E.C.A. Proteus Plus Installatio And User's Operating Instructions

Page 1
PLUS
23,3 kW Room Sealed Fan Assisted Gas Combination Boiler (monothermic type)
INSTALLATION AND USER’S OPERATING INSTRUCTIONS
Page 2
...-- .I
CONTENTS
PREFACE GUARANTEE & SERVICE SYMBOLS'
DEFINITIONS
SAFETY
INSTRUCTIONS
AND
WARNINGS
PRODUCT
General Specifications Product Notation Technical
Data
L J
BOILER
PACKAGING
INSTALLATION
Selection Of The Boiler Location
Mounting The Boiler
CONNECTIONS
Flue Connection
Gas Supply & Water Systems
Electricity
Supply
BOILER
START-UP
Final Checks And Operations Before Boiler
Start-up
Control
Panel Operating The Boiler Timer
GAS TYPE
CONVERSION
Gas Pressure
Adjustments
Replacement Of The Burner
Injectors
Jumper Adjusment
FAULT & FAILURE
FINDING MAINTENANCE STANDARDS AND
REGULATIONS
APPENDIX
2
Page 3
PREFACE
Proteus Plus 23,3 kW room sealed fan assisted gas combination boilers have been designed for providing efficient, safe and comfortable central heating (CH) and domestic hot water (DHW). The boilers are supplied for use with either natural gas or LPG.
This manual contains installation and users operating instructions. The detailed information about technical data, selection of the boiler location, fitting the connections (water systems, gas supply, flue connection and electricity supply), gas type conversion, maintenance and fault & failure finding are placed in your manual. Please read the instructions carefully for operating the boiler a long time period and to maximize benefit from the boiler specifications.
Please keep all your documents safe.
GUARANTEE & SERVICE
The appliance has guarantee period against faulty workmanship or material in condition that the instructions and precautions in this manual must be obeyed. The service operations and general maintenance must be carried out only by qualified person.
The warranty certificate must be registered by Service in the installation day.
Your appliance need not any repairs if operated according to this manual. For assistance
additional information, consult qualified person, installer or gas supplier.
or
SYMBOLS DEFINITIONS
The symbols have been placed on particular points to make some instructions more noticeable. The symbols definitions are described as follows:
- CAUTION: Property damage and/or non-severe injury can happen.
- WARNING: Severe injury or death can happen.
: The important explanations to be considered by users.
: The situations that can only be interfered by qualified person.
2
Page 4
SAFETY INSTRUCTIONS AND PRECAUTIONS
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
Safety Instructions
When a gas leak is found or suspected:
- Turn off the gas valve of the boiler and other appliances which operate with gas.
- Shut off the oven, cooker and similar appliances to put their flame out.
- Do not light match, lighter etc. and put cigarette out.
- Allow fresh air into the room by opening doors and windows.
- Do not touch the electrical appliances switches and plugs.
- Turn off gas supply at the gas meter.
- Do not use telephones in the environment where a gas leak is suspected.
- Call your qualified person as soon as possible.
Do not place and use flammable and explosive liquid or materials around the boiler. Keep soap and water solution away from electrical connections during cleaning, gas leak test etc.
Do not block air vents, openings made in the walls of the room, which provide fresh air to the
installation room.
Do not lay the LPG container down.
Water Systems & Gas Supply Line
Before installation of the boiler, the water systems (CH and DHW circuit) and gas supply line must be completed in accordance with the relevant regulations and standarts by user.
Gas Type Conversion
The appliance should be purchased depending on operating gas type. In case of a demanding gas
type conversion, this is made with charge.
Gas type conversion from LPG to natural gas or from natural gas to LPG must be carry out only by qualified person. After gas type conversion, gas leak test must be performed by qualified person.
Maximum pressure regulator must be sealed and the self-adhesive conversion label must be placed on the boiler after gas type conversion.
Installation
The boiler must be installed in accordance with national and local requirements, gas safety regulations, relevant standarts and this manual by qualified installer.
The appliance should be mounted against a closed wall. The appliance must be positioned so that the plug is accessible. The appliance should not be positioned having a direct contact to steam or gases.
Any change of flue position must not be made without consulting qualified person.
3
4
3
2
1
Page 5
Boiler Start-up
Boiler start-up must be performed certainly by qualified person.
Gas type (natural gas/LPG), gas supply pressure (mbar), maximum DHW operating water presure
(bar) and electricity supply voltage (V) data which are detailed on the information plate must be suitable with mains supply conditions. This is checked by qualified person.
After boiler start-up, you should request information about operating the boiler and safety precautions from qualified person.
Operating The Boiler And Maintenance
Read carefully instructions and precautions in this manuel against wrong usage which causes unsafe conditions.
The boiler should be checked and serviced for general maintenance once a year. Maintenance and service operations must be carried out only by qualified person.
Only a damp cloth should be used for cleaning the outer surface of the boiler and then the surfaces should be dried completely. Do not use chemical subtances or solutions which cause rust and scratches in your appliance.
