EATON ELLIPSE ECO 1200 USB, ELLIPSE ECO 1600 USB, ELLIPSE ECO 500, ELLIPSE ECO 650, ELLIPSE ECO 650 USB User Manual

...
www.eaton.com
Ellipse ECO
500/650/800/ 1200/1600
Installation and user manual
English - Français Deutsch - Italiano Español - Nederlands
Português -
Polski - Česky Solvenčina - Slovensko
Magyar - Türkçe
РУCCКИЙ
Svenka - Suomi
Eλληνiκά
4
2
5
3
1
IEC models
USB models
Packaging
p
3
2
p
3
2
3
2
Caution!
l Before installing the Ellipse,
read the booklet safety instructions to be respected. Then follow the instructions given in this manual
l Avant l'installation de Ellipse,
lire le livret consignes de sécurité à respecter. Suivre ensuite les instructions du présent manuel
l Vor Installation des Ellipse
die im Heft Sicherheitsvorschriften lesen. Anschließend die Anweisungen im vorliegenden Handbuch befolgen.
l Prima dell’installazione del
Ellipse, leggere attentamente le istruzioni di sicurezza riportate sul libretto In seguito, attenersi alle istruzioni riportate sul presente manuale
l Antes de la instalación del Ellipse,
leer el manual instrucciones de seguridad a cumplir. A continuación, seguir las instrucciones del presente manual
2
.
l Lees voordat u het Ellipse
gaat installeren eerst de veiligheidsinstructies in boekje Volg daarna de instructies van deze handleiding
2
2
3
qui présente les
2
3
genannten
3
.
3
2
.
3
containing the
.
.
que presenta las
2
l Antes da instalação do Ellipse,
ler o caderno as instruções de segurança a respeitar. Depois, seguir as instruções do presente manual
l Przed zainstalowaniem Ellipse,
należy przeczytać instrukcję która zawiera niezbędne zalecenia bezpieczeństwa. Następnie należy zapoznać się z zaleceniami zawartymi w niniejszej instrukcji
l Před instatací zdroje Ellipse
si prostudujte příručku najdete bezpečnostní předpisy, které je třeba dodržovat.
2
.
Dále postupujte podle pokynů uvedených v příručce
l Pred inštaláciou výpustky si
prečítajte knižku uvedené bezpečnostné príkazy, ktoré je potrebné dodržať. Potom postupujte podľa pokynov tejto príručky
l Preden instalirate Ellipse,
3
.
preberite knjižico
varnostna navodila, ki jih je treba upoštevati. Nato sledite navodilom
tega priročnika
3
onde constam
2
.
2
.
2
3
2
3
, v ktorej sú
3
, v kateri so
.
kde
.
l Az Ellipse telepítése előtt
olvassa el a
betartandó biztonsági előirásokat
tartalmazza. Ezután kövesse a jelen,
2
2
.
-ös kezikönyv utasításait.
l Ellipse'in tesisatini yapmadan
önce, uyulacakgüvenliktalimatlarini gösteren okuyunuz. Dana sonra isbu sayili ei kitabindaki talimatlara uyunuz.
3
,
l Innan installation av Ellipse,
läs instruktionsmanualen
3
innehållande
3
-es könyvet, mely a
3
sayili kitapçiği
2
säkerhetsinstruktionerna och följ sedan dem. Följ sedan instruktionerna som ges i denna manual
l Lue nämä ohjeet ennen
Ellipse asennusta turvallisuusohjeet käyttöohjeet
.
2
ja
3
.
2
614-06803-00
Quick start
FR / DIN IEC
A
B
500 / 650 / 800
C
D
USB models
1200 / 1600
614-06803-00
3
Quick start
a
b
c
d
e
a
b
c
d
e
E
Battery disposal and safety
l Caution. Battery service life is reduced by 50 % for
every ten degrees above 25 °C.
l The battery elements must be replaced exclusively
by qualified personnel (risk of electrocution), with
new elements approved by EATON to ensure correct operation of the UPS.
Battery change
Ellipse 500 / 650 / 800
F
USB models
Register warranty at: powerquality.eaton.com
l The battery must be disposed of in accordance
with applicable regulations. To remove the battery elements, shut down the UPS (button the power cord and proceed as indicated in page 4 "Battery change".
12
OFF), remove
Ellipse 1200 / 1600
l Warning: take care not to inverse the polarity + (red) and - (black) when connecting the batteries as this will
destroy the device.
4
614-06803-00
Technical characteristics
Ellipse ECO 500 650 800 1200 1600
l UPS power 500 VA /
300 W
l Nominal input voltage 184 V - 264 V, adjustable to 161 V - 284 V l Input frequency 50/60 Hz (46 - 70 Hz working range) l Voltage/frequency of battery backup
9
outlets
l Total output current for all outlets 10 A max l Output current of battery backup
outlets
l Leakage current 0.4 mA l Input protection 10 A resettable circuit breaker l Transfer time 5 ms typical l Telephone surge protection Tel, ISDN, ADSL, Ethernet l Sealed lead-acid battery 12 V, 4.5 Ah 12 V, 7 Ah 12 V, 9 Ah 2x12V, 7 Ah 2x12V, 9 Ah l Automatic battery test Once a week l Average battery life 4 years typical, depending on temperature and amount of discharge cycles l Operating temperature 0 to 35 °C l Storage temperature -25 °C to +55 °C l Operating relative humidity 0 to 85 % l Operating elevation 0 to 2000 m l Safety standards IEC 60950-1, IEC 62040-1, CE certied l Electromagnetic compatibility
in battery mode
9
2.3 A max 3 A max 3.6 A max 5.5 A max 7.3 A max
standards
l Warranty 2 years l Dimensions (mm) 263 x 81 x 235 305x81x312 l Weigth (Kg) 2.9 3.6 6.7 7.8
(*) Warning: Output cables should not exceed 10m length.
