Air performance measured as per ISO
5801 Installation Category A. For detailed
information on the measuring set-up,
please contact ebm-papst. Suction-side
noise levels: LwA measured as per ISO
13347 / LpA measured with 1m distance to
fan axis. The values given are valid under
the measuring conditions mentioned above
and may vary according to the actual
installation situation. With any deviation
from the standard set-up, the specific
values have to be checked and reviewed
with the unit installed.
Measured values
U
V
1
2
3
4
230
230
230
230
f
Hz
50
50
50
50
n
min
2800
2790
2775
2800
P
-1
W
215
237
246
227
I
1
A
0.95
1.03
1.07
0.99
LpA
dB(A)
69
65
62
66
LwA
in
dB(A)
78
74
71
74
qv
in
m3/h
1495
1290
1000
630
p
Pa
0
200
400
550
sf
Item no.: 11456-5-9980 · Revision status: KM73571 · Print-out on 25/02/2011 · Created by Y. Uhlmann (VM-TDO) · Page 4 of 5
Air performance measured as per ISO
5801 Installation Category A. For detailed
information on the measuring set-up,
please contact ebm-papst. Suction-side
noise levels: LwA measured as per ISO
13347 / LpA measured with 1m distance to
fan axis. The values given are valid under
the measuring conditions mentioned above
and may vary according to the actual
installation situation. With any deviation
from the standard set-up, the specific
values have to be checked and reviewed
with the unit installed.
Measured values
U
V
1
2
3
4
230
230
230
230
f
Hz
60
60
60
60
n
min
3200
3155
3090
3150
P
-1
W
345
364
386
365
I
1
A
1.51
1.59
1.68
1.59
LpA
dB(A)
73
67
65
70
LwA
in
dB(A)
81
76
73
80
qv
in
m3/h
1710
1425
1115
670
p
Pa
0
300
500
700
sf
Item no.: 11456-5-9980 · Revision status: KM73571 · Print-out on 25/02/2011 · Created by Y. Uhlmann (VM-TDO) · Page 5 of 5