Eaton Digitrip 520V, Digitrip 520MCV Instructions Manual

I.L. 66A7534H04
Instructions for Digitrip Models 520V and 520MCV for use only in Cutler-Hammer T ype VCP-T, VCP-TR and T -V AC, T-VACR Circuit Breakers
Table of Contents
I.L. 66A7534H04
Page 1
1.0 General Description of Digitrip Trip Units ................. 2
1.1 Protection ............................................................... 3
1.2 Mode of Trip and S tatus Information ........................ 3
1.3 Installation and Removal.......................................... 3
1.3.1 Installation of the Trip Unit............................ 3
1.3.3 Trip Unit/Rating Plug Removal...................... 4
1.4 Installing the CH T ype-V Curent Sensors................. 5
1.4.1 Installation of the Rating Plug...................... 5
1.4.2 CH T ype-V Current Sensor Functiionality .... 5
1.5 Plexiglass Cover ..................................................... 5
1.6 Ground Alarm/Power Supply Module (520MCV)....... 5
1.6.1 Auxilary Power............................................ 7
1.6.2 Ground Alarm .............................................. 7
1.6.3 Ground Fault Trip ........................................ 7
1.6.4 Ground Fault Alarm..................................... 7
1.7 Display Feature (520MCV) ...................................... 7
1.8 UL, CSA and CE Recognition.................................. 8
2.0 General Description of VCP-T , VCP-TR
2.1 General ...................................................................8
2.2 Low Energy Trip Actuator ........................................ 9
2.3 Ground Fault Protection .......................................... 9
2.3.1 General ........................................................ 9
2.3.2 Zero Sequence Sensing ............................... 9
2.3.3 Residual Sensing......................................... 9
2.3.4 Ground Fault Settings................................ 10
3.0 Principles of Operation .......................................... 12
3.1 General ................................................................. 12
3.2 Trip and Operation Indicators................................. 12
3.3 Zone Interlocking ............................................. 12, 28
4.0 Protection Settings ............................................... 14
4.1 General ................................................................. 14
4.2 Long Delay Current Setting ................................... 14
4.3 Long Delay Time Setting ....................................... 14
4.4 Short Delay Current Setting................................... 15
4.5 Short Delay Time Setting ...................................... 15
4.6 Instantaneous Current Setting ............................... 15
4.7 Ground Fault Current Setting................................. 16
4.8 Ground Fault Time Delay Setting .......................... 16
4.9 INCOM (520MCV).................................................. 16
4.9.1 Breaker Interface Module (BIM) .................. 16
4.9.2 Remote Master Computer .......................... 16
4.9.3 INCOM Network Interconnections .............. 17
5.0 Test Procedures.................................................... 18
5.1 Test Precautions ................................................... 18
5.2 When to Test ........................................................ 18
5.3 Functional Field Testing ........................................ 18
5.3.1 Field Test Kit............................................... 18
5.3.2 Handheld Functional Test Kit...................... 19
5.3.2.1 Description of Handheld Test Kit...... 19
5.3.2.2 Test Procedure................................ 19
5.3.2.3 Currents .......................................... 19
5.3.2.4 Batteries ......................................... 19
5.4 Performance T esting of Digitrip Trip Units .............. 19
5.4.1 General ...................................................... 19
5.4.2 Testing using MS-2 MultiAMP® Tester....... 19
5.4.2.1 Description of MS-2 T ester .............. 19
5.4.2.2 Primary Injection Testing ................. 20
5.4.2.3 Secondary Injection Testing............. 21
6.0 Battery................................................................. 23
6.1 General ................................................................. 23
6.2 Battery Check....................................................... 23
6.3 Battery Installation and Removal ........................... 23
7.0 Frame Ratings
(Sensor Ratings and Rating Plugs)....................... 24
8.0 Record Keeping .................................................... 24
9.0 References ............................................................ 24
9.1 Medium V oltage T ype VCP Circuit Breakers.......... 2 4
9.2 Time-Current Curves .............................................. 24
Appendix A Zone Interlocking Examples..................... 28
Appendix B Troubleshooting Guide ............................ 30
Appendix C T ypical Breaker Master
Connection Diagram................................ 32
Appendix D MODBUS Translator Wiring .................... 33
Manufacturer’s Statement ............................................. 34
Effective 8/2006
Page 2
WARNING
DO NOT A TTEMPT TO INST ALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. DEA TH OR SEVERE PERSONAL INJURY CAN RESUL T FROM CONTACT WITH ENERGIZED EQUIPMENT . AL W A YS VERIFY THA T NO VOL T AGE IS PRESENT BEFORE PROCEEDING . AL W A YS FOLLOW SAFETY PROCEDURES. CUTLER-HAMMER IS NOT LIABLE FOR THE MISAPPLICA TION OR MISINST ALLA TION OF ITS PRODUCTS.
