Eaton Magnum SB Series, Magnum DS Series, Magnum IEC Series Technical Product Manual

Magnum DS, SB and IEC low voltage power circuit breakers
Courtesy of NationalSwitchgear.com
Technical product guide
Table of content
Courtesy of NationalSwitchgear.com
1 Overview of the Magnum low voltage circuit breaker
2 Family features and characteristics
Design configuration flexibility .........................................11
3 Magnum DS - Product specic information
Standards and certifications ...........................................17
Selection and identification of ratings for Magnum DS ......................17
Catalog number selection table ........................................18
4 Magnum SB - Product specic information
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5 Magnum IEC - Product specic information
6 Magnum DC - Product specic information
PUBLICATION TITLE CA000000 00E—April 2017 www.eaton.com 2
1
1
1
1
1
1
1
Table of content
Courtesy of NationalSwitchgear.com
7 Magnum trip units and communication devices
8 Accessory devices and connections
9 Technical data and endurance information for installation
10 Applications and other miscellaneous engineering data
11 Magnum drawings and outlines
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
PUBLICATION TITLE CA000000 00E—April 2017 www.eaton.com 3
Overview of the Magnum low voltage circuit breaker
Courtesy of NationalSwitchgear.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Eatons Magnum low voltage power circuit breakers have set industry standards for decades for the global market. The broad and powerful circuit breaker offering provides comprehensive solutions to meet and/or exceed the unique and wide-ranging requirements of todays power distribution systems.
This innovative circuit breaker offering is designed for ultimate performance, custom configuration, and application exibility. Magnum circuit breakers combine many years of successful circuit breaker protection experience with the latest technological advances in circuit breaker, trip unit, and communications performance.
Ever since introducing the first microprocessor-based trip unit, Eaton has advanced the technology with its versatile family of Digitrip RMS trip units designed exclusively for Magnum circuit breakers. Customers have the capability of providing an electrical distribution system with:
Superior programmable protection/coordination
Advanced warning capabilities
System diagnostics/ monitoring/communications
Eatons Magnum family address the needs of a wide range of varying global application requirements. You will find product details, dimensional information, maintenance recommendations, and more when you take a closer look within this Magnum product guide.
Magnum consists of four product families. Each provides specic ratings, features and approvals to optimize performance in concert with the application:
Magnum DS for ANSI rated switchgear applications
Magnum SB for UL rated switchboard applications
Magnum IEC for power distribution and switchboard applications
Magnum DC switches for demanding UL or IEC rated DC applications
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com4
Overview of the Magnum low voltage circuit breaker
Courtesy of NationalSwitchgear.com
Magnum DS family
Magnum DS low voltage power circuit breakers are UL listed, designed, tested and certied to all applicable ANSI, NEMA, UL, CSA, IEC, EC and IEEE standards. Specically, the circuit breakers meet or exceed the following:
UL 1066
ANSI C37.13
ANSI C37.16
ANSI C37.17
ANSI C37.50
IEC 60947-2 (ed.4)
GB14048.2-2008
CSA TIL No. D-34 ”Interim certification
requirements for low voltage power circuit breakers”.
Table 1. Magnum DS ANSI breaker family ratings (Class UL 1066)
Interruption rating (kA) @ 508 Vac
200
800 Amp Frame
In addition, Magnum DS is suitable for use in: UL 1558 “Certied Magnum DS low voltage metal- enclosed switchgear, UL 891 “Standard for LV switchboards, UL CSA TIL No. D-34. Refer to Figure 1 for a visual reference and Table 1 for a quick ratings reference.
Product family characteristics:
Up to 635 Vac operating voltage
Up to 200 kA interruption ratings
Up to 130 kA short time withstand ratings
200–5000A continuous current
Three- and four-pole configurations
Fixed and drawout
1200 Amp Frame
1600 Amp Frame
2000 Amp Frame
Magnum DS low voltage circuit breakers
2500 Amp Frame
3200 Amp Frame
4000 Amp Frame
5000 Amp Frame
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
1
1
130
100
85
65
50
42
1
Interruption rating shown based on breaker equipped with integral Digitrip RMS trip unit.
2
Refer to Section 2 for a detailed ratings table.
3
6000A is available in fan cooled switchgear. See www.eaton.com/lva
= Magnum DS standard frame = Magnum DS narrow frame = Magnum DS double narrow frame = Magnum DS double standard frame
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 5
Overview of the Magnum low voltage circuit breaker
Courtesy of NationalSwitchgear.com
Magnum SB family
1
Magnum SB low voltage
1
insulated case power circuit breakers are certied by UL
1066. The SB Family was
1
designed for the performance and economic requirements
1
of UL891 switchboard class applications overall. Refer to
1
Figure 2 for a visual reference and Table 2 for a quick ratings
1
reference.
1
1
1
1
1
Product family characteristics:
Switchboard class
Up to 635 Vac
Three- and four-pole configurations
Drawout and fixed mounted
200A to 5000A continuous current
50 kA to 150 kA interrupting ratings
Short-time withstand up to 100 kA
Magnum SB insulated case circuit breakers
1
1
1
Table 2. Magnum SB insulated case breaker family ratings (Class UL 891)
Interruption
1
rating (kA) @ 440 Vac Icu =Ics
1
150
800 Amp Frame
1200 Amp Frame
1600 Amp Frame
2000 Amp Frame
1
1
130
1
100
1
1
85
1
1
65
1
1
50
1
2500 Amp Frame
3000 Amp Frame
4000 Amp Frame
5000 Amp Frame
3
1
1
1
Interruption rating shown based on breaker equipped with integral Digitrip RMS trip unit.
2
Refer to Section 2 for a detailed ratings table.
3
6000A is available in fan cooled switchgear. See www.eaton.com/lva
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com6
= Magnum SB standard frame = Magnum SB narrow frame = Magnum SB double narrow frame = Magnum SB double standard frame
Overview of the Magnum low voltage circuit breaker
Courtesy of NationalSwitchgear.com
Magnum IEC family
Magnum IEC low voltage air circuit breakers are designed, tested and certied for IEC rated switchboards. They meet or exceed all applicable standards including EN/IEC 60947-2. Refer to Figure 3 for a visual reference and Table 3 for a quick ratings reference.
Table 3. Magnum IEC 60947-2 rated air circuit breakers
Product family characteristics:
Up to 690 Vac operating voltage
Up to 125 kA Icu =Ics at 440 Vac
200–6300A continuous current
Three- and four-pole configurations
Fixed and drawout
Magnum IEC low voltage fixed and drawout breakers
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Interruption rating (kA) @ 440 Vac Icu =Ics
125
100
85
65
50
40
1
Interruption rating shown based on breaker equipped with integral Digitrip RMS trip unit.
3
Refer to Section 2 for a detailed ratings table.
800 Amp Frame
1250 Amp Frame
1600 Amp Frame
2000 Amp Frame
2500 Amp Frame
3200 Amp Frame
4000 Amp Frame
= Magnum IEC standard frame = Magnum IEC narrow frame = Magnum IEC double narrow frame = Magnum IEC double standard frame
5000 Amp Frame
6300 Amp Frame
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 7
Overview of the Magnum low voltage circuit breaker
(kA Interruption)
Courtesy of NationalSwitchgear.com
Magnum DC switch family
1
Magnum DC switches provide
1
disconnect and switching capabilities to meet UL 1066, UL 489 and IEC 60947-2
1
standards. The switches share the same frames and
1
accessories as the circuit breakers, but do not include
1
trip units. Refer to Figure 4 for a visual reference and Figure 5
1
for a quick ratings reference.
1
1
1
1
1
Product family characteristics:
Up to 1000 Vdc
800–3200A continuous current
50 to 65 kA withstand rating
Fixed and drawout
Magnum DC switches
1
1
1
Magnum DC switch ratings
1
1
1
1
1
1
1
1
1
100
80
60
40
20
0
(up to 3200A continuous) (up to 3200A continuous) (up to 5000A continuous)
= UL 1066 interrupting/withstand = UL 489 interrupting/withstand = IEC 60947-2 withstand = IEC 60947-2 interrupting
1
1
65kA
50kA 50kA
25kA
@300 Vdc @600 Vdc @1000 Vdc
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com8
Universal family features
Courtesy of NationalSwitchgear.com
As mentioned, Magnum low voltage power circuit breakers consist of four product families. Although each family has its own unique performance and features, each Magnum breaker boasts a wide array of common design elements. These common design elements deliver proven performance with expanded capabilities, no matter which product family is applied. To fulll the latest market needs with proven reliability and performance, Magnum is the clear choice for low voltage applications.
