Disclaimer of Warranties and Limitation of Liability
The information, recommendations, descriptions and safety notations in this document are
based on Eaton Corporation’s (“Eaton”) experience and judgment and may not cover all
contingencies. If further information is required, an Eaton sales office should be consulted.
Sale of the product shown in this literature is subject to the terms and conditions outlined in
appropriate Eaton selling policies or other contractual agreement between Eaton and the
purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR
IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING
CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE
OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME
PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including
negligence), strict liability or otherwise for any special, indirect, incidental or consequential
damage or loss whatsoever, including but not limited to damage or loss of use of equipment,
plant or power system, cost of capital, loss of power, additional expenses in the use of
existing power facilities, or claims against the purchaser or user by its customers resulting
from the use of the information, recommendations and descriptions contained herein. The
information contained in this manual is subject to change without notice.
Cover Photo: C441 PROFIBUS Module.
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.comi
C441 PROFIBUS Module User Manual
Support Services
The goal of Eaton is to ensure your greatest possible satisfaction with the operation of our
products. We are dedicated to providing fast, friendly, and accurate assistance. That is why
we offer you so many ways to get the support you need. Whether it’s by phone, fax, or email,
you can access Eaton’s support information 24 hours a day, seven days a week. Our wide
range of services is listed below.
You should contact your local distributor for product pricing, availability, ordering, expediting,
and repairs.
Website
Use the Eaton website to find product information. You can also find information on local
distributors or Eaton’s sales offices.
Website Address
www.eaton.com/electrical
EatonCare Customer Support Center
Call the EatonCare Support Center if you need assistance with placing an order, stock
availability or proof of shipment, expediting an existing order, emergency shipments,
product price information, returns other than warranty returns, and information on local
distributors or sales offices.
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.comv
C441 PROFIBUS Module User Manual
WARNING
WARNING
CAUTION
WARNING
Safety
Definitions and Symbols
This symbol indicates high voltage. It calls your attention
to items or operations that could be dangerous to you
and other persons operating this equipment. Read the
message and follow the instructions carefully.
This symbol is the “Safety Alert Symbol.” It occurs with
either of two signal words: CAUTION or WARNING, as
described below.
Indicates a potentially hazardous situation which, if not
avoided, can result in serious injury or death.
Indicates a potentially hazardous situation which, if not
avoided, can result in minor to moderate injury, or serious
damage to the product. The situation described in the
CAUTION may, if not avoided, lead to serious results.
Important safety measures are described in CAUTION (as
well as WARNING).
Warnings and Cautions
This manual contains clearly marked cautions and warnings
which are intended for your personal safety and to avoid any
unintentional damage to the product or connected
appliances.
Please read the information included in cautions and
warnings carefully.
Hazardous High Voltage
Motor control equipment and electronic controllers are
connected to hazardous line voltages. When servicing
drives and electronic controllers, there may be exposed
components with housings or protrusions at or above
line potential. Extreme care should be taken to protect
against shock.
Stand on an insulating pad and make it a habit to use only
one hand when checking components. Always work with
another person in case an emergency occurs. Disconnect
power before checking controllers or performing
maintenance. Be sure equipment is properly grounded. Wear
safety glasses whenever working on electronic controllers or
rotating machinery.
viC441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Overview
Overview
The C441 PROFIBUS communication adapter is a DPV0
slave device used to connect the C441 Motor Insight
®
and
C440 protective relay and S611 and S811+ soft starters to a
PROFIBUS network. The C441Q/S PROFIBUS adapter
connects to the side of the Motor Insight and the S611 soft
starter, and allows the user to access setup parameters and
IO data of the Motor Insight and the S611 over a PROFIBUS
network.
The C441QS/SS is a stand-alone PROFIBUS adapter that
connects to the C440, S611 and S811+ via hardwired
connections (DO/DI) and allows the user to access setup
parameters and IO data of the C440, S611 and S811+ over
a PROFIBUS network.
The C441QS/SS can also be used as a 4 digital input, 2 relay
output stand-alone IO module on a PROFIBUS network.