PRODUCT
General Specifications
ProteusPlus 23,3 kW room sealed fan assisted gas combination boilers are for providing central heating and domestic hot water. The boilers are supplied for use with either natural gas or LPG.
Boiler has space saving design which provides easy servicing and maintenance. It has also a elegant appearance with compact dimensions (720x400x330 mm).
Control panel has been designed ergonomically to provide user friendliness. The display panel has a yellow backlight LCD display and err or led. Operating modes, actual and setpoint Central Heating & Domestic Hot Water temperatures. manometer and timer-(optional) are on the conrol panel, boiler functions and fault/error conditions can be seen on the LCD display .
Microcontroller board (main board) provides all the functionality and safety of the boiler. The controller drives gas valve, fan, pump and 3-way valve. Flame modulation can be seen through the observation glass on the front panel.
CAUTION: Do not directly contact the observation glass while observing the flame
modulation to avoid burning injury.
Burner, is made of stainless steel, withstands thermal stress. Burner performs silently and provides efficient and clean combustion as a result of the homogeneous dispersion of gas. Combustion chamber has ideal dimensions for burner and perfect insulation of heat and has been designed to provide loss of low heat, high efficiency and low emission of gas. These specifications of burner and combustion chamber provide energy saving and minimum noise level.
Pump has an automatic air vent and 3 operation mode. The boiler has pump over-run behaviour so that pump continues to run for a certain time after ending of CH or DHW heat demand to prevent from thermal accumulation in water circuit.
Heat exchanger is made of copper and designed for thermal shock absorbing. It has long life, high productivity and is non-calcerous as well.
4
6
5
Page 6
Plate heat exchanger makes hot water more efficient in monothermic types. The safety systems in your appliance provide entire safety for you and your appliance. The safety
systems are:

Flue Gas Safety System
Flame Failure Safety System
Over-heat Safety System (105 0C)
DHW (Domestic Hot Water) Over-heat Safety System (71 0C)
High Water Pressure Protection System (3 bar)
Low Water Pressure Protection System (0,6 bar)
Low Voltage Protection System (165 VAC)
Thermal Accumalation Protection System (with by-pass circuit and pump over-run)
Frost Protection System (The appliance must be on stand-by mode to activate frost protection system) Pump Anti-sieze Function 3 Way Anti-sieze Function (in monothermic types) Automatic Air Vent
Expansion Vessel (7lt)
Product Notation
Table 1
Technical Data
Proteus Plus 23,3 kW room sealed fan assisted gas combination boiler is a C type boiler (EN 483). C type boilers have a sealed combustion chamber. Required fresh air for combustion is provided independently from the installation room by concentric air/flue ducts and products of combustion can
be also discharged appliances.
by
the
same
air/flue
ducts.
Therefore,
they are
named
as air
independent
gas
5
Notation
Des
criptio
n
PRP 24 HM
Proteus Plus 23,3 kW Room Sealed Fan Assisted Gas Combination Boiler (monothermic type)
Page 7
kW
kW
kW
m3/h
o
C
o
C
watt
kg
For gas consumption calculation ; Natural gas: Hu=9,59 kWh/m
3
LPG: Hu=12,793 kWh/kg
*the following gas categories can also be used
6
PRP 24 HM
Gas Categories
II
2H
3B/P
II
2E
3B/P
II
2E+ 3+
Table 2.2
PRP 24 HM
Unit
Gas Category *
Boiler Type
Type of gas
Performances
P
min
, Min. Heat Output
P
maks
, Max. Heat Output
P
%80
, Heat Output
Q
min
, Min. Thermal Load
Q
maks
, Max. Thermal Load
Q
%80
, Thermal Load
Gas Consumption
Natural Gas (Max. Load)
Natural Gas (Min. Load)
LPG
Gas Supply Pressure
Natural Gas
LPG
Domestic Hot Water
Min. Flow Rate For Activating
Max. Flow Rate
Min. Operating Pressure
Max. Operating Pressure
Set Temperature Range
Central Heating
Min. Operating Pressure
Max. Operating Pressure
Set Temperature Range
General
Electrical Supply
Electrical Power Consumption
Expansion Vessel
Insulation Class
Dimensions (HxWxL)
Weight (Net)
NOx
II
2H
3B/P
C
12x C32x C42x C52x
Natural gas
LPG
8,2 23,3 18,7
9,2 25,6 20,5
2,67 0,96 2,00
20
28 / 37
3
10 (t=33,4)
0,3 / 30
10 / 1
35-64
0,6
3
40-80
230V AC- 50Hz
95
8
IPX4D
720x400x330
35
2
kW
kW
kW
m3/h
kg/h
mbar mbar
ltr/min
ltr/min bar / kPa bar/ MPa
bar bar
V AC / Hz
ltr
mm
Page 8
D
Wiring Diagram
PRP
24HM
I
Ill
f
El
12
1
15
L_,
I I
CNS
.
8
E::::::::l
c::::::::J
CN1
4
...
