EBM-PAPST PAPST W2E250-H Datasheet

W2E250-HL06-19
Nominal data
Type W2E250-HL06-19
Motor M2E068-CF
AC axial compact fan
sickled blades (S series)
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 · D-74673 Mulfingen Phone +49 7938 81-0 Fax +49 7938 81-110 info1@de.ebmpapst.com www.ebmpapst.com
Limited partnership · Headquarters Mulfingen
County court Stuttgart · HRA 590344
General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen
County court Stuttgart · HRB 590142
Phase 1~ 1~ 1~
Nominal voltage VAC 230 230 230
Frequency Hz 50 60 60
Type of data definition fa fa fa
Valid for approval / standard CE CE UL 2111
Speed min-12450 2600 2600
Power input W 115 150 165
Current draw A 0.51 0.66 0.70
Motor capacitor µF 3 3 3
Capacitor voltage VDB 400 400 400
Capacitor standard P0 (CE) P0 (CE) UL
Max. back pressure Pa 90 75 75
Min. ambient temperature °C -25 -25 -25
Max. ambient temperature °C 75 60 55
Starting current A 0.88 0.87 0.87
ml = Max. load · me = Max. efficiency · fa = Running at free air · cs = Customer specs · cu = Customer unit Subject to alterations
Item no. 11848-5-9980 · Revision 80549 · Release 2014-02-17 · Page 1 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
W2E250-HL06-19
AC axial compact fan
sickled blades (S series)
Technical features
Size 250 mm
Surface of rotor Coated in black
Material of blades Sheet steel, coated in black
Housing material Die-cast aluminium
Number of blades 7
Direction of air flow "V"
Direction of rotation Counter-clockwise, seen on rotor
Type of protection IP 44; Depending on installation and position
Insulation class "F"
Humidity class F0
Max. permissible ambient motor temp. (transp./ storage)
Min. permissible ambient motor temp. (transp./storage)
Mounting position Any
Condensate discharge holes None
Operation mode S1
Motor bearing Ball bearing
Touch current acc. IEC 60990 (measuring network Fig. 4, TN system)
Electrical leads Via terminal strips, integrated capacitor connected via terminal strips
Motor protection Thermal overload protector (TOP) wired internally
Cable exit Variable
Protection class I (if protective earth is connected by customer)
Product conforming to standard EN 60335-1; CE
Approval CCC; UL 2111; CSA C22.2 Nr.77
+ 80 °C
- 40 °C
< 0.75 mA
Item no. 11848-5-9980 · Revision 80549 · Release 2014-02-17 · Page 2 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
W2E250-HL06-19
Product drawing
AC axial compact fan
sickled blades (S series)
1 Direction of air flow "V"
Connection screen
U1 blue Z brown U2 black
PE green/yellow
Item no. 11848-5-9980 · Revision 80549 · Release 2014-02-17 · Page 3 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
W2E250-HL06-19
Charts: Air flow 50 Hz
200
190
180
170
160
150
140
130
120
110
100
p fs[Pa]
90
80
70
60
50
40
30
20
10
0
Druck p f s[Pa]für Rho=1,2kg/m^3
qv [cfm]
qv [m³/h]
AC axial compact fan
sickled blades (S series)
1.2001.1001.0009008007006005004003002001000
0,8
0,75
0,7
0,65
0,6
0,55
0,5
0,45
4
3
2
p fs[Pa]
1
0,4
0,35
0,3
0,25
0,2
0,15
0,1
0,05
0
2.2002.0001.8001.6001.4001.2001.0008006004002000
pfs _E[IN H2O]
Measurement: LU-60083
Air performance measured as per ISO 5801 Installation category A. For detailed information on the measuring set-up, please contact ebm-papst. Suction-side noise levels: LwA measured as per ISO 13347 / LpA measured with 1m distance to fan axis. The values given are valid under the measuring conditions mentioned above and may vary according to the actual installation situation. With any deviation from the standard set-up, the specific values have to be checked and reviewed with the unit installed.
Measured values
U
V
1
2
3
4
U = Supply voltage · f = Frequency · n = Speed · Pe= Power input · I = Current draw · qv = Air flow · pfs= Pressure increase
230
230
230
230
f
Hz
50
50
50
50
n
min
2450
2450
2390
2320
P
-1
W
115
118
124
130
I
e
A
0.51
0.51
0.54
0.57
qv
m3/h
1835
1695
1535
1275
p
Pa
0
30
60
90
fs
Item no. 11848-5-9980 · Revision 80549 · Release 2014-02-17 · Page 4 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
W2E250-HL06-19
Charts: Air flow 60 Hz
160
155
150
145
140
135
130
125
120
115
110
105
100
95
90
85
80
p fs[Pa]
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
Druck p f s[Pa]für Rho=1,2kg/m^3
qv [cfm]
qv [m³/h]
AC axial compact fan
sickled blades (S series)
1.2001.1001.0009008007006005004003002001000
0,64
0,62
0,6
0,58
0,56
0,54
0,52
0,5
0,48
0,46
0,44
0,42
0,4
0,38
0,36
0,34
4
3
2
p fs[Pa]
1
0,32
0,3
pfs _E[IN H2O]
0,28
0,26
0,24
0,22
0,2
0,18
0,16
0,14
0,12
0,1
0,08
0,06
0,04
0,02
0
2.2002.0001.80 01.6001.4001.2001.0008006004002000
Measurement: LU-60085
Air performance measured as per ISO 5801 Installation category A. For detailed information on the measuring set-up, please contact ebm-papst. Suction-side noise levels: LwA measured as per ISO 13347 / LpA measured with 1m distance to fan axis. The values given are valid under the measuring conditions mentioned above and may vary according to the actual installation situation. With any deviation from the standard set-up, the specific values have to be checked and reviewed with the unit installed.
Measured values
U
V
1
2
3
4
U = Supply voltage · f = Frequency · n = Speed · Pe= Power input · I = Current draw · qv = Air flow · pfs= Pressure increase
230
230
230
230
f
Hz
60
60
60
60
n
min
2600
2525
2420
2310
P
-1
W
150
155
159
164
I
e
A
0.66
0.67
0.69
0.71
qv
m3/h
1910
1760
1595
1355
p
Pa
0
25
50
75
fs
Item no. 11848-5-9980 · Revision 80549 · Release 2014-02-17 · Page 5 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Loading...