WARNING
OBSERVE ALL RECOMMENDA TIONS, NOTES, CAU­TIONS, AND W ARNINGS RELA TING TO THE SAFETY OF PERSONNEL AND EQUIPMENT. OBSERVE AND COMPL Y WITH ALL GENERAL AND LOCAL HEAL TH AND SAFETY LAWS, CODES, AND PROCEDURES.
I.L. 66A7534H04
NOTE: The recommendations and information contained herein are based on experience and judgement, but should not be considered to be all inclusive or to cover every application or circumstance which may arise.
NOTE: If you have any questions or need additional information or instructions concerning the operation or installation of this device, please contact your local representative or the Cutler Hammer Customer Support Center.
1.0 GENERAL DESCRIPTION OF DIGITRIP TRIP UNITS
The Digitrip Trip Unit is a breaker subsystem that provides the protective functions for a circuit breaker. The trip unit s are in removable housings, installed in the circuit breaker, and can be replaced or upgraded in the field by the customer.
This instruction book specifically covers the application of the Digitrip Trip Unit s (See Figure 1.1) installed in T ype VCP-T , VCP-TR, T -V AC or T -V ACR Medium V oltage Circuit Breakers.
Figure 1.1 Digitrip T rip Unit with Rating Plug
The Digitrip 520V and 520MCV trip units may be applied on both 50 and 60 Hertz systems. It detects the power and frequency and adjusts itself automatically .
The Digitrip 520V and 520MCV are self powered and self protecting trip units designed to function only with the associated CH T ype-V current sensors.
Effective 8/2006
I.L. 66A7534H04
Page 3
CAUTION
CONNECTING THIS TRIP UNIT TO CURRENT SEN­SORS OTHER THAN CH TYPE-V MIGHT DAMAGE OR DESTROY IT .
All trip unit models are microprocessor-based AC protec­tion devices that provide true RMS current sensing for the proper coordination with the thermal characteristics of conductors and equipment. The primary function of this Digitrip trip unit is circuit protection. The Digitrip analyzes the secondary current signals from the CH T ype-V current sensors and, when preset current levels and time delay settings are exceeded, will send an initiating trip signal to the Trip Actuator of the circuit breaker, causing it to “open.”
In addition to the basic protection function, the Digitrip 520V and 520MCV provide modes of trip indication such as:
Long Time trip (overload)
Short Time trip
Instantaneous trip
Ground (Earth) Fault trip
The CH T ype-V current sensors provide the power to the trip unit. As current begins to flow through the breaker , the sensors generate a secondary current which powers the trip unit. No auxilary power is needed to trip the circuit breaker.
The Digitrip 520V and 520MCV trip units have five phase and two ground (time-current) curve shaping adjustments. T o satisfy the protection needs of any specific inst allation, the exact selection of the available protection function adjustments is necessary . The short delay and ground fault pick-up adjustments can be set for either FLA T or I2t response. A pictorial representation of the applicable time­current curves for the selected protection functions is provided, for user reference, on the face of the trip unit as shown in Figure 1.1. The user chooses the settings according to the needs of his application. (See Sections
4.0 & 9.2)
Status LED will also blink at a faster rate if the Digitrip is
in a “Long Pick-up” (overload) mode. Four red LEDs on the face of the trip units flash to indicate
the cause of trip for an automatic trip operation... i.e.: Long Delay (overload), Short Delay, Inst antaneous or Ground (Earth) Fault. A battery , inside the rating plug compartment of the Digitrip unit, maintains the trip indica­tion until the Reset/Battery T est button is pushed. The battery is satisfactory if its Battery Check LED lights green when the Battery Check button is pushed (See
Section 6).
