Installation Instructions for D65C Series
Current Monitoring Relays
Installation and Wiring
Please refer to the diagrams below for information on installing & wiring this unit.
Without External CT
M
M
Control
Voltage
Typical Installation without
Current
Monitor
Relay
External CT
Motor
M
Typical Installation with
External CT
Monitored
Current
Wiring for 8-Pin
(L1)
4
3
2
1
Socket
5
8
Input
Voltage
(L2)
6
7
IL04914002E
Monitored
Current
6
75
48
39
210
1
11
(L1) (L2)
Wiring for 11-Pin
Socket
Figure 1.
Wiring Diagrams
Product Setup
Refer to the appropriate series below for information on how to set up the product:
D65CE Series
Adjust the pick-up setting between the MIN & MAX values of the monitored current range of the unit.
The drop-out setting is fixed at 95% of the pick-up setting. The LED is Green when input voltage is
applied. The relay energizes (and the LED is Red) when the monitored current is above the pick-up setting. The relay de-energizes (and the LED is Green) when the monitored current is below the drop-out
setting & input voltage remains.
D65CEK Series
Adjust the pick-up setting between the MIN & MAX values of the monitored current range of the unit.
Then adjust the drop-out setting between 50 & 95% of the pick-up setting. The LED is Green when
input voltage is applied. The relay energizes (and the LED is Red) when the monitored current is above
the pick-up setting. The relay de-energizes (and the LED is Green) when the monitored current is
below the drop-out setting & input voltage remains.
Pick-Up
Monitored
Current
Input
Power
(Voltage)
Relay
Output
Figure 2.
Standard Current Monitoring
D65CH Series
Adjust the pick-up setting between the MIN & MAX values of the monitored current range of the unit.
The drop-out setting is fixed at 95% of the pick-up setting. Set the time delay on pick-up between 0.1 &
10 seconds. The LED is Green when input voltage is applied. The relay energizes (and the LED is Red)
when the monitored current is above the pick-up setting for a period longer than the set time delay.
The relay de-energizes (and the LED is Green) when the monitored current is below the drop-out
setting & input voltage remains.
Current
Drop-Out
Current
On
Off
On
Off
Effective 04/09 1

Monitored
Current
Pick-Up
Current
Drop-Out
Current
IL04914002E
On
Off
On
Off
TT
Figure 3.
Input
Power
(Voltage)
Relay
Output
Overcurrent Monitoring
D65CHK Series
Adjust the pick-up setting between the MIN & MAX values of the monitored current range of the unit.
Then adjust the drop-out setting between 50 & 95% of the pick-up setting. Set the time delay on pickup between 0.1 & 10 seconds. The LED is Green when input voltage is applied. The relay energizes
(and the LED is Red) when the monitored current is above the pick-up setting for a period longer than
the set time delay. The relay de-energizes (and the LED is Green) when the monitored current is below
the drop-out setting & input voltage remains.
D65CL Series
Adjust the drop-out setting between the MIN & MAX values of the monitored current range of the unit.
The pick-up setting is fixed at +5% of the selected drop-out setting. Set the time delay on drop-out
between 0.1 & 10 seconds. The LED is Green when input voltage is applied. The relay energizes (and
the LED is Red) when the monitored current is above the pick-up. The relay de-energizes (and the LED
is Green) when the monitored current is below the drop-out setting for a period longer than the set
time delay & input voltage remains.
Pick-Up
Current
Drop-Out
Current
On
Off
On
Off
T
Figure 4.
Monitored
Current
Input
Power
(Voltage)
Relay
Output
Undercurrent Monitoring
Troubleshooting
If the unit fails to operate properly, check that all connections are correct per the appropriate wiring
diagram. If problems continue, contact EATON TRC 1-800-809-2772 for assistance.
Effective 04/09 2