650 VA /
400 W
800 VA /
500 W
1200 VA /
750 W
220 V / 230 V / 240 V +15 % -20 % (50/60 Hz ± 1 %)
IEC 62040-2, C1*
1600 VA /
1000 W
Performances tested according to IEC 61643-1 (class 3) standard for 8/20 µs surge wave
AC input source protection, Ellipse ECO:
l Uoc
(common mode / differential mode)
l Up
(common mode / differential mode)
l In 3 kA
Dielectric isolation
l AC Ground 1500 Vac, 50 Hz l AC / TEL 3000 Vac, 50 Hz l Tel / Ground 1000 Vac, 50 Hz
Temporary overvoltage (TOV)
l Uc 250 Vac l Ut 430 Vac
Energy dissipation
614-06803-00
500 650 800 1200 1600
6 kV / 2 kV 6 kV / 1.8 kV
1.8 kV / 0.7 kV 1.5 kV / 1 kV
461 Joules
5
Operating conditions
8
9
Ellipse 1200 / 1600Ellipse 500 / 650 / 800
9
8
12
13 13
10
11
l This product is an Uninterruptible
Power Supply (UPS) for computers
and their peripherals, television sets, stereo systems and video recorders... It must not be used to supply other electrical equipment (lighting, heating, household appliances, etc.).
l UPS can be installed in
ENGLISH
horizontal, vertical position, or placed in Rack 2U (optional kit).
UPS connections
1
l Connect the UPS
AC-power system via a wall outlet with an earth connector, using the supplied cord FR/DIN sockets or with the supply
to the
4
for a UPS with
cord of your computer for a UPS with IEC sockets (see gure A).
l Plug critical equipment
(computer, monitor, modem, etc.) into the outlets battery backup power and surge
9
providing
protection (see gure B), taking
care not to exceed the rated current indicated in amperes.
l Other devices (printer, scanner,
fax, etc.) can be connect to the
ltered outlets surge protection (see gure B). The
8
that provide
ltered outlets are not backed up
by battery power in the event of a power outage.
l Optional Internet modem /
Network connection:
A modem or Ethernet data line can be protected against surges by connecting it via the UPS. Connect the existing device cable between the wall outlet and the UPS, and use a similar cable between the UPS and the device, as indicated in
gure C (cable not supplied).
l Optional USB connection:
The UPS device can be connected to the computer using the USB
5
supplied.
cable The software is available on the CD-ROM from powerquality.eaton.com
5
or downloadable
(see gures D and F).
Register for the warranty on powerquality.eaton.com.
Master and EcoControl outlets operating procedure
In order to limit energy consumption of peripherals (scanner, printer) in standby mode, the Ellipse ECO is equipped with EcoControl outlets that are dependent on the Master outlet. When the main application supplied by the Master outlet (computer) is shut down, the EcoControl outlets are
6
automatically deactivated and the peripherals shut down. This function (deactivated by
default) is validated and congured using the conguration tool
integrated in the software.
Note: When the function is activated, do not connect critical applications to EcoControl outlets.
Threshold setup
A default setup ensures the correct operation of the EcoControl function. However, depending on the consumption of the main load, the trigger threshold of the EcoControl function may
have to be modied using the conguration software supplied
with the UPS:
l First, make sure that the function
is activated in the "EcoControl
Function" tab of the conguration
tool.
l If the peripherals connected
to the EcoControl outlets do not switch off when the main load is not in normal operation (ex: when in standby mode), the detection threshold value must be set to High.
l If the rated consumption level
of the main load is low and the EcoControl outlets shut down when the main load is operating normally, the detection threshold value must be set to Low.
Operation
8
: Filtered outlets.
9
: Battery backup outlets.
10
: LED ON indicate that surge
protection is active
11
: LED ON indicate a UPS fault.
12
: ON/OFF button for the battery
backup outlets.
13
: Protection circuit breaker.
l Battery charge: The UPS
charges the battery as soon as it is connected to the AC outlet, whether
12
button
used for the rst time, the battery
is pressed or not. When
will only provide its maximum
.
autonomy after it has been charged for 8 hours. It is recommended that the UPS be permanently connected to the AC power supply to ensure the best possible autonomy.
l Switching-on the UPS: press
12
button
l Filtered outlets
battery backup: Equipment
connected to these outlets is supplied as soon as the AC cord is plugged in. They are not affected by button
l Battery backup outlets
Equipment connected to these outlets is supplied as soon as button E). These outlets can be turned on even if the UPS is not connected to AC power (button
l AC-power disturbance: If AC
for about 1 second.
8
without
12
.
12
turns green (see gure
12
ashes).
9
4
:
power is disturbed or fails, the UPS continues to operate on battery power. Button In normal mode, the audio alarm
12
ashes green.
beeps every ten seconds, then every three seconds when the end of battery backup time is near. In silent mode (see the section on settings), the audio alarm simply beeps once when the UPS transfers to battery power.
l If the power outage lasts longer
than the battery backup time, the UPS shuts down and automatically restarts when power is restored. Following a complete discharge, a few hours are required to recharge the battery back to full backup time.
l To save battery power, it is possible
to press button of power to the devices connected
12
to cut the supply
to the battery backup outlets.
l Lightning protection: All outlets,
whether backed up or simply
ltered, include surge protection,
whatever the position of button
l Shutdown of the battery backup
9
outlets
more than two seconds.
: Press button 12 for