Table 14: MPCV Relay Primary / Secondary / Cause Decoding..........................................................73
Table 15: MPCV Relay Product ID Decoding....................................................................................74
2
EATON CORPORATION www.eaton.com
Instructions for DNP MINT Translator Module
I.L.66A7638H03
Installation and Use
Instruction Leaflet IL66A7638H03
Effective December 2010
1.0GENERAL DESCRIPTION
The DNP MINT (DNP Master INCOM Network
Translator) Module, as seen in Figure 1, is a
Eaton Electrical accessory product that will
provide communication between a DNP 3.0
network master and an INCOM (INdustrial
COMmunications) network of MPCV Relays
(see Figure 2). The module is transparent to the
DNP network master. It communicates to a
master on the DNP network using the DNP 3.0
protocol. It communicates to slave devices on
the INCOM network using the IMPACC
(Integrated Monitoring, Protection, And Control
Communication) protocol.
2.0FEATURES
The DNP MINT module is a slave device on the
DNP network and as such requires a master that
will poll/accept DNP objects from the DNP
MINT module.
•DNP communications data transfer rates of
1200, 9600, or 19200 baud with 1 start bit, 8
data bits, no parity and either one or two
stop bits.
3.0INSTALLATION
The DNP MINT module is designed to be
installed, operated and maintained by adequately
trained personnel. These instructions do not
cover all of the details or variations of the
equipment for its storage, delivery, installation,
checkout, safe operation or maintenance. When
mounting the DNP MINT verify that a “C”
Shape 32mm or Standard 35/7.5mm DIN Rail
is used and that it is within an enclosed space.
WARNING
DO NOT ATTEMPT TO INSTALL OR
PERFORM MAINTENANCE ON
EQUIPMENT WHILE IT IS ENERGIZED.
DEATH OR SEVERE PERSONAL INJURY
CAN RESULT FROM CONTACT WITH
ENERGIZED EQUIPMENT. ALWAYS
VERIFY THAT NO VOLTAGE IS
PRESENT BEFORE PROCEEDING.
ALWAYS FOLLOW SAFETY
PROCEDURES. EATON ELECTRICAL
INC. IS NOT LIABLE FOR THE
MISAPPLICATION OR
MISINSTALLATION OF ITS PRODUCTS.
•Up to 16 devices such as the MPCV Relay
connected to the INCOM network port.
•Flashing Status LED to indicate an active
module.
•LED indicators for DNP RS-485 transmit
and receive communications exchanges.
•LED indicators for INCOM transmit and
receive communications exchanges.
•Input power for the module from either 120
VAC or 24 to 125 VDC.
•DIN rail mount package.
• -40ºC to 85ºC ambient operation.
EATON CORPORATION www.eaton.com
3
Instruction Leaflet IL66A7638H03
I.L.66A7638H03
Effective December 2010
DNP3.0
DNP3.0
RS-485
RS -485
DNP
DNP
MINT
MIN T
Figure 2: DNP MINT in a Communications Network
MPCV
MPCV
STREETLEVELVENT/GRATING
STREET LEVELVENT/GRATING
INCOMNetwork
INCOM Network
MPCV
MPCV
Instructions for DNP MINT Translator Module
Installation and Use
UNDERGROUND
UNDERGROUND
MPCVMPCV
MPCVMPCV
3.1INCOM Network
The following simplified rules apply to a given
system consisting of a single daisy chained main
cable link between master and slave devices (see
Figure 2). For more complex considerations
including star configurations, please refer to the
IMPACC wiring specification T.D. 17513.
•Recommended INCOM cable styles are
Belden 3073F or C-H style 2A957805G01.
•The maximum system capacity is 8,000 feet
of communications cable and 16 slave
devices such as the MPCV Relay on the
INCOM network under the DNP MINT.
•Non-terminated taps, up to 200 feet in
length, off the main link are permitted, but
add to the total cable length.
Make sure that there is twisted-pair wire that is
recommended for IMPACC network use. Use
shielded twisted-pair wire to connect each slave
to the INCOM network, daisy-chain style. The
polarity of the twisted pair is not important.
3.2DNP RS-485 Network
The following simplified rules apply to a given
system consisting of a cable link between master
and slave devices (see Figure 2).
•The recommended DNP cable has
twisted-pair wires (24 AWG stranded 7x32
conductors with PVC insulation) having an
aluminum/mylar foil shield with drain wire.
•Make sure that there is twisted-pair wire that
is recommended for serial DNP RS-485
network use. Use shielded twisted-pair wire
to connect each slave to the DNP network,
daisy-chain style.The polarity of the
twisted pair is critically important.
4.0DNP MINT CONNECTIONS
Refer to Figure 3 and the following three pin
out tables for installation specifics.
4
EATON CORPORATION www.eaton.com
Instructions for DNP MINT Translator Module
I.L.66A7638H03
Installation and Use
Instruction Leaflet IL66A7638H03
Effective December 2010
DNP
DNP
BACOMSHD
B A COM SHD
Figure 3: Connections
4.1Power Connections
Connect the shield wire to ground at master
device end only. Interconnect shielding where
devices are daisy chained.
4.3RS-485 Connections
DNP RS-485 Connector: This 4-pin connector
provides the interface to the DNP network. The
polarity is “critically” important. Refer to Table
RS-485 Network-A is the inverting differential
connection for the DNP network. RS-485
Network-B is the non-inverting differential
connection for the DNP network.
Power Connector: Module power uses a 5-pin
input connector (seeFigure 3). Power
requirements are 120 VAC, 60 Hz or
24-125VDC. Refer to Table 1.
Pin #Input Power
1Chassis Ground
2 & 3VAC Neut. / VDC Common
4 & 5VAC Line / 24-125 VDC+
Table 1: Power Connector Pin Outs
4.2INCOM Connections
INCOM Connector: This 3-pin connector
provides the interface to the INCOM network.
Refer to Table 2.