The C441 PROFIBUS communication adapters provide the
user with the ability to:
●
Configure C441 Motor Insight, C440 OL relay, S611 and
S811+ soft starter and stand-alone IO setup parameters
over a PROFIBUS network
●
Create custom IO assemblies based upon their
applications needs
●
Exchange IO between a master and slave over a
PROFIBUS network
●
Read out diagnostic information concerning the health
of the devices connected to the C441 PROFIBUS
interface modules
Surge (IEC61000-4-5)±2 kV Line to PE and ±1 kV Line-to-Line
RF Conducted (IEC61000-4-6)10 V, 0.15–100 MHz
Magnetic Field (IEC61000-4-8)DNA
Voltage Dips (IEC61000-4-11)DNA
Protection Degree (IEC60947-1)IP20
CE (Low Voltage Directive, EMC Directive)
C-TICK
EN 55011 Class A
80% amplitude modulation at 1 kHz
±1 kV communications
Table 8. Input Power Supply Requirements
Electrical/EMCRating
Voltage Range18–30 Vdc
Current Draw (Maximum)30 mA
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com3
Ratings
WARNING
Table 9. Material Requirement
DescriptionRequirement
Certification of Compliance to
the EU Directive 2011/65/EU
(RoHS 2.0)
ReachYes
PCB LaminateManufactured by a UL Recognized
Yes
(ZPMV2) printed wiring board
manufacturer, which meets the
requirements in UL 508, paras. 15.1, 15.3,
36.12, & 39.4(b). CB to be marked with
Vendor UL-ID code, Vendor Date Code,
material, flammability rating. Polarized
components shall be marked so polarity
can be verified after assembly
The C441Q and C441QS provide connection for four
AC input points. The ratings for these inputs are:
Table 10. 120 Vac Input Specification
SpecificationValue
Number of Inputs4
Voltage Category120 Vac
Operating Range80–140 Vac
Operating Frequency50/60 Hz
Signal Delay Max30 ms
Off State Voltage0–30 Vac
On State Voltage79–140 Vac
On State Current Max15 mA
SupplyExternal Supply
The C441S and C441SS provide connection for four DC input
points. The ratings for these inputs are:
Table 11. 24 Vdc Input Specification
SpecificationValue
Number of Inputs4
Supply Voltage24 Vdc
TypeCurrent Sinking
On State Voltage15–30 Vdc
Steady State Current Max15 mA
Off State Voltage0–5 Vdc
24 Vdc source current limit50 mA
Isolation Voltage250 Vac
The C441Q, C441S, C441QS and C441SS provide two
output relays. The ratings of the relay outputs are:
Table 12. Relay Specification
SpecificationValue
Number of Contacts2 independent relays
Thermal Contact5 A
Rated Insulation Voltage300 Vac
Operating Voltage240 Vac
Operating AC Current (Rated)3 A at 120 Vac; 1.5 A at 240 Vac
Operating DC Current (Rated)0.24 A at 110 Vdc, 0.1 A at 220 Vdc
Min Operating Current10 mA at 5 Vdc
Resistive Load Rating5 A at 240 Vac, 5 A at 30 Vdc
Inductive Loading2 A at 240 Vac, 2 A at 30 Vdc
(one Form A, one Form C)
Table 13. Pilot Duty Relay Requirements
SpecificationValue
Pilot Duty RatingB300
Thermal Continuous Test Current 5 A
Maximum Current
(120 Vac)—Make/Break
Maximum Current
(240 Vac)—Make/Break
Max VA (Volt-Amperes)—
Make/Break
30 A / 3 A
15 A / 1.5 A
3600 VA / 360 VA
Note: Any UL Listed power supply with an isolated 24 Vdc
voltage output can be used provided that a UL listed
or recognized fuse rated no more then 4 A maximum
is installed.
Only apply 24 Vdc to the C441 communication module
power supply connector. use of any other voltage may
result in personal injury, property damage and damage
to the module.
4C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Mounting and Dimensions
C441Q and C441S
Mounting
The C441 PROFIBUS adapters are designed to be installed
on the right side of the Motor Insight base unit or the S611.
Figure 1. Installation Diagram
Mounting and Dimensions
1.Align module with side of Motor Insight base unit or
the S611.
2.Slide module bottom pegs into appropriate slots.
3.Rotate module up and gently click the base unit and
module together.
4.Connect 24 Vdc power, PROFIBUS cable, and IO
connector if desired.
