1. SAFETY REGULATIONS AND NOTES
Please read these operating instructions carefully before starting to work with the device. Observe the following warnings to prevent malfunctions or physical damage to both property and people. These operating instructions are to be regarded as part of this device. If the device is sold or transferred, the operating instructions must accompany it. These operating instructions may be duplicated and forwarded for information about potential dangers and their prevention.
11. SAFETY REGULATIONS AND NOTES
11.1 Levels of hazard warnings
11.2 Staff qualification
11.3 Basic safety rules
11.4 Electrical voltage
21.5 Safety and protective functions
21.6 Electromagnetic radiation
21.7 Mechanical movement
21.8 Emission
21.9 Hot surface
21.10 Storage
21.11 Disposal
32. PROPER USE
43. TECHNICAL DATA
43.1 Product drawing
53.2 Nominal data
53.3 Data according to ErP directive
53.4 Technical features
53.5 Mounting data
53.6 Transport and storage conditions
63.7 Electromagnetic compatibility
64. CONNECTION AND START-UP
64.1 Connecting the mechanical system
64.2 Connecting the electrical system
74.3 Connection in terminal box
84.4 Factory settings
94.5 Connection screen
104.6 Checking the connections
104.7 Switch on device
104.8 Switching off the device
105. INTEGRATED PROTECTIVE FUNCTIONS
116. MAINTENANCE, MALFUNCTIONS, POSSIBLE
126.1 Cleaning
126.2 Safety test
1.1 Levels of hazard warnings
These operating instructions use the following hazard levels to indicate potentially hazardous situations and important safety regulations:
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Compliance with the measures is mandatory.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Exercise extreme caution while working.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or damage of property.
NOTE
A potentially harmful situation can occur and, if not avoided, can lead to property damage.
1.2 Staff qualification
The device may only be transported, unpacked, installed, operated, maintained and otherwise used by qualified, trained and authorised technical staff. Only authorised specialists are permitted to install the device, to carry out a test run and to perform work on the electrical installation.
1.3 Basic safety rules
Any safety hazards stemming from the device must be re-evaluated once it is installed in the end device. Observe the following when working on the unit:
; Do not make any modifications, additions or conversions to the
device without the approval of ebm-papst.
1.4 Electrical voltage
; Check the electrical equipment of the device at regular intervals, refer
to chapter 6.2 Safety test.
; Replace loose connections and defective cables immediately.
DANGER Electrical load on the device
Risk of electric shock
→ Stand on a rubber mat if you are working on an electrically
charged device.
WARNING Terminals and connections have voltage even with a unit that is shut off
Electric shock
→ Wait five minutes after disconnecting the voltage at all poles
before opening the device.
Item no. 50307-5-9970 · ENG · Revision 82542 · Release 2014-05-08 · Page 1 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G355-AY40-01
Operating instructions
CAUTION In the event of failure, there is electric voltage at the rotor and impeller
The rotor and impeller are base insulated.
→ Do not touch the rotor and impeller once they are installed.
CAUTION If control voltage is applied or a speed setpoint is stored, the motor automatically restarts, e.g. after a power failure.
Danger of injury
→ Keep out of the danger zone of the device.
→ When working on the device, switch off the mains
supply voltage and secure the latter from being switched on again.
→ Wait until the device stops.
→ After working on the device, remove any used tools or
other objects from the device.
1.5 Safety and protective functions
DANGER Missing safety device and non-functioning safety device
If there is no safety device, you could be seriously injured, for example if you reach into the running device or your hands are sucked into it.
→ Operate the device only with a fixed and isolating safety
protection and a fixed guard grille. The guard must withstand the kinetic energy of a fan blade detaching at maximum speed.
→ The device is a built-in component. You, the owner/
operator, are responsible for providing adequate protection for the device.
→ Shut down the device immediately if you detect a
missing or ineffective protective feature.