Pin #Input / Output Signal
1INCOM Carrier Network
2INCOM Carrier Network
3Shield
5.0SWITCHES AND INDICATOR
LEDS
Figure 4: Switches
Table 2: INCOM Connector Pin Outs
Refer to Figure 1 to locate the Status LED for
the DNP MINT. Figure 4 shows the location of
the configuration switches.
EATON CORPORATION www.eaton.com
5
Instruction Leaflet IL66A7638H03
I.L.66A7638H03
Effective December 2010
Instructions for DNP MINT Translator Module
Installation and Use
5.1DNP RS-485 Network Rx LED
[Green]
The LED will be illuminated whenever the DNP
MINT is receiving content from activity on the
DNP network.
5.2DNP RS-485 Network Tx LED
[Green]
The LED will be illuminated whenever the DNP
MINT is transmitting on the DNP network.
5.3INCOM Network Rx LED [Green]
The LED will be illuminated whenever the DNP
MINT is receiving messages from the INCOM
network.
5.4INCOM Network Tx LED [Green]
The LED will be illuminated whenever the DNP
MINT is transmitting messages on the INCOM
network.
5.5Status LED [Green]
This indicator will begin flashing after the
module has powered up, its processor has
performed its RAM tests and the microcontroller
is executing instructions. The flashing rate is
approximately 1 second ON / 1 second OFF.
This indicator will flash at a rate of
approximately 5 times a second during an auto
learn dip switch detection sequence (see Section
7.0).
After accepting a configuration request, the DNP
MINT will hold this LED ON for approximately
2.5 seconds.
5.7DNP RS-485 Baud Rate DIP
Switch (SW2)
To set the data transfer rate for the DNP
network, two switches in dip switch SW2
(SW2-2 and SW2-3) should be moved to either
the “CLOSE” or the “OPEN” position based on
the rate required. Refer to Table 4. SW2-1 is
for DNP MINT configuration.
To configure the DNP access settings and the
INCOM device access settings within the DNP
MINT, the SW2-1 dip switch must be moved to
the “OPEN” position. Refer to Table 5.
Normally, this switch is in the “CLOSE”
position. Changing this dip switch
automatically forces a reset of the DNP MINT.
BaudSW2-1SW2-2SW2-3
ConfigureOPENXX
NormalCLOSEXX
Table 5: RS-485 Diagnostics Enable
(Configuration Mode) Switch
5.9DNP/RS-485 121 ΩΩ Termination
DIP Switch (SW3)
This switch should be set to the “ON” position
only when it is the last unit in a chain or if it is
the only outstation device on the DNP Network.
5.6INCOM 100 ΩΩ Termination DIP
Switch (SW1)
This switch should be moved to the “ON”
position only when it is the last unit in a chain of
units or if it is a single unit.
6
EATON CORPORATION www.eaton.com
6.0DNP V3.00 DEVICE PROFILE
The DNP V3.00 device profile for the DNP
MINT is listed in Appendix A.
.
Instructions for DNP MINT Translator Module
I.L.66A7638H03
Installation and Use
Instruction Leaflet IL66A7638H03
Effective December 2010
7.0DNP MINT CONFIGURATION
USING AUTO LEARN
Settings in the DNP MINT can be configured
automatically to allow it to operate with a DNP
Master and up to 16 INCOM devices such as the
MPCV Relay. To ensure this auto learn feature
is not accidentally initiated, the baud rate dip
switches (SW2-2 and SW2-3, see Section 5.7
and Table 4) must be sequenced in a particular
pattern with the diagnostics enable switch
SW2-1 set in the enabled “OPEN” position (see
Section 5.8 and Table 5).
If the DNP MINT is power up with all of the
SW2 dip switch settings in the OPEN position,
detection to enter the auto learn mode begins.
This is indicated by the STATUS LED flashing
at 5 times a second for the duration of the auto
learn detection sequence. If the sequence of
state changes:
STATE1SW2-3 changed to CLOSED
STATE2SW2-2 changed to CLOSED
STATE3SW2-3 changed to OPEN
STATE4SW2-2 changed to OPEN
completes within 20 seconds (note: to avoid
debounce conditions on the dip switches,
intermediate states are ignored), the DNP MINT
enter the auto learn mode. The DNP MINT
Summary Table is initialized to its default state
(see Table 8) and all 16 devices are removed.
This initializes the “DNP Master Address” at
12402 (3072
) and disables a DNP MINT
16
“DNP Address”. The STATUS LED will
remain ON while this initialization process
(writing to non-volatile EEPROM) is being
performed. When completed, the STATUS
LED will flash at the rate of 1 second ON / 1
second OFF. The INCOM network is then
searched for devices from address 001
FFF
(indicated by activity on the INCOM
16
through
16
Network Tx LED). If a device listed in Table 6
is found, the device’s “INCOM Address” is also
assigned to its “DNP Address” and the listed
default “Configuration Tag” information is
entered. It is extremely important that the
INCOM network is properly terminated during
this procedure.
The DNP MINT will exit the auto learn mode if:
(1)16 device are configured,
(2)the search completes (INCOM
address FFF
is reached), or
16
(3)the operator changes any SW2 dip
switch.
Since searching all INCOM addresses can take
approximately 5 minutes, the operator may want
to exit sooner using the dip switches if it is
certain that all the addresses on the INCOM
network have been accessed.
Note that DNP communications in the DNP
MINT is disabled during the auto learn sequence
and process.
Settings in the DNP MINT must be configured
to allow it to operate with a DNP Master and up
to 16 INCOM devices such as the MPCV Relay.
To enable the configuration mode, set switch
SW2-1 to the enabled “OPEN” position (see
Section 5.8 and Table 5).
There are three configuration levels allowed
with the DNP MINT. All levels use a particular
subset of the DNP V3.00 transfer protocol, with
each level increasing in both complexity and
functionality. Each level is described in the
sections below. While in the configuration
mode, the DNP MINT will accept the DNP
transfer requests using either the DNP source
and destination addresses:
(1) both set at self address 65532 (FFFC
16
), or
(2) each set at a previously configured source
“Master Station DNP address” and
destination DNP MINT’s “DNP address”.