NOTE: The Digitrip unit provides all protection functions independant of the status of the battery . The battery is used only to maintain the automatic trip indication.
1.3 Installation and Removal
1.3.1 Installation of the Trip Unit
Align the Digitrip unit with the guide pins and spring clip of the circuit breaker. Press the unit into the breaker until the pins on the trip unit seat firmly into the connector housing and the unit clicks into place (see Figure 1.2).
1.3.2 Installation of the Rating Plug
Insert the rating plug into the cavity on the right-hand side of the trip unit. Carefully align the three pins on the plug with the sockets in the cavity . The plug should fit with a slight insertion force.
WARNING
DO NOT CLOSE THE CIRCUIT BREAKER WHEN THE DIGITRIP IS REMOVED OR DISCONNECTED. DAMAGE TO ASSOCIA TED CURRENT TRANSFORMERS MA Y OCCUR DUE TO AN OPEN CIRCUIT CONDITION. THERE IS NO PROTECTION FOR THE LOAD CIRCUIT .
1.1 Protection
The Digitrip trip system; including associated CH T ype-V current sensors, require no external control power to operate their protection systems. They operate from current signal levels derived through the CH Type-V current sensors.
1.2 Mode of Trip and S tatus Information
A green light emitting diode (LED), labeled Unit Status in Figure 1.1, blinks approximately once each second to indicate that the trip unit is operating normally . This Unit
Effective 8/2006
CAUTION
IF A RATING PLUG IS NOT INST ALLED IN THE TRIP UNIT, THE UNIT WILL INITIATE A TRIP WHEN IT IS ENERGIZED. IN ADDITION THE INST ANT ANEOUS LED OF THE DIGITRIP TRIP UNIT WILL LIGHT DUE TO A MISSING OR BAD RA TING PLUG .
Page 4
J3 (3 point) J4 (4 point) Connectors
Ground Alarm/Power Supply Module (520MCV option only)
Trip Actuator
Mounting Boss
Steel Mounting Plate
Guide / Rejection Pin
Digitrip 520V / 520MCV Dimple
Pin 1 Connector K2
M-4 x 80mm Mounting Screw
Rating Plug (3 Pins)
Pin 1 - Connector K1
0.045 Dia. Pin s Exiting
0.045 Dia. Pin s Exiting Digitrip Housing
Digitrip Housing
I.L. 66A7534H04
Wires with Connectors
Connector I1
Figure 1.2 Installation of the Digitrip Unit into Breaker (Side View)
CAUTION
THE M4 SCREW SHOULD BE TIGHTENED ONL Y UNTIL IT IS SNUG BECAUSE THERE IS NO STOP. DO NOT USE A LARGE SCREWDRIVER. A 1/8" (3mm) WIDE SCREWDRIVER BLADE IS ADEQUA TE.
1.3.3 Trip Unit/Rating Plug Removal
T o remove the rating plug from the trip unit, make sure the circuit breaker is open. Now open the left side of the rating plug door. Use a 1/8" (3mm) wide screwdriver to loosen and remove the M4x80mm mounting screw. Pull the rating plug from the trip unit.
T o remove the trip unit from the circuit breaker , remove the breaker cover screws using a 10mm driver. Deflect the spring clip under the trip unit to release the unit from the steel mounting plate. Pull the unit straight forward to disengage the two 9-pin connectors from the circuit breaker control circuit. (See Figure 1.2).
Spring Clip
CAUTION
DO NOT FORCE THE RATING PLUG INT O THE CA VITY . USE A 1/8" (3MM) WIDE SCREWDRIVER TO TIGHTEN THE M4 SCREW AND SECURE THE PLUG AND THE TRIP UNIT TO THE CIRCUIT BREAKER (See Figure 1.3). CLOSE THE RA TING PLUG DOOR.