1.6 Electromagnetic radiation
Interference from electromagnetic radiation is possible, e.g. in conjunction with open and closed-loop control devices. If unacceptable emission intensities occur when the fan is installed, appropriate shielding measures have to be taken by the user.
NOTE Electrical or electromagnetic interferences after integrating the device in installations on the customer's side.
→ Verify that the entire setup is EMC compliant.
1.7 Mechanical movement
DANGER Flying parts
Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds, causing bodily harm.
→ Take appropriate safety measures.
WARNING Rotating device
Long hair, loose items of clothing and jewellery could become entangled and pulled into the device. You could be injured.
→ Do not wear any loose clothing or jewellery while working
on rotating parts.
→ Protect long hair by wearing a cap.
1.8 Emission
WARNING Depending on the installation and operating conditions, a sound pressure level greater than 70 dB(A) may arise.
Danger of noise-induced hearing loss
→ Take appropriate technical safety measures.
→ Protect operating personnel with appropriate safety
equipment, e.g. hearing protection.
→ Also observe the requirements of local agencies.
1.9 Hot surface
CAUTION High temperature at the electronics enclosure
Danger of burn injuries
→ Ensure that sufficient protection against accidental contact is
provided.
1.10 Storage
; Store the device, partially or fully assembled, in a dry and
weatherproof manner in the original packing in a clean environment.
; Protect the device from environmental impacts and dirt until the final
installation.
; We recommend storing the device for a maximum up to one year to
guarantee proper operation and longest possible service life.
; Even devices explicitly suited for outdoor use are to be stored as
described prior to being commissioned.
; Maintain the storage temperature, see
chapter 3.6 Transport and storage conditions.
; Please make sure that all screwed cable glands are fitted with
dummy plugs.
DANGER Rotating device
Body parts that come into contact with the rotor and impeller can be injured.
Translation of the original operating instructions
Item no. 50307-5-9970 · ENG · Revision 82542 · Release 2014-05-08 · Page 2 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
→ Secure the device against accidental contact.
→ Before working on the system/machine, wait until all
parts have come to a standstill.
1.11 Disposal
When disposing of the device, please comply with all relevant requirements and regulations applicable in your country.
R3G355-AY40-01
Operating instructions
2. PROPER USE
The device is exclusively designed as a built-in device for conveying air according to its technical data. Any other usage above and beyond this does not conform with the intended purpose and constitutes misuse of the device. Customer equipment must be capable of withstanding the mechanical and thermal stresses that can arise from this product. This applies for the entire service life of the equipment in which this product is installed.
Proper use also includes:
Use the device in power systems with earthed neutral (TN/TT power
systems) only.
Only using the device in stationary systems.
Carrying out all maintenance.
Moving air with a density of 1.2 kg/m³.
Using the device in accordance with the permitted ambient
temperature, see chapter 3.6 Transport and storage conditions and chapter 3.2 Nominal data.
Operating the device with all protective features in place.
Minding the operating instructions.
Improper use
Using the device in the following ways is particularly prohibited and may cause hazards:
Operating the device with an imbalance, e.g. caused by dirt deposits
or icing.
Operation in medical equipment with a life-sustaining or lifesaving
function.
Operation with external vibrations.
Moving solids content in flow medium.
Painting the device
Connections (e.g. screws) coming loose during operation.
Opening the terminal box during operation.
Moving air that contains abrasive particles.
Moving highly corrosive air, e.g. salt spray mist. Exceptions are
devices that are intended for salt spray mist and protected accordingly.
Moving air that contains dust pollution, e.g. suctioning off saw dust.
Operating the device close to flammable materials or components.
Operating the device in an explosive atmosphere.
Using the device as a safety component or for taking on safety-
related functions.
Operation with completely or partially disassembled or modified
protective features.
In addition, all application options that are not listed under proper use.