T
N
F
22
1
2
3 4
5
MAIN BOARD
SUPPLY
CABLE
ELECTRIC 3 WAY
VALVE
GASVALVE
FAN
PUMP
9 OUTS DE
TEMPERATURE
SENSOR (Optional)
10 DHW
FLOW SENSOR
11 DHW
TEMPERATURE SE
NSOR
12
DIFFERENTIAL A R PRESSURE
SWITCH
13
LIMIT THERMOSTAT
14
WATER
PRESSURE SWITCH
15
CH
TEMPERATURE SE
NSOR
16 TIMER
(Optoi nal)
17 TIMER
SUPPLY
18
19
20
21
22
23
24
TERMINAL
GAS VALVE
MODULATOR
ROOM
THERMOSTAT (Opti
onal)
TERM NAL
COMMUNICATION CABLE DHW
TEMPERATURE CONTROL POTE
NTIOMETER
CH
TEMPERATURE CONTROL POTENTIOMETER
6
I
GNmON
ELECTRODE
7
IONI
ZATION EL.ECTRODE
8 FUSE 2A
25
STATUS POTENTIOMETER
26 ERROR LEO
27 LCD D SPLAY
...:I
27
. 2
0
23 24 25
11
1
s=:
_=-:_
=
-
_=_=_=_-,
=-==,==-
;Kj
--, ® 16
21
' I
17
19
20
5
4
-
0
CN9
CN8
9
Page 9
fig. 1
BOILER PACKAGING
CAUTION: The instructions on the boiler package should be considered during
transportation and storage.
- The product is covered with a cardboard box of which dimensions are 867x 470x400 mm (HxWxL) and supported by upper and lower styrofoams (fig. 2a).
a)
b)
fig. 2
The required parts (Wall bracket, 5 pieces gasket for water and gas connections and screews) for installation of the boiler is put into the upper styrofoam (fig. 2b). The other parts which seen in the
a) Mounting bracket b) CH connecting pipes (3/4’’, 2 pieces) c) DHW connecting pipes (1/2’’, 2 pieces) d) Gas supply pipe (3/4’’, 1 piece) e) Nipples (1/2’’, 2 pieces – 3/4’’, 3 pieces) which are held with spring clips. h) 4 pieces ½” gasket, 6 pieces ¾” gasket for water and gas connections.
8
Page 10
- For room sealed fan assisted operation,
apart
from the
boiler
package,
concentric
air/flue
kit
( 60/100) is given with a cardboard box.
Air/flue kit consists of the following
parts: a) Flat sealing ring b) Flange c) 900 Concentric elbow d) Screws e) Fixing Collar f) Sealing ring, EPDM g) Concentric Terminal (100mm)
fig. 3
9
Page 11
INSTALLATION
Selection Of The Boiler Location
The boiler must be installed in accordance with gas safety regulations and relevant standards. Additionally, the clearances around the boiler should be as shown in fig. 4 in order to make service, maintenance and usage easier.
Fig. 4 indicates minumum clearances from the ceiling and the sides.
a)
b)
fig. 4
WARNING: The appliance must be positioned so that the plug is accessible.
- The appliance should be mounted against a closed wall.
- The outer surface of the boiler do not exceed 85 oC in maximum running mode so do not take additional precautions againts constructional materials (combustible materials).
10
Page 12
Room Sealed Fan Assisted Operation
WARNING: For room sealed fan assisted appliance, the boiler location and air/flue
terminal position must obey national and local requirements, gas safety regulations and relevant standarts.
The room sealed fan assisted boiler is not suitable for external installation. It should be
within in the building.
- In case of gas leakage, it is necessary to vent the installation room according to national and local requirements, although the room sealed fan assisted boilers are independent of room volume and ventilation.
WARNING: Do not block the air vents which provide fresh air to the installation room.
The air/flue terminal must be exposed to the external air and allow free passage of air cross it
at all times.
- The minumum acceptable dimensions from the terminal to obstructions and ventilation openings must obey national and local requirements.
- The air/flue ducts should be fitted at a slight % 10 or 20 downwards incline to prevent any water or condensation from entering the boiler.
Mounting The Boiler
Having determined the boiler location,
- Use the paper template to mark out the positions of the fixing holes of wall and mounting brackets.
- Drill the wall and fix the wall bracket to the wall with the 3 screws, then also the mounting bracket with the 2 screws.
- Hang the boiler up on the wall bracket.
a)
b)
11
Page 13
fig. 7
CONNECTIONS
Flue Connection
3 different types of air/flue system can be designed for 23,3 kW room sealed fanned
boilers: a) The air/flue system is designed by horizontal concentric ducts. b) The air/flue system is designed by two separate ducts. c) The air/flue system is designed by vertical concentric ducts.
: The air/flue kit, given with your room sealed fan assisted appliance,
is only suitable for horizontal air/flue design. For the other types,
you should order required accessories from qualified service.
Connection by horizontal concentric ducts
- 900 Concentric elbow can be mounted on the boiler in different positions (fig. 9).