While in the configuration mode, the DNP
MINT will transfer information to the DNP
Master using the
UNCONFIRMED_USER_DATA data link
function code and with the application
confirmation request, CON bit, reset.
8.1Configuration With Pre-Defined
Tables
The DNP MINT contains pre-configured tables
that can be selected by a Write (Function Code
02) Counter (Group 20) Object request using
Variation 6 (16-bit Binary Counter without
Flag), Qualifier 00 or 01 (no Preindex, 8-bit or
16-bit start and stop ranges). These counter
object points are defined in Table 7. Points 0
through 5 are “Read Only” DNP MINT
variables. Points 6 through 56 are read/write
counters. The DNP MINT will only accept a
write configuration request when content of
information in the request message includes, as a
minimum:
(1)the “Master Station DNP address”
(Point 6), and/or
(2)the DNP MINT’s “DNP address” and
“DNP MINT Configuration Tag”
(Points 7 and 8), and/or
(3)one or multiple INCOM device’s
“DNP Address”, “INCOM Address”
and “Configuration Tag” (Points 9, 10,
and 11 for Device #1, for example).
A valid “DNP Address” is a value in the range
of 0000
through FFEF16 that is unique to any
16
other device “DNP Address” on the DNP link.
The setting of an invalid DNP MINT’s “DNP
Address” will only allow access to the DNP
MINT with the self address 65532 (FFFC
16
) in
the configuration mode. Normal (run-time)
access of these DNP MINT counters will,
therefore, not be available. Setting an invalid
device’s “DNP Address” will not allow normal
(run-time) DNP access to the device.
A valid “INCOM Address” is a value in the
range 0001
through 0FFF16. Setting an invalid
16
device’s “INCOM Address” will disable
INCOM communications between the DNP
MINT and the device. This will result in all of
the device’s points being off-line during normal
(run-time) access.
All “Configuration Tag” values must be within
the valid range of tags for the write request to be
accepted. A configuration tag request value set
to 0 will leave the current tag value and it’s
corresponding information unmodified and only
update the associated DNP MINT “DNP
address” or device’s “DNP Address” and
“INCOM Address”. If non-zero, the DNP
MINT’s tag must be 1 (only one pre-defined
DNP MINT summary table exists in the DNP
MINT, as listed in Table 8). A device’s tag
must be 1 through the value listed in the
“Number Of Pre-Defined Device Configuration
Tags” (Point 5, = 34) to configure the
pre-defined device settings corresponding to the
tag’s Point List assignments listed in AppendixB. (Refer to IL 17384 for the INCOM
Communication Protocol definitions for all
INCOM devices. For devices which have preassigned configurations as defined in the
9DNP Address
10Device #1INCOM Address
11Configuration Tag ( = 1 through < Point 5 value>, FFFF16 to remove )
12DNP Address
13Device #2INCOM Address
14Configuration Tag ( = 1 through < Point 5 value>, FFFF16 to remove )
15DNP Address
16Device #3INCOM Address
17Configuration Tag ( = 1 through < Point 5 value >, FFFF16 to remove )
18DNP Address
19Device #4INCOM Address
20Configuration Tag ( = 1 through < Point 5 value >, FFFF16 to remove )
21DNP Address
22Device #5INCOM Address
23Configuration Tag ( = 1 through < Point 5 value >, FFFF16 to remove )
24DNP Address
25Device #6INCOM Address
26Configuration Tag ( = 1 through < Point 5 value >, FFFF16 to remove )
27DNP Address
28Device #7INCOM Address
29Configuration Tag ( = 1 through < Point 5 value >, FFFF16 to remove )
30DNP Address
31Device #8INCOM Address
32Configuration Tag ( = 1 through < Point 5 value >, FFFF16 to remove )
33DNP Address
34Device #9INCOM Address
35Configuration Tag ( = 1 through < Point 5 value >, FFFF16 to remove )
36DNP Address
37Device #10INCOM Address
38Configuration Tag ( = 1 through < Point 5 value >, FFFF16 to remove )
39DNP Address
40Device #11INCOM Address
41Configuration Tag ( = 1 through < Point 5 value >, FFFF16 to remove )
42DNP Address
43Device #12INCOM Address
44Configuration Tag ( = 1 through < Point 5 value >, FFFF16 to remove )
45DNP Address
46Device #13INCOM Address
47Configuration Tag ( = 1 through < Point 5 value >, FFFF16 to remove )
48DNP Address
49Device #14INCOM Address
50Configuration Tag ( = 1 through < Point 5 value >, FFFF to remove )
51DNP Address
52Device #15INCOM Address
53Configuration Tag ( = 1 through < Point 5 value >, FFFF16 to remove )
54DNP Address
55Device #16INCOM Address
56Configuration Tag ( = 1 through < Point 5 value >, FFFF16 to remove )
Table 7: Pre-Configured Counter Assignments
EATON CORPORATION www.eaton.com
9
Instruction Leaflet IL66A7638H03
I.L.66A7638H03
Effective December 2010
Appendix B configuration tables, enter the
respective Configuration Tag for that selection.
For INCOM devices without a specific predefined configuration, select the most
appropriate Generic Device or Generic Trip Unit
configuration after review of IL 17384.)
A device’s tag value of FFFF
device from the DNP MINT, which will also
force the device’s “DNP Address” and “INCOM
Address” settings to FFFF
unused/non-configured virtual DNP slave device
state.
