4,90 11,79 2,00 13,93 5,00 11,72 2,10 13,85 5,10 11,64 2,20 13,78 5,20 11,57 2,30 13,71 5,30 11,49 2,40 13,63 5,40 11,42 2,50 13,56 5,50 11,35 2,60 13,48 5,60 11,27 2,70 13,41 5,70 11,20 2,80 13,34 5,80 11,13 2,90 13,26 5,90 11,05
O221
CO
2max
CO
2gem
CO
2max
-----------------------------------------------
× %==
O
2
21
CO
2max
CO
2gem
CO
2max
-----------------------------------------------
× %==
Ratio between O2- and CO2- for heavy oil (CO
2
max =15,90%)
% O
2
% CO2 % O2 % CO2
0,00 15,90 3,00 13,63 0,10 15,82 3,10 13,55 0,20 15,75 3,20 13,48 0,30 15,67 3,30 13,40 0,40 15,60 3,40 13,33 0,50 15,52 3,50 13,25 0,60 15,45 3,60 13,17 0,70 15,37 3,70 13,10 0,80 15,29 3,80 13,02 0,90 15,22 3,90 12,95 1,00 15,14 4,00 12,87 1,10 15,07 4,10 12,80 1,20 14,99 4,20 12,72 1,30 14,92 4,30 12,64 1,40 14,84 4,40 12,57 1,50 14,76 4,50 12,49 1,60 14,69 4,60 12,42 1,70 14,61 4,70 12,34 1,80 14,54 4,80 12,27 1,90 14,46 4,90 12,19 2,00 14,39 5,00 12,11 2,10 14,31 5,10 12,04 2,20 14,23 5,20 11,96 2,30 14,16 5,30 11,86 2,40 14,08 5,40 11,81 2,50 14,01 5,50 11,74 2,60 13,93 5,60 11,66 2,70 13,86 5,70 11,58 2,80 13,78 5,80 11,51 2,90 13,70 5,90 11,43
O221
2max
CO
2gem
CO
2max
-----------------------------------------
× %==
Page 36
36
Exhaust Gas Test
Trouble Shooting Instructions
Exhaust gas loss
Exhaust gas loss by way of free heat will occur as a result of the temperature difference between the fuel-air mixture entering the furnace chamber and the gases discharged. Any increase in the excess of air and the resultant higher exhaust gas volume will cause the exhaust gas loss to rise. The exhaust gas loss can be calculated as follows:
q
A
tAtL–()
A
1
CO
2
-----------
B+
=
q A = exhaust gas loss in % t A = exhaust gas temperature
in °C
t L = combustion air temperature
in °C
CO2= volumetric content of carbon
dioxide in %
Example: Data measured in fuel oil mode: CO2 content of exhaust gases 12,8%
Exhaust gas temperature 195°C Air intake temperature 22°C
The exhaust gas loss can be calculated as follows:
Light oilELHeavy oil
S
A
1
= 0,50 0,490
B = 0,007 0,007
In any case of trouble proceed with checking the basic conditions for a proper operation of the boiler system:
1.Is electric power available?
2.Is fuel oil contained in the tank?
3.Are the shut-off valves opened?
4.Are all control and safety instruments
such as boiler thermostat, water supply failure cut-out, limit switches,
etc. properly set?
1. Ignition failure
Cause Remedy
Ignition elec­trode short cir­cuit.
Adjust electrodes.
Wide ignition electrode spacing.
Adjust electrodes.
Dirty and wet electrodes.
Clean electrodes.
Cracked insulator.
Replace insulator.
Defective igni­tion transformer.
Replace transformer.
Defective auto­matic furnace controller.
Replace controller.
Burnt ignition cable.
Replace cable; search for cause and eliminate.
Pilot burner failure.
Adjust ignition gas pressure
Ignition gas valve does not open.
Search for cause and elimi­nate
Defective solenoid.
Replace
2. Motor running failure
Cause Remedy
Motor protection relay and fuses.
Check and replace if required.
Air pressure switch not changed over or defective.
Check and replace if required.
Defective motor. Replace motor. Defective power
contactor.
Replace contactor.
Air fan motor starts but stops after 20-25 secs.
Check for solenoid leaks
Air fan motor starts, but stops after about 10 secs in pre-venti­lating mode.