High performance interruption & withstand levels
Magnum provides Magnum provides large range withstand and interrupting ratings to maximize selectivity and system coordination.
A range from 42kA up to 200 kA interrupting - application on power distribution systems with higher available fault currents.
Up to 130 kA withstand (short-time) - total selectivity/selective coordination/discrimination between main, feeder, and branch circuit breakers.
Current limiting performance - lower let-through currents for superior equipment protection.
Optional Arc Flash Reduction Maintenance System (ARMS™) - reduces arc flash hazards and improves operator and maintenance safety.
Circuit breakers performance tested - meet or exceed all applicable ANSI, NEMA, UL, CSA, IEC, EC and IEEE standards. Specifically, the circuit breakers meet or exceed the following: UL 1066, ANSI C37.13, ANSI C37.16, ANSI C37.17, ANSI C37.50, IEC 60947-2, GB14048.2-2008, and CSA TIL No. D-34.
Family features and characteristics
Narrow frame (800 – 2000 Amps): Promoting the most compact modular enclosures.
Standard frame (800 – 3200 Amps): Ideally suited for vertically stacked modular construction.
Double narrow frame (4000 Amps): Decreased footprint when space is at a premium.
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Continuous current ratings
800 to 5000A (UL1066), 800 to 6300A (IEC) - ensuring maximum uptime over expansive frame rating range.
100% rated – designed for continuous operation at 100% of current rating.
Reverse feed capable - top or bottom feed for multiple source applications.
Sizes, dimensions, weights and congurations
Magnum circuit breakers are available in four physical frame sizes, all centered around a modular design approach. The versatile Magnum design concept maximizes enclosure density with the same basic height and depth, differing only in width.
ote:N For detailed Magnum breaker outline drawings, please refer to
Section 11: Magnum drawings and outlines
Double standard frame (3200 – 5000A): Ideal for main and tie applications.
Increased ratings in less space provide the flexibility to design more robust electrical distribution systems, capable of handling larger available fault currents while providing better coordination with downstream devices.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 9
Family features and characteristics
Courtesy of NationalSwitchgear.com
Table 4. Magnum family dimensions & weights
Dimension type Narrow frame Standard frame Double narrow frame Double standard frame
Drawout
2
version - (D/O in cass w/terminals) (mm/in)
1
1
1
Pole spacing
Fixed dimensions
1
mm/in
1
1
Table 5. 4 Pole type
1
1
Drawout version - (D/O in cass w/terminals)
1
(mm/in)
1
1
Pole spacing
Fixed
1
dimensions mm/in
1
1
Vol (dm3/ft3) 83.5/2.94 107.3/ 3.79 165.7/5.86 225.8/7.98 Width (mm/in) 33 6/13.2 432 /17. 0 667/26.3 909/35.8 Height (mm/in) 524/20.6 524/20.6 524/20.6 524/20.6 Depth - w/o adapters (mm/in) 474/18.7 474/18.7 474/18.7 474/18.7
Adapters ar e part of Cassett e
Bkr + Cass=Total Wgt (lbs) 108 + 61 = 169 138 + 117 = 255 214 + 106 = 320 303 + 199 = 502 Distance (mm/ in) 95/3.75 12 7/ 5.0 95/3.75 127/ 5.0 Vol (dm3/ft3) 50 .4 /1.77 65.1/2. 3 109.5/3.86 139.6/4.93 Width (mm/in) 318/12.5 411.5/16. 2 633/24.9 8 2 3/31.1 Height (mm/in) 426 /16.8 426/16.8 426/16.8 426/16.8 Depth (mm/in) 371/14.6 371/14.6 415/16.3 415/16.3 Weight - Fixed bkr (lbs) 95 118 177 237 253
Dimension type Narrow frame Standard frame Double narrow frame Double standard frame
Vol (dm3/ft3) 83.5/2.94 107.3/3.7 9 165.7/5.86 225.8/7.98 Width (mm/in) 4 3 2 / 17. 0 559/22.0 844/33.2 1163/45.8 Height (mm/in) 524/20.6 524/20.6 524/20.6 524/20.6 Depth - w/o adapters (mm/in) 474/18.7 474/18.7 474/18.7 474/18.7
Adapters ar e part of Cassett e
Bkr + Cass=Total Wgt (lbs) 136 + 70 = 206 194 + 123 = 317 214 + 106 = 320 366 + 250 = 616 Distance (mm/ in) 95/3.75 12 7/ 5.0 95/3.75 127/ 5.0 Vol (dm3/ft3) 50 .4 /1.77 65.1/2. 3 109.5/3.86 139.6/4.93 Width (mm/in) 413/16.3 53 8/21.2 824/ 32.4 1120 /44 .1 Height (mm/in) 426 /16.8 426/16.8 426/16.8 426/16.8 Depth (mm/in) 371/14.6 371/14.6 415/16.3 415/16.3 Weight - Fixed bkr (lbs) 120 160 177 319
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com10
Design congurationexibility
Courtesy of NationalSwitchgear.com
Family features and characteristics
The modular Magnum design affords customers the opportunity to meet the increasingly complex requirements of modern distribution systems.
Fixed mounting: Standard horizontally mounted primary connections with vertical adapters available for other bus configurations. Integral mounting feet firmly secure the breaker in position.
Drawout mounting: Zero clearance mounting provides for vertical stacking economy. DISCONNECT, TEST and CONNECT positions can be accessed with the door closed with clear visual indication of position.
Through-the-door design: Provides access to trip unit, controls, indicators, and other operational functions with the door closed for operator safety and convenience.
Drawout breaker levering: Can be accomplished with compartment door closed using a standard 3/8 drive extension, without the need for special levering tool.
Manually or electrically operated: The closing spring on all breakers can be charged manually. A stored energy spring can be charged by an optional electrical charging motor. Electrically operated Magnum breakers allow operation without manual charging which can allow application to remote switching, automatic transfer, load shed/add, and other advanced applications. The charging motor can be factory or field installed in a manually operated breaker.
2
1
1
1
1
1
1
1
1
1
1
1
1
1
3-Pole/4-Pole Configurations: Allows application to any system configuration and requirement.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 11
Family features and characteristics
Courtesy of NationalSwitchgear.com
User friendly front cover features
The front cover contains a conveniently accessible operating
2
panel with clear words and symbols identifying functions while guiding operations. This intuitive interface permits an authorized operator to proceed with condent control and precise
1
configurations.
1
Prominently displayed nameplate provides important circuit breaker specific information. Magnum breakers must be
1
applied within their nameplate ratings.
1
1
1
1
1
1
1
1
1
1
Complete access to the ON” pushbutton can be prevented with optional prevent close cover.
Programmable Digitrip microprocessor-based true rms sensing trip unit, which provides protection, information, and communication choices.
1
1
1
Some field installable accessories easily identified by name and rating through viewing windows. They are the shunt trip, spring release and undervoltage release.
ote:N Non-automatic breakers (AC OR DC type disconnect switches) do
not contain a trip unit or current sensors. They are covered in more depth later in this section. Refer to Section 7 for specific Digitrip trip unit and communication information.
1
1
1
Optional padlockable cover limits access to ON” and OFF” pushbuttons.
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com12
Front cover details
Courtesy of NationalSwitchgear.com
Family features and characteristics
Controls and indicators are functionally grouped on the breaker faceplate to optimize the user interface, visibility and ease of use. The modern, through-the-door design delivers maximum safety and convenience.
1. Accessor y Viewing Windows for:
Shunt Trip Attachment (ST)
Spring Release Device (SR)
Undervoltage Release (UVR) Device or Second ST
2. Digitrip RMS Trip Units protected by clear cover, with thumb screw knobs that give provisions to wire tie the cover shut for extra security
3. Red Mechanical Trip Flag Pop-out Indicator (Optional) Interlocked Indicator Requiring Manual Reset is also Available
4. Contact Status Indicators:
OPEN (Green)
CLOSED (Red)
5. Spring Status Indicators:
Charged (Yellow)
Discharged (White)
6. Push OFF (Open) Pushbutton (Red)
7. Push ON (Close) Pushbutton (Green)
8. Manual Spring Charging Handle: to charge stored energy springs
9. Mechanical Operations Counter (Optional)
2 3 1
10
11
12
2
1
1
1
4
5
6
7
8
1
1
1
1
9
1
1
1
1
1
1
1
10. Key Off Lock (Optional, not shown)
11. Padlockable Levering Device Shutter: for drawout breakers only
12. Color-Coded Position Indicator for drawout breakers:
CONNECT (Red)
TEST (Yellow)
DISCONNECT (Green)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 13
Family features and characteristics
Courtesy of NationalSwitchgear.com
Construction characteristics
From the inside out, safety is of paramount importance with
2
special attention given to live parts insulation and segregation between phases. Careful selection of materials, meticulous assembly, rigorous testing, and unsurpassed experience make
1
Magnum a proven reliable product.