Air/flue kit parts is mounted as shown in fig. 10.
- Stick the flat sealing ring (96,3/128 mm) on the elbow.
- Fix the sealing ring (60 mm) to interior joint of the elbow – fan outlet.
- Fix the sealing ring (60 mm) to interior joint of the elbow – tube (L=860 mm).
- Fix the sealing ring (100mm) to interior joint of the elbow – tube (L=860 mm).
- Screw the 900 elbow to the boiler with 4 screws.
:The air/flue ducts should be fitted at a slight % 10 or 20 downwards
incline to prevent any water or condensation from entering the boiler.
12
a
Page 14
fig. 9
Room Sealed Fan Assisted Operation
fig. 10
If the air/flue kit length is insufficient, additional flue
accessories qualified service. Do not use any other type / brand name of
should
be
ordered
through
- Horizontal air/flue kit accessories (fig 11): a) Concentric extension, L=500 mm, 60/100 mm
Concentric extension, L=1000 mm, 60/100 mm b) 900 Concentric elbow, 60/100 mm c) 450 Concentric elbow, 60/100 mm
a)
b)
c)
fig. 11
13
Page 15
Room Sealed Fan Assisted Operation
The total length of horizontal air/flue system must not exceed 3 m. Furthermore, each extra
90
0
concentric elbow or two pieces of 450 concentric elbow decreases the maximum length 1m
a)
b)
c)
fig. 12
14
Page 16
Room Sealed Fan Assisted Operation
Mounting the restrictor: The restrictor should be mounted on the fan outlet according to the length of the air/flue connection to provide efficient combustion and suitable combustion products.
Table 3
(mm)
fig. 13
15
Product
Elbow
L (m)
L
max
(m)
restrictor
PRP 24 HM
1x90
0
≤ 1
3
47
1x90
0
1< ≤ 2
49
0
1x90
2< ≤ 3
-
2x90
0
≤ 1
2
49
2x90
0
1< ≤ 2
-
3x90
0
≤ 1 1 -
Page 17
Room Sealed Fan Assisted Operation
Connection by two separate ducts
Maximum length of the air ducts and flue ducts are seen in Table 4. The air ducts and flue
ducts must be parallel (fig. 15).
- The twin air/flue kit and its accessories (fig. 14): a) The twin air/flue kit b) Extension, L=500 mm, 80 mm
Extension, L=1000 mm, 80 mm c) 900 elbow, 80 mm d) 450 elbow, 80 mm
a)
b)
c)
d)
fig. 14
fig. 15
16
b
Page 18
Room Sealed Fan Assisted Operation
Table 4
(mm)
Connection by vertical concentric ducts
Vertical flue connection can be designed by 60/100 mm or 80/125 mm concentric ducts.
The total length is 3 m for 60/100 mm vertical air/flue system and 8 m for 80/125 mm vertical air/flue system. Furthermore, each extra 900 concentric elbow or two pieces of 450 concentric elbow
decreases the maximum length 1 m (fig. 17).
- Vertical air/flue kit (60/100) accessories (fig. 16): a) Concentric vertical connector, 60/100 mm b) 900 Concentric elbow, 60/100 mm c) Concentric extension, L=500 mm, 60/100 mm
Concentric extension, L=1000 mm, 60/100 mm d) Pitched roof flashing
e) Concentric vertical top, 60/100 mm f) 450 Concentric elbow, 60/100 mm
fig. 16
17
c
Product
Elbow
L
max
(m)
restrictor
PRP 24 HM
0
1x90
4
42
2x90
0
3
42
Page 19
Room Sealed Fan Assisted Operation
Table 5 The restrictors for 60/100 mm concentric ducts
(mm)
In the use of 80/125 mm concentric ducts,
- up to 2 m length, the same restrictors (shown in Table 5) should be used
- between 2m and 8m, no restrictor should be used.
a)
b)
c)
Sample connections by 60/100 mm vertical concentric ducts
fig. 17
18
Product
Elbow
L (m)
L
max
(m)
restrictor
PRP 24 HM
1x90
0
≤ 1
3
47
1x90
0
1< ≤ 2
49
0
1x90
2< ≤ 3
-
2x90
0
≤ 1
2
49
2x90
0
1< ≤ 2
-
3x90
0
≤ 1 1 -
Page 20
Gas
Supply & Water Systems
(Optional)
-
Water & gas connections between the boiler and the mounting bracket can be fixed with the
optional
pipes and the nipples as shown in fig.
18.
1\!Iounting
Bracket
Nipp le (3/4"
t
b
t
c
t
e
t
d
a
fig.
18
a) CH flow
3/4"
b) DHW outlet
1/2"
c) Gas inlet
3/4"
d) DHW inlet
1/2"
e) CH return
3/4"
-
A Suitable valve should be mounted on the gas inlet and CH - DHW water circuits.
In addition,
a
water fiher should be mounted on CH (3/4") return and DHW (1/2")
inlet.