Air pressure switch fails to change over; replace switch if defective; clean switch if dirt has accumulated; check electrical connections.
3. Pump oil delivery failure
Cause Remedy
Shut-off valves closed.
Open valves.
Filter blocked by dirt.
Clean filter or
replace cartridge. Filter leaks. Replace filter Oil lines leak. Retighten scre-
wed unions; tigh-
ten oil lines. Suction valve
leaks.
Remove and
clean or replace. Direction of rota-
tion of pump.
Check irection of
rotation. Damaged gear-
box.
Replace pump.
Reduced pump output.
Replace pump.
-Strong mechanical noise. Pump takes in air Retighten scre-
wed unions. High vacuum in
oil pipe
Clean filter; fully
open valves. For heavy oil:
Incorrect oil tem­perature.
Check pre-hea-
ter:
thermostat set-
ting, dirt
Page 37
37
Trouble Shooting Instructions
8. Cleaning and lubricating instructions
Depending on the amount of dirt intro­duced by the combustion air it will be necessary to clean the fan impeller, ignition electrodes, flame sensors and air dampers as required.
For burner with mechanical compound controller: Lubricate the ball heads of the com­pound controller setting screws with grease.
The bearing points of the burner moving parts require no maintenance. Damages of ball bearings should be detected and eliminated at an early stage to avoid greater subsequent trouble. Listen to the motor bearing noise to identify possible irregularities.
4. Unsteady atomization
Cause Remedy
Loosened nozzle.
Tighten nozzle
Hole partly clog­ged.
Remove and clean or replace.
Worn by long­time use.
Replace by new
one. Oil flow blokkage Due to clogged
nozzle.
Remove and
clean. Nozzle leaking. Replace nozzle. Shut-off valve in
nozzle rod lea­king.
Replace valve.
5. No response to flame by automatic furnace controller with flame sensor
Cause Remedy
Dirty flame sen­sor.
Clean flame
sensor. Burner fails to
start.
Check
connection of
automatic fur-
nace controller. Trouble lamp
lights; flame trouble.
Unlock and
search for cause
Weak flame sen­sor signals.
Check combus-
tion setting. Burner starts
without flame formation. Solenoid valve fails to open.
Defective coil or
rectifier.
Check connec-
tion.
6. Mixing unit gives poor com­ bustion data due to heavy inside accumulation of oil or coke
Cause Remedy
Incorrect set­tings.
Correct settings.
Incorrect mix­ture ignition unit.
Replace unit.
Nozzle too large or too small.
Replace nozzle.
Incorrect angle of spray.
Replace nozzle.
High or low com­bustion air flow rate.
Readjust burner.
Furnace cham­ber not suf­ficiently ventilated.
Furnace cham­ber to be ventila­ted through a non-closed ope­ning with a cross section of min. 50 % of all chim­ney cross sec­tions of the furnace system. Take care to observe the application regu­lations.
7. Solenoid valve fails to open
Cause Remedy
Defective coil. Replace coil. Defective auto-
matic furnace controller.
Replace auto­matic furnace controller.
Valve does not close tightly; dirt accumulated on sealing surfaces.
Open valve; remove foreign matter; replace valve if required.
Page 38
38
Servicing Instructions
Operating Trouble
In case of operating trouble it should be checked whether the system is in proper working order.
Make a check for the following:
1.Availability of fuel. Availability of fuel oil in the tank.
2.Availability of electric power in the burner system.
3.Proper functional order and setting of all control and safety instruments such as temperature controller, safety limiter, water failure cut-out, electrical limit switches, etc. If the trouble is not found to be due to any of the above­mentioned points it will be necessary to test the burner functions very carefully.
Prevailing conditions:
The burner will be found to be out of operation and in faulty and interlocked position.
Proceed with searching for the cause of the trouble and eliminate it. Unlock the automatic furnace controller by pressing the fault eliminate key and start the bur­ner.
Do not press the fault eliminate key longer than 10 seconds.
The start-up program will be initiated and should be carefully monitored. The possible cause of the fault may be quickly found by reference to the fault indicator of the automatic furnace con­troller and watching the start-up and operating program.