1
Rigid frame housing
1
Magnum circuit breakers use a rigid frame housing construction
1
of durable engineered thermoset composite resins.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Strong and lightweight material with strength to weight ratio twice that of steel. Proven able to withstand high dynamic and thermal stresses.
Excellent dielectric characteristics, resisting arc tracking.
Three piece construction
The 3-piece construction (rear housing, front housing, and cover) provides support while isolating and insulating power conductors
A 2-piece case encloses current paths and arc chambers. Chambers act to channel arc gases up and out during interruption.
The operating mechanism and accessories sit on the front of the case. Only the insulating front cover needs to be removed to access mechanism and/or accessories .
The operating mechanism achieves a longer life as a result of reduced frame deflection during operation along with stiff component mounting.
Two-step stored energy mechanism
Magnum circuit breakers are equipped with a true 2-step stored energy mechanism.
Closing springs can be charged manually or electrically.
5 to 7 downward strokes on the charging handle completes charging process.
Mechanism provides for a complete OPEN – CLOSE – OPEN cycle.
Unsurpassed performance design
The performance characteristics of the Magnum breaker are attributed in many ways to a C-loop current path design and movement. Contact fingers perform both the main and arcing contact functions on different parts of the same finger. A complete movable contact assembly is a combination of a number of single contact fingers. The exact number of contact ngers required depends upon the frame size and interrupting rating of the breaker. Braided connectors (exible shunts) are used to attach each contact finger. The result is an efcient and uniquely functional main contact system with the following advantages:
Eliminate bolted joints reducing hot spots.
Reduced mounting space for primary contacts.
Smaller and lighter operating mechanism for longer life.
Higher interrupting and short time (withstand) ratings.
5-cycle or less closing.
Improved contact material.
Contact wear indicator for each primary contact structure.
Individually removable arc chambers insulate/isolate each pole.
Able to withstand high dynamic and thermal stresses.
Value added features
Magnum provides numerous other internal and external features that further enhance the reliability, maintenance and safety of this industry leading product offering. A number of additional common features are highlighted below. See Section 7 for trip units, and Section 8 for accessories, for more in-depth information.
Available Arcflash Reduction Maintenance System™ on Digitrip 520MC and 1150, to lower personnel risk and PPE levels in the arcflash boundary.
Field installable trip units, sensors and accessories.
Mechanical and electrical anti-pump features.
Easily removable arc chutes for inspection.
Common accessories for all frame sizes (electrical and mechanical).
Automatic drawout primary shutters.
Conveniently located finger proof secondary contacts.
Will accommodate a variety of primary terminal types/ configurations.
Breaker mounting congurations
Most Magnum circuit breakers are available in both fixed and drawout congurations. In a small number of instances, however, only a fixed conguration is available.
Fixed mounted breakers
All Magnum circuit breakers, except for the MDSL breaker, can be fixed mounted. The breaker bolts directly to the enclosure main bus, which allows for efcient current transfer under loaded conditions. Metal mounting feet are provided as a standard feature for use in securely bolting the breaker to the enclosure. Fixed circuit breaker construction is simple and economic because there are no drawout system components.
A fixed circuit breaker is supplied with horizontal, pre-drilled primary terminal pads for terminating the breaker to the bus.
ote:N Optional vertical primary adapters are available to accommodate
different bus configurations. See Section 11 for a complete overview of detailed dimensions.
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com14
Family features and characteristics
Courtesy of NationalSwitchgear.com
Drawout mounting
A drawout circuit breaker is used in combination with a cassette. The cassette provides for all the required drawout features for both primary and secondary connections. Mounting locations for cassette mounted cell switches, primary safety shutters and various key interlocks are part of the cassette design, to allow for customized customer options. Refer to Section 11 for specic drawout circuit breaker and cassette dimensions.
Cassettes Available styles
Narrow frame Cassettes (for narrow frame and double narrow frame breakers)
For narrow frame circuit breakers, there is one type of cassette design, which uses horizontal stabs. Horizontal customer busbar terminals are available (sold separately). Optional bolt-on 90 -degree adapters can be used to rotate the cassettes primary terminals to a vertical orientation as required.
Standard frame Cassettes (for standard frame and double standard frame breakers)
For standard and double frame circuit breakers, there are three cassette styles, all with vertical stabs available:
Basic Cassette with copper stabs - This cassette comes with factory installed copper stab/terminals on the cassette.
Basic Cassette without copper stabs - The basic cassette can also be ordered without factory supplied copper stab/ terminals. Ordering without stabs allows the switchgear builder to integrate the cassette by using their vertical busbars.
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 15
Family features and characteristics
Courtesy of NationalSwitchgear.com
Universal Cassette - A set of flat pad terminals on the rear of the cassette are provided. They can be adapted to vertical, horizontal, or front connection.
2
1
1
1
1
1
1
1
1
1
1
1
1
ote:N The MDSL circuit breaker with integral current limiters is 6.00 inch-
es (152.4 mm) deeper than the MDS or MDSX circuit breaker. Therefore, the MDSL cassette is 6.00 inches (152.4 mm) deeper than the standard MDS cassette. It is available in drawout only.
1
Renewal parts for extended life and
1
longevity
1
There are many parts and kits available to assist customers to maintain and increase the life of their investment in their
1
Magnum low voltage breakers. Please refer to the Renewal Parts Guide found here or in the documents section on
1
www.eaton.com/magnum.
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com16
Standards and certications
Courtesy of NationalSwitchgear.com
Magnum DS - Product specific information
The Magnum DS family (identied as a medium gray front cover) of low voltage power circuit breakers is ANSI designed, tested and certied to UL 1066. UL 1066 Listed type DS low voltage power circuit breakers are intended to provide main and feeder circuit protection in accordance with UL1066 “Standard for Safety for Low-Voltage AC and DC Power Circuit Breakers Used in Enclosures.
UL and ANSI test certications
Magnum DS meets or exceeds the applicable ANSI, NEMA standards, including:
ANSI C37.13 “Low Voltage AC Power Circuit Breakers Used in Enclosures”
ANSI C37.16 “Preferred Ratings, Related Requirements, and Application Recommendations for Low Voltage Power Circuit Breakers and AC Power Circuit Breakers”
ANSI C37.17 “Trip Devices for AC and General Purpose DC Low Voltage Power Circuit Breakers”
ANSI C37.50 “Test Procedures for Low Voltage AC Power Circuit Breakers Used in Enclosures”
®
, UL and CSA®
UL 1066 “Standard for Low Voltage AC and DC Power Circuit Breakers Used in Enclosures”
CSA TIL No. D-34 ”Interim Certification Requirements for Low Voltage Power Circuit Breakers”.
Comprehensive enclosure solutions
Magnum DS has proven performance in Eaton manufactured switchgear with the following test certications:
UL 1558 “Certified Magnum DS Low Voltage Metal- Enclosed Switchgear”
UL 1008 “Standard for Safety Transfer Switch Equipment”
C22.2 No. 31-14 Switchgear Assemblies
Approvals and marks
UL listed: Magnum DS Breaker UL File No. E52096 and Cassette UL File No. E204565
ABS (American Bureau of Shipping) Type Listed Certificate Number 04-HS422844A-DUB
Additional Magnum DS approvals and certificates can be found on
www.eaton.com
Magnum DS family
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Selection and identication of ratings for Magnum DS
Nameplate identication and markings
It is always advisable to be familiar with the location and information provided on a breakers nameplate. All low voltage power circuit breakers must be applied within their nameplate ratings. Nameplates are prominently displayed on the front of the circuit breaker, and provide important information relative to that specic circuit breaker.
A Magnum DS circuit breaker is easily identified by its specific nameplate designation. Review the nameplate example provided below.