Translation of the original operating instructions
Item no. 50307-5-9970 · ENG · Revision 82542 · Release 2014-05-08 · Page 3 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G355-AY40-01
3. TECHNICAL DATA
3.1 Product drawing
Operating instructions
All measures have the unit mm.
1 Cable diameter: min. 4 mm, max. 10 mm; tightening torque: 4±0.6 Nm 2 Accessory part: inlet nozzle 35675-2-4013 not included in the standard scope of delivery; other inlet nozzles on request 3 Depth of screw 12 - 16 mm 4 Tightening torque 3.5±0.5 Nm
Translation of the original operating instructions
Item no. 50307-5-9970 · ENG · Revision 82542 · Release 2014-05-08 · Page 4 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G355-AY40-01
Operating instructions
3.2 Nominal data
Motor M3G112-GA
Phase 3~ Nominal voltage / VAC 400 Nominal voltage
380 .. 480
range / VAC Frequency / Hz 50/60
Type of data definition ml Speed / min
-1
2600
Power input / W 1700 Current draw / A 2.6 Min. ambient temperature
-25
/ °C Max. ambient
40
temperature / °C
ml = Max. load · me = Max. efficiency · fa = Running at free air cs = Customer specs · cu = Customer unit
Subject to alterations
3.3 Data according to ErP directive
Installation category A Efficiency category Static Variable speed drive Yes Specific ratio
*
Specific ratio = 1 + pfs / 100 000 Pa
*
1.01
Actual Request
2013
Overall efficiency ηes / % 66.1 50 54 Efficiency grade N 74.1 58 62 Power input Ped / kW 1.72 Air flow qv / m³/h 4325 Pressure increase total psf / Pa 885 Speed n / min
Data definition with optimum efficiency.
The ErP data is determined using a motor-impeller combination in a standardised measurement configuration.
-1
2585
3.4 Technical features
Mass 13 kg Size 355 mm Surface of rotor Coated in black Material of electronics housing Material of impeller Sheet aluminium, welded Number of blades 7 Direction of rotation Clockwise, seen on rotor Type of protection IP 54 Insulation class "B"
Translation of the original operating instructions
Humidity class F4-1 Mounting position Shaft horizontal or rotor on bottom; rotor
Condensate discharge holes Operation mode S1 Motor bearing Ball bearing
Die-cast aluminium
on top on request Rotor-side
Request 2015
Technical features - PFC, passive
- Control input 0-10 VDC / PWM
- Over-temperature protected electronics / motor
- Alarm relay
- Integrated PID controller
- Input for sensor 0-10 V or 4-20 mA
- Output for slave 0-10 V
- RS485 MODBUS RTU
- Motor current limit
- Soft start
- Line undervoltage / phase failure detection
- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- External 24 V input (programming)
Touch current acc.
<= 3.5 mA
IEC 60990 (measuring network Fig. 4, TN system) Electrical leads Via terminal box Motor protection Thermal overload protector (TOP) wired
internally
Protection class I (if protective earth is connected by
customer)
Product conforming
CE
to standard Approval EAC; UL 1004-7 + 60730
For cyclic speed loads, note that the rotating parts of the device are designed for maximum one million load cycles. If you have specific questions, contact ebm-papst for support.
3.5 Mounting data
; Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).
Strength class for
8.8
mounting screws
You can obtain additional mounting data from the product drawing if necessary.
3.6 Transport and storage conditions
; Use the device in accordance with its protection type.
Max. permissible ambient motor temp. (transp./ storage) Min. permissible ambient motor temp. (transp./storage)
+80 °C
-40 °C
Item no. 50307-5-9970 · ENG · Revision 82542 · Release 2014-05-08 · Page 5 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G355-AY40-01
Operating instructions
3.7 Electromagnetic compatibility
EMC interference immunity EMC interference emission
If several devices are switched in parallel on the mains side so that the line current of the arrangement is in the range of 16 - 75 A, then this arrangement conforms to IEC 61000-3-12 provided that the short-circuit power Ssc at the connection point of the customer system to the public power system is greater than or equal to 120 times the rated output of the arrangement. It is the responsibility of the installation engineer or operator/ owner of the device to ensure, if necessary after consultation with the network operator, that this device is only connected to a connection point with a Ssc value that is greater than or equal to 120 times the rated output of the arrangement.