Note: For S611 Soft Starter applications, it is recommended
to mount a C441QS or C441SS module beside the
S611 and wire the D0/D1 terminals between the two
devices. More information on this is provided later in
this document.
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com5
Mounting and Dimensions
Dimensions
Figure 2. C441Q and C441S Product Dimensions (Attached to C441 Base Unit)
6C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Mounting
C441QS and C441SS
The modules are designed to be installed on the DIN rail or
panel surface by screw. Screw fixing dimensions reference
below.
Figure 3. Mounting of Stand-Alone Model
Mounting and Dimensions
DIN rail width is 35 mm.
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com7
Mounting and Dimensions
Dimensions
Figure 4. Stand-Alone Dimensions
8C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Connections and Switch Settings
C441QS/SS
1 — 5
2 — 4
4 — 2
5 — 1
C441QS/SS
Connections and Switch Settings
Connecting the C441, C440, S611 and S811+
to a PROFIBUS Network
Connecting a C441Q/C441S to a C441 Motor
Insight or S611 Soft Starter
The C441Q and the C441S modules connect to the C441
Motor Insight and S611 Soft Starter by plugging these
PROFIBUS modules into the side of the C441 Motor Insight
and S611. As an option, the C441QS and C441SS may also
be wired to the S611 soft starter via the DO/DI terminals on
each product as shown below.
Connecting a C441QS/C441SS to a C440 Overload,
S611 Soft Starter or S811+ Soft Starter
The C441QS/SS modules communicate to the C440, S611
and S811+ by wiring the D0 terminal on the C441QS/SS to
the D0 terminal on the C440, S611 and S811+ and the D1
terminal on the C441QS/SS to the D1 terminal on the C440,
S611 and S811+. The C440 requires a C440-XCOM to be
added to the C440 per the following. The D0/D1 terminals for
the C440 are on the C440-XCOM module. All the other
devices listed above have D0/D1 terminals on a connector
directly attached to each product.
Figure 5. C440 to a C441QS/SS
S811+ to the C441QS/SS
The D0/D1 terminals are on a separate terminal strip from
where the 24 Vdc terminals are located on the S811+.
Connect D0 on the S811+ to D0 on the C441QS/SS and D1
on the S811+ to D1 on the C441QS/SS.
PROFIBUS Connection
The PROFIBUS port uses the standard DB9 PROFIBUS
connection. Refer to the figure below for details on the pin
out of this connector.
Figure 7. Pin Out for PROFIBUS DB9
24 Vdc Power
The C441 PROFIBUS adapter is powered from an external
24 Vdc supply wired into the 5-pin black header (J2) located
on the top of the adapter next to the 8 pos DIP switch.
Note: Connections to pins 2 and 4 for the C441Q/S modules
are only required if Modbus communications are to be
implemented.
Connections to pins 2 and 4 for the C441QS/SS are
the required communication connections to interface
the C440, S611 and S811+ devices to a PROFIBUS
network.
Figure 6. S611 to a C441QS/SS
Table 14. 24 Vdc Supply Connection
Pin #CircuitDescription
1Common24 Vdc common input connection
2D1Transceiver terminal 1, V1 Voltage, Data + (V1 > V0
for binary 1 [OFF] state)
Connection for Remote Modbus Port
for binary 0 [ON] state)
Connection for Remote Modbus Port
5+24 Vdc+24 Vdc supply input connection
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com9
Connections and Switch Settings
Notice
Notice
Figure 8. Power and Modbus RS-485 Connections
Setting the PROFIBUS Address
PROFIBUS Address
The PROFIBUS address is set using the DIP switches
located on the top of the C441 communication adapter. The
address can only be set with the hardware DIP switches. The
address is in binary with the major units numbered to the
right of the switch on the label. Adding up the major units set
to ON will provide the address of the adapter on the
PROFIBUS network.
Table 15. PROFIBUS DIP Switch Settings
DIP SwitchValue
764
632
516
48
34
22
11
The address specified in the switches is only used by the
adapter at the time the adapter is powered on. Changing
these switches during operation will have no affect until the
next power cycle or reset.
A PROFIBUS address setting of 0 will result in the C441
using the default Station Address of 125. Any PROFIBUS
Station Address setting greater than 125 will result in the
C441 using the default Station Address of 125.