Page 39
39
System Diagram
1 Burner blower 2 Oil filter 3 Stop valve 4 Oil level indicator 5 Suction valve 6 Tank 7 Leak indicator 8 Quick-acting valve 9 Filling line 10 Limit transmitter 11 Vent line 12 Pump unit 13 Pressure holding valvel
Stepless control, with supply pump and ring line system
Stepless control, direct intake
1 Burner blower 2Oil filter 3Stop valve 4 Oil level indicator 5 Suction valve 6 Tank
7 Leak indicator 8 Quick-acting valve 9 Filling line 10 Limit transmitter 11 Vent line
Page 40
40
Product description
Brenner E10.12000/14000 L-EUF
Product description
The type E 10.12000/14000 LE-UF burners are oil burners for the combustion of EL fuel oil to DIN 51603-1. They are equipped with a free-flame burner head for low-NOx combustion. Other com
­ponents of the burners are: combustion-air fan, air-pressure monitor with test pushbut
­ton, air box with servomotor for the air dam­pers, oil atomizer with high-pressure oil pump, nozzle piping, return nozzle, oil hydraulics block (with pressure monitors, val
­ves and control shaft), flexible pressure tubing, and electrical igniter for fuel-oil opera
­tion. The burners can be linked up with an electronic controller for interconnected ope
­ration, or can be equipped with their own electronics for interconnected operation. Speed control and O
2
control are options.
Important information
The burners should be installed and put into operation by an engineering specialist who is familiar with, and adheres to, the applicable regulations and guidelines. Only the manu
­facturers, or persons appointed by them, are permitted to do any repair work on monitors, limiters and automatic firing systems as well as any other safety-relevant equipment. Also the replacement of original components is the sole responsibility of specialists. The bur
­ner should be maintained at least once a year by a duly qualified person. To this end, a maintenance contract is recommended to be concluded. The burner must not be operated in rooms exposed to aggressive vapours (e.g. sprays, perchloroethylene, tetrachloro-hydrocarbon, solvents) or dust. For a proper combustion­air supply, the firing system zone shall be sufficiently ventilated.
Oil-based operation Start-up
When the firing system is turned on, the bur­ner control circuit will close and the program will be started. The burner will then be put into operation as soon as the program has been executed. This start-up process is con
­trolled and monitored by the automatic firing unit (which is a component of the electronic burner controller). The fan starts to run, and the electric servomotor moves the closed air damper into the pre-ventilation position so that the burner can ventilate the combustion chamber and exhaust with the required air quantity. After the required pre-ventilation time, the air damper is moved into the ignition position. Ignition is initiated, and the oil supply is released. The solenoid valves open and let the pressurized oil flow to the nozzle and return line. The oil is then atomized, mixed with the combustion air, and ignited. A pro
-
per, stable flame will form within the safety
period. Until the end of this safety period, a "flame" signal will be applied via the flame monitor to the automatic firing unit, and is maintained until normal shut-down. The bur
-
ner start-up program is completed.
Operation
Following the formation of the flame, the bur­ner will for a short time remain at the separa­tely set ignition load level and is then reduced to the minimum power level. The
­reafter, power control is released, i.e. the power controller automatically regulates the burner within the range from partial to full load. Depending on the heat required, the controller sends an "open" or "close" signal to the servomotor to increase or reduce the oil and air rate. In this "interconnected" con
­trol mode, both the oil control valve and the air damper are set and, thus, the oil quantity controlled in relation to the air quantity. Thanks to this stepless volume control, the burner can be set to any point between par
­tial and full load. When the burner is out of operation, the air damper is closed so that no cold air can flow through the burner, heat generator and chimney.
General safety functions (oil)
If no flame forms after burner starting (fuel release), the burner will shut down when the safety period has elapsed (shut-down on faults). Flame failure during operation and air pressure failure during pre-ventilation or during burner operation result in a fault shut­down. Any failure of the flame signal after the safety period and a flame signal during pre­ventilation (external light control) result in a fault shut-down, and the automatic firing unit (component of the electronic burner control
­ler) is locked. Unlocking is possible immedia­tely after the fault shut-down. The firing unit will return to its start position and resume the burner restarting process. A power failure results in a normal shut-down of the burner. After voltage recovery, the burner can be automatically restarted provided no other locks are active (e.g. one set by a safety chain). As a rule, fuel supply is immediately cut off when a trouble occurs.
Page 41
41
Page 42
44
Customer Service:
ECB GmbH
Struppener Strasse 01796 Pirna
Loading...