Translation of the original operating instructions
Acc. to EN 61000-6-2
Acc. to EN 61000-6-3
4. CONNECTION AND START-UP
4.1 Connecting the mechanical system
CAUTION Cutting and crushing hazard when removing the fan from the packaging
→ Carefully hold the impeller to remove the device from its
packaging. Make sure to avoid any shock.
→ Wear safety shoes and cut-resistant safety gloves.
CAUTION Heavy load when taking out the device
Bodily harm, e.g. back injuries, are possible.
→ Two people should remove the device out of its packaging
together.
; Check the device for transport damage. Damaged devices must no
longer be installed.
; Install the undamaged device according to your application.
4.2 Connecting the electrical system
DANGER Electric voltage on the device
Electric shock
→ Always install a protective earth first.
→ Check the protective earth.
DANGER Incorrect insulation
Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation
requirements for voltage, current, insulation material, load etc.
→ Route cables such that they cannot be touched by any
rotating parts.
DANGER Electrical load (>50 µC) between mains wire and protective earth connection after switching of the supply when switching multiple devices in parallel.
Electric shock, risk of injury
→ Make sure that sufficient protection against accidental contact
is provided. Before working on the electrical connection, the connections to the mains supply and PE must be shorted.
CAUTION Electrical voltage
The fan is a built-in component and features no electrically isolating switch.
→ Only connect the fan to circuits that can be switched off with
an all-pole separating switch.
→ When working on the fan, you must switch off the
installation/machine in which the fan is installed and secure it from being switched on again.
NOTE Interferences and failures are possible
Maintain a distance to the power supply line when routing the control lines of the device.
→ Ensure a sufficiently large clearance.
Recommendation: clearance > 10 cm (separate cable routing)
Item no. 50307-5-9970 · ENG · Revision 82542 · Release 2014-05-08 · Page 6 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G355-AY40-01
Operating instructions
NOTE Water penetration into leads or wires
Water enters at the cable end on the customers side and can damage the device.
→ Make sure that the cable end is connected in a dry
environment.
Connect the device only to circuits that can be switched off using an all-pole disconnecting switch.
4.2.1 Prerequisites
; Check whether the data on the type plate agree with the connection
data.
; Before connecting the device, ensure that the supply voltage matches
the operating voltage of the device.
; Only use cables designed for current according to the type plate.
For determining the cross-section, follow the basic principles in accordance with EN 61800-5-1. The protective earth must have a cross-section equal to or greater than the outer conductor cross­section. We recommend the use of 105°C cables. Ensure that the minimum cable cross-section is at least AWG26/0.13 mm².
4.2.2 Power supply connection, fuse protection
Assignment of conductor cross-sections and the fuse protection required for them (overload protection only, no device protection).
Nominal voltage
3/PE AC 380 - 480 VAC 3/PE AC 380 - 480 VAC 3/PE AC 380 - 480 VAC 3/PE AC 380 - 480 VAC
* AWG = American Wire Gauge
4.2.3 Idle current
The values lie in a range of typical < 250 mA.
Translation of the original operating instructions
The effective power in this operating state (readiness for operation) is
simultaneously at typical < 5 W.
Safety fuse
VDE UL VDE mm² *AWG 16 A 15 A C16A 1.5 16
20 A 20 A C20A 2.5 14
25 A 25 A C25A 4.0 12
32 A 30 A C32A 6.0 10
Because of the EMC filter integrated for compliance with EMC limits (interference emission and interference immunity), idle currents in the mains cable can be measured even when the motor is at a standstill and the mains voltage is switched on.