Figure 1.3 Installating the Rating Plug & Mounting Screw
Effective 8/2006
I.L. 66A7534H04
Page 5
1.4 Installing the CH Type-V Current Sensors
The internal components of the circuit breaker, and how they are wired out to the breaker secondary contacts are shown in Figures 1.4, 1.5, 1.6 and 2.3. Also refer to the master connection diagram provided in Appendix C.
1.4.1 Installation Procedure
The CH T ype-V Current Sensors/Rating Plug Kit supplied with this breaker must be installed and wired by the user . The installation steps are as follows:
a. PRIMARY - Mount one CH T ype-V current sensor on the insulated bushing behind the circuit breaker . The bushing must be rated for the system Lightning Impulse Withstand Volt age (LIWV), and the ground (earth) shield terminal or ground (earth) shield surface must be connected to the ground (earth) bus. Confirm that the polarity mark (red dot) on the front of the current sensor faces the circuit breaker.
b. SECONDARY - Connect secondary terminals of the current sensor to the correct terminals in the switchgear control circuit using #14 A WG T ype SIS wire. Terminal X1 is the one nearest to the polarity mark. Refer to Appendix C for distinction between Fixed and Drawout variations. Consult manufacturer if length of wire to device exceeds 12 feet (3.7m).
c. Use ring terminals on current sensor terminals. Use AMP #66598-2 female sockets to connect to breaker’s secondary connector.
d. Ground (Earth) the non polarity terminal of each sensor. Also Ground the bushing shield surfaces.
circuit breaker when functional protection settings are exceeded.
If the CH T ype-V current sensors and circuit breaker enclosure label are changed to a different ratio, the rating plug must also be changed. The associated rating plug must match the current sensors installed and as specified on the circuit breaker enclosure label. Refer to Figure 2.3 for CH T ype-V current sensors available.
1.5 Plexiglass Cover
A clear , tamper-proof, plexiglass door sits on the breaker cover. This door allows the settings to be viewed but not changed, except by authorized personnel. The plexiglass cover meets applicable tamper-proof requirements. The cover is held in place by two screws. Security is insured by the insertion of a standard meter seal through the holes in both of the cover retention screws. The plexiglass cover has an access hole for the Reset/Battery T est push button.
1.6 Ground Alarm/Power Supply Module (520MCV Models Only)
The Ground Alarm/Power Supply Module (See Figure 1.7) is a required accessory to enable communications on the Digitrip 520MCV model. The module can be installed beneath the metal mounting plate of the trip unit in the Magnum Circuit Breaker. The module covers the following input voltage ratings: 120 V AC (7802C83G1 1), 230 V AC (7802C83G12), 24-48 VDC (7802C82G12) and 125VDC (7802C8213). The burden of the Power/Relay Module is 10VA.
e. Install rating plug into the Digitrip 520V and 520MCV trip units for the matching CH T ype-V current sensors. Also attach the additional rating plug label to the circuit breaker enclosure as a future reference indicating which CH T ype-V current sensors used in this application.
1.4.2 CH Type-V Current Sensor Functionality
The three CH Type-V current sensors are inst alled external to the circuit breaker over the main circuit conductors by means of bushings equipped with a ground shield. The current sensor rating defines the breaker rating (In)... i.e. 1200A:1A sensors are used on a 1200A rated breaker . There are four auxiliary current transformers with a ratio of 10:1 which further step down the rated current to 100 milli­amperes, which is equivalent to 100% (In) to the Digitrip.
The primary current sensors produce an output signal proportional to the load current and furnish the Digitrip trip units with the information and energy required to trip the
Effective 8/2006
Figure 1.4 CH T ype-V Current Sensor Installation
Page 6
I.L. 66A7534H04
Figure 1.5 Secondary Block “A” Connections
Figure 1.6 Secondary Block “B” Connections
Effective 8/2006
I.L. 66A7534H04
1.6.1 Auxiliary Power
When the module is wired as shown in Figure 1.8, it will provide an auxiliary power supply so that the 520MCV liquid crystal display (LCD) will be functional even when the circuit breaker has no load. A Digitrip 520MCV tripunit without auxiliary power will not display data until load current reaches approximately 30% 1 phase or 10% 3 phase of the (In) rating.