These DNP MINT counter object points (Table
7) are returned to the DNP master in response to
a Read (Function Code 01) Counter (Group 20)
Object request using Variations 2 or 6 (16-bit
Binary Counter with or without Flag), Qualifier
00, 01 or 06 (no Preindex, 8-bit, 16-bit start and
stop ranges or no ranges) during both
configuration and normal (run-time) modes,
with normal mode dependent on a valid DNP
MINT’s “DNP Address” setting. Note that
points 0 through 5 are read only DNP MINT
variables.
will remove the
16
, an
16
Instructions for DNP MINT Translator Module
Installation and Use
Preindex, 16-bit start and stop ranges or no
ranges). The most significant byte of the range
fields is used to distinguish which summary
table is being accessed, 0 (00
DNP MINT summary table and 1 (01
16 (10
) pertaining to each of the 16 devices.
16
The least significant byte of the range fields
defines the counters being accessed and start at
128 (80
) so that the DNP MINT summary table
16
does not overlap the pre-defined table described
in Section 8.1. Also note that these counters
will not be returned along with the pre-defined
table counters with a Qualifier 06 (no Preindex,
no ranges) read request.
Summary information is entered into the DNP
MINT using a Write (Function Code 02)
Counter (Group 20) Object request using
Variation 6 (16-bit Binary Counter without
Flag), Qualifier 01 (no Preindex, 16-bit start and
stop ranges or no ranges). The DNP MINT will
only accept the request when the counter range
field pertains to one and only one DNP MINT or
device summary table. Also, when selecting the
DNP MINT summary table counters, the request
cannot be intermixed with the pre-defined
counters described in Section 8.1.
) pertaining to the
16
) through
16
8.2Configuration Of Summary Table
Settings
The DNP MINT contains a summary table (see
Table8) providing various configuration
settings for overall DNP MINT operation. It
also contains a summary table (see Table 9) for
each INCOM device providing various
configuration settings required by the DNP
MINT for interaction pertaining to/with the
device. This information can only be read and
written from a DNP master device when the
DNP MINT is placed in the configuration mode
(see Section 5.8). The information is returned
from the DNP MINT in response to a Read
(Function Code 01) Counter (Group 20) Object
request using Variations 2 or 6 (16-bit Binary
Counter with or without Flag), Qualifier 01 (no
8.2.1DNP Master Station Address
The DNP Master Station Address setting is the
DNP source address value the DNP MINT will
accept in a request message and thus return as
the destination address in the corresponding
response message. It is also applied as the
destination address in a generated unsolicited
message. A valid setting is 0000
FFEF
. The DNP MINT will not accept a write
16
request with an invalid setting. This value is set
in the DNP MINT summary table and applies to
all DNP MINT messages (DNP MINT counters
and its 16 devices).
through
16
10
EATON CORPORATION www.eaton.com
Instructions for DNP MINT Translator Module
I.L.66A7638H03
Installation and Use
Instruction Leaflet IL66A7638H03
Effective December 2010
CounterDefinition
0080
0081
0082
0083
0084
0085
0086
0087
0088
0089
008A
008B
DNP Master Station Address(equivalent to Section 8.1, Counter 6)3072
16
DNP MINT’s DNP Address(equivalent to Section 8.1, Counter 7)FFFF
16
DNP MINT’s Configuration Tag(equivalent to Section 8.1, Counter 8)0001
3-0Data Link Confirmation Retry Count0
4Enable Unsolicited Event Data Link Confirm0
5Enable Solicited Static/Event Data Link Confirm0
6Enable Solicited Static Application Confirm0
High Byte = Unsolicited Event Generation Bits:
9Enable Unsolicited Class 1 Events0
10Enable Unsolicited Class 2 Events0
11Enable Unsolicited Class 3 Events0
DNP network idle time to initiate unsolicited transmission(1 count = 10ms)50 = 500ms
16
DNP network unsolicited retry random time increment mask (1 count = 10ms)007F16 = 1.27s
16
DNP Data Link Confirmation Wait Timeout(1 count = 10ms)50 = 500ms
The DNP Address setting is the DNP destination
address value the DNP MINT will accept in a
request message for one of its DNP MINT or 16
configured devices and thus return as the source
address in the corresponding response message.
It is also applied as the source address in a
generated unsolicited message. A valid setting
is 0000
through FFEF16. A write request with
16
an invalid setting will disable access to the
selected DNP MINT objects or device objects on
the DNP network.
8.2.3Configuration Tag
The Configuration Tag setting provides a label
for the existing configuration table in the DNP
MINT. A request containing a tag setting
corresponding to any of the pre-defined tables
(DNP MINT summary table 01 or device
summary tables 01 through 34) will initialize all
summary settings to the selected pre-defined
values before modifying (over-writing) any of
the other requested counter changes determined
by the write request message.
Acceptance of a write message without the tag
counter request included or with a tag value
outside this pre-defined range will require an
already existing configuration to be resident. A
tag value request of 0 will leave the current tag
value present. A DNP MINT tag value of
FFFF
of FFFF
will not be accepted. A device tag value
16
will remove that device from the DNP
16
MINT. All other tag values will simply be
written as the new tag value.
EATON CORPORATION www.eaton.com
11
Instruction Leaflet IL66A7638H03
I.L.66A7638H03
Effective December 2010
Instructions for DNP MINT Translator Module
Installation and Use
8.2.4DNP Transfer Protocol
The DNP Transfer Protocol settings modify the
DNP MINT interface procedures to the DNP
network. These settings are only used when the
DNP MINT is functioning in the run (non
configuration) mode.
A DNP MINT or device setting with the “Enable
Solicited Static/Event Data Link Confirm” bit
reset / set will return solicited data to the master
device using the
UNCONFIRMED_USER_DATA/
CONFIRMED_USER_DATA data link function
code, respectively. If set, data link transfers that
do not receive a confirmed response will be
retried depending on the “Data Link
Confirmation Retry Count” setting.
A device setting with the “Enable Unsolicited
Event Data Link Confirm” bit reset / set will
send unsolicited data to the master device using
the UNCONFIRMED_USER_DATA /
CONFIRMED_USER_DATA data link function
code, respectively. If set, data link transfers that
do not receive a confirmed response will be
retried depending on the “Data Link
Confirmation Retry Count” setting.