-
A plastic hose should be ftxed the outlet tap of the 3 bar relief valve and the hose should be
connected to the drain
line.
-
The connection between
the
appliance and gas supply must be made with a flexible
pipe.
19
Page 21
Electricity Supply
Electrical installation should be made according to the national and local instructions. The boiler must be earthed and a standard 230 V AC - 50 Hz supply is required.
WARNING: Disconnect power supply to prevent electrical shock before connecting
the electricity supply.
WARNING: If the supply cord is damaged, it must be replaced by a special cord or
assembly available from the manufacturer or its service agent
Room Thermostat Connection (Optional)
It is possible to use one of the 2 different type of Honeywell room thermostats together with your appliance optionally, for providing temperature control of the system.
Room thermostat (T6360A1004)
Programmable digital r
oom
thermostat (
T6651E
1011)
fig. 19
a simple room thermostat +10 0C +30 0C
7-day program Up to 4 level changes per day Programmable frost protection
: The brand name of the room thermostat must be Honeywell, otherwise it may cause failure in your appliance. In that case, no responsibility will be accepted.
- Room thermostat connection is seen in the wiring diagrams (page-7, fig.1).
- Disconnect the bridge between pole number 3 and pole number 4 of terminal number 21.
- Connect the room thermostat connections to the terminal same poles.
20
Page 22
BOILER START-UP
Final Checks And Operations
: Having completed the installation and connections (flue, electricity
supply, gas supply and water circuits) of the boiler according to the authorized gas company regulations and relevant standards, the final checks and operations must be carried out by qualified person.
Filling the boiler and central heating circuit with water.
- Firstly, turn on all the radiator valves.
- Check inlet and outlet CH valves. The valves must be open.
- Remove the front panel, combustion body cover (in room sealed fan assisted boiler) and right side panel respectively.
- Open manual air vent on heat exchanger1).
- Open filling tap
2)
slowly to fill the system.
- Turn off the air vent on heat exchanger when water starts to squirt.
- Keep up filling until water pressure measures 1,5 – 2 bar on the thermomanometer.
- Turn off the filling tap.
CAUTION: Donot forget to turn off the filling tap, water can leak and cause damage.
- Turn on the air vents to set air free until water squirts. Repeat this process for all the radiators.
- Check the CH water pressure on the thermomanometer again, and turn on the filling tap to increase water pressure to 1,5-2 bar level.
- Check radiator vents whether any air in the water pipes or not. Air must be purged out entirely for efficient heating.
- Check any leakage in the radiator and the water pipes finally.
Open hot water tap to check DHW circuit. Check any leakage water pipes.
Check whether flue kit is comprised of original parts or not according to the instructions and regulations.
In addition, Electricity connections of boiler must be earthed and suitable with main supply conditions (230 V AC - 50 Hz).
Gas supply must be checked by the qualified gas company. Call qualified service to boiler start-up after all these processes are completed.
: Boiler start-up must be performed certainly by qualified person.
: After boiler start-up, you should request information about operating
the boiler and safety precautions from qualified person.
21
3
2
1
Page 23
2
) The filling tap is not available in some models based on national and local
regulations.
II
Control Panel
The control panel shown in fig. 20 consists of the following parts as detailed
below.
Fault & Error
LED
Manometer
Status
Potentiometer
Central Heating
Potentiometer
fig.20
Domestic Hot
Water
Temperature
Potentiometer
[I] Status
-
Pl
(Winter/Summer
and Off-Reset
mode)
Status has 4
functions
a) To select Summer (
-
)
mode
b) To select Winter (
*)
mode.
c) To select Off "
e
"
position
d) Reset
position
[I]
Central
Heating (CH)
Temperature - P2
- CH can set up between 35°C and 80°C with summer or winter
mode
-During
the Selection of summer mode, the boiler runs only for Domestic Hot Water not for CH
[1] Domestic Hot Water (DHW)
Temperature - P3
DHW can set up between 35°C and 64°C temperature depends on user
demand.
[I]
Display Panel: Yellow backlit LCD
display
Boiler functions, CH/DHW temperature, fault/error conditions, set and actual values can be
seen
on
LCD.
- In case of error, the error codes appear automatically on the display (See page 29-
30).
Domestic Hot Water
Mode
Burner ON
Fault &
Error
LED
Central
Hot
Water
Mode
Fault
Reset
DHW & CH
Temp.
22
Page 24
[!]
Error
I Reset Mode
- Error code and error led will be flashing countinusly If the errors cause a lock out condition,
tum
to Status (Pl) to
Reset" e "position
and hold it for 5 sec. to get to the normal operation (winter
or
summer) mode
again.
[!]
Monometer
CH operating water pressure can be read on the
manometer.
[1]
Timer
(Optional)
The timer provides automatic control of the boiler based on set operating programs.
It
is possible
to
enter
8
programs allocatable over the
week.
[!] Control Panel
Cover
Whilst CH, DHW and Status s are under its plastic cover, boiler functions and fault/error
conditions
can be seen without opening the
cover.