1.6.2 Ground Alarm
A second function of the module is to provide either a ground trip or ground alarm only output contact via the relay supplied in the module. An LED on the front of the unit also provides an indication of ground fault trip.
1.6.3 Ground Fault Trip
When the Ground Alarm/Power Supply module is used, this unit will provide ground fault trip contacts when the circuit breaker trips on a ground fault. You must then push the Reset button on the Digitrip in order to reset the contacts (See Figure 1.8, Note 3).
Page 7
1.6.4 Ground Fault Alarm
A ground fault alarm alerts a user to a ground fault condi­tion without tripping the circuit breaker. A red Alarm Only LED on the front of the trip unit will indicate the presence of a ground fault condition that exceeds the programmed setting.
The ground fault alarm relay is energized when the ground current continuously exceeds the ground fault pickup setting for a time in excess of a 0.1 second delay . The alarm relay will reset automatically if the ground current is less than the ground fault pickup (See Figure 1.8, Note 4).
1.7 Display Feature (520MCV only)
The Digitrip 520MCV model has a user interface in addition to the green and red LED trip indicators. This seven element display performs a metering function and can be used to monitor load currents.
When the Step button on the face of the trip unit is pressed and released, the display will show PH 1, for Phase 1 or A, and the current value. If the S tep button is not pressed again, the display will continue to show the current value for Phase 1. Each time that the Step button is pressed, the next monitored function will be displayed. The other real time readings can be displayed in the following sequence:
Figure 1.7 Ground Alarm/Power Supply Module for the
520MCV T rip Unit
PH 2 Phase 2 (B) PH 3 Phase 3 (C) PH 4 Neutral PH 5 Ground H I Highest phase current OL Overload (Digitrip in overload mode)
Pushing the Step button while the unit is in the OL mode will have the unit again display the overload current value.
HELP This message can indicate more than one problem
with the trip unit. If the rating plug is missing, a HELP message and an Instantaneous trip LED light will be observed. The rating plug needs to be installed and the Instantaneous trip LED must be cleared by pressing the Reset/Battery Test button.
Effective 8/2006
Page 8
I.L. 66A7534H04
This message could also indicate that the trip unit is out of calibration and should be replaced at the earliest opportunity .
Ground
Control V oltage
2
3
Fault Trip
Remote
A-10
J3-3
J3-2
Output -
J3-1
G-Alarm
Ground Alarm / Power Supply Module
K2-3
K2-1
K2-6
G-ALM 1
Output +
1
Ground Fault Alarm
A14
A-11
J4-4
J4-3
J4-2
ATR V o lt.
G-ALM 2
Digitrip 520MCV
1.8 UL, CSA and CE Recognition
The Digitrip 520V and 520MCV Trip Units are a UL
®
(Underwriters Laboratories, Inc.) Recognized Component under File E146559 for use in Type VCP-T, VCP-TR and Type T-V AC, T-V ACR Medium V oltage Circuit Breakers. They have also been tested by the Canadian Standards Association (CSA).
This Digitrip 520V and 520MCV have also passed the IEC 947-2 test program which includes radiated and conducted
A-15
J4-1
ATR CO M
emissions testing. As a result, all units carry the CE mark.
Co ntact Ra ting (r esist ive lo a d)
1
AC 0.5A @ 230VAC
Available
Input Voltages
120 VAC 230 VAC
24-48 VDC
125 VDC
Style
Number 7802C83G01 7802C83G02
7802C82G02
7802C82G02
7802C82G03
2
AC 1A @ 120VAC DC 1A @ 48VDC DC 0.35A@ 125VDC
Verify input voltage rating before energizing circuit.
2
When used in conjunction with a T. U. Cat .
3
5ARMVLSIG will indicate GF trip.
Figure 1.8 Wiring Diagram for 520MCV with Ground Alarm/Power Supply Module
In addition, the Digitrip 520MCV will display and freeze the magnitude of the trip value after a trip event if auxilary power is available. Use the Step pushbutton to view each phase value. The highest value that can be presented is
9999. Any fault current s greater than this value will be shown as “HI.” Pushing the Reset pushbutton will clear this data.