A DNP MINT or device setting with the “Enable
Solicited Static Application Confirm” bit set will
return solicited data to the master device with
the CON bit set (requesting a confirmation).
Note that all event data being returned are
required to set this CON bit.
A device setting with an “Enable Unsolicited
Class 1/2/3 Events” bit set will send unsolicited
data to the master device after the occurrence of
an event for that enabled class.
The DNP MINT binary counter objects cannot
be enabled for unsolicited messaging (i.e., set to
Class 1, 2 or 3). Thus setting the “Enable
Unsolicited Event Data Link Confirm” or
“Enable Unsolicited Class 1/2/3 Events” bits for
the DNP MINT summary would provide no
functionality.
8.2.5DNP Network Idle Time To
Initiate Unsolicited Transmission
The DNP Network Idle Time To Initiate
Unsolicited Transmission setting is the number
of 10 ms increments the DNP MINT will wait
for the DNP network to be silent (inactive)
before it will attempt to transfer a pending
unsolicited message. This value is set in the
DNP MINT summary table and applies to all
DNP MINT messages (DNP MINT counters and
its 16 devices).
8.2.6DNP Network Unsolicited Retry
Random Time Increment Mask
The DNP Network Unsolicited Retry Random
Time Increment Mask setting is used to mask a
random number generated by the DNP MINT
which will be added (in 10 ms increments) to the
DNP MINT to retry an unsuccessful
(unconfirmed) unsolicited message transfer
attempt. The additional time increment is added
to the DNP Network Idle Time if a message
different from the expected confirmation is
received. It is added to the DNP Application
Confirmation Wait Timeout if no response is
received. This value is set in the DNP MINT
summary table and applies to all DNP MINT
messages (DNP MINT counters and its 16
devices).
8.2.7DNP Data Link Confirmation
Wait Timeout
The DNP Data Link Confirmation Wait Timeout
setting is the number of 10 ms increments the
DNP MINT will wait for a Data Link
confirmation from the master device, providing
data link confirmations are enabled (see Section
8.2.4). This value is set in the DNP MINT
summary table and applies to all DNP MINT
messages (DNP MINT counters and its 16
devices).
12
EATON CORPORATION www.eaton.com
Instructions for DNP MINT Translator Module
I.L.66A7638H03
Installation and Use
Instruction Leaflet IL66A7638H03
Effective December 2010
8.2.8DNP Application Confirmation
Wait Timeout
The DNP Application Confirmation Wait
Timeout setting is the number of 10 ms
increments the DNP MINT will wait for an
application confirmation from the master device.
This value is set in the DNP MINT summary
table and applies to all DNP MINT messages
(DNP MINT counters and its 16 devices).
8.2.9INCOM Scan Level Settings
Configuration of each of the 16 virtual INCOM
devices requires information such as an INCOM
command scan list and various object point lists
that the device will support. (This information is
automatically generated when, for instance, a
pre-defined configuration tag is selected.) In run
mode, the DNP MINT will continually scan the
16 devices and enter the obtained information in
a database. The scan sequence for the devices
can be configured with a priority scheme to
allow more important information to be
refreshed in the database more often. The DNP
MINT will sequence through all the Scan Level
1 (Poll) commands for all 16 devices. Upon
completion the DNP MINT will then obtain all
Scan Level 2 (Interleaved) commands for one of
the devices. If the device has any Scan Level
2/3 (Timer2/Timer3) commands and the
corresponding “INCOM Level 2/3 Scan Timer”
has expired, the command will be included in
the Interleaved command list. These “INCOM
Level 2/3 Scan Timer” settings are the number
of 1 second increments the DNP MINT will wait
to insert the command into the Interleaved
sequence.
Associated with each Scan Level is an “INCOM
Scan Level Count To Generate Point Off-Line”
setting. This setting is the number of
consecutive times an object’s data is not
received from the INCOM device to flag a DNP
“off-line” state. Note that each object (point)
has an associated Scan Level. These settings
have a count range of 0 to 15. A setting of 0
will force the “off-line” flag state. Any attempt
to set a count to a value greater than 15 will
force the setting to 15.
8.2.10DNP Object Variation Default
Settings
A Read (Function Code 01) request using
Variation 0 from the master device allows the
outstation to select the object variation of the
response data. For the DNP MINT counter
objects, the Variation will default to 6 (16-bit
Binary Counter without Flag). For the 16
devices, the default Variation for each Group
can be set, as listed in Table 9. If a setting
contains a value not defined by DNP, that value
will be indicated but the default value shown in
the table will be used.
8.2.11INCOM Address Settings
In order for one of the 16 virtual devices to be
enabled and communicate to an INCOM device,
a valid INCOM address must be configured.
The “INCOM Main Address” setting must
match the selected device’s INCOM address.
An invalid “INCOM Main Address” setting will
disable communications on the INCOM network
for that virtual device. Note that valid INCOM
addresses range from 1 through 4095 (0FFF
The “INCOM Sub-Network Address” is
reserved for future sub-network device access
and cannot be changed from its 0 setting.
).