:
The CH has no effect anymore on the system if the system
has t e room
t1Jermostat
and also it is
active.Additionally,CH
should be the
maximum position.
Operating
The
Boiler
[]
Start
up
I
Shut off the
boiler
Turn the Status Pot. desireable position (Winter or Summer) to (fig.21). When the
winter
mode is
selected,
-
After the sequence test is completed successfully, LED L3 will turn ON to indicate the
stand
by mode
ifthere're
neither DHW or CH request.
lfCH
is in winter mode, ignition
sequence
will be started automatically to fire the bwner and then CH will be
active.
OFF-Reset
*
·
MIN.
CD
23
Page 25
- In case of failed ignition, automatic ignition sequence is repeated 5 times. If all ignition trials are failed, flame failure lockout happens. Error LED (red) will turn ON and blink to indicate this error
condition (fig.22). Turn Status s knob to the reset
position and hold it for 5 sec. to get to the
normal operation again If the lockout condition continues after reset read the Fault/Error finding.
- Turn the Status Pot. to ‘ OFF-Reset position to shut off the boiler. LCD backlight will turn OFF.
CH (Central Heating) Mode
By adjusting the CH , summer mode or winter mode can be selected.
a) Summer mode
- Rotate the CH to the
position. In the summer mode, any CH heat demands can not be satisfied.
The summer mode is only to satisfy domestic hot water demand.
b) Winter mode
- Rotate the CH to the position. In the winter mode, your appliance satisfies central heating and also domestic hot water.
- Adjust any CH water flow temperature between 40 and 80 oC with the Central Heating . The boiler will modulate to the desired temperature. CH symbol on the LCD indicates that CH is active. If there is a DHW request, it interrupts the CH mode until DHW request is finished.
24
2
Page 26
- Rotate the CH to minumum position. The summer mode will be active and the system will go back to stand-by mode again.
Frost Protection
The appliance goes on and off automatically depending on actual water temperature values measured by the sensors for protecting water circuits against freezing. This function protects both CH and DHW systems. Frost protection has 2 level:
a) Frost protection level 1
- When the appliance in stand-by mode and the CH sensor measures a low water temperature in the system (less than 8 °C ), the pump runs. When the CH water temperature goes above 10 °C (measured on the CH sensor), the pump will stop.
b) Frost protection level 2
- When the appliance in stand-by mode and the CH sensor measures a low water temperature in the system (less than 6 °C ), the boiler starts as if there was a CH demand. When the CH water temperature goes above 15 °C (measured on the CH sensor), the CH demand will end (burner will be off). During frost protection the burner will run with minimum capacity.
- The same situation occurs when DHW sensor measures less than 6 °C. The boiler starts and when the water temperature goes above 15 °C, the boiler will turn stand-by mode.
: The appliance must be on stand-by mode to activate frost protection
system.
Pump Anti-Seize Function
Anti-seize protections function prevents the pump from probable blocking when the pump stays inactive for a long period of time. This function goes on automatically if the pump has been inactive for at least 24 hours and runs the pump for 5 sn. in CH mode. In monothermic types, pump anti-seize
function and 3-way valve protection becomes active together and the 3-way valve changes position against blocking.
his
Timer (Optional) The timer on the control panel provides setting indepentendly 8 programs over the week.
Setting the timer
- Set the right sliding button to
.
- Set the day using
button. (Arrow on top shows 1:Monday, 2:Tuesday…7:Sunday)
- Set hour using h button.
- Set minute using m button.
- Set the right sliding button to RUN
25
4
3
Page 27
fig. 21
Programming the Unit
- Set the right sliding button to P.
- See the program number that you want to set while pressing P button. (If the program to be set is
startup program,
sign will appear. 1,3,5,7,9,11,13,15 are startup programs; 2,4,6,8,10,12,14,16 are
shutdown programs)
- Set the day of startup or shutdown program by pressing
button. (1:Monday, 2:Tuesday,
7:Sunday) Apart from one day setting, you can make settings for only workdays, only weekends and all days except Sunday and for all days using this button.
- Set the hour by pressing h button.
- Set the minute by pressing m button.
- After setting startup and shutdown times, set the sliding button to RUN.
Ignoring the program
- If you want to turn off your unit while program is running or if you want to turn on the unit before
the program activates the device, press the
button. Pressing this button while device is running
turns off the unit. Pressing this button before program activates the unit, turns on the device immediately, unit stops running at the end of program time. This button works only when sliding button is at RUN position, and the button sign appears on display.
Manual
Control
- In order to control the unit manually use sliding button on the left of the clock. Unit runs continuously while sliding button is at I position. Unit stops running when sliding button is at 0
Resetting The Clock
- In order to reset the clock, press R button while sliding button is at RUN” position. All programs
set will be erased from the memory.
Programming On Winter Mode
- Set your program on the program timer.
- Set the turn ON/OFF button to ON.
- Set the temperature thermostat to any level you wish.