Also related to the phase value after a trip event are four dashes “----”. This message means that the microproces­sor could not complete its writing of the trip event’s magnitude into its non volatile memory . A possible cause of this would be the lack or loss of auxilary power during the trip event.
2.0 GENERAL DESCRIPTION of VCP-T, VCP-TR or T-V AC, T -V ACR CIRCUIT BREAKERS
2.1 General
The circuit breakers are tripped automatically on overload and fault current conditions by the combined action of three components:
1. The sensors, which measure the current level
2. The Digitrip Trip Unit, which provides a tripping signal to the Trip Actuator , when current and time delay settings are exceeded.
3. The low-energy T rip Actuator , which actually trips the circuit breaker.
This arrangement provides a very flexible system, covering a wide range of tripping characteristics described by the time-current curves referenced in Section 9.2.
Effective 8/2006
I.L. 66A7534H04
Page 9
2.2 Low-Energy Trip Actuator
The mechanical force required to initiate the tripping action of the circuit breaker is provided by a special low-energy Trip Actuator . This device is located behind the molded platform on which the Digitrip units are supported. (See Figure 1.2) The T rip Actuator cont ains a permanent magnet assembly , moving and stationary core assemblies, a spring, and a coil. Nominal coil resistance is 25 ohms and the black lead is positive. The circuit breaker mechanism automatically resets the T rip Actuator each time the circuit breaker opens.
When the T rip Actuator is reset by the operating mecha­nism, the moving core assembly is held in readiness against the force of the compressed spring by the perma­nent magnet. When a tripping action is initiated, the low­energy T rip Actuator coil receives a tripping pulse from the Digitrip trip unit. This pulse overcomes the holding effect of the permanent magnet, and the moving core is released to upset the trip latch of the circuit breaker mechanism.
2.3 Ground Fault Protection
2.3.2 Zero Sequence Sensing
Zero Sequence Sensing, also referred to as vectorial summation, is applicable to mains, feeders, and special schemes involving zone protection. An optional CH Type-V Zero Sequence current transformer (See Figure 2.1), having taps for 100A and 200A ratings is available for this application. The torroidal sensor has a 4.8” I.D. (12.192cm) with a 7.6” O.D. (19.304cm). Its style number 69C3016G01. (See Figure 2.3 and Appendix C)
2.3.1 General
When employing a ground fault scheme, the distribution system characteristics (i.e. system grounding, number of sources, number and location of ground points, etc.) must be considered along with the manner and location in which the circuit breaker is applied to the system. These ele­ments are discussed in Sections 2.3.2 through 2.3.4.
The Digitrip uses two modes of sensing to detect ground fault currents: residual and zero sequence (See T able 2.1). The breaker’s secondary contact inputs B-6, B-7, that were shown in Figure 1.6, are used to configure the breaker cell positions for the two schemes. Having no jumper from B-6 to B-7 programs the unit for a residual ground fault scheme, while installing a jumper from B-6 to B-7 programs the unit for zero sequence configuration. If present, this jumper resides on the stationary side of the switchgear assembly . The proper current sensor input is required on the external sensor input terminals B-4, B-5 of the breaker secondary contacts.
Ground (Earth)
Fault
Sensing Method
Residual No Jumper 2.2 element R5 Zero Sequence Jumper B6 to B7 2.3 element R4
Breaker Se condary
Contacts Req’d Figure
Ref
Digitrip GF
Sensing
Element Used
Figure 2.1 Zero Sequence Current T ransformer
2.3.3 Residual Sensing
Residual is the standard operating mode of ground fault sensing. This mode utilizes one current sensor on each phase conductor (See Figure 2.2). If the system neutral is grounded, but no phase to neutral loads are used, the Digitrip includes all of the components necessary for ground fault protection. This mode of sensing vectorily sums the outputs of the three or four individual CH T ype-V current sensors. Residual ground fault sensing features are adaptable to main and feeder breaker applications.