A. Low voltage power circuit
breaker family name
B. Breaker family
designation number
C. Breaker frame size in
amperes
D. Interrupting capacity
rating
E. Factory equipped
accessories
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 17
A
B
C
1
1
1
1
D
1
1
E
1
1
1
1
Magnum DS - Product specific information
Courtesy of NationalSwitchgear.com
Catalog number selection
A Magnum DS circuit breaker is dened by a 25 character catalog number created through a simple selection process from to these applicable tables. If the breaker is a drawout breaker, the associated drawout cassette would be dened by a 15 character
3
catalog number. The cassette selection process is similar with selections made from cassette conguration table.
1
1
1
1
1
ote:N The selection examples shown at the top of each table. UL and
ANSI test certifications.
Magnum DS ANSI breaker product family (first 14 of 25 digits, see next page for 15-25 digits)
MD S 4 12 3 V E A 06 MU
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Breaker type
MD =Magnum DS
Frame type
S
=
Standard or double
N
=
Narrow or double
=
narrow
D
=
MDDX only
E
=
High endurance
4
=
42
5
=
50
6
=
65
8
=
85
C
=
100
H
=
130 (DSH)
E
=
150 (DSE)
X
=
200 (DSX/DDX)
L
=
200 (DSL)
Interrupting/
withstand rating
Continuous amperes and
phasing (facing front of
breaker)
08
=
800 ABC
12
=
1200 ABC
16
=
1600 ABC
20
=
2000 ABC
25
=
2500 ABC
30
=
3000 ABC
32
=
3200 ABC or ABCABC
3N
=
3200 AABBCC
4N
=
4000 AABBCC
5N
=
5000 AABBCC
40
=
4000 ABCABC
50
=
5000 ABCABC
Poles and neutral
(facing front of breaker)
34==Three
Four (neutral left)
Mounting configuration
and load terminals
H
=
Fixed horizontal
V
=
Fixed vertical
L
=
Drawout (MDN)
W
=
Drawout (MDS)
Nameplate language
EA==English
Spanish
Sensor and
rating plug rating
NN
=
None
01
=
100
02
=
200
05
=
250
03
=
300
04
=
400
06
=
600
08
=
800
10
=
1000
Current limiter selection
A
=
Non-DSL (no limiter)
D
=
MA250
E
=
MA300
F
=
MA400
G
=
MA600
H
=
MA800
K
=
MB1200
L
=
MB1600
M
=
MB2000
N
=
MD2500
P
=
MD3000
12
=
1200
13
=
1250
16
=
1600
20
=
2000
25
=
2500
30
=
3000
32
=
3200
40
=
4000
50
=
5000
1
1
1
Trip unit and protection,
and external control voltage
when required
Non-automatic
NN
=
(no trip unit)
520 LSI
52
=
520 LSIG
5G
=
520M LSI
M2
=
520M LSI (24/48 Vdc)
MT
=
520M LSI (120 Vac)
MU
=
520M LSI (240 Vac)
MV
=
520M LSI (125 Vdc)
MQ
=
520M LSIG
MG
=
520M LSIG (24/48 Vdc)
MH
=
520M LSIG (120 Vac)
MM
=
520 LSIG (240 Vac)
MN
=
520M LSIG (125 Vdc)
MX
=
520M LSIA (24/48 Vdc)
ME
=
520 LSIA (120 Vac)
MC
=
520M LSIA (240 Vac)
MF
=
520M LSIA (125 Vdc)
MZ
=
520MC LSI (24/48 Vdc)
CT
=
520MC LSI (120 Vac)
CU
=
520MC LSI (240 Vac)
CV
=
520MC LSI (125 Vdc)
CQ
=
520MC LSIG (24/48 Vdc)
CH
=
520MC LSIG (120 Vac)
CM
=
520MC LSIG (240 Vac)
CN
=
520MC LSIG (125 Vdc)
CX
=
520MC LSIA (24/48 Vdc)
CE
=
520MC LSIA (120 Vac)
CC
=
520MC LSIA (240 Vac)
CF
=
520MC LSIA (125 Vdc)
CY
=
1150 LSI (24/48 Vdc)
1A
=
1150 LSI (120 Vac)
1C
=
1150 LSI (240 Vac)
1E
=
1150 LSI (125 Vdc)
1Q
=
1150 LSIG (24/48 Vdc)
1F
=
1150 LSIG (120 Vac)
1G
=
1150 LSIG (240 Vac)
1H
=
1150 LSIG (125 Vdc)
1X
=
1150 LSIA (24/48 Vdc)
1J
=
1150 LSIA (120 Vac)
1K
=
1150 LSIA (240 Vac)
1M
1150 LSIA (125 Vdc)
1Y
=
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com18
Magnum DS ANSI breaker product family continued
Courtesy of NationalSwitchgear.com
(15 through 25)
A W C H N E H K L A X
Magnum DS - Product specific information
Shunt Trip (ST)
N
=
None
A
=
110–127 Vac/Vdc
R
=
208–240 Vac/Vdc
C
=
24 Vdc
H
=
48 Vdc
B
=
110–127 Vac/Vdc (100% duty)
S
=
220–250 Vac/Vdc (100% duty)
D
=
24 Vdc (100% duty)
K
=
48 Vdc (100% duty)
J
=
60 Vdc (100% duty)
6
=
60 Vdc
Motor operator
M
=
Manual operated
N
=
110–125 Vac (5-sec)
W
=
110–125 Vdc (5-sec)
T
=
220–250 Vdc (5-sec)
P
=
208–277 Vac (5-sec)
L
=
24 Vdc (5-sec)
K
=
48 Vdc (5-sec)
S
=
60 Vdc (5-sec)
1
=
110–125 Vac (3-sec)
2
=
220–250 Vac (3-sec)
4
=
24 Vdc (3-sec)
8
=
48 Vdc (3-sec)
5
=
110–125 Vdc (3-sec)
9
=
220–250 Vdc (3-sec)
N A R C H S
Spring Release Device
(SRD)
=
None
=
110–127 Vac/Vdc
=
208–240 Vac/Vdc
=
24 Vdc
=
48 Vdc
=
60 Vdc
Undervoltage Release (UVR)
or 2nd Shunt Trip (ST)
N
=
None
A
=
UVR (110–127 Vac)
R
=
UVR (208–240 Vac)
C
=
UVR (24 Vdc)
H
=
UVR (48 Vdc)
D
=
UVR (60 Vdc)
E
=
UVR (110–125 Vdc)
F
=
UVR (220–250 Vdc)
G
=
UVR (32 Vdc)
X
=
UVR (380–415 Vac)
J
=
UVR (480 Vac)
K
=
UVR (600 Vac)
1
=
2nd ST (110–127 Vac Vdc)
2
=
2nd ST (208–250 Vac Vdc)
3
=
2nd ST (24 Vdc)
4
=
2nd ST (48 Vdc)
6
=
2nd ST (60 Vdc)
B
=
2nd ST (110–127 Vac/ Vdc 100% duty)
O
=
2nd ST (220–250 Vac/ Vdc 100% duty)
I
=
2nd ST (24 Vdc 100% duty)
nd
Q
=
2
ST (48 Vdc 100% duty)
9
=
2nd ST (60 Vdc 100% duty)
Auxiliary switch
N
=
None
2
=
2A/2B
4
=
4A/4B
6
=
6A/6B
Bell Alarms Switch (OTS) with
2a/2b contacts and/or mechanical
trip indicator
Mech. inter- lock for manual reset
No No Yes Yes No
No
No
Yes
Yes
Yes
E N Y M L F
G
H
I
J
K
= = = = = =
=
=
=
=
=
Mech. trip indicator
No Yes Yes Yes Yes Yes
Yes
Yes
Yes
Yes
Yes
OTS switch with two form C contacts
No No Yes No Yes Yes with 24V reset Yes with 120V reset Yes with 240V reset Yes with 24V reset Yes with 120V reset Yes with 240V reset
Padlock provisions for blocking
close and/or open ACB manual
pushbuttons
N
=
None
M
=
Metal (block close and open)
P
=
Plastic (block close and open)
C
=
Metal (block close only)
H
=
Plastic (block close only)
S
=
Metal swbd lock-off (block close, depress open)
Operations counter and/
or keylock provisions
Counter
N
=
No counter
K
=
No counter
C
=
No counter
R
=
No counter
S
=
No counter
A
=
Counter
Y
=
Counter
L
=
Counter
H
=
Counter
E
=
Counter
Latch check switch/trip unit
metering voltage connection for
digitrip 1150 trip unit
Latch check switch
N =
None
M =
None
L =
LCS wired to SRD
Y =
LCS Wired to SRD
C =
LCS Wired External
D =
LCS Wired External
Keylock provisions
No locks Kirk lock Castell lock Ronis lock CES lock No lock Kirk lock Castell lock Ronis lock indicator CES lock
1150 voltage connection
Upper terminals Lower terminals Upper terminals
Lower terminals
Upper terminals
Lower terminals
Frame use
X = All breakers
Breaker shipping options
and instructions
A
=
Fixed breaker alone with door kit
B
=
Fixed breaker alone with door kit and pre-wired
F
=
Fixed breaker alone without door kit
A
=
Drawout breaker alone without door frame kit
C
=
Drawout breaker in cassette (un-wired)
P
=
Drawout breaker in cassette (shutters)
S
=
Drawout breaker in cassette (shutters)
W
=
Drawout breaker in cassette (pre-wired and shutters)
Double frame drawout breakers cannot ship in cassette without cassette drawout.