- Your unit will turn itself on when the timer reaches to time you have set and system will keep the temperature constant at the level you set. Unit will turn it self off when the timer reaches the time you have set.
GAS TYPE CONVERSION
: Gas type conversion from LPG to natural gas or from natural gas toLPG
must be carried out only by qualified person.
-
Gas type conversion can be divided in 3 sections: 1-gas pressure adjustments, 2- replacement of the burner injectors and 3-changing the parameter of the gas type (00-NG or 01-LPG).
26
Page 28
Gas Pressure Adjustments
The operating pressure varies depending on the type of gas. Therefore, minumum and maximum operating gas pressure must be set by means of the adjusment screws that are on top of the gas valve.
The heat output directly depends on the operating pressure. When the operating gas pressure range is adjusted, minimum and maximum heat output is also adjusted (mechanically).
- Firstly, operate the boiler at maximum load while adjusting maximum operating pressure and operate the boiler at minimum load while adjusting minumum operating pressure.
- Undo the 2 screws which are located on the lower edge to remove the front panel.
- Undo the 2 screws which are located on the corners of the control panel.
- Pull the control panel outwards to reach the gas valve.
Maximum operating pressure adjustment:
- Operate the boiler at maximum load.
- Connect the tube of a clocking gas meter to outlet pressure tap whose diameter is =9 mm after loosening the taps screw.
(fig. 22)
- Remove cap screw from maximum pressure regu lator to expose pressure regulator adjusment screw which is seen as (2) in fig. 22.
- Turn the adjustment screw clockwise to increase or counter-clockwise to decrease gas flow to the burner.
- Check gas pressure measurements on the gas meter to satisfy the desired value.
In LPG operation, the adjustment screw (2) is tightened to the end for 28 / 35 supply pressure.
Minimum operating pressure adjustment:
- Operate the boiler at minimum load.
- Connect the tube of a clocking gas meter to the outlet pressure tap.
- Turn the adjustment screw which is seen as (1) in fig. 22 counter-clockwise to increase or clockwise to decrease gas flow to the burner.
- Check gas pressure measurements on the gas meter to satisfy the desired value.
- Ensure that the taps screw is tightened after making the adjustments.
- Replace pressure regulator cap screw.
- Reassemble the front panel and the control panel.
27
Table 7
Proteus Plus 23,3 kW
Natural Gas
Max. operating gas pressure (mbar)
11,9
Min. operating gas pressure (mbar)
1,4
LP
G
Max. operating gas pressure (mbar)
28
Min. operating gas pressure (mbar)
3,6
Page 29
fig. 22
Replacement Of The Burner Injectors
WARNING:Keep the gas valve on the boiler and electricity supply closed during
replacement of the burner injectors.
- Shut off the boiler by turning the status to OFF-Reset position and turn off the gas valve on the boiler.
- Undo the 2 screws which are located on the lower edge to remove the front panel.
- Undo the 2 screws which are located on the corners of the control panel.
- Pull the control panel outwards.
- Undo the 6 screws which are located around the body to remove the combustion body cover (in room sealed fan assisted boiler).
- Undo the 4 screws which fasten the manifold to the burner to remove the burner.
- Fix the suitable burner injectors according to type of gas (11 pieces of injectors used in 23,3 kW )
- Reassemble in the reverse order.
Polidora
Parameter Adjustment (Gas Type conversion)
Gas type conversion from LPG to natural gas or from natural gas toLPG must be carried out only by qualified person. Conversion gas parameter value(P02) is 00 for natural gas (NG) and 01 for LPG.
WARNING: Maximum pressure regulator must be sealed and the self-adhesive
conversion label must be placed on the boiler after gas type
conversion.
WARNING: In case of gas leak, fire or explosion hazard, property damage,
severe injury or death can happen. Therefore, gas leak test must be performed by qualified person after gas type conversion.
28
Table 8
Injectors Diameter for
Wor
gas
Injectors Diameter for
Natural Gas
1,35 mm
1,32 mm
LPG
0,79 mm
0,79 mm
Page 30
.. GAS LEAK TEST
);-
Apply a rich soap and water
solution
to the surface of all pipe
connections.
Bubbles
indicate a gas
leak
);­);­);-
In case of gas leak,
tighten
the pipe
connection.
Check the pipe
connection
again for gas
leak.
Replace
the
part/parts
if gas leak can not be
stopped.
A CAUTION: Keep soap and water solution away from electrical connections
during
gas leak test .
FAULT/ERROR
FINDING
Several
checks
are
included
to protect the boiler and its
environment.
In case of error
condition,
the
error is
displayed
by the alarm
LED's
on the display panel (Table 9) and heat
demands
will
bedisabled
..
Error
conditions
can be
divided
in 2
groups:lockout conditions
and
blocking conditions.
a) Lockout
conditions,
flame failure
lockout,
high limit lockout and APS error, can only be
cleared
by turning the status knob (P1) to Offi'Reset
position
and wait for 5
seconds
then back to
previous position.