Example: To set a MAC ID of 25, DIP switches 5, 4, and 1
need to be turned ON, with all others OFF.
10C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Connections and Switch Settings
Pin 1
Pin 12
NET
24 Vdc
+
-
+
I1
I2
I3
I4
C
NO
NO
NC
I1
I2
I3
I4
C
C
Q1
NO
Pin 1
24 Vdc
Pin 12
NET
+
-
+
0V
+
-
24
Example: Isolated 24 Vdc Input Source
- The inputs must be supplied by an
external power source.
- Do not connect the external supply to
terminals 0V and 24.
- Connect isolated power source between
C and Inputs.
Example: Non-Isolated 24 Vdc Input Source
- Input source power is taken from the 5-pin
connector.
- Connect C and 0V together.
- Use 24 to source inputs.
24 Vdc
24 Vdc
I/O Power
AC/DC
AC/DC
24 Vdc
AC/DC
AC/DC
C
Q1
Q2
Q2
I1
I2
I3
I4
C
NO
NO
NC
I1
I2
I3
I4
C
C
Q1
NO
0V
+
-
24
C
Q1
Q2
Q2
Power and I/O Wiring Diagrams for the C441Q
and C441S Modules
The C441Q module contains four 24 Vdc inputs and two
relay outputs. The two relay outputs provided are one
form A (NO) and one form C (NO, NC).
Figure 9. C441Q: 24 Vdc Wiring Diagram
24 Vdc Inputs
The 24 Vdc input circuit is capable of both isolated and
unisolated behavior. The isolated inputs share a single
common tie point. A 24 Vdc current limited source/ground is
provided in the situations that require locally supplied input
signal voltage. To use the unisolated inputs, tie the 24 Vdc
ground/common to the isolated common.
Note: Do not connect a 24 Vdc source to pins 6 and 7. The
“I/O Power: 24 Vdc” is to be used only in conjunction
with the inputs. It is a 24 Vdc output intended to only
supply signal power for the inputs. When using the
24 Vdc input supply, pin 6 should only be connected to
pin 5 (24 Vdc input supply common to input common).
See example wiring diagram above. Any device using
the provided 24 Vdc input supply must have 500 V
isolation from ground. Example devices include
pushbuttons and auxiliary contacts.
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com11
Connections and Switch Settings
Example 120 Vac IO Module
- All inputs are isolated.
- All Common terminals are connected
together internally.
AC/DC
AC/DC
120 Vac
Pin 1
Pin 12
NET
24 Vdc
+
-
I1
I2
I3
I4
C
C
C
NO
NO
NO
C
NC
I1
I2
I3
I4
C
C
C
Q1
Q1
Q2
C
Q2
The C441S module contains four 120 Vac inputs and two
relay outputs. The two relay outputs provided are one
form A (NO) and one form C (NO, NC).
Figure 10. C441S: 120 Vac Wiring Diagram
12C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Connections and Switch Settings
D0D1
To C440, S611
or S811+
D0D1
To C440, S611
or S811+
Example: Non-isolating
24 Vdc input source
- Input source power is taken
from 5-pin connector
- Connect C and OV together
- Use 24 to source inputs
24 Vdc
24 Vdc
I/O power
Pin 1
Pin 12
AC/DC
AC/DC
I1
I2
I3
I4
C
OV
24
NO
NO
NO
C
NC
I1
I2
I3
I4
C
–
+
Q1
Q1
Q2
C
Q2
Example: Isolated 24 Vdc input source
- The inputs must be supplied
by an external power source
- Do not connect the external
supply to terminals OV and 24
- Connect isolated power source
between C and inputs
24 Vdc
24 Vdc
I/O power
Pin 1
Pin 12
AC/DC
AC/DC
I1
I2
I3
I4
C
OV
24
NO
NO
NO
C
NC
I1
I2
I3
I4
C
–
+
Q1
Q1
Q2
C
Q2
24 Vdc
Power and I/O Wiring Diagrams for the
C441QS and C441SS Modules
The C441QS module contains four 24 Vdc inputs and two
relay outputs. The two relay outputs provided are one
form A (NO) and one form C (NO, NC).