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 19
Magnum DS - Product specific information
Courtesy of NationalSwitchgear.com
Cassette Magnum DS ANSI breaker product family
M E 32 3 C A DN N NNN W C
3
1
1
1
1
1
1
1
1
1
1
1
1
Cassette family
ML==Standard or double
frame Narrow or double narrow frame
Interrupt type
D
=
MDDX cassettes (200kA)
N
=
Cassettes (up to 100 kA)
L
=
MDSL cassettes (200 kA)
X
=
MDSX cassettes (200 kA)
Continuous amperes
16
=
Up to 1600A
20
=
Up to 2000A
32
=
2500 to 3200A
40
=
1600 to 4000A
50
=
2000 to 5000A
Poles
34==Three-pole
Four-pole
1
The arc hood option 'D' is recommended for use of ATS applications as well as on Magnum ANSI DC breakers, 'DAS' and 'DBS' configurations
Cassette frame and rear terminals
P
=
Basic cassette (without vertical bus stabs)
C
=
Basic cassette with stabs (with vertical bus stab kit)
H
=
Narrow frame cassette (with horizontal terminal pads)
U
=
Universal cassette (with universal terminal pads)
Arc hood
AD==Arc hood installed
Dual baffled arc hood for ATS and DC applications
Door frame and gasket kit
DNXN==Door frame and gasket kit
included Door frame and gasket kit not included
1
NS==Un-wired
NNN = All cassettes
Shutters
NS==No shutters
Shutters installed
Cassette shipping
CB==Cassette only
Breaker shipped in cassette
Cassette wiring
Cassette wired
Future use
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com20
Magnum DS - Product specific information
Courtesy of NationalSwitchgear.com
Magnum DS - Continuous amperage, interruption and withstand ratings tables
Table 6. Magnum DS switchgear class UL 1066 low voltage power circuit breakers ANSI
rms Symmetrical current ratings kA 50/60 Hz
Breaker type
Frame amperes
800 MDN-408 Narrow 42 42 42 42 42 n/a 200, 250, 300,
1200 MDN -412 Narrow 42 42 42 42 42 n/a 200, 250, 300,
1600 MDN-416 Narrow 42 42 42 42 42 n/a 3 & 4
1
Interrupting ratings shown based on breaker equipped with integral Digitrip™ rms trip unit. Interruption ratings for non-automatic breakers are equal to the published withstand rating.
2
Magnum MDSL current limiting power circuit breaker with integral current limiters. Current limiter selected determines short time and fixed instanta- neous trip rating.
3
Magnum MDSX current limiting power circuit breaker with fast opening contacts.
4
Product to be tested. Contact Eaton for product rating.
5
Breaker applied in a tested fan cooled enclosure.
6
Not released.
catalog position 1–6
MDN-508 Narrow 50 50 50 50 50 n/a 3 & 4 MDN-608 Narrow 65 65 65 65 65 n/a 3 & 4 MDN-C08 Narrow 100 10 0 65 20 20 18xIn 3 & 4 MDS-408 Standard 42 42 42 42 42 n/a 3 & 4 MDS-508 Standard 50 50 50 50 50 n/a 3 & 4 MDS-608 Standard 65 65 65 65 65 n/a 3 & 4 MDS-808 Standard 85 85 85 85 85 n/a 3 & 4 MDS-C08 Standard 100 10 0 100 85 85 85 3 & 4 MDS-H08 Standard 130 130 13 0 85 85 85 3 MDS-L08 Standard 200 200 200 n/a 3 MDS-X08 Standard 200 200 65 30 30 30 3
MDN -512 Narrow 50 50 50 50 50 n/a 3 & 4
MDN -612 Narrow 65 65 65 65 65 n/a 3 & 4 MDN -C12 Narrow 100 100 65 25 25 18xIn 3 & 4 MDS -X12 Standard 200 200 65 30 30 30 3 & 4 MDS -512 Standard 50 50 50 50 50 n/a 3 & 4 MDS -612 Standard 65 65 65 65 65 n/a 3 & 4 MDS -812 Standard 85 85 85 85 85 n/a 3 & 4 MDS -C12 Standard 100 10 0 100 85 85 n/a 3 & 4 MDS -H12 Standard 130 130 130 85 85 85 200, 250, 30 0,
MDN-516 Narrow 50 50 50 50 50 n/a 3 & 4 MDN-616 Narrow 65 65 65 65 65 n/a 3 & 4 MDN-C16 Narrow 10 0 100 65 30 30 18xIn 3 & 4 MDS -516 Standard 50 50 50 50 50 n/a 3 & 4 MDS -616 Standard 65 65 65 65 65 n/a 3 & 4 MDS -816 Standard 85 85 85 85 85 n/a 3 & 4 MDS -C16 Standard 100 100 10 0 85 85 85 3 & 4 MDS -H16 Standard 130 130 130 85 85 85 3 MDS- L16 Standard 200 200 200 n/a 3 MDS -X16 Standard 200 200 65 30 30 30 3
2
3
2
3 6
Frame type
Interruption ratin g at 254 Vac
Interruption ratin g at 508 Vac
Interruption ratin g at 635 Vac
1
Shor t time withstand ratin g @254/ 508 Vac
2 2
2 2
Shor t time withstand ratin g @6 35Va c
Fixed internal inst trip
Available current sensor and rating plugs f or digit rip rms trip un it (establishes breaker I rating)
400, 600, 800
400, 600, 800, 1000, 1200
400, 600, 800, 1000, 1200, 1600
n
Poles available
3 & 4
3 & 4
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 21
Magnum DS - Product specific information
Courtesy of NationalSwitchgear.com
Table 6. Magnum DS switchgear class UL 1066 low voltage power circuit breakers ANSI continued
rms Symmetrical current ratings kA 50/60 Hz
Breaker
3
Frame amperes
1
2000 MDN-620 Narrow 65 65 65 65 65 n/a 200, 250, 300,
1
1
1
1
2500 MDS-625 Standard 65 65 65 65 65 n/a 200, 250, 300,
1
1
3200 MDS-632 Standard 65 65 65 65 65 n/a 200, 250, 300,
1
1
1
4000 MDS-840 Double 85 85 85 85 85 n/a 2000, 2500,
1
1
1
1
1
1
5000 MDS-850 Double 85 85 85 85 85 n/a 2500, 3200,
1
1
1
1
1
1
1
Interrupting ratings shown based on breaker equipped with integral digitrip rms trip unit. Interruption ratings for non-automatic breakers are equal to the published withstand rating.
2
Magnum MDSL current limiting power circuit breaker with integral current limiters. Current limiter selected determines short time and fixed instanta- neous trip rating.
3
Magnum MDSX current limiting power circuit breaker with fast opening contacts.
4
Product to be tested. Contact Eaton for product rating.
5
Breaker applied in a tested fan cooled enclosure.