T able 2.1 Digitrip Sensing Modes
Effective 8/2006
Page 10
A
A
A
I.L. 66A7534H04
2.3.4 Ground Fault Settings
The adjustment of the ground fault functional settings (FLA T response or I
2
t) is discussed in Section 4.8. The effect of these settings is illustrated in the ground fault time-current curve referenced in Section 9. The residual ground fault pick-up settings are from 0.25x, 0.3x, 0.35x,
0.4x, 0.5x, 0.6x, 0.75x and OFF.
Source
L
A
L
B
L
C
CAUTION
IF THE PHASE CONNECTIONS ARE INCORRECT , A NUISANCE TRIP MA Y OCCUR. ALW A YS OBSER VE THE POLARITY MARKINGS ON THE INST ALLA TION DRA W­INGS. TO INSURE CORRECT GROUND F AUL T EQUIP­MENT PERFORMANCE, CONDUCT FIELD TESTS TO INSURE PROPER GROUND F AULT FUNCTIONALITY.
Black
K1-2 K1-3
Digitrip 520V
or 520MCV
Trip Actuator
+
-
10:1
K1-9
K1-8 K1-7
1
K1-6
R/1
A-4
-19
A-5
-20
CSA1
CSA2
CSB1
CSB2
K1-5
R/1
A-6
-21
B-5 B-4
CSC1
CSC2 X1
X2
K1-4 K2-9
K2-8
10:1 AUX. CT
Load
Notes:
1
In this scheme, all breaker secondary currents (at the 100 mA level) are summed together at the PC board donut transformer to sense ground fault via element R5.
2
Do not jumper secondary contacts B-6, B-7. This will defeat the residual ground fault protection.
R5
Figure 2.2 Breaker Using Residual GF Sensing
Effective 8/2006
I.L. 66A7534H04
A
B
C
100A 69C3011H01 3.42 5.35 1.55
2 X
17
1:1
0
0
200A 3.42 5.35 1.55
1
7
1
: 2
0
0
250A 3.42 5.35 1.55
1
8
1
: 2
5
0
300A 3.42 5.35 1.55
1
8
1
: 3
0
0
400A 3.42 5.35 1.55
1
7
1
: 4
0
0
600A 3.42 5.35 1.55
1
8
1
: 6
0
0
630A 3.42 5.35 1.55
1
8
1:
6
3
0
800A 3.42 5.35 1.55
1
9
1
:
80
0
1000A 3.42 5.35 1.55
1
9
1
:10
0
0
1200A 3.42 5.35 1.55
1
9
1
:12
0
0
1250A 3.42 5.35 1.55
1
9
1
:12
5
0
1600A 2000A
3.42
3.42
5.35
5.35
1.55
1.55
2
0
2
1
1:1
600
1
:
20
0
0
3.0
6
1.1
7
4
.67
7
.25
2
.
2
9
2.9
3
1
.
871
.
2
1
0.4
7
0.6
10.
5
6
0
.
310
.
0
9
R
d
c
(O
h
m
s +
/
-
1
5
%
)
RAT
I
O
W
IRE
G
A
U
G
E
C (max)B (max)A (min )DESCRIPTION
POLARITY MARK SECONDARY “X1
L
A
B
E
L
2
.
0
0.7
5
LA
B
EL
INF
O
R
M
A
TIO
N
:
CU
TLE
R-H
A
M
M
E
R P
A
R
T N
U
M
BER
RA
T
ING
C-
H
Ty
p
e
V
C
U
R
REN
T S
E
N
S
O
R
DA
T
E C
O
D
E (
YR
M
O
D
Y L
O
C
)
69C3011H02
69C3011H2 5 69C3011H03 69C3011H04
69C3011H06
69C3011H63
69C3011H08
69C3011H10
69C3011H12 69C3011H13
69C3011H16 69C3011H20
2 x 10-32 Bra ss
Slot Head Terminal Screws
POLARITY MARK PRIMARY “H1”
2500A
6
9C3
0
1
1
H
5
2
3.4
2
5.35 1. 55
1
: 2
5
0
0
8.9021
Page 11
R/1
R/1
Figure 2.3 Zero Sequence Sensing Scheme
Figure 2.4 Digitrip Phase Sensor (CH T ype-V)
Effective 8/2006
Loading...
+ 23 hidden pages