Figure 11. C441QS—24 Vdc Input Specification
24 Vdc Inputs
The 24 Vdc input circuit is capable of both isolated and
unisolated behavior. The isolated inputs share a single
common tie point. A 24 Vdc current limited source/ground is
provided in the situations that require locally supplied input
signal voltage. To use the unisolated inputs, tie the 24 Vdc
ground/common to the isolated common.
The C441SS module contains four 120 Vac inputs and two
relay outputs. The two relay outputs provided are one
form A (NO) and one form C (NO, NC).
Figure 12. C441SS—120 Vac Input Specification
Example: 120 Vac IO module
- All inputs are isolated
- All common terminals are
connected together internally
Pin 1
120 Vac
NO
AC/DC
NO
NO
NC
AC/DC
Pin 12
I1
I2
I3
I4
C
C
C
C
24 Vdc
D0D1
To C440, S611
or S811+
I1
I2
I3
I4
C
C
C
Q1
Q1
Q2
C
Q2
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com13
Connections and Switch Settings
PROFIBUS Status Indicators
PROFIBUS Status LEDs
There are three LED indicators (ON, BF, and SF) to clarify the working state
of the PROFIBUS module/network.
Table 16. PROFIBUS Status LEDs
ON (GREEN,
the left one)
ONOFFOFFEverything OK
ONONOFFNo communication
ONBlinkingOFFCommunication, but not in data exchange
ONONONConfiguration not OK
BF (RED,
the middle one)
SF (RED,
the right one)
Fault
Condition
Connecting and Disconnecting a C441
PROFIBUS Module from the C440, C441, S611,
S811+ or as a Stand-Alone I/O Module
A C441 PROFIBUS module will work with whatever device it
is connected to out-of-box, C440, C441, S611, S811+ or as a
stand-alone I/O module.
If a C441 PROFIBUS module has previously been connected
to one device type and then needs to be connected to
another device type, the following procedure must be
performed.
1.Disconnect the C441 PROFIBUS module from the
existing device.
2.Set the DIP switches on the C441 PROFIBUS module to
a value of three per Figure 13.
3.Toggle the top switch shown in Figure 13 5times
(off-on-off is one cycle). A reset will occur after the fifth
cycle indicated by all LEDs turning ON, then OFF again.
Turn power off to the module.
4.Connect the C441 PROFIBUS module to the new device
or use it as a stand-alone I/O module. When it is
powered up again, it will begin working with the new
device or as a stand-alone I/O module.
Figure 13. DIP Switch Service 3 Example
14C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Configuration Using the PROFIBUS Configuration File
Notice
Configuration Using the PROFIBUS Configuration File
The C441 PROFIBUS adapters give the user the ability to
enable/disable protections, set up trip thresholds, set up trip
delays, and reset delays for the C441 Motor Insight relay, the
C440 Overload relay, the S611 Soft Starter and the S811+
Soft Starter over a PROFIBUS network.
Upon reception of the parameterization telegram, device
parameter data is range checked. If the data is outside the
range specified in the GSD file, the parameterization will be
rejected and parameterization will fail. Data for parameters
such as Overload FLA, Low kW Trip Level, High kW Trip
Level, and GND Fault Trip Level whose ranges vary based on
model will be “adjusted.” If the value is greater than the
maximum allowed value, the parameter is set to its
maximum value. Likewise, if a parameter is set to a value
less than its minimum value, the parameter will be set to its
minimum value.
Note: Values must still fall within the range specified in the
GSD file for parameterization to be successful.
The “Enable Device Parameterization” parameter must be
enabled for the connected device parameters to be
downloaded into the device. If the “Enable Device
Parameterization” parameter is set to “Ignore” (0), device
parameters are “ignored” by the C441 PROFIBUS adapter
and are not downloaded into the connected device.
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com15
Configuration Using the PROFIBUS Configuration File
C441 Motor Insight Overload Protection Relay
Table 17. C441 Motor Insight Configuration File
Parameter NameLocationNotes
Enable Device ParameterizationAdapter0 = Ignore user data,
Com Adapter Outputs ComLoss BehaviorAdapter0 = Fail Safe (outputs disabled),
CT MultiplierMotor InsightCat No C441BB, C441CB, C441DB