16
EATON CORPORATION www.eaton.com
13
Instruction Leaflet IL66A7638H03
I.L.66A7638H03
Effective December 2010
Instructions for DNP MINT Translator Module
Installation and Use
Counter
(Device YY)
YY80
16
YY81
16
YY82
16
YY83
16
YY84
16
YY85
16
YY86
16
YY87
16
YY88
16
YY89
16
YY8A
16
YY8B
16
Definition
DNP Address(equivalent to device’s Counter of Section 8.1)FFFF
Configuration Tag(equivalent to device’s Counter of Section 8.1)1 - 34
DNP transfer protocol:0000
3-0Data Link Confirmation Retry Count0
4Enable Unsolicited Event Data Link Confirm0
5Enable Solicited Static/Event Data Link Confirm0
6Enable Solicited Static Application Confirm0
High Byte = Unsolicited Event Generation Bits:
9Enable Unsolicited Class 1 Events0
10Enable Unsolicited Class 2 Events0
11Enable Unsolicited Class 3 Events0
DNP Object Variation Defaults:
Low Byte: Group 01 (Binary Input) Object Variation Default1
High Byte: Group 02 (Binary Input Change) Object Variation Default1
Low Byte: Group 20 (Binary Counter) Object Variation Default1
High Byte: Group 21 (Frozen Counter) Object Variation Default1
Low Byte: Group 22 (Binary Counter Change) Object Variation Default1
High Byte: Group 23 (Frozen Counter Change) Object Variation Default1
Low Byte: Group 30 (Analog Input) Object Variation Default1
High Byte: Group 31 (Frozen Analog Input) Object Variation Default1
Low Byte: Group 32 (Analog Input Change) Object Variation Default1
High Byte: Group 33 (Frozen Analog Input Change) Object Variation Default1
Low Byte: Group 34 (Analog Input Deadband) Object Variation Default2
High Byte: (reserved)0
INCOM Main Address(equivalent to device’s Counter of Section 8.1)FFFF
INCOM Sub-Network Address(reserved)0000
be reduced to any value less than the original
Configuration of each of the 16 virtual INCOM
devices requires information such as an INCOM
command scan list and various object point lists
that the device will support. (This information is
tags scan number. If the initial configuration has
a custom (file transferred) configuration tag the
number can only be reduced from the current
setting.
automatically generated when, for instance, a
pre-defined configuration tag is selected.) The
“INCOM Scan List Index” setting provides two
bytes associated with the INCOM command
scan list. The high byte provides the number of
commands in the scan list. After initial
configuration, this byte value may be reduced to
remove the later commands in the scan list. If
The low byte provides an enabling write
setpoints feature. If the current INCOM scan list
contains a read setpoints command (3 C 9) as the
xth command in the list and this setting is set to
x, write setpoints will be enabled. Any value not
corresponding to the read setpoints command
will disable the write setpoints feature.
the initial configuration has a pre-defined
14
EATON CORPORATION www.eaton.com
Instructions for DNP MINT Translator Module
I.L.66A7638H03
Installation and Use
Instruction Leaflet IL66A7638H03
Effective December 2010
8.3Configuration With File Transfers
All configuration features within the DNP
MINT are actually contained in EEPROM using
configuration tables. The DNP MINT itself only
requires the summary table described in Table
8. Each of the 16 virtual devices require a set of
4 tables:
(1)a summary table (Table9) and
appended INCOM scan command list,
(2)a binary points list,
(3)a non-binary points list and
(4)a control (operate) list.
For almost all applications, the pre-defined
configurations described in Section 8.1, with
possibly minor modifications described in
Section 8.2, would self configure the DNP
MINT and generate all the required
configuration tables.
Each of these tables can be obtained from the
DNP MINT in configuration mode with a simple
form of the Read (Function Code 2) File (Group
70, Variation 5=Transport, Qualifier 5B
objects prefixed with 2 octet object size, free
formatted) request. (Note: since this is a
non-run mode, or configuration only, feature this
simple File transaction does not require any
Open/Close/etc. DNP File procedures.) The
=
16
prefixed with 2 octet object size contains the
number of bytes to follow. The table requested
is defined by a 32-bit File Handle field
containing the DNP MINT (0) or device (1-16)
ID followed by a 32-bit Block Number field
containing the value 00 (summary table and
appended INCOM scan command list
information), 01 (binary points list information),
02 (non-binary points list information) or 03
(control list information).
The DNP MINT provides the ability to
configure its summary table and/or the devices
and their set of object points with a simple form
of the Write (Function Code 2) File (Group 70,
Variation 5=Transport, Qualifier 5B
= objects
16
prefixed with 2 octet object size, free formatted)
request using file downloads. The format is
equivalent to the read file function except the
file information is appended.
These configurations require an extensive
knowledge of the INCOM protocol.
Additionally, its complexity and the need to
interlinked settings between tables prohibit their
discussion. Please contact Eaton Electrical if a
specific configuration outside the pre-defined
configurations is required.
EATON CORPORATION www.eaton.com
15
Instruction Leaflet IL66A7638H03
Effective December 2010
Instructions for DNP MINT Translator Module
Installation and Use
16
EATON CORPORATION www.eaton.com
Instructions for DNP MINT Translator Module
I.L.66A7638H03
Installation and Use
Instruction Leaflet IL66A7638H03
Effective December 2010
Appendix A
DNP V3.00DEVICE PROFILE DOCUMENT
Vendor Name:Eaton Corporation
Device Name:DNP MINT Translator V1.00
Highest DNP Level Supported:For Requests: DNP-L1 (DNP-L3 without Freeze functionality)
For Responses: DNP-L1 (DNP-L3 without Freeze functionality)
Device Function:Slave
Maximum Data Link Frame Size:Received: 292
(octets)Transmitted: 292
Maximum Application Fragment Size:Received: 249
(octets)Transmitted:1280
Maximum Data Link Retries:Configurable from 0 to 15 (default set at 0) (Note 1)
Maximum Application Layer Retries:None
Requires Data Link Confirmation:Configurable (Note 1)
Requires Application Link Confirmation:1) When sending multi-fragment responses
(all except final fragment)
Timeouts While Waiting For:
Data Link Confirm:Configurable from 0 to 655.35 seconds (default: 0.50 seconds) (Note 1)
Complete Application Fragment:None
Application Confirm:Configurable from 0 to 655.35 seconds (default: 5.00 seconds) (Note 1)
Complete Application Response:None
Executes Control Operations:
Write Binary OutputsNever
Select/OperateAlways (Only accepts requests for single CROB object header with:
(Select-to-Operate timeoutGroup = 12, Varation = 01, Qualifier = 17
= 10 seconds)Latch On/Off, Count = 1, onTime = 0, offTime = 0, Status = 0)
Direct OperateAlways (Only accepts requests for single CROB object header with:
Direct Operate – No ACKAlways (Only accepts requests for single CROB object header with:
Reports Binary Input Change Events when no specific variation requested:Only non-time-tagged
Reports timed-tagged Binary Input Change Events when no specific variation requested:Never
Sends Unsolicited Responses:Configurable (default: disabled) (Note 1)
Sends Static Data in Unsolicited Responses:Never
Default Counter Object/Variation:Delta and Frozen counters are not implemented.