6
Not released.
type catalog position 1–6
MDN-C20 Narrow 100 10 0 65 35 35 18xIn 3 & 4 MDS-620 Standard 65 65 65 65 65 n/a 3 & 4 MDS-820 Standard 85 85 85 85 85 n/a 3 & 4 MDS-C20 Standard 100 10 0 100 85 85 85 3 & 4 MDS-H20 Standard 130 130 13 0 85 85 85 3 MDS-L20 Standard 200 200 200 n/a 3 MDS-X20 Standard 200 200 65 30 30 30 3
MDS-825 Standard 85 85 85 85 85 n/a 3 & 4 MDS-C25 Standard 100 10 0 100 100 85 85 3 & 4 MDS-H25 Standard 130 130 13 0 85 85 85 3
MDS-832 Standard 85 85 85 85 85 n/a 3 & 4 MDS-C32 Standard 100 10 0 100 85 85 85 3 & 4 MDS-H32 Standard 130 130 13 0 85 85 85 3 MDS-X32 Double 200 200 50 50 50 3
MDS-C40 Double 100 100 10 0 100 100 n/a 3 & 4 MDS-H40 Double 130 130 130 130 130 n/a 3 MDS-X40 Double 200 200 50 50 50 3 MDN-640 Double
MDN-840 Double
MDN-C40 Double
MDD-X40 Double 200 200 10 0 100 100 n/a 3
MDD-X50 Double 200 200 10 0 100 100 n/a 3 MDS-C50 Double 10 0 100 100 100 100 n/a 3 & 4 MDS-H50 Double 130 130 130 130 130 n/a 3 MDS-X50 Double 200 200 50 50 50 3
2
3
3
3
3 5
Frame type
Narrow
Narrow
Narrow
Interruption ratin g at 254 Vac
65 65 65 65 65 n/a 3 & 4
85 85 65 85 65 n/a 3 & 4
100 100 65 100 65 n/a 3 & 4
Interruption ratin g at 508 Vac
Interruption ratin g at 635 Vac
4
4
4
1
Shor t time withstand ratin g @254/ 508 Vac
2 2
Shor t time withstand ratin g @6 35Va c
Fixed internal inst trip
Available current sensor and rating plugs f or digit rip rms trip un it (establishes breaker I rating)
400, 600, 800, 1000, 1200, 1600, 2000
400, 600, 800, 1000, 1200, 1600, 2000, 2500
400, 600, 800, 1000, 1200, 1600, 2000, 2500, 3200
3200, 4000
4000, 5000
n
Poles available
3 & 4
3 & 4
3 & 4
3 & 4
3 & 4
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com22
Magnum DS - Product specific information
Courtesy of NationalSwitchgear.com
Magnum DS - Current limiting circuit breakers
MDSL circuit breaker
Magnum MDSL current limiting power circuit breakers utilize integral current limiters to provide interruption ratings of 200 kA at 600 Vac with continuous limitation with lower let through currents for superior protection of downstream equipment. The MDSL breaker is available only in a drawout conguration.
Current limiters are held in place in a 6 inch (152.4 mm) extension provided on the back of the circuit breaker. The current limiters can only be removed from the breaker and replaced when the MDSL breaker is removed from its associated compartment.
A blown limiter indicator provides a visual indication on the front of the MDSL when a current limiter in any phase has interrupted a short circuit. The indicator itself is a red pop-out button located on the lower left portion of the breakers front cover. The direct trip actuator trips the circuit breaker, and an output to the indicator causes the button to pop out.
Current limiter selection
Current limiters can be selected from the current limiter selection table (Table 7) and are categorized for selection in three ways:
Minimum current limiter
Recommended current limiter
Maximum current limiter
The selection of a suitable limiter rating for a given application is generally governed by a choice of the following two types of protection:
(A) Maximum protection of downstream components:
Type MDSL breakers are often used for this purpose even when the maximum available fault currents are within the interruption rating of the corresponding unfused Magnum breakers.
(B) Protection of circuit breaker only:
Case A would tend to use the smallest available limiter; Case B the largest.
Current limiter
Blown limiter indicator
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Table 7. Magnum MDSL sensor/rating plug vs. Current limiter selection
Sensor and Rating plug I
200 MA250 MA300 MA400 MA600 MA800 M B1200 MB16 00 MB2000 MD2500 MD3000 250 MA400 MA600 MA800 MB1200 MB16 00 MB2000 MD2500 MD3000 300 MA400 MA600 MA800 MB1200 MB16 00 MB2000 MD2500 MD3000 400 MA600 MA800 MB120 0 MB160 0 MB2000 MD2500 MD3000
600 MA800 MB1200 MB1600 MB2000 MD2500 MD3000 800 MB12 00 MB1600 MB2000 MD2500 MD3000 1000 MB16 00 MB2000 MD2500 MD3000 1200 MB2000 MD2500 MD3000 1600 MD3000 2000 MD3000
1
Select the current limiter based on the Magnum breaker frame and current sensor and rating plug as shown.
2
Refer to MDSL current limiter curves for let-through and time characteristics.
3
The recommended ratings provide for reduced current let-through and breaker coordination within the trip unit settings. Selection of current limiters below the recommended ratings shown provides lower current let-through, however, trip unit settings must be considered to avoid nuisance operation.
MDSL current limiter sele ctio n char t
n
1
2
3
3
3
3
3
3
3
3
3
3
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 23
1
1
1
1
1
1
1
1
1
1
1
Magnum DS - Product specific information
Peak instantaneous let-through current kilo – amperes x 10
100
1000
10000
Courtesy of NationalSwitchgear.com
Trip curve charts
Type Magnum DSL limiters, peak let-through current characteristics
3
1
1
1
1
1
1
1
1
1
1
1
90 80 70 60
50
40
30
20
10
9 8 7 6
5
4
3
2
1 .9 .8 .7 .6
.5
.4
.3
.2
.1
.09 .08 .07 .06
.05
.04
.03
.02
1
100
200
300
400
500
600
700
800
900
1000
2000
3000
4000
5000
6000
7000
1
8000
Available current, rms symmetrical amperes x 10
1
1
Type Magnum DSL limiters average melting time-current characteristics
900 800 700 600 500
400
300
200
MD3000 MD2500 MD2000 MD1600 MD1200 MA800
MA600
MA400 MA300 MA250
9000
10000
20000
30000
40000
50000
70000
80000
90000
60000
100000
60 50 40
30
20
10
9 8 7 6 5
4
Time in seconds
3
2
1 .9 .8 .7 .6 .5
.4
.3
.2
.1 .09 .08 .07 .06 .05
.04
.03
.02
.01
1
2345678
9
10
20304050607080
MA250
MA300
MA400
MA500
MA800
MB1200
MB1600
MB2000
MB2500
MB3000
90
100
200
300
400
500
600
700
Scale x 100 = Current in amperes
ote:N For time/current curves, see www.eaton.com/tcc
800
900
1000
2000
3000
4000
5000
6000
7000
8000
9000
MDSX circuit breaker
1
The Magnum MDSX is a current limiting circuit breaker of the
1
Magnum DS Family. It has a 200 kA interrupting rating without the need for current limiters at 4 80 Vac with continuous current ratings up to 5000A. MDSX circuit breakers utilize fast opening
1
contacts, and are available in both drawout and fixed mounting configurations.
1
Current limiting performance of the MDSX family of current limiting circuit breakers is shown in above. The label on the
1
breaker indicates its current-limiting characteristics. The MDSX provides all the same operational features normally associated
1
with Magnum DS.
1
Non-automatic breaker (switch)
The non-automatic Magnum DS breaker (switch) shares the
1
same frame and accessories as the circuit breaker. It does not, however, have the following:
1
Trip Unit
1
1
Sensors
Overcurrent Release
The switch is available in both three-pole and four-pole fixed and drawout configurations.
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com24
A non-automatic power circuit breaker includes separable contacts for movement between a closed position and an open position, and an operating mechanism for moving the separable contacts between the two positions. This breaker can be applied where a local means of disconnect or isolation is required. It can be operated either manually or electrically. It should be noted, since the Magnum Non-Automatic Breaker (switch) does not include any overcurrent protection, it cannot be used in branch or feeder circuit protection applications.
MDE circuit breaker
The Magnum DS Family includes the MDE High Endurance Circuit Breaker. The MDE circuit breaker is rated for 15,000 Open-Close operating cycles between scheduled maintenance periods. It is a specially designed and manufactured Magnum DS Circuit Breaker intended for especially robust applications that require a higher than normal number of operating cycles without maintenance. Contact Eaton for additional details.
Special customer requests
The 25th digit in the catalog number congurator now offers several special customer designs, for very specic environments or applications. Please click here or search 'Volume 4 Tab 3' on www.eaton.com
Standards and certications
Courtesy of NationalSwitchgear.com
Magnum SB - Product specific information
The Magnum SB low voltage insulated case power circuit breaker is certied to UL 1066, but is specically designed for the performance requirements of UL 891 switchboard class applications.
