How to use the time clock input on the DLVP Low-Voltage Power Module
INS #
Distributed Low-Voltage Power System
Overview
The DLVP power module provides an onboard time clock input, that can be used to control lighting normally or
implement partial on/ partial off controls. The power module provides inputs for an external dry contact closure.
Time clock commands can be sent to the power module via dry contact input. The table below defines the system
actions based on various input conditions and settings.
DLVP Time Clock / Occupancy State
Distributed Low-Voltage Power System
Time Clock
Status
Open (After
Hours)
Closed
(Business
Hours)
Alert Mode
Closed
Alert Mode
Open
Settings Space Condition
Mode
(DIP - 1)
Occupancy
(O)
Occupancy
(O)
Vacancy (V) Lights: Manual ON
Occupancy
(O)
Occupancy
(O)
Vacancy (V) Lights: Manual ON
Partial On
(DIP - 2)
Disabled (N) Lights: Scene 6
Enabled (Y) Lights: 50%
Disabled (N) Lights: Scene 6
Enabled (Y) Lights: 50%
Occupied Unoccupied No Sensor
Rec/BMS:
Energized /
Occupied
Switchpack:Follows
zone 1 lighting
loads
Rec/BMS:
Energized /
Occupied
Switchpack:Follows
zone 1 lighting
loads
Rec/BMS:
Energized /
Occupied
Switchpack:Follows
zone 1 lighting
loads
Rec/BMS: Manual
ON Energized /
Occupied
Switchpack:Follows
zone 1 lighting
loads
Rec/BMS:
Energized /
Occupied
Switchpack:Follows
zone 1 lighting
loads
Rec/BMS:
Energized /
Occupied
Switchpack:Follows
zone 1 lighting
loads
All light fixtures are FULL ON. Receptacle switchpack turns OFF. Wallstation, occupancy, daylight
controls, demand response, and handheld remotes are disabled.
System is returned to normal function leaving lighting in previous state. If the previous state is OFF,
lighting will initiate a blink warn sequence and turn OFF five minutes later.
Lights: OFF
Rec/BMS: De-energized
unoccupied
(30-seconds after lights
turn OFF)
Switchpack: Follows zone 1 lighting
loads
Lights: OFF
Rec/BMS: De-energized
unoccupied
(30-seconds after lights
turn OFF)
Switchpack: Follows zone 1 lighting
loads
Lights: OFF
Rec/BMS: De-energized
unoccupied
(30-seconds after lights
turn OFF)
Switchpack: Follows zone 1 lighting
loads
Lights: Scene 5
Rec/BMS: Energized / Occupied
Switchpack: Follows zone 1 lighting
loads
Lights: Scene 5
Rec/BMS: Energized / Occupied
Switchpack: Follows zone 1 lighting
loads
Lights: Scene 5
Rec/BMS: Energized / Occupied
Switchpack: Follows zone 1 lighting
loads
Lights: Manual ON - 1 hour
Blink-warn - 5 min
Rec/BMS: Energized / Occupied
De-energized / unoccupied
(30-seconds after lights turn
OFF)
Switchpack: Follows zone 1 lighting loads
Lights: Manual ON - 1 hour
Blink-warn - 5 min
Rec/BMS: Energized / Occupied
De-energized / unoccupied
(30-seconds after lights turn
OFF)
Switchpack: Follows zone 1 lighting loads
Lights: Manual ON - 1 hour
Blink-warn - 5 min
Rec/BMS: Energized / Occupied
De-energized / unoccupied
(30-seconds after lights turn
OFF)
Switchpack: Follows zone 1 lighting loads
Lights: Scene 5
Rec/BMS: Energized/Occupied
Switchpack: Follows zone 1 lighting loads
Lights: Scene 5
Rec/BMS: Energized/Occupied
Switchpack: Follows zone 1 lighting loads
Lights: Scene 5
Rec/BMS: Energized/Occupied
Switchpack: Follows zone 1 lighting loads
www.eaton.com/lightingsystems
2
Distributed Low-Voltage Power System
Time Clock Wiring
Connect the dry contact closure to the appropriate terminal for the application. The terminal block is removable for
ease of wiring. Use 18 AWG unshielded, 2 conductor twisted pair wiring for connection. Maximum distance must
not exceed 1000ft. (300m).
TRIM
DEMAND
+ -
CLOCK
+ -
LOW HIGH
ALERT
+ -
Note: time clock contact closer source may be simple time clocks, lighting control panels, etc.
Note: DLVP does not support time sweeps
Time Clock Settings
The DLVP system may behave differently based on time clock input (during or after business hours) and settings
established by switches on the low-voltage power module.
Occ / Vac
Partial On
Select Occ
Occ Share
1
VY
O
1 2345
23
YNY
N
45
N
Occupancy Mode
Partial ON disabled
3
www.eaton.com/lightingsystems
Occ / Vac
Partial On
Select Occ
Occ Share
1
VY
O
1 2345
23
YNY
N
45
N
Occupancy Mode
Partial ON enabled
Occ / Vac
Partial On
Select Occ
1
VY
O
12345
23
YNY
N
45
N
Vacancy Mode
Partial ON N/A
Occ Share
Distributed Low-Voltage Power System
How time clock functions work
Out of the box, the time clock contact closure is open (after hours mode) and the system is in vacancy mode.
Occ / Vac
1
V Y
O
Partial On
2 3
N
Select Occ
Occ Share
4 5
YNY
N
DEMAND
+ -
CLOCK
+ -
1 1 REC
LOW HIGH
ALERT
+ -
TRIM
4
www.eaton.com/lightingsystems