Counters Roll Over at:Configurable from 0 through 0FFFFFFFF
Sends Multi-Fragment Responses:Yes
(idle wait time configurable from 0 to 655.35 seconds,
default: 0.50 seconds) (Note 1)
or 2816,
16
or 2816,
16
or 2816,
16
(Note 1)
16
Additional Notes:
The list of object headers in a read request may not exceed what can be placed into a single frame.
Only Binary Counter 0 (Primary/Secondary/Cause), 1 (Product ID) and Setpoints can produce an event, if assigned to a class.
The “deadband” is set to 0001
. All other Binary Counter “deadbands” are set to 0FF (0FFFFFFFF16).
16
Note 1: Configurable by download configuration.
EATON CORPORATION www.eaton.com
17
Instruction Leaflet IL66A7638H03
I.L.66A7638H03
Effective December 2010
Instructions for DNP MINT Translator Module
Installation and Use
OBJECTREQUESTRESPONSE
GrpVarDescriptionFC
10Binary Input: any variation (Def 1)100, 01, 0612900, 01
11Binary Input
12Binary Input with Status100, 01, 0612900, 01
20Binary Input Change: any variation (Def 1)106, 07, 0812917
21Binary Input Change without time106, 07, 0812917
220Counter Change Event: any variation (Def 1)106, 07, 0812917
221Counter Change Event: 32-bit without time106, 07, 0812917
222Counter Change Event: 16-bit without time106, 07, 0812917
300Analog Input: any variation (Def 1)100, 01, 0612900, 01
301Analog Input: 32-bit100, 01, 0612900, 01
302Analog Input: 16-bit100, 01, 0612900, 01
303Analog Input: 32-bit without flag100, 01, 0612900, 01
304Analog Input: 16-bit without flag100, 01, 0612900, 01
305Analog Input: Short Floating Point100, 01, 0612900, 01
320Analog Input Change: any variation (Def 1)106, 07, 0812917
321Analog Input Change: 32-bit without time106, 07, 0812917
322Analog Input Change: 16-bit without time106, 07, 0812917
325 (!)Analog Input Change: Short Float w/o time106, 07, 0812917
340Analog Deadband: any variation (Def 2)100, 01, 0612900, 01
341Analog Deadband: 16-bit
342Analog Deadband: 32-bit
343Analog Deadband: Short Floating Point
601Class 0 data
602Class 1 data
603Class 2 data
604Class 3 data
801Internal Indicators
1
2
1
2
1
2
1
2 (****)
1
2 (****)
1
2 (****)
1
22
1
20, 21, 22
1
20, 21, 22
1
20, 21, 22
1
2
Qual Codes
(hex)
00, 01, 06
00, 01, 17, 28 (*)
00, 01, 06
00, 01, 17, 28 (*)
00, 01, 06
00, 01, 17, 28 (*)
00, 01, 06
00, 01, 17, 28
00, 01, 06
00, 01, 17, 28
00, 01, 06
00, 01, 17, 28
06
06 (**)
06, 07, 08
06 (**)
06, 07, 08
06 (**)
06, 07, 08
06 (**)
00, 01, 06
00, 01 (***)
FC
129
129
129
129
129
129
129
129
129
129
129
Qual Codes
(hex)
00, 01
(NULL)
00, 01
(NULL)
00, 01
(NULL)
00, 01
(NULL)
00, 01
(NULL)
00, 01
(NULL)
see BIN, BCNT, AIN
(NULL)
see BIN, BCNT, AIN
(NULL)
see BIN, BCNT, AIN
(NULL)
see BIN, BCNT, AIN
(NULL)
00, 01
(NULL)
(*)Function Code 2 supported for Setpoint Objects only (if setpoint write feature for device is configured).
(**)Function Code 22 sub-headers supported: see BIN, BCNT, AIN Function Code 1.
(***)Function Code 2 Internal Indicator write supports Range start = 7, end = 7 only.
(****)Analog Deadbands are stored in non-volatile memory, and are therefore preserved through reset.