UL and ANSI test certications
Magnum SB meets or exceeds all applicable ANSI, NEMA, UL and CSA standards, including:
ANSI C37.13 (low voltage AC power circuit breakers used in enclosures)
ANSI C37.16 (preferred ratings, related requirements, and application recommendations for low voltage power circuit breakers and AC power circuit breakers)
ANSI C37.17 (trip devices for AC and general purpose DC low voltage power circuit breakers)
ANSI C37.50 (test procedures for low voltage AC power circuit breaker used in enclosures)
UL 1066 (standard for low voltage AC and DC power circuit breakers used in enclosures)
Comprehensive enclosure solutions
Magnum SB has proven performance in Eaton manufactured switchboards with the following test certications:
UL 891 (certified Pow-R-Line C low voltage switchboards)
C22.2 No. 31-14 Switchgear assemblies
Approvals and marks
UL listed: Magnum SB breaker UL file E52096 and Cassette UL file E204565
Additional Magnum SB approvals and certificates can be found on www.
eaton.com/magnum
Magnum SB circuit breaker details
Magnum SB is a low voltage insulated- case circuit breaker family designed for the performance requirements of UL 891 switchboards. These characteristics are:
Magnum SB breakers have short time current ratings and fixed internal instantaneous trip ratings, which is characteristic of UL 489 molded-case breakers commonly used in UL 891 switchboards. This provides for improved coordination and selectivity for most commercial switchboard applications.
The instantaneous trip function facilitates feeder circuit breaker protection in UL 891 switchboards with 3-cycle bus bracing. This yields reduced energy let through to downstream circuits by eliminating the fault current above the fixed instantaneous trip point.
Magnum SB insulated- case circuit breakers have Interruption ratings up to 150 kA with continuous current ratings up to 5000A.
Magnum SB non-automatic breaker (switch)
The non-automatic Magnum SB breaker (switch) shares the same frame and accessories as the circuit breaker. It does not, however, have the following:
Trip unit
Sensors
Overcurrent release
Like the Magnum SB breaker, the switch is available in both three-pole and four-pole, fixed and drawout configurations.
A non-automatic circuit breaker includes separable contacts for movement between a closed position and an open position, and an operating mechanism for moving the separable contacts between the two positions. It cannot be used for branch- circuit protection.
Magnum SB family
3
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 25
Magnum SB - Product specific information
Courtesy of NationalSwitchgear.com
Selection and identication of ratings for Magnum SB
Nameplate identication
3
Nameplates are prominently displayed on the front of the
4
circuit breaker, and provide important information relative to that specic circuit breaker.
1
All low voltage circuit breakers must be applied within their
1
nameplate ratings. It is always advisable to be familiar with
1
the location and information provided on a breakers nameplate.
1
1
1
A Magnum SB circuit breaker is easily identified by its specific nameplate designation. Review the nameplate example provided below.
A. Low voltage power circuit
breaker family name
B. Breaker family
designation number
C. Breaker frame size in
amperes
D. Interrupting capacity
rating
E. Factory equipped
accessories
1
1
1
1
A
B
C
D
E
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com26
Magnum SB - Product specific information
Courtesy of NationalSwitchgear.com
Catalog number selection
Just like the Magnum DS, the Magnum SB circuit breaker is dened & ordered by a 25 character catalog number created through a simple selection process from two conguration tables. If the breaker is a drawout breaker, the associated cassette would be dened by a 15 character catalog number. The cassette selection process is similar to that of the circuit breaker.
ote:N The selection examples shown at the top of each table, and that all
combinations are not possible.
3
4
1
Magnum SB breaker product family (first 14 of 25 digits, see next page for 15-25 digits)
SB S 4 12 3 V E A 06 MU
Breaker type
SB = Magnum switchboard
NN
Frame type
S
=
Standard or double
N
=
Narrow or double
=
narrow
D
=
MDDX only
E
=
High endurance
withstand rating
4
=
42
5
=
50
6
=
65
8
=
85
C
=
100
H
=
130 (DSH)
E
=
150 (DSE)
X
=
200 (DSX/DDX)
L
=
200 (DSL)
Continuous amperes and
08 12 16 20 25 30 32 3N 4N 5N 40 50
Interrupting/
phasing (facing front of
breaker)
=
800 ABC
=
1200 ABC
=
1600 ABC
=
2000 ABC
=
2500 ABC
=
3000 ABC
=
3200 ABC or ABCABC
=
3200 AABBCC
=
4000 AABBCC
=
5000 AABBCC
=
4000 ABCABC
=
5000 ABCABC
Poles and neutral
(facing front of breaker)
34==Three
Four (neutral left)
Mounting configuration
and load terminals
H
=
Fixed horizontal
V
=
Fixed vertical
L
=
Drawout (SBN)
W
=
Drawout (SBS)
Nameplate language
EA==English
Spanish
=
01
=
02
=
05
=
03
=
04
=
06
=
08
=
10
=
Current limiter selection
A
=
Non-DSL (no limiter)
D
=
MA250
E
=
MA300
F
=
MA400
G
=
MA600
H
=
MA800
K
=
MB1200
L
=
MB1600
M
=
MB2000
N
=
MD2500
P
=
MD3000
Sensor and
rating plug rating
None
12
100 200 250 300 400 600 800 1000
=
13
=
16
=
20
=
25
=
30
=
32
=
40
=
50
=
1200 1250 1600 2000 2500 3000 3200 4000 5000
Trip unit and protection,
and external control voltage
when required
Non-automatic
NN
=
(no trip unit)
520 LSI
52
=
520 LSIG
5G
=
520M LSI
M2
=
520M LSI (24/48 Vdc)
MT
=
520M LSI (120 Vac)
MU
=
520M LSI (240 Vac)
MV
=
520M LSI (125 Vdc)
MQ
=
520M LSIG
MG
=
520M LSIG (24/48 Vdc)
MH
=
520M LSIG (120 Vac)
MM
=
520 LSIG (240 Vac)
MN
=
520M LSIG (125 Vdc)
MX
=
520M LSIA (24/48 Vdc)
ME
=
520 LSIA (120 Vac)
MC
=
520M LSIA (240 Vac)
MF
=
520M LSIA (125 Vdc)
MZ
=
520MC LSI (24/48 Vdc)
CT
=
520MC LSI (120 Vac)
CU
=
520MC LSI (240 Vac)
CV
=
520MC LSI (125 Vdc)
CQ
=
520MC LSIG (24/48 Vdc)
CH
=
520MC LSIG (120 Vac)
CM
=
520MC LSIG (240 Vac)
CN
=
520MC LSIG (125 Vdc)
CX
=
520MC LSIA (24/48 Vdc)
CE
=
520MC LSIA (120 Vac)
CC
=
520MC LSIA (240 Vac)
CF
=
520MC LSIA (125 Vdc)
CY
=
1150 LSI (24/48 Vdc)
1A
=
1150 LSI (120 Vac)
1C
=
1150 LSI (240 Vac)
1E
=
1150 LSI (125 Vdc)
1Q
=
1150 LSIG (24/48 Vdc)
1F
=
1150 LSIG (120 Vac)
1G
=
1150 LSIG (240 Vac)
1H
=
1150 LSIG (125 Vdc)
1X
=
1150 LSIA (24/48 Vdc)
1J
=
1150 LSIA (120 Vac)
1K
=
1150 LSIA (240 Vac)
1M
1150 LSIA (125 Vdc)
1Y
=
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 27
Magnum SB - Product specific information
Courtesy of NationalSwitchgear.com
Magnum SB breaker product family continued (15 through 25)
A W C H N E H K L A X
3
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Shunt Trip (ST)
N
=
None
A
=
110–127 Vac/Vdc
R
=
208–240 Vac/Vdc
C
=
24 Vdc
H
=
48 Vdc
B
=
110–127 Vac/Vdc (100% duty)
S
=
220–250 Vac/Vdc (100% duty)
D
=
24 Vdc (100% duty)
K
=
48 Vdc (100% duty)
J
=
60 Vdc (100% duty)
6
=
60 Vdc
Motor operator