Automatic circuit breaker
Wire cross­section
Wire cross­section
4.2.4 Residual current operated device
Only universal (type B or B+) RCD protective devices are permitted. Like frequency inverters, RCD protective devices cannot provide personal safety while operating the device. When switching on the power supply of the device, pulsed charge currents from the capacitors in the integrated EMC filter can lead to the RCD protective devices triggering without delay. We recommend residual current devices with a trigger threshold of 300 mA and delayed triggering (super-resistant, characteristic K).
4.2.5 Leakage current
For asymmetrical power systems or if a phase fails, the leakage current can increase to a multiple of the nominal value.
4.2.6 Locked-rotor protection
Due to the locked-rotor protection, the start-up current (LRA) is equal to or less than the nominal current (FLA).
4.3 Connection in terminal box
4.3.1 Preparing connection lines for the connection
Strip the cable just enough so that the screwed cable gland is tight and the terminals are relieved of strain. Tightening torque, see chapter 3.1 Product drawing.
Fig. 1: Recommended stripping lengths in mm (inside the terminal box) Legend: CL = control lines
4.3.2 Connecting cables with terminals
WARNING Terminals and connections have voltage even with a unit that is shut off
Electric shock
→ Wait five minutes after disconnecting the voltage at all poles
before opening the device.
; Remove the cap from the screwed cable gland.
Remove the cap only in those places where cables are inserted.
; Mount the screwed cable glands with the seal inserts provided in the
terminal box.
; Insert the line(s) (not included in the standard scope of delivery) into
the terminal box.
; First connect the "PE" (protective earth) connection.
; Connect the lines to the corresponding terminals.
Use a screwdriver to do so. During the connection work, ensure that no cables splice off.
Item no. 50307-5-9970 · ENG · Revision 82542 · Release 2014-05-08 · Page 7 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G355-AY40-01
Operating instructions
4.4 Factory settings
Factory settings with which the device is pre-set by ebm-papst.
Control mode parameter set 1 Control mode parameter set 2 Fan / device adress 01 Max. PWM / % 100 Min. PWM / % 5 Save set value to EEPROM Set value control Analogue (linear) Control function parameter set 1 Control function parameter set 2
PWM controlling
PWM controlling
Yes
Positive (heating)
Positive (heating)
Fig. 2: Connecting the wires to terminals
; Seal the terminal box.
4.3.3 Cable routing
No water may penetrate along the cable in the direction of the cable gland. When routing the cable, ensure that the screwed cable glands are arranged at the bottom. The cables must always be routed downwards.
Translation of the original operating instructions
Fig. 3: Cable routing for fans installed upright.
Item no. 50307-5-9970 · ENG · Revision 82542 · Release 2014-05-08 · Page 8 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G355-AY40-01
Operating instructions
4.5 Connection screen
No. Conn. Designation Function / assignment KL 1 1 L1 Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz KL 1 2 L2 Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz KL 1 3 L3 Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz PE PE Earth connection, PE connection KL 2 1 NO Status relay, floating status contact; normally open; close with error KL2 2 COM Status relay; floating status contact; changeover contact; common connection; contact rating 250 VAC / max.