(!)Not Supported for DNP MINT Version 1.00
18
EATON CORPORATION www.eaton.com
Instructions for DNP MINT Translator Module
I.L.66A7638H03
Installation and Use
Instruction Leaflet IL66A7638H03
Effective December 2010
Appendix B
Pre-defined Configuration Points Lists
TagINCOM DeviceNotes
1MPCV RelayRead Setpoints; Remote Control
2MPCV RelayRead Setpoints; No Control
3MPCV RelayNo Setpoints; Remote Control
4MPCV RelayNo Setpoints; No Control
5MPCV RelayRead/Write Setpoints; Remote Control
6Generic DeviceFast Status S7,S6; 305 IA IB IC
7Generic DeviceFast Status S7,S6; 305 IA IB IC IX
8Generic DeviceFast Status S7,S6; 30F/03 IA IB IC
9Generic DeviceFast Status S7,S6; 30F/03 IA IB IC IG
10Generic DeviceFast Status S7,S6; 30F/03 IA IB IC IN
11Generic DeviceFast Status S7,S6; 30F/03 IA IB IC IG IN
12RMS Trip UnitFast Status S7,S6/Flags; 305 IA IB IC
13RMS Trip UnitFast Status S7,S6/Flags; 305 IA IB IC IX
14OPTIM Trip UnitFast Status S7,S6/Flags; 30F/03 IA IB IC
15OPTIM Trip UnitFast Status S7,S6/Flags; 30F/03 IA IB IC IG
16OPTIM Trip UnitFast Status S7,S6/Flags; 30F/03 IA IB IC IN
17OPTIM Trip UnitFast Status S7,S6/Flags; 30F/03 IA IB IC IG IN
18DigiTrip 520MC301; IA IB IC
19DigiTrip 520MC301; IA IB IC IG
20DigiTrip 520MC301; IA IB IC IN
21DigiTrip 520MC301; IA IB IC IG IN
22DT3000
23DP4000Without Energy
24DP4000With Energy
25DIM
26Addressable Relay
27DigiTrip 1150 cv0302; IA IB IC
28DigiTrip 1150 cv0302; IA IB IC IG
29DigiTrip 1150 cv0302; IA IB IC IN
30DigiTrip 1150 cv0302; IA IB IC IG IN
31DigiTrip 1150 cv1>301; IA IB IC
32DigiTrip 1150 cv1>301; IA IB IC IG
33DigiTrip 1150 cv1>301; IA IB IC IN
34DigiTrip 1150 cv1>301; IA IB IC IG IN
Table 10: Device Assignments for Pre-Defined Configuration Tags
EATON CORPORATION www.eaton.com
19
Instruction Leaflet IL66A7638H03
I.L.66A7638H03
Effective December 2010
Instructions for DNP MINT Translator Module
Installation and Use
Configuration Tag 1:MPCV Relay with Read Setpoints and Remote Control
Configuration Tag 5:MPCV Relay with Read/Write Setpoints and Remote Control
Command
Number
0300Fast StatusPoll
1300 with 3C8Fast Status & Flags BufferPoll
2305Current BufferInterleaved
33CDMPCV Transformer And Network VoltagesInterleaved
430F N=3BMPCV Phasing Voltage Phasors BufferInterleaved
5308Power Buffer (1)Interleaved
6309Power Buffer (2)Interleaved
73CAMPCV Temperature BufferInterleaved
83C9Setpoints BufferTimed3
Binary
Input
0StatusDevice On-LineVirtual
1StatusOpen (S7-S6 state = 00)Poll
2StatusClosed (S7-S6 state = 01)Poll
3StatusTripped (S7-S6 state = 10)Poll
4StatusAlarm (S7-S6 state = 11)Poll
5StatusBreaker ClosedPoll
6StatusRemote TripPoll
7StatusProtective Remote ClosePoll
8StatusAux #2 ActivePoll
9StatusAux #3 ActivePoll
10StatusAux #4 ActivePoll
11StatusProtector Failed To Open AlarmPoll
12StatusProtector Failed To Close AlarmPoll
13StatusAux #2 In AlarmPoll
14StatusAux #3 In AlarmPoll
15StatusAux #4 In AlarmPoll
16StatusBreaker PumpingPoll
17SetpointCBA RotationTimed3
18SetpointStraight Line Master LineTimed3
19SetpointWatt / Var EnabledTimed3
20SetpointPump EnabledTimed3
21SetpointAux #2 In UseTimed3
22SetpointAux #2 Alarm EnabledTimed3
23SetpointAux #2 Normally Closed ContactTimed3
24SetpointAux #3 In UseTimed3
0DataPrimary / Secondary / CausePoll
1DataINCOM Product IDPoll
2DataFirmware Version / RevisionTimed3
3SetpointSystem FrequencyTimed3
4SetpointSystem VoltageTimed3
5SetpointNWP CT RatioTimed3
6SetpointMaster Line (0.1V increments)Timed3
7SetpointPhasing Line (positive degrees, where –5o set as 355o)Timed3
8SetpointPhasing Line 1 (positive degrees, where –5o set as 355o)Timed3
9SetpointLeft Hand Master Line (positive degrees)Timed3
10SetpointReverse Trip (0.01% increments)Timed3
11SetpointTime Delay (1/4 second increments)Timed3
12SetpointOvercurrentTimed3
13SetpointPump CyclesTimed3
14SetpointPump TimeTimed3
15SetpointPump Lockout Reset DelayTimed3
Control
Output
Latch ONLatch OFF
0Open Circuit Breaker and Block OpenClear Block Open
1Protective CloseClear Protective Close
2Reset Pumping Fault-----
Scan
Level
EATON CORPORATION www.eaton.com
21
Instruction Leaflet IL66A7638H03
I.L.66A7638H03
Effective December 2010
Configuration Tag 2:MPCV Relay with Read Setpoints and No Remote Control
Instructions for DNP MINT Translator Module
Installation and Use
Command
Number
0300Fast StatusPoll
1300 with 3C8Fast Status & Flags BufferPoll
2305Current BufferInterleaved
33CDMPCV Transformer And Network VoltagesInterleaved
430F N=3BMPCV Phasing Voltage Phasors BufferInterleaved
5308Power Buffer (1)Interleaved
6309Power Buffer (2)Interleaved
73CAMPCV Temperature BufferInterleaved
83C9Setpoints BufferTimed3
Binary
Input
0StatusDevice On-LineVirtual
1StatusOpen (S7-S6 state = 00)Poll
2StatusClosed (S7-S6 state = 01)Poll
3StatusTripped (S7-S6 state = 10)Poll
4StatusAlarm (S7-S6 state = 11)Poll
5StatusBreaker ClosedPoll
6StatusRemote TripPoll
7StatusProtective Remote ClosePoll
8StatusAux #2 ActivePoll
9StatusAux #3 ActivePoll
10StatusAux #4 ActivePoll
11StatusProtector Failed To Open AlarmPoll
12StatusProtector Failed To Close AlarmPoll
13StatusAux #2 In AlarmPoll
14StatusAux #3 In AlarmPoll
15StatusAux #4 In AlarmPoll
16StatusBreaker PumpingPoll
17SetpointCBA RotationTimed3
18SetpointStraight Line Master LineTimed3
19SetpointWatt / Var EnabledTimed3
20SetpointPump EnabledTimed3
21SetpointAux #2 In UseTimed3
22SetpointAux #2 Alarm EnabledTimed3
23SetpointAux #2 Normally Closed ContactTimed3