M
=
Manual operated
N
=
110–125 Vac (5-sec)
W
=
110–125 Vdc (5-sec)
T
=
220–250 Vdc (5-sec)
P
=
208–277 Vac (5-sec)
L
=
24 Vdc (5-sec)
K
=
48 Vdc (5-sec)
S
=
60 Vdc (5-sec)
1
=
110–125 Vac (3-sec)
2
=
220–250 Vac (3-sec)
4
=
24 Vdc (3-sec)
8
=
48 Vdc (3-sec)
5
=
110–125 Vdc (3-sec)
9
=
220–250 Vdc (3-sec)
N A R C H S
Spring Release Device
(SRD)
=
None
=
110–127 Vac/Vdc
=
208–240 Vac/Vdc
=
24 Vdc
=
48 Vdc
=
60 Vdc
Undervoltage Release (UVR)
or 2nd Shunt Trip (ST)
N
=
None
A
=
UVR (110–127 Vac)
R
=
UVR (208–240 Vac)
C
=
UVR (24 Vdc)
H
=
UVR (48 Vdc)
D
=
UVR (60 Vdc)
E
=
UVR (110–125 Vdc)
F
=
UVR (220–250 Vdc)
G
=
UVR (32 Vdc)
X
=
UVR (380–415 Vac)
J
=
UVR (480 Vac)
K
=
UVR (600 Vac)
1
=
2nd ST (110–127 Vac Vdc)
2
=
2nd ST (208–250 Vac Vdc)
3
=
2nd ST (24 Vdc)
4
=
2nd ST (48 Vdc)
6
=
2nd ST (60 Vdc)
B
=
2nd ST (110–127 Vac/ Vdc 100% duty)
O
=
2nd ST (220–250 Vac/ Vdc 100% duty)
I
=
2nd ST (24 Vdc 100% duty)
nd
Q
=
2
ST (48 Vdc 100% duty)
9
=
2nd ST (60 Vdc 100% duty)
Auxiliary switch
N
=
None
2
=
2A/2B
4
=
4A/4B
6
=
6A/6B
Bell Alarms Switch (OTS) with
2a/2b contacts and/or mechanical
E N Y M L F
G
H
I
J
K
= = = = = =
=
=
=
=
=
trip indicator
Mech. trip indicator
No Yes Yes Yes Yes Yes
Yes
Yes
Yes
Yes
Yes
Mech. inter- lock for manual reset
No No Yes Yes No
No
No
Yes
Yes
Yes
OTS switch with two form C contacts
No No Yes No Yes Yes with 24V reset Yes with 120V reset Yes with 240V reset Yes with 24V reset Yes with 120V reset Yes with 240V reset
Padlock provisions for blocking
close and/or open ACB manual
pushbuttons
N
=
None
M
=
Metal (block close and open)
P
=
Plastic (block close and open)
C
=
Metal (block close only)
H
=
Plastic (block close only)
S
=
Metal swbd lock-off (block close, depress open)
Operations counter and/
or keylock provisions
Counter
N
=
No counter
K
=
No counter
C
=
No counter
R
=
No counter
S
=
No counter
A
=
Counter
Y
=
Counter
L
=
Counter
H
=
Counter
E
=
Counter
Latch check switch/trip unit
metering voltage connection for
digitrip 1150 trip unit
Latch check switch
N =
None
M =
None
L =
LCS wired to SRD
Y =
LCS Wired to SRD
C =
LCS Wired External
D =
LCS Wired External
Keylock provisions
No locks Kirk lock Castell lock Ronis lock CES lock No lock Kirk lock Castell lock Ronis lock indicator CES lock
1150 voltage connection
Upper terminals Lower terminals Upper terminals
Lower terminals
Upper terminals
Lower terminals
Breaker shipping options
A
=
Fixed breaker alone with door kit
F
=
Fixed breaker alone without door kit
A
=
Drawout breaker alone with- out door frame kit
C
=
Drawout breaker in cassette (un-wired)
P
=
Drawout breaker in cassette (shutters)
S
=
Drawout breaker in cassette (shutters)
W
=
Drawout breaker in cassette (pre-wired and shutters)
Double frame drawout breakers ship without cassette drawout. ACBs ship in narrow and universal cassettes only.
Frame use
X = All breakers
and instructions
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com28
Cassette Magnum SB breaker product family
Courtesy of NationalSwitchgear.com
M E 32 3 C A DN N NNN W C
Magnum SB - Product specific information
Cassette family
ML==Standard or double
frame Narrow or double narrow frame
Interrupt type
EN==SB cassette (150 kAIC)
Cassettes (up to 100 kA)
Continuous amperes
16
=
Up to 1600A
20
=
Up to 2000A
32
=
2500 to 3200A
40
=
4000 to 1600A
50
=
5000 to 2000A
34==Three-pole
Four-pole
Poles
Cassette frame and rear terminals
P
=
Basic cassette (without vertical bus stabs)
C
=
Basic cassette with stabs (with vertical bus stab kit)
H
=
Narrow frame cassette (with horizontal terminal pads)
U
=
Universal cassette (with universal terminal pads)
Arc hood
A = Arc hood installed
Door frame and gasket kit
DNXN==Door frame and gasket kit
included Door frame and gasket kit not included
NS==Un-wired
NNN = All cassettes
Shutters
NS==No shutters
Shutters installed
Cassette shipping
CB==Cassette only
Breaker shipped in cassette
Cassette wiring
Cassette wired
Future use
3
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com 29
Magnum SB - Product specific information
Courtesy of NationalSwitchgear.com
Magnum SB - Continuous amperage, interruption and withstand ratings tables
Table 8. Magnum DS switchgear class UL 1066 low voltage power circuit breakers ANSI
3
rms Symmetrical current ratings kA 50/60 Hz
4
Frame
1
amperes
800 SBN-508 Narrow 50 50 35 20 18xI
1
1
1
1
1200 SBN-512 Narrow 50 50 35 25 18x I
1
1
1
1
1
1600 SBN-516 Narrow 50 50 35 30 18 xI
1
1
1
1
2000 SBN-620 Narrow 65 65 65 35 18xIn 200, 250, 300,
1
1
1
1
1
Interrupting ratings shown based on breaker equipped with integral digitrip rms trip unit.
1
1
1
1
These interruption ratings are based on the standard duty cycle consisting of an open operation, a 15 second interval and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle for short time ratings consists of maintaining the rated current for two periods of 1/2 seconds each, with a 15 second interval of zero current between the two periods.
3
Product to be tested. Contact Eaton for product rating
4
Magnum SBSE current limiting power circuit breaker with fast opening contacts.
5
Breaker applied in a tested fan cooled enclosure
6
Not released
Breaker type catalog position 1–6
SBN-608 Narrow 65 65 42 20 18xI SBN-C08 Narrow 100 100 65 20 18 xI SBS-608 Standard 65 65 65 20 18x I SBS-808 Standard 85 85 85 20 18xI SBS-C08 Standard 100 100 85 20 18xI SBS-H08 Standard 13 0 130 13 0 20 18xI SBS-E08 Standard 200 150 65 30 30 3
SBN-612 Narrow 65 65 42 25 18x I SBN-C12 Narrow 100 10 0 65 25 18xI SBS- 612 Standard 65 65 65 25 18xI SBS- 812 Standard 85 85 85 25 18x I SBS-C12 Standard 100 100 85 25 18x I SBS-H12 Standard 130 13 0 130 25 18 xI SBS-E12 Standard 200 150 65 30 30 3
SBN -616 Narrow 65 65 42 30 18xI SBN -C16 Narrow 10 0 100 65 30 18xI SBS-616 Standard 65 65 65 30 18xI SBS-816 Standard 85 85 85 30 18xI SBS-C16 Standard 100 10 0 85 30 18xI SBS-H16 Standard 130 130 13 0 30 18x I SBS-E16 Standard 200 150 65 30 30 3
SBN-C20 Narrow 100 100 65 35 18 xIn 3 & 4 SBS-620 Standard 65 65 65 35 18x In 3 & 4 SBS-820 Standard 85 85 85 35 18xIn 3 & 4 SBS-C20 Standard 100 100 85 35 18xIn 3 & 4 SBS-H20 Standard 130 130 130 35 18xIn 3 SBS-E20 Standard 200 150 65 30 30 3
Frame type
4
6
4
4
Interruption ratin g at 254 Vac
Interruption ratin g at 508 Vac
Interruption ratin g at 635 Vac
1
Shor t time Withstand rating
Fixed internal inst trip
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Available current sensor and rating plugs f or digit rip rms trip un it (establishes breaker I rating)
200, 250, 30 0, 400, 600, 800
200, 250, 30 0, 400, 600, 800, 1000, 1200
200, 250, 30 0, 400, 600, 800, 1000, 1200, 1600
400, 600, 800, 1000, 1200, 1600, 2000
n
Poles available
3 & 4 3 & 4 3 & 4 3 & 4 3 & 4 3 & 4 3
3 & 4 3 & 4 3 & 4 3 & 4 3 & 4 3 & 4 3
3 & 4 3 & 4 3 & 4 3 & 4 3 & 4 3 & 4 3
3 & 4
1
1
1
1
MAGNUM PRODUCT GUIDE CA013002EN—April 2017 www.eaton.com30