2 A (AC1) / min. 10 mA
KL2 3 NC Status relay, floating status contact; break with error KL 3 1 RSA Bus connection RS-485, RSA, MODBUS RTU; SELV KL 3 2 RSB Bus connection RS-485, RSB, MODBUS RTU; SELV KL 3 3 / 10 GND Signal ground for control interface; SELV KL 3 4 Ain1 U Analogue input 1, set value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain1; SELV
KL 3 5 + 10 V Fixed voltage output 10 VDC, +10 V ±3%, max. 10 mA, short-circuit-proof, power supply for external
devices (e.g. potentiometer), SELV
KL 3 6 Ain1 I Analogue input 1, set value: 4-20 mA; Ri = 100 Ω, parametrisable curve, only usable as alternative to input
Ain1 U; SELV
KL 3 7 Din1 Digital input 1: enabling of electronics,
enabling: open pin or applied voltage 5-50 VDC disabling: bridge to GND or applied voltage <1 VDC reset function: triggers software reset after a level change to <1 VDC; SELV
KL 3 8 Din2 Digital input 2: parameter set switch 1/2, according to EEPROM setting, the valid/used parameter set can be
selected via bus or via digital input DIN2. Parameter set 1: open pin or applied voltage 5-50 VDC Parameter set 2: bridge to GND or applied voltage <1 VDC; SELV
KL 3 9 Din3 Digital input 3: controller function of integrated controller, according to EEPROM setting, the controller function
of the integrated controller is normally/inversely selectable per bus or per digital input normal: open pin or applied voltage 5-50 VDC inverse: bridge to GND or applied voltage <1 VDC; SELV
KL 3 11 Ain2 U Analogue input 2, actual value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain2; SELV
KL 3 12 + 20 V Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof, power supply for external
Translation of the original operating instructions
devices (e.g. sensors); SELV
KL 3 13 Ain2 I Analogue input 2, actual value: 4-20 mA, Ri = 100 Ω, parametrisable curve, only usable as alternative to
input Ain2 U; SELV
KL 3 14 Aout Analogue output 0-10 VDC, max. 5 mA, output of the current motor level control coefficient / motor speed
parametrisable curve; SELV
Item no. 50307-5-9970 · ENG · Revision 82542 · Release 2014-05-08 · Page 9 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G355-AY40-01
Operating instructions
4.6 Checking the connections
; Make sure that the power is off (all phases).
; Secure it from being switched on again.
; Check the correct fit of the connection lines.
; Screw the terminal box cover closed again. Terminal box tightening
torque, see chapter 3.1 Product drawing.
; Route the connecting cables in the terminal box so that the terminal
box cover closes without resistance.
; Use all plug screws (the entire number). In doing so, insert the
screws manually to avoid damage to the thread.
; Make sure that the terminal box is correctly closed and sealed and
that all screws and screwed cable glands are properly tightened.
4.7 Switch on device
The device may only be switched on if it has been installed properly and in accordance with its intended use, including the required safety mechanisms and professional electrical connection. This also applies for devices which have already been equipped with plugs and terminals or similar connectors by the customer.
WARNING Hot motor housing
Fire hazard
→ Ensure that no combustible or flammable materials are
located close to the fan.
; Inspect the device for visible external damage and the proper function
of the protective features before switching it on.
; Check the air flow paths of the fan for foreign objects and remove any
that are found.
; Apply the nominal voltage to the voltage supply.
; Start the device by changing the input signal.
5. INTEGRATED PROTECTIVE FUNCTIONS
The integrated protective functions cause the motor to switch off automatically in case of faults described in the table.
Malfunctions Description / Function of
safety feature
Rotor position detection error An automatic restart occurs. Locked rotor ; After the blockage is
removed, the motor restarts
automatically. Line under-voltage (mains input voltage outside of permitted nominal voltage) Phase failure A phase of the supply voltage
; If the mains supply voltage
returns to permitted values, the
motor restarts automatically.
fails for at least 5 s.
; If all phases are correctly
supplied again, the motor
automatically restarts after 10 -
40 s.
4.8 Switching off the device
Switching off the device during operation:
; Switch off the device via the control input.
; Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.
Switching off the device for maintenance work:
; Switch off the device via the control input.
; Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.
; Disconnect the device from the supply voltage.
; When disconnecting, be sure to disconnect the earth wire connection
last.
Translation of the original operating instructions
Item no. 50307-5-9970 · ENG · Revision 82542 · Release 2014-05-08 · Page 10 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G355-AY40-01
Operating instructions
6. MAINTENANCE, MALFUNCTIONS, POSSIBLE CAUSES AND REMEDIES
Do not perform any repairs on your device. Return the device to ebm­papst for repair or replacement.