If the lockout
condition continius
after the reset , check the gas inlet and supply valves. If the
problem
continues
call
qualified service.
b)
Blocking conditions,
CH NTC error (short circuit or open
circuit),
DHW NTC error (short
circuit
or open circuit), and low water
pressure,
will reset as soon as the cause of the
problem disappears.
For
example,
when CH sensor is out of
operating
range,
blocking condition
will be
generated
and keep
the
system
off until the sensor is within
operating
range
again.
Table 10
29
ERROR I FAILURE CODES
ERROR/FAULT DEFINATIONS
Fl
Lockout
for
overheating
F2
DHW probe
damaged
F3
Primary circuit probe
damaged
F4
Lockout (ionization
problem)
F5
Air
Pressure
switch
Problem (exhaust thermostat problem)
F6
External
Probe
damaged
F7
No water
pressure
F8
Main
voltage failure
Page 31
Table 11
CC: When the power supply is switched On
showed on LCD display means Outside temp.
Sensor correctly disconnected and the function enabled.
OC: When the power supply is switched On “
showed on LCD display means Outside temp.
Sensor correctly connected and the function enabled.
30
Fault/Error
Cause
Solution
1- The boiler does not start up
by turning Status to winter or summer” position.
- Lack of electricity.
-Check the electricity connections.
2- Flame failure lockout: When turning the Status to winter or summer position, F4 error code appears on LCD and error (red) led turns ON by flashing to indicate the lockout position
(F4)
- No flame in burner after 3 ignition trials.
- Turn the Status Konb (P1) to Off/Reset position and waith for 5 seconds. - If the lockout condition continues after the reset, check the gas inlet and supply valves.
- Having all tries expired, consult qualified service.
3- CH NTC error: F3 error code appears on LCD and error (red) led turns ON by flashing to indicate the lockout position (F3)
- CH sensor is out of operating range and this condition lasted for more than 10 seconds.
- Check the CH inlet valve and radiator valves whether it is open or not.
- The system stays in blocking condition until CH sensor is in operating range. If repeated, consult qualified service.
4- DHW NTC error: F2 error code appears on LCD and error (red) led turns ON by flashing to indicate the lockout position (F2)
- DHW sensor is out of operating range and this condition lasted for more than 10 seconds.
- Check the CH inlet valve and radiator valves whether it is open or not.
- The system stays in blocking condition until DHW sensor is in operating range. If repeated, consult qualified service.
5- High limit lockout: F1 error code appears on LCD and error (red) led turns ON by flashing to indicate the lockout position (F1)
- If limit thermostat is open, error will be generated.
- Check the flue connections / chimney.
- Reset the boiler, turn the Status (P1) to Off­Reset position and waith for 5 seconds.- If the lockout condition continues after the reset, consult qualified service.
6- APS Error: F5 error code appears on LCD and error (red) led turns ON by flashing to indicate the lockout position (F5)
- Insufficient flue draught.
- Check the flue connections.
- Reset the boiler, turn the Status Potentiometer (P1) to Off-Reset position and waith for 5 seconds.- If the lockout condition continues after the reset, consult qualified service.
7- Low water pressure: F7 error code appears on LCD and error (red) led turns ON by flashing to indicate the lockout position (F7)
- Operating water pressure is not suitable for your appliance.
- The system stays in blocking condition until water pressure is back to nominal value. ­Check the valves whether is open or not.
- Check circuits for leaks.
8- Low voltage : F8 error code appears on LCD and error (red) led turns ON by flashing to indicate the lockout position (F8)
- The main voltage is not suitable for your appliance.
- The system stays in blocking condition until main voltage is back to nominal value. -
9- OTC Exthernal Probe Fault:
F6 error code appears on LCD
(F6)
- Check to the OTC terminal connections and cabels.
- The Boiler can work without OTC (outside temp. Sensor)
- Consult qualified service for the solution.
Page 32
MAINTENANCE
- The boiler should be checked and serviced for general maintenance once a year. Maintenance and service operations must be carried out only by qualified person.
- Only a damp cloth should be used for cleaning the outer space of the boiler and then the surfaces should be dried completely. Do not use chemical subtances or solutions which cause rust in your appliance.
STANDARDS AND REGULATIONS
During the installation and operation of the boiler, the instructions and precautions detailed in this manual and also all relevant standards and local regulations must be obeyed.
APPENDIX
Pumps characteristic curve (height & flow)
23,3 kW gas combination boilers capacity & operating gas pressure diagrams for natural gas
31
2
1
Page 33
23,3 kW gas combination boilers capacity & operating gas pressure diagrams for (LPG) Propan
ALL RIGHTS RESERVED
Product specifications are subject to change without notice.
Manufacturer :
EMAS MAKİNA SANAYI A.Ş.
Organize Sanayi Bölgesi Mustafa Kemal Bulvarı No:13 MANİSA Pbx: +90 236 213 00 21 Fax: +90 236 213 08 59
www.emas.com.tr
32
3
Loading...