WARNING Terminals and connections have voltage even with a unit that is shut off
Electric shock
→ Wait five minutes after disconnecting the voltage at all poles
before opening the device.
CAUTION If control voltage is applied or a speed setpoint is stored, the motor automatically restarts, e.g. after a power failure.
Danger of injury
→ Keep out of the danger zone of the device.
→ When working on the device, switch off the mains
supply voltage and secure the latter from being switched on again.
→ Wait until the device stops.
→ After working on the device, remove any used tools or
other objects from the device.
If the device remains out of use for some time, e.g. when in storage, we recommend switching the device on for at least two hours to allow any condensate to evaporate and to move the bearings.
Malfunction/error Possible cause Possible remedy Impeller running roughly
Motor does not turn Mechanical blockage Switch off, de-
Translation of the original operating instructions
Imbalance in rotating parts
Mains supply voltage faulty
Faulty connection De-energise, correct
Motor winding broken Replace device
Clean the device; if imbalance is still evident after cleaning, replace the device. If you have attached any weight clips during cleaning, make sure to remove them afterwards.
energise, and remove mechanical blockage. Check mains supply voltage, restore power supply. Important! The error message resets automatically. The device starts up again automatically without advance warning.
connection, see connection diagram.
Thermal overload protector responded
Insufficient cooling Improve cooling. Let
Ambient temperature too high
Unacceptable operating point (e.g. counterpressure is too high)
Allow motor to cool off, locate and rectify cause of error, if necessary cancel restart lock-out
the device cool down. To reset the error message, switch off the mains supply voltage for a min. of 25 s and switch it on again. Alternatively, reset the error message by applying a control signal of <0.5 V to DIN1 or by short circuiting Din1 to GND. Reduce the ambient temperature. Let the device cool down. To reset the error message, switch off the mains supply voltage for a min. of 25 s and switch it on again. Alternatively, reset the error message by applying a control signal of <0.5 V to DIN1 or by short circuiting Din1 to GND. Correct the operating point. Let the device cool down. To reset the error message, switch off the mains supply voltage for a min. of 25 s and switch it on again. Alternatively, reset the error message by applying a control signal of <0.5 V to DIN1 or by short circuiting Din1 to GND.
Item no. 50307-5-9970 · ENG · Revision 82542 · Release 2014-05-08 · Page 11 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G355-AY40-01
If you have any other problems, contact ebm-papst.
6.1 Cleaning
NOTE Damage to the device during cleaning.
Malfunction possible
→ Do not clean the device using a water jet or high-pressure
washer.
→ Do not use any cleaners containing acids,
bases or solvents.
→ Do not use any pointed or sharp-edged objects to clean.
6.2 Safety test
NOTE High-voltage test
The integrated EMC filter contains Y capacitors. Therefore, the trigger current is exceeded when AC testing voltage is applied.
→ Test the device with DC voltage when you carry out the
high-voltage test required by law. The voltage to be used corresponds to the peak value of the AC voltage required by the standard.
What has to be tested?
Check the protective casing against accidental contact for damage and to ensure that it is intact Check the device for damage to blades and housing Mounting the connection lines Check the insulation of the wires for damage Impeller for wear/deposits/ corrosion and damage Tightness of screwed cable gland
Translation of the original operating instructions
Condensate discharge holes for clogging, as necessary
How to test? Frequency Which
Visual inspection At least every
Visual inspection At least every
Visual inspection At least every
Visual inspection At least every
Visual inspection At least every
Visual inspection At least every
Visual inspection At least every
6 months
6 months
6 months
6 months
6 months
6 months
6 months
Operating instructions
measure?
Repair or replacement of the device
Replacement of the device
Fasten
Replace wires
Clean or replace impeller
Retighten, replace if damaged Open bore holes
Item no. 50307-5-9970 · ENG · Revision 82542 · Release 2014-05-08 